HomeMy WebLinkAboutPROJECT INFORMATION L--r wrigni Projecty Summary Job: GARAGE LEFT
Date: JAN.5,2022
Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
Project • •
For: HUDSON 4 MODEL, SYNERGY BUILDERS
430 SE GASPARILLA AVENUE, PORT ST LUCIE, FL34983
Notes:
Design Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 °F Outside db 90 °F
Inside db 70 °F Inside db 75 °F
Design TD 28 °F Design TD 15 °F
Daily range M
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 18300 Btuh Structure 18501 Btuh
Ducts 5249 Btuh Ducts 7632 Btuh
Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 23549 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipmenf sensible load 24826 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 3391 Btuh
Ducts 2048 Btuh
Central vent (0 cfm) 0 Btuh
Heating Coolingg (none)
Area (ft2) 1833 1833 Equipment latent load 5439 Btuh
Volume (ft3) 17168 17168
Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 30265 Btuh
Equiv.AVF (cfm) 109 57 Req. total capacity at 0.70 SHR 3.0 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Rheem
Trade Trade RHEEM
Model Cond RA1436AJ1
AH RI ref Coil RH 1 P3617STAN
AHRI ref 201184296
Efficiency 100 EFF Efficiency 11.5 EER, 14 SEER
Heating input 10.0 kW Sensible cooling 23800 Btuh
Heating output 34121 Btuh Latent cooling 10200 Btuh
Temperature rise 27 °F Total cooling 34000 Btuh
Actual air flow 1133 cfm Actual air flow 1133 cfm
Air flow factor 0.048 cfm/Btuh Air flow factor 0.043 cfm/Btuh
Static pressure 1.00 in H2O Static pressure 1.00 in H2O
Space thermostat Load sensible heat ratio 0.83
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
�•••,.)Oft—ord- wrigl 2022-Jan-05 17:18:39
Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1
= ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name Entire House M BATH
2 Exposed wall 166.9 ft 20.0 ft
3 Room height 9.4 ft 8.0 ft heat/cool
4 Room dimensions 6.0 x 14.0 ft
5 Room area 1833.0 ft2 84.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�j13A-4ocs 0.143 n 4.00 2.19 372 322 1290 705 48 48 192 105
2 glazing,clr low-e 0.550 n 15.40 13.49 41 0 628 550 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 9 0 76 90 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 572 542 2170 1186 0 0 0 0
11 2 glazing,clr low-e 0.300 a 8.40 29.48 30 0 252 885 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 160 125 499 273 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 15 15 126 149 0 0 0 0
D 11DO 0.390 s 10.92 10.34 20 20 223 211 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 392 362 1449 792 112 112 448 245
2 glazing,clr low-e 0.300 w 8.40 29.48 30 0 252 885 0 0 0 0
C 1613-30ad 0.032 0.90 1.60 1833 1833 1642 2933 84 84 75 134
F 22A-tph 1.358 38.02 0.00 1833 167 6347 0 84 20 760 0
6 c)AED excursion 0 -23
Envelope loss/gain 14954 8657 1476 462
12 a) Infiltration 3346 943 358 101
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 8900 300
Subtotal(lines 6 to 13) 18300 18501 1834 863
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 18300 18501 1834 863
15 Duct loads 29% 41% 5249 7632 29% 41% 526 356
Total room load 23549 26133 2360 1219
Air required(cfm) 1133 1133 114 53
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 1
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name M WIC MASTER BEDROOM
2 Exposed wall 9.0 ft 29.0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 9.0 x 14.0 ft 15.0 x 14.0 ft
5 Room area 126.0 ft2 210.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�j13A-4ocs 0.143 n 4.00 2.19 72 72 288 158 120 111 444 243
2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 9 0 76 90
13A-40
cs 0.143 e 4.00 2.19 0 0 0 0 112 97 388 212
11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 15 0 126 442
LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0
C 16B-30ad 0.032 0.90 1.60 126 126 113 202 210 210 188 336
F 22A-tph 1.358 38.02 0.00 126 9 342 0 210 29 1103 0
6 c)AED excursion -10 -50
Envelope loss/gain 743 349 2325 1273
12 a) Infiltration 161 45 519 146
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 1200
Subtotal(lines 6 to 13) 904 394 2844 2619
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 1 2 0 0
14 Subtotal 906 397 2844 2619
15 Duct loads 29% 41% 260 164 29% 41% 816 1080
Total room load 1166 560 3660 3699
Air required(cfm) 56 24 176 160
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 2
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name BEDROOM 3 CLST 3
2 Exposed wall 11.0 ft 0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 1.0 x 149.0 ft 2.0 x 8.0 ft
5 Room area 149.0 ft2 16.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 88 73 292 160 0 0 0 0
2 glazing,clr low-e 0.300 w 8.40 29.48 15 0 126 442 0 0 0 0
C 16B-30ad 0.032 0.90 1.60 149 149 134 238 16 16 14 26
F 22A-tph 1.358 38.02 0.00 149 11 418 0 16 0 0 0
6 c)AED excursion 184 -1
Envelope loss/gain 970 1024 14 25
12 a) Infiltration 197 55 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 500 0
Subtotal(lines 6 to 13) 1167 1580 14 25
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 12 20 -14 -25
14 Subtotal 1178 1600 0 0
15 Duct loads 29% 41% 338 660 29% 41% 0 0
Total room load 1516 2260 0 0
Air required(cfm) 7319810 0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 3
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name KITCHEN/DINING BATH 2
2 Exposed wall 26.0 ft 6.0 ft
3 Room height 12.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 1.0 x 376.0 ft 12.0 x 6.0 ft
5 Room area 376.0 ft2 72.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�j13A-4ocs 0.143 n 4.00 2.19 132 91 365 200 0 0 0 0
2 glazing,clr low-e 0.550 n 15.40 13.49 41 0 628 550 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 180 165 661 361 0 0 0 0
11 2 glazing,clr low-e 0.300 a 8.40 29.48 15 0 126 442 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 48 48 192 105
2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0
C 1613-30ad 0.032 0.90 1.60 376 376 337 602 72 72 65 115
F 22A-tph 1.358 38.02 0.00 376 26 989 0 72 6 228 0
6 c)AED excursion -147 -19
Envelope loss/gain 3106 2008 485 201
12 a) Infiltration 698 197 107 30
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 3400 500
Subtotal(lines 6 to 13) 3803 5605 592 731
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 16 27 9 15
14 Subtotal 3819 5632 601 747
15 Duct loads 29% 41% 1095 2323 29% 41% 172 308
Total room load 4914 7955 773 1054
Air required(cfm) 236 345 37 46
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 4
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name BEDROOM 2 HALL
2 Exposed wall 12.0 ft 0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 12.0 x 12.0 ft 1.0 x 39.0 ft
5 Room area 144.0 ft2 39.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 96 81 324 177 0 0 0 0
2 glazing,clr low-e 0.300 w 8.40 29.48 15 0 126 442 0 0 0 0
C 16B-30ad 0.032 0.90 1.60 144 144 129 230 39 39 35 62
F 22A-tph 1.358 38.02 0.00 144 12 456 0 39 0 0 0
6 c)AED excursion 183 -2
Envelope loss/gain 1036 1033 35 61
12 a) Infiltration 215 61 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 500 0
Subtotal(lines 6 to 13) 1250 1594 35 61
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 13 23 -35 -61
14 Subtotal 1263 1616 0 0
15 Duct loads 29% 41% 362 667 29% 41% 0 0
Total room load 1626 2283 0 0
Air required(cfm) 781 991 0 0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 5
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name CLST 2 LAUNDRY
2 Exposed wall 0 ft 0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 2.0 x 8.0 ft 7.0 x 8.0 ft
5 Room area 16.0 ft2 56.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0
11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0
C 1613-30ad 0.032 0.90 1.60 16 16 14 26 56 56 50 90
F 22A-tph 1.358 38.02 0.00 16 0 0 0 56 0 0 0
6 c)AED excursion -1 -18
Envelope loss/gain 14 25 50 72
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 600
Subtotal(lines 6 to 13) 14 25 50 672
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution -14 -25 200 130
14 Subtotal 0 0 250 802
15 Duct loads 29% 41% 0 0 29% 41% 72 331
Total room load 0 0 322 1132
Air required(cfm) 01 01 15 49
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 6
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name AHU CLST GREAT ROOM
2 Exposed wall 0 ft 14.0 ft
3 Room height 8.0 ft heat/cool 12.0 ft heat/cool
4 Room dimensions 3.0 x 3.0 ft 1.0 x 250.0 ft
5 Room area 9.0 ft2 250.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 0 0 0 0 168 168 673 368
11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0
C 1613-30ad 0.032 0.90 1.60 9 9 8 14 250 250 224 400
F 22A-tph 1.358 38.02 0.00 9 0 0 0 250 14 532 0
6 c)AED excursion 0 -58
Envelope loss/gain 8 14 1429 710
12 a) Infiltration 0 0 376 106
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 1400
Subtotal(lines 6 to 13) 8 14 1805 2215
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution -8 -14 544 302
14 Subtotal 0 0 2348 2517
15 Duct loads 29% 41% 0 0 29% 41% 674 1038
Total room load T0 0 3022 3556
Air required(cfm) 0 0 145 154
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 7
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name FOYER CLST 4
2 Exposed wall 7.0 ft 2.0 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 1.0 x 112.0 ft 1.0 x 16.0 ft
5 Room area 112.0 ft2 16.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0
I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0
13A-40
cs 0.143 e 4.00 2.19 0 0 0 0 16 16 64 35
11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0
LV�✓ 13A-40cs 0.143 s 4.00 2.19 56 36 143 78 0 0 0 0
I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0
D 11DO 0.390 s 10.92 10.34 20 20 223 211 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0
2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0
C 1613-30ad 0.032 0.90 1.60 112 112 100 179 16 16 14 26
F 22A-tph 1.358 38.02 0.00 112 7 266 0 16 2 76 0
6 c)AED excursion -13 -2
Envelope loss/gain 732 455 154 59
12 a) Infiltration 125 35 36 10
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 857 490 190 69
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution -857 -490 -190 -69
14 Subtotal 0 0 0 0
15 Duct loads 29% 41% 0 0 29% 41% 0 0
Total room load 0 0 0 0
Air required(cfm) 01 01 0 0
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 8
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
IL
w„y" Right-J®Worksheet Job: GARAGE LEFT
Entire House Date: JAN.5,2022
By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name BEDROOM 4/DEN
2 Exposed wall 30.9 ft
3 Room height 8.0 ft heat/cool
4 Room dimensions 1.0 x 158.0 ft
5 Room area 158.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area Load
number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6V�j13A-4ocs 0.143 n 4.00 2.19 0 0 0 0
2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0
2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0
V�✓ 13A-4ocs 0.143 e 4.00 2.19 96 96 384 210
11 l C 2 glazing,clr low-e 0.300 e 8.40 29.48 0 0 0 0
13A-4ocs 0.143 s 4.00 2.19 104 89 356 195
2 glazing,clr low-e 0.300 s 8.40 9.95 15 15 126 149
D 11DO 0.390 s 10.92 10.34 0 0 0 0
13A-4ocs 0.143 w 4.00 2.19 48 48 192 105
2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0
C 16B-30ad 0.032 0.90 1.60 158 158 142 253
F 221%-tph 1.358 38.02 0.00 158 31 1176 0
6 c)AED excursion -24
Envelope loss/gain 2376 888
12 a) Infiltration 555 156
b) Room ventilation 0 0
13 Internal gains: Occupants @ 230 0 0
Appliances/other 500
Subtotal(lines 6 to 13) 2931 1544
Less external load 0 0
Less transfer 0 0
Redistribution 325 165
14 Subtotal 3256 1709
15 Duct loads 29% 41% 934 705
Total room load 4190 2414
Air required(cfm) 202 105
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- 34k -r"- wrigl 2022-Jan-0517:18:39
Right-Suite®Universal 2021 21.0.02 RSU08101
Page 9
...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
L-7 wrignI Duct System Summary Job: GARAGE LEFT
Date: JAN.5,2022
Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM
Project • •
For: HUDSON 4 MODEL, SYNERGY BUILDERS
430 SE GASPARILLA AVENUE, PORT ST LUCIE, FL34983
Heating Cooling
External static pressure 1.00 in H2O 1.00 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 1.00 in H2O 1.00 in H2O
Supply/ return available pressure 0.500/ 0.500 in H2O 0.500/0.500 in H2O
Lowest friction rate 1.000 in/100ft 1.000 in/100ft
Actual air flow 1133 cfm 1133 cfm
Total effective length (TEL) 142 ft
Supply Branch DetailTable
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk
BATH 2 c 1054 37 46 1.000 6.0 Ox 0 VIFx 5.0 95.0
BEDROOM 2 c 2283 78 99 1.000 7.0 Ox0 VIFx 10.0 95.0
BEDROOM 3 c 2260 73 98 1.000 7.0 Ox0 VIFx 22.0 115.0 SO
BEDROOM 4/DEN h 4190 202 105 1.000 7.0 Ox0 VIFx 23.4 95.0
GREAT ROOM c 3556 145 154 1.000 8.0 Ox 0 VIFx 25.5 115.0 st2
KITCHEN/DINING c 2652 79 115 1.000 7.0 Ox0 VIFx 25.5 115.0 st2
KITCHEN/DINING-A c 2652 79 115 1.000 7.0 Ox0 VIFx 20.1 115.0 st2
KITCHEN/DINING-B c 2652 79 115 1.000 7.0 Ox0 VIFx 20.4 115.0 st1
LAUNDRY c 1132 15 49 1.000 6.0 Ox0 VIFx 4.5 95.0
M BATH h 2360 114 53 1.000 6.0 Ox 0 VIFx 26.8 115.0 st 1
M WIC h 1166 56 24 1.000 5.0 Ox 0 VIFx 23.3 115.0 st 1
MASTER BEDROOM h 3660 176 160 1.000 8.0 Ox0 VIFx 23.0 115.0 st1
• • Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st2 Peak AVF 303 384 1.000 704 10.0 0 x 0 VinlFlx
st1 Peak AVF 498 450 1.000 633 12.0 0 x 0 VinlFlx
- --eft- 1•F wrigl 2022-Jan-05 17:18:43
Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1
�L u ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
TableReturn Branch Detail
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb1 Ox0 1133 1133 0 0 0 0 Ox 0 VIFx
— --311ft°S-'1•F wrigl 2022-Jan-05 17:18:43
Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 2
�L u ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW
This document was created with Win2PDF available at http://www.win2pdf.com.
The unregistered version of Win2PDF is for evaluation or non-commercial use only.
This page will not be added after purchasing Win2PDF.