HomeMy WebLinkAboutPROJECT INFORMATION L--r wrigni Projecty Summary Job: GARAGE LEFT Date: JAN.5,2022 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM Project • • For: HUDSON 4 MODEL, SYNERGY BUILDERS 430 SE GASPARILLA AVENUE, PORT ST LUCIE, FL34983 Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 °F Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 18300 Btuh Structure 18501 Btuh Ducts 5249 Btuh Ducts 7632 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 23549 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipmenf sensible load 24826 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3391 Btuh Ducts 2048 Btuh Central vent (0 cfm) 0 Btuh Heating Coolingg (none) Area (ft2) 1833 1833 Equipment latent load 5439 Btuh Volume (ft3) 17168 17168 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 30265 Btuh Equiv.AVF (cfm) 109 57 Req. total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1436AJ1 AH RI ref Coil RH 1 P3617STAN AHRI ref 201184296 Efficiency 100 EFF Efficiency 11.5 EER, 14 SEER Heating input 10.0 kW Sensible cooling 23800 Btuh Heating output 34121 Btuh Latent cooling 10200 Btuh Temperature rise 27 °F Total cooling 34000 Btuh Actual air flow 1133 cfm Actual air flow 1133 cfm Air flow factor 0.048 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.83 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �•••,.)Oft—ord- wrigl 2022-Jan-05 17:18:39 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1 = ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name Entire House M BATH 2 Exposed wall 166.9 ft 20.0 ft 3 Room height 9.4 ft 8.0 ft heat/cool 4 Room dimensions 6.0 x 14.0 ft 5 Room area 1833.0 ft2 84.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�j13A-4ocs 0.143 n 4.00 2.19 372 322 1290 705 48 48 192 105 2 glazing,clr low-e 0.550 n 15.40 13.49 41 0 628 550 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 9 0 76 90 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 572 542 2170 1186 0 0 0 0 11 2 glazing,clr low-e 0.300 a 8.40 29.48 30 0 252 885 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 160 125 499 273 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 15 15 126 149 0 0 0 0 D 11DO 0.390 s 10.92 10.34 20 20 223 211 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 392 362 1449 792 112 112 448 245 2 glazing,clr low-e 0.300 w 8.40 29.48 30 0 252 885 0 0 0 0 C 1613-30ad 0.032 0.90 1.60 1833 1833 1642 2933 84 84 75 134 F 22A-tph 1.358 38.02 0.00 1833 167 6347 0 84 20 760 0 6 c)AED excursion 0 -23 Envelope loss/gain 14954 8657 1476 462 12 a) Infiltration 3346 943 358 101 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 8900 300 Subtotal(lines 6 to 13) 18300 18501 1834 863 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 18300 18501 1834 863 15 Duct loads 29% 41% 5249 7632 29% 41% 526 356 Total room load 23549 26133 2360 1219 Air required(cfm) 1133 1133 114 53 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 1 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M WIC MASTER BEDROOM 2 Exposed wall 9.0 ft 29.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 9.0 x 14.0 ft 15.0 x 14.0 ft 5 Room area 126.0 ft2 210.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�j13A-4ocs 0.143 n 4.00 2.19 72 72 288 158 120 111 444 243 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 9 0 76 90 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 112 97 388 212 11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 15 0 126 442 LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 126 126 113 202 210 210 188 336 F 22A-tph 1.358 38.02 0.00 126 9 342 0 210 29 1103 0 6 c)AED excursion -10 -50 Envelope loss/gain 743 349 2325 1273 12 a) Infiltration 161 45 519 146 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1200 Subtotal(lines 6 to 13) 904 394 2844 2619 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 1 2 0 0 14 Subtotal 906 397 2844 2619 15 Duct loads 29% 41% 260 164 29% 41% 816 1080 Total room load 1166 560 3660 3699 Air required(cfm) 56 24 176 160 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 2 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 CLST 3 2 Exposed wall 11.0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 149.0 ft 2.0 x 8.0 ft 5 Room area 149.0 ft2 16.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 88 73 292 160 0 0 0 0 2 glazing,clr low-e 0.300 w 8.40 29.48 15 0 126 442 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 149 149 134 238 16 16 14 26 F 22A-tph 1.358 38.02 0.00 149 11 418 0 16 0 0 0 6 c)AED excursion 184 -1 Envelope loss/gain 970 1024 14 25 12 a) Infiltration 197 55 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 0 Subtotal(lines 6 to 13) 1167 1580 14 25 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 12 20 -14 -25 14 Subtotal 1178 1600 0 0 15 Duct loads 29% 41% 338 660 29% 41% 0 0 Total room load 1516 2260 0 0 Air required(cfm) 7319810 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 3 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name KITCHEN/DINING BATH 2 2 Exposed wall 26.0 ft 6.0 ft 3 Room height 12.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 376.0 ft 12.0 x 6.0 ft 5 Room area 376.0 ft2 72.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�j13A-4ocs 0.143 n 4.00 2.19 132 91 365 200 0 0 0 0 2 glazing,clr low-e 0.550 n 15.40 13.49 41 0 628 550 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 180 165 661 361 0 0 0 0 11 2 glazing,clr low-e 0.300 a 8.40 29.48 15 0 126 442 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 48 48 192 105 2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0 C 1613-30ad 0.032 0.90 1.60 376 376 337 602 72 72 65 115 F 22A-tph 1.358 38.02 0.00 376 26 989 0 72 6 228 0 6 c)AED excursion -147 -19 Envelope loss/gain 3106 2008 485 201 12 a) Infiltration 698 197 107 30 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 3400 500 Subtotal(lines 6 to 13) 3803 5605 592 731 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 16 27 9 15 14 Subtotal 3819 5632 601 747 15 Duct loads 29% 41% 1095 2323 29% 41% 172 308 Total room load 4914 7955 773 1054 Air required(cfm) 236 345 37 46 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 4 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 HALL 2 Exposed wall 12.0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 12.0 x 12.0 ft 1.0 x 39.0 ft 5 Room area 144.0 ft2 39.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 96 81 324 177 0 0 0 0 2 glazing,clr low-e 0.300 w 8.40 29.48 15 0 126 442 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 144 144 129 230 39 39 35 62 F 22A-tph 1.358 38.02 0.00 144 12 456 0 39 0 0 0 6 c)AED excursion 183 -2 Envelope loss/gain 1036 1033 35 61 12 a) Infiltration 215 61 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 500 0 Subtotal(lines 6 to 13) 1250 1594 35 61 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 13 23 -35 -61 14 Subtotal 1263 1616 0 0 15 Duct loads 29% 41% 362 667 29% 41% 0 0 Total room load 1626 2283 0 0 Air required(cfm) 781 991 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 5 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name CLST 2 LAUNDRY 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 2.0 x 8.0 ft 7.0 x 8.0 ft 5 Room area 16.0 ft2 56.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0 C 1613-30ad 0.032 0.90 1.60 16 16 14 26 56 56 50 90 F 22A-tph 1.358 38.02 0.00 16 0 0 0 56 0 0 0 6 c)AED excursion -1 -18 Envelope loss/gain 14 25 50 72 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 600 Subtotal(lines 6 to 13) 14 25 50 672 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -14 -25 200 130 14 Subtotal 0 0 250 802 15 Duct loads 29% 41% 0 0 29% 41% 72 331 Total room load 0 0 322 1132 Air required(cfm) 01 01 15 49 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 6 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name AHU CLST GREAT ROOM 2 Exposed wall 0 ft 14.0 ft 3 Room height 8.0 ft heat/cool 12.0 ft heat/cool 4 Room dimensions 3.0 x 3.0 ft 1.0 x 250.0 ft 5 Room area 9.0 ft2 250.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 168 168 673 368 11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 0 0 0 0 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0 C 1613-30ad 0.032 0.90 1.60 9 9 8 14 250 250 224 400 F 22A-tph 1.358 38.02 0.00 9 0 0 0 250 14 532 0 6 c)AED excursion 0 -58 Envelope loss/gain 8 14 1429 710 12 a) Infiltration 0 0 376 106 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1400 Subtotal(lines 6 to 13) 8 14 1805 2215 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -8 -14 544 302 14 Subtotal 0 0 2348 2517 15 Duct loads 29% 41% 0 0 29% 41% 674 1038 Total room load T0 0 3022 3556 Air required(cfm) 0 0 145 154 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 7 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name FOYER CLST 4 2 Exposed wall 7.0 ft 2.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 112.0 ft 1.0 x 16.0 ft 5 Room area 112.0 ft2 16.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft�°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V�/ 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 I;�C 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 0 0 0 0 13A-40 cs 0.143 e 4.00 2.19 0 0 0 0 16 16 64 35 11 2 glazing,clr low-e 0.300 a 8.40 29.48 0 0 0 0 0 0 0 0 LV�✓ 13A-40cs 0.143 s 4.00 2.19 56 36 143 78 0 0 0 0 I!-G� 2 glazing,clr low-e 0.300 s 8.40 9.95 0 0 0 0 0 0 0 0 D 11DO 0.390 s 10.92 10.34 20 20 223 211 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 0 0 0 0 C 1613-30ad 0.032 0.90 1.60 112 112 100 179 16 16 14 26 F 22A-tph 1.358 38.02 0.00 112 7 266 0 16 2 76 0 6 c)AED excursion -13 -2 Envelope loss/gain 732 455 154 59 12 a) Infiltration 125 35 36 10 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 857 490 190 69 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution -857 -490 -190 -69 14 Subtotal 0 0 0 0 15 Duct loads 29% 41% 0 0 29% 41% 0 0 Total room load 0 0 0 0 Air required(cfm) 01 01 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 8 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW IL w„y" Right-J®Worksheet Job: GARAGE LEFT Entire House Date: JAN.5,2022 By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BEDROOM 4/DEN 2 Exposed wall 30.9 ft 3 Room height 8.0 ft heat/cool 4 Room dimensions 1.0 x 158.0 ft 5 Room area 158.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6V�j13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 2 glazing,clr low-e 0.550 n 15.40 13.49 0 0 0 0 2 glazing,clr low-e 0.300 n 8.40 9.95 0 0 0 0 V�✓ 13A-4ocs 0.143 e 4.00 2.19 96 96 384 210 11 l C 2 glazing,clr low-e 0.300 e 8.40 29.48 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 104 89 356 195 2 glazing,clr low-e 0.300 s 8.40 9.95 15 15 126 149 D 11DO 0.390 s 10.92 10.34 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 48 48 192 105 2 glazing,clr low-e 0.300 w 8.40 29.48 0 0 0 0 C 16B-30ad 0.032 0.90 1.60 158 158 142 253 F 221%-tph 1.358 38.02 0.00 158 31 1176 0 6 c)AED excursion -24 Envelope loss/gain 2376 888 12 a) Infiltration 555 156 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 500 Subtotal(lines 6 to 13) 2931 1544 Less external load 0 0 Less transfer 0 0 Redistribution 325 165 14 Subtotal 3256 1709 15 Duct loads 29% 41% 934 705 Total room load 4190 2414 Air required(cfm) 202 105 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - 34k -r"- wrigl 2022-Jan-0517:18:39 Right-Suite®Universal 2021 21.0.02 RSU08101 Page 9 ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW L-7 wrignI Duct System Summary Job: GARAGE LEFT Date: JAN.5,2022 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM Project • • For: HUDSON 4 MODEL, SYNERGY BUILDERS 430 SE GASPARILLA AVENUE, PORT ST LUCIE, FL34983 Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply/ return available pressure 0.500/ 0.500 in H2O 0.500/0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 1133 cfm 1133 cfm Total effective length (TEL) 142 ft Supply Branch DetailTable Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk BATH 2 c 1054 37 46 1.000 6.0 Ox 0 VIFx 5.0 95.0 BEDROOM 2 c 2283 78 99 1.000 7.0 Ox0 VIFx 10.0 95.0 BEDROOM 3 c 2260 73 98 1.000 7.0 Ox0 VIFx 22.0 115.0 SO BEDROOM 4/DEN h 4190 202 105 1.000 7.0 Ox0 VIFx 23.4 95.0 GREAT ROOM c 3556 145 154 1.000 8.0 Ox 0 VIFx 25.5 115.0 st2 KITCHEN/DINING c 2652 79 115 1.000 7.0 Ox0 VIFx 25.5 115.0 st2 KITCHEN/DINING-A c 2652 79 115 1.000 7.0 Ox0 VIFx 20.1 115.0 st2 KITCHEN/DINING-B c 2652 79 115 1.000 7.0 Ox0 VIFx 20.4 115.0 st1 LAUNDRY c 1132 15 49 1.000 6.0 Ox0 VIFx 4.5 95.0 M BATH h 2360 114 53 1.000 6.0 Ox 0 VIFx 26.8 115.0 st 1 M WIC h 1166 56 24 1.000 5.0 Ox 0 VIFx 23.3 115.0 st 1 MASTER BEDROOM h 3660 176 160 1.000 8.0 Ox0 VIFx 23.0 115.0 st1 • • Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 303 384 1.000 704 10.0 0 x 0 VinlFlx st1 Peak AVF 498 450 1.000 633 12.0 0 x 0 VinlFlx - --eft- 1•F wrigl 2022-Jan-05 17:18:43 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 1 �L u ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW TableReturn Branch Detail Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Ox0 1133 1133 0 0 0 0 Ox 0 VIFx — --311ft°S-'1•F wrigl 2022-Jan-05 17:18:43 Right-SuiteO Universal 2021 21.0.02 RSU08101 Page 2 �L u ...ts\Wrightsoft HVAC\HUDSON 4-GASPARILLAAVE.rup Calc=MJ8 Front Door faces: NW This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.