May 30, 2017
FILE
Project information:
Islandia I
9550 S. Ocean Dr,
Jensen Beach, FL
Suite # 510
To whom it may concern:
The'following Wind Load Pressure Calculations have been performed at the aforementioned address
utilizing the ASCE-7-10 (Part 4- Buildings with height of 15-80 ft) Components and Cladding pressure
formulas and were performed at the request of the Contractor —.Natural Flow. "
Building Information : Exposure D - Importance Factor #1
Height: 60 ft — 5t" Floor
Wind Speed: 170 mph
Minimum. Required Opening Pressures:
Openings that are 20 sgft to 50 : Zone 4 = +50.9 / -51.1 psf
Zone 5 = +50.9 / -91.4 psf
Openings that are 50 sgft to 100:
Openings that are 100 sgft to 500:
Zone 4 = +47.2 / -49.3 psf
Zone 5 = +47.2 / -82.6 psf
Zone 4 = +44.0 / -47.2 psf
Zone 5 = +44.0 / -75.7 psf
If there are any comments or concerns please contact me.