HomeMy WebLinkAboutLetter - Wind Load Pressurer sir RANI�ELD ■_. C"ITECTS RECEIVED JUN 12 2017 1653 N 5. JENraEN MACH 5L vcD. ENc-;EN 3EALit, FLORIDA 34957 PHONE: 772-253-6032 FAN: 77Z-253-6150 May 30, 2017 FILE Project information: Islandia I 9550 S. Ocean Dr, Jensen Beach, FL Suite # 510 To whom it may concern: The'following Wind Load Pressure Calculations have been performed at the aforementioned address utilizing the ASCE-7-10 (Part 4- Buildings with height of 15-80 ft) Components and Cladding pressure formulas and were performed at the request of the Contractor —.Natural Flow. " Building Information : Exposure D - Importance Factor #1 Height: 60 ft — 5t" Floor Wind Speed: 170 mph Minimum. Required Opening Pressures: Openings that are 20 sgft to 50 : Zone 4 = +50.9 / -51.1 psf Zone 5 = +50.9 / -91.4 psf Openings that are 50 sgft to 100: Openings that are 100 sgft to 500: Zone 4 = +47.2 / -49.3 psf Zone 5 = +47.2 / -82.6 psf Zone 4 = +44.0 / -47.2 psf Zone 5 = +44.0 / -75.7 psf If there are any comments or concerns please contact me. Sincerely, .5f&wa,k+ e ► Stewart Granfield Granfield Architects PLLC stewa @granarch.comcastbiz.net IN iC z ON =- 5 7-0-H-9 51 brabham 6 uhns d.6-y Ul