HomeMy WebLinkAboutRHVAC LoadsExpress :191.6 Cali Right Psi HVAC Load -Calculations for Express Homes Rum'"w"VAC RgVsA1D�I�I'TiAL = Prepared By: Kristin Kelly' Florida Breeze 6928 Vickie Circle Suite B West Melboume;-Fl 32904 3219518767 Thursday, September:22, 2016 Rhvac is -an_ ACCA approved Manual J and Manual D. computer program. ' Calculations: are performed perACCA Manual J 8th Edition, Version 2, and ACCA ManuaGD��:� Designed By: . Kristin Kelly Protect Date:. September22, 2016, Client Name: Express Homes :Company Name., Florida Breeze: Company Representative: Kristin Kelly Company Address: -6928 Vickie Circle Suite B. ss Company City. West Melbourne,'Fl 132004 1" Company Phone:.. 3219518767. . t®}e ign Data Reference City: Fort Pierce Florida :Building Orientation: Front door faces South Daily -Temperature Range;, Medium Latitude: 27 Degrees Elevation: 25 - ft: :Altitude Factor:. 0.999 Outdoor' Outdoor Outdoor Indoor Indoor Grains Dry Bulb. Wet Bulb . Rel.Hum Rel.Hum . - :Dry Bulb Difference Winter: 42 39.4 n/a n/a 70 : n/a" Summer:, 90 78 50% 50% 75 61 Check ,' res i Total Building Supply CFM: 1,230 CFM Per Square ft.; 0.642 i Square ft. of Room: Area: 1,916 Square ft. Per Ton: 676 t3} Volume (f.of Cond. Space: 16,861 13 idn• aa•s Total Heating Required Including Ventilation Air: 32,102 Btuh 32;102 ' MBH - ? Total Sensible Gain: " 27,029 ' Btuh 79 % ° Total Latent Gain: 6,977 i3tuh; 21 % Total Cooling Required Including Ventilation Air: 34,006 Btuh. 2.83 Tons (Based On Sensible + Latent): i 1 N tes - Rhvac is.an ACCA approved Manual J and Manual D:computer program. i Calculations are performed per ACCA Manual J 8th. Edition, Version 2 and_ ACCA Manual D. All,' computed results are estimates as building use 'andIweather may vary. Be sure to select a unit that meets both :sensible and latent: Ioads.abcording to the manufacturer's performance. data at your:design cbnditions. a C:1.::1EXPRESS 1916 CALI RIGHT PSL.rh9 i Thursday, September 22, 201,6, 10:34 AM lmmer: 90 78 59%. 50% 75 61:09 set S z Ina i Main Trunk: :: Runouts . . alculate:: Yes Yes ae Schedule; Yes Yes ugliness Factor:. 0.01000 U1,000 *essure Drop:. 0.1000:. in.wg.%100 ft. 0.1:000 in.wg./100;ft.: inimum:Velbeity: 550 ft./min 450 ft./min aximum Velocity: 660 ft./min 750..ft./min iriimum Height: 0 in. .. . Q''in. aximum Height:... 0 in. 0 in. utsi � e i<4lc l7afa Winter .- ..._ _ _ .. _ . S'umme Filtration Specified: 0.380 AC/hr 0.200 AC/hr 107 CFM 56 CFM filtration Actual: 01380 AC/hr 0.200 -AC/hr )ove Grade Volume: X 16.861 Cu.ft.: X 16:861 Cu.ft. 6,407 Cu.ft./hr 'k,:0.0167 3,372 Cu.ft./hr X 0.0167 ►tal Building Infiltration: 107 CFM 56 ':CFM )tal Building Ventilation:. 0 CFM 0 CFM --System 1--1. . . 'iltratiori:& Ventilation Sensible Gain Multiplier:: : 1.6.49 (1.10 X 0.099 X 15.00 Summer.Temp. Difference) Filtration.& Ventilation Latent'Gain Multiplier: 41.60 = (0.68 X:0.999 X 61.09 Grains: Difference) Filtration & Ventilation :Sensible Loss Multiplier: 30.77 =..(1.16 X 0.990 X 28,00 Winter Temp.: Difference) inter Infiltration Specified: 0.380 AClhr.(107 CFM), Construction: Average immerinfiltration Specified: 0.200 AClhlr (56 CFM), Construction; -Average 1 Return' Attic 16B 0.12 :6 474 No C:1...IEXPRESS 1916 CALI RIGHT 08L.rh9 Thursday, September22, 2016, 10:34.AM Rhvac Res►dent►al 8 U ht Commerc► 1 FiVAC Loads 14 A/C Serv►te;MastetsLL`C� f?aim Ba' ;AFL 82909r �, Elite Sofhvare Development Inc . Express 1916 Cali ftigh Pst Pa e 4 :Duct Sr7e Previevu Room or Duct Name Source Minimum Maximum.' Rough.l 1 Velocity Velocity YFacton Design SR Duct t1100 Loss. Velocfty4Length Duct Htg Cfg ACt. Duet . Flovi Flow Size System 1 Supply Runouts Zone 1 ....... 1-Whole House: Other Ducts. in System 1 t3ultt In .450 750 0:01: 0.1 521:9: 4171: 1,230 12-6 Supply;MalnTrunk Bulk -In 560 600 0.01 0;1.." 563.7 :;. 4171 1;230 20 Summary System 1 Heating Flow, 417 'Cooling Flow: : 1230 . 1 f i E C:\ ..-.1EXPRESS 1016 CALI RIGHT- PSL.rh9 Thursday; September 22, 2016., 10:34 AM F`Rh�raa Residential &Light Gommerc�at,HVAC,Loads _ AIC'Service Masters, LLC .' �f Palm Ba ` FL 32609..' j System. ' Summa, , ;L.oads 12A-v-o: Glazing -Double pane low-e (e = 0.60), operable, f w. doy�r,, vinyl frame, u-value 0:34, SHGC 0.35 . 2A=v-d: Glazing -Double pane low-e (e = 0.60),. sliding glass door, vinyl:frame, u-value 0.63;:SHGC 0.32 11J: Door -Metal - Fiber glass Core 13A13-0fcs: Wall -Block, no blanket or board insulation; filled core, siding finish ' 12C-0sw: Wall -Frame; .R-13 f%Cinsulation in 2 XA tud cavity --no board insulation, siding .fin sh, wood studs 16B-38: Rooeiling-Under Atficwith Insulation on AM. e- Fioo:r (also use for.Knee Walis and Partition i Ceilings), Vented Attic, No Radiant Barrier; Dark Asphalt.Shingles or Dark Metal, Tar and Gravel or. Membrane, R-38 insulation 22A-pm: Floor -Slab on grade; No edge insulation;' no l insulation below floor; any floor cover; passive, heavy dry or light wet soil Subtotals for -structure: People:..... Equipment: Lighting: Ductwork::. . i Infiltration: Winter CFM: 107, Summer CFM:. 56 Ventilation_ Winter CFM: 0, SummerC_ FM::0. System 1 Load Totals: Supply CFM: 1,230 Square ft:.of Room Area: 1,91.6 Volume (ft3) 'of Cond. Space:. 16,861 . 3 Sofia a veeDr lopment, [nc A- press1996,CafiiighPs1; 124.5 1,192 0.. 2,380 -2,380 4fl.8 720 0:' 660 •660 36A4 612 0. 568 568 1236.1 6,334 0 3,936 3,936 31:3.1 798 0 612 ' 612. 1916 1,395 0 2.491 -2,491 199 6,575 0 0 0 11,626 0 10,647 10,647 5 1;000 1,.150. 2,150. 1,020 3,563 4,583 0 0: 0 11,190 2,624 _ 10,742 13,366 3,286 2,333 927 .3-260 0 0: _ 0 32,102 6,977 27,029� 34,006 CFM Per Square ft. 0.642 Square ft. Per Ton: 676 imai rieating icequirea.incivamg ventilation Air: 32,102 ,Btuh 32.:102 MBH Total Sensible Gain: 27,029 ' Btuh 79 61. Total Latent Gain: 6,977 Btuh 21 % Total Cooling Required Including Ventilation. Air. 34,006. Btuh 2.83 Tons (Based On Sensible + L-atent) . Knvao is an ._ approvecl Manualand Manual.computer program, Calculations are performed per ACCA Manual J 8th Edition, Version 2, and.ACCA Manual D. All. computed results are estimates as building use'aind weather may vary. Be sure to select a unit:that meets both.sensible and latent loads. according to the manufacturer's performance data at your design conditiion"s. I i C:1... kEXPRESS 1916 CALI RIGHT P8L.rh9 Thursday, September'22,'2016, 10:34AM -Rhvac --Residential Light.,Comme rpi A/C .Service Vas4r 6C .Oilin F12 32009_ _q i Fduipm,&ht Data -System I 1 Cooling 1 Systerh. Type: Air Source,H6at'Pump Outdoor Model: 25HBC536A**30 in"do'o"r, Model: FV4CNB006. Tradename: . BASE 15 PURON HP Outdoor M666fa6tdrer: CARRIER AIR, CONDITIONING Description: Air SourceHeat Pump AHRI'Rbference,N o.: 3646041 : Capacity: -86412 Efficiency: 15.5 SEER System Type' Air Source Heat Pump Model: 25HBC536A**30 Traden8me: BASE 1'5''PURON HP Manufacturer: CARRIER AIR CONDITIONING Descriptio'n: Air Source Heat Pump Capacity: '34000. Effidency: 9 HSPF - hsystem s-eFouip-rrie ht was 'selected . iff. accordance- With AtCAManual S. r 'Manual S equipmorit'sizing data: -SOD5A - OF', SQWB:.7.8F, WODB:. 42F,'SIDB:--76F',-SIRH: 50%, WID . B,:, 70r,' Sen. gain: 27,629 Btuh, Lat. gain: 6,97.7 Btuh, Sen. loss: 32,1.02 Btuh, Entering dlg'. c6pbb: 75F, , Ente ri , ng, cIg roil WB: 62.5F, Entering htg.,coil DB: 70F,.Cid. coil TD: 20F, Htg. -coil TD: 70F, Req. clg: :airflow: 1230 CFM; Req.',htg. airflow: 417 CFM- C:\..:.\EXP,RESS 1916 CALI RIGHT PSL.rh9 Thdrsday, SeptqMbet 22, 2016, 10.-34 AM I Whole House 1,016 321:102 417. 12-6 522: 27,029 4;363. 1,230 1,230 Duct Latent :. 2,624 System-1 total -1;916 32,102.. 4.17 27,029 6:97:7 1,230: _1;230 _System 1 Main Trunk. Size: .20 in: Velocity: 564 ft./min Loss per 100 ft.: 0.040 in.wg. . Net Required: 2.83 79%'/ 213/6 27,029 6 97V 34,006 _ Actual: 3;03 88% / u% 31,9.52 4460 36 412 E • ui . gent, Data Heating System Cooling System Type; Air Source. Heat Pump Air SouVde Heat :Pump. Model: _ 25HBC536A**30 25HBC536A**30 Indoor Model: FV.4CNB606 Brand: BASE 15 PURON HP BASE 15 PURON.HP:. Description: Air Source Heat Pump Air Source Heat -Pump Efficiency:: 9 HSPF 15.5 SEER. Sound: 0 .. 0 i Capacity: 34,600 Btuh 36,412 Stuh Sensible Capacity: n/a 31,952:Btuh .. Latent :Capacity: n/a 4,460 Btuh AHRI Reference No::_ n/a, 3645941 E This system's-equipment uvas: selected' in accordance_.with.ACCA:(liianual_S Marival,S equipment sizing data: SORB:'90F, 80W11; 78F, WODB:-42F, SI, B: 75F;:SIRH:.50%; WIDB: 70F, Sen..gain: 27,029 Btuh, Lat. gain: 6,977 Btuh, Sen. loss: 32,102 Btuh, Entering clg.:coil DB: 75F, Entering clg. coil WB: 62.5F, Entering htg. coil D& 70F. Clg. coil TD:-20F,'Htg. coil TD: 70F, Req. clg. airflow: 1230-CFM, Req. htg::oirflow:-417 CFM { C:I .:.\EXPRESS 1916 CALI RIGHT: PSL.rh9 Thursday, September 22, 201.6, 10.-34-AM s l!rC�rrFuisipcax��ia d A Form, RPER- 1.01. 8 Mar 10 county, I own; municipaury, j.unsaiction Header Information Contractor Florida:Breeze REQUIRED ATTACHMENTS' ATTACHED. Manual A Form (and supporting worksheets): 'Yes pX No 0 Mechanical License # CAC181411.3. or. MAAE Fottn� (and supporting Wort sheets): Yes Q .No OEM performance data.(heating, cdoling, blower): _ Yes 0- No Q Building Plan # Manual D Friction Rate Worksheet: Yes ❑ No 0 Duct distribution system sketch: Yes ❑ No QX Home Address (Street or Lot#, Block, Subdivision) Winter Design Conditions Building Outdoor temperature 42 OF Orientation (Front door faces) South Indoor temperature 70 o F North, East, West, South, Northeast. Northwest; Southeast, Southwest Total heat loss 32102 . Btu/h Number of bedrooms A �t :. Summer Design .Conditions Conditioned floor. area , 1 916. Sq 'Ft Outdoor temperature �90 of Number of occupants .5 Indoor temperature 75 OF Windows, Grains difference. .:61 A Gr @ 50:: % Rh Eave overhang depth Roof - 2.7 F#: . Sensible: heat gain 27029 BtWh Internal, shade a Eave Latent heat gain 6977 .Btu/h Blinds, drapes, elo Depth Window Total.hheatgain. ._ 34.006- :BtU/h Number of skylights. 0 1 EQUIPMENT SELECTION , Heating Equipment.Data Cooling Equipment Data Blower Date Equipment type Heat pump Equipment type Heat'pump Heating CFM 1293:10FM Fumace, Heat pump 90 er, etc. Air Cgnd'itipner, Heal pump, etc Model 25HBC536A**30 Model 25HBC536A**30 .Cooling CFM .. 1293 CFM Heating output capacity::' 34000 8tujh Sensible cooling:capacity 31952 Btu/h Heatpurops- ca�acliyatwinterdesignoutdoorconditians :Latent6o61ingcapacity 4460 Btu/h. Auxiliary heat output: capacity Btu/h Total cooling capacity 3641.2 :Btu/h Design, airflow CFM External Static Pressure (ESP) lWC Component.Pressure Losses (CPL)' IWC Available Static Pressure (ASP). PC ASP = ESP - CPL. . Longest Supply duct: Ft Duct Materials Used (circle) Trunk Duct: Duct board, flex, Sheet metal,. Longest return duct: FtLined sheet metal, Other (specify) Total:Etfective Length (TEL): Ft . Braricb Duct' Duct -board, Flex, Sheet metal, Friction Rate- i�VC Lined sheet metal, Other (specify) Friction.Rate= (ASP x 100) -TEL Contractor's Printed Name. K istin. Kelly Date 7/10/2015 Contractor's Signature Reserved for use.Municipality, or Authority having jurisdiction. ' The AHJ shall have the discreff66-joi accept Required Attachments printed: from approved ACCA sofhvare'vendors, see list on page 2 of instructions.. ' If abridged version of Manual J is used for load calculation, then verify.residence meets requirements,. see Abridged Edition Checldist on page 13 of instructions. Form generated by ACCA-approved Manual J. Eighth Edition Version 2 Elite Software Rhvac program. Air Conditioping Contractors of America Manual S (Resid'ential Equipment Selection) rro}ect inrormauon Name: , City:. State; Altitude: Altitude Adjustment: 1.00 i uooung uesign inrormation Outdoor Design Temp: 91 `.:'F db Summer' Outdoor.Design Temp: 43 • • IF db )Winter- Indoor Design Temp: 75 °F db 50 %RH 63' : IF wb anua o .. , a cu a ions . , ....... Total:Load Sensible Latent SHR Heat Loss 34006 27029 6977 0.795� -Ai'rflow Calculations Design TD for Airflow 19 Design Sensible CFM F1293 —OEM Information •. Manufacturer: Ioarri6r. Furnace Model #: :.. AFUET7 Coil'or. Fan -Coil Model #: FU4CNB600- Condenser Model #: 25HBC536A SEIER:F 15.5 HSPF:: 9.00 tn)w1auwa4tu[er b 1,001ing rerrormance- uata Entering Coil Temperature = 75 (F db) Rated CFM @ Rated RA Temperature Rate'd.CFM @ Desrgn RA Temperature Rated CFM @.Rated RA Temperature (u) nnanuracturers t:000ng,Nertormance Data Entering Coil Temperature:=.15 (F db) Rated CFM @ Rated RA Temperature Rated CFM @ Design RA Temperature Rated CFM @ Rated RA Temperature Lower Return Air Outdoor Temperature = 95. 1 (F db)' CFM (F wb) Total BTUH Sensible BTUH Latent'BTUH SHR 67 37;900 27,120 10,780 0,7156 10 5 0-1 35,204 F 4.148 0.8822 62-7-1 r 34.530 - 32,040 ,2,490: 0.9279 Higher Return•Ak Outdoor Temperature {F db) CFM (F wb) Total BTUH Sensible BTUH' Latent,BTUH SHR' 67 .- 39,270 30,570' F 8,7007 o.7785 1350 637-1 F 36,694:.. 35,266 i.428. 0.9611 62 :736,050 36,440 -390 1,01078 ,v,anuiaowiea to %,vunng rurrgrrnance uama tinterpoiateo) Design Return Air Outdoor Temperature- 95 (F. db). CFM (F wb) Total BTUH. Sensible BTUH Latent BTUH SHR 34,470 - 1,943 0,9467 Excess Latent Capacity Calculation +-2,517.:: -2,517 Capacity @ Design CFM / RA (F wb) 1293.3 .63. 36,412 31,952 4,460: 0.878 Equipment Capacity as a. % of Design 107.08% 118.22% 63.92% - Manufacturer's Heat Pump Data Capacity Capacity Balance Supplemental @ 47 IF db @ 17 °F db Point Heat Required 34,800 18.820 :-18.3 -15.87 ' C7 Manufacturer's Furnace, Data Input 0utput Desired Calculated FEATURES ..: Environmentally .'Sound Re&ieeiant Technology •. PuroA chlorine=free non ozone iiepleting refrigerant • Theirmostatic F.acpansion Valve_(T`XV),designed to maximize performance with Purohe refrigerant .. .. .. ... ... e. Energy Eff"icieut Operation • .Electmpically Commutating Motor.(ECM)'tiperates'efficientiy at all:speeds,' . • MaXimlies efficieneyof heating and'aooling systems • ..Ultra Tow power eonsum to Burin fan onl o.eration , , Indoor Weather "Control • Wanit, camfortableaieating air temperatures „ . • Unmatched humidity confio_l; especially with "Carrier s Thermidistat-•Control Airflow and 'Sound :Technolo ■ Diffuserair dischargeaection for high at ow effieiencyand quiet, smooth: operation • High duct static capability (iv igt�ct"srthztt�e� n��teo0 in rtt r qu�t11 t ez tT;(hiis.i tuiopr Condensate Control and Disposal Technology +; Minimal standing waterless;microbial growth for improved lAQ and reduced condensate line clogging and related condensate leakage : Condensate. fittings ielocated'away. from hrrbnient arrflo�Y •patterns ar the blower entrance for improved condensate control performance • Overflow feature for siope coil units allows condensate to exit the unit without• damage to product under clogged primaryand secondary line:conditions Tested for condensate disposal. at:conditions much more.severe than those required by AHRi • Primary and. secondary: drain connections to comply with HUD'- • All paiis constructed of an injection, moidedglass=filled polycaiboriate engineered resin mateiia1, with brass drain connections. :-HighdensitY, P su ei thick: cabinetry insulation with vapor barrier . _ ;% Pre -painted galvanized sheet-nietai cabinet Heat Transfer Technology • Grooved copper: tubing Lanced sine wave'alumifiUm fns . Aiscreetrefined counter4lowrefrigerant circuitry • Bi=flow hard shut=oft: TXV metering device : . ArmorCoat', coil protection available - Quality Assisting, Ease, of Installation and Service Features •' All unitsmuttipaise... . • Provision made for suspending from rc of or -ceiling joints • Modularcabinet`oil 063.thru 606 units • Sweat connections for leak free service Multiple efectrical,enti'y ' for Iication flexibility (high and tow voltage) Low voltage terminal.strip, to safely hold connections within the cabinet' . inspection plate on A -coil models for quick coil, cleanliness inspection • Cabinet:construcfion features .innovations designed to prevent cabinet sweating :Controls and Electrical.Featturts • Easy Select"Board to maximiie comfort, efficiency, and safe heater airflow operation „Bast' plug connection.provW d for:quick installation' of accessory, heater packages :• d0. A.20>1/230v transformer .::. • Replaceable S arrip blade=type auto fuse proiects.against transformer secondary short Filter Features : ..... . • .Factory supplied filter ► CI anable,polyester filter media • Filter "spriont for easy access - no tools required ngs" . • Newly improved •filter lack area - filter door insulation' added for an: improved air seal 2...