March 22, 2022
Crystal Chilson
5420 Cassia Drive
Ft. Pierce, Florida
Re: Visual Site Inspection
5420 Cassia Drive
Fort Pierce, Florida
KSM 2202418
To Whom It May Concern:
Based upon a request from Crystal Chilson, we have been asked to conduct a visual site inspection
to determine the approximate footer size. We measured under the footer and found the footer to be
generally 10” deep and 12” wide as indicated by random location checks on the north, west, and
east sides. The south side did not have access.
We have also been asked to conduct a Rebound “Swiss” Hammer test in accordance with ASTM
C805 to evaluate the approximate compressive strength of the concrete slab for the above-
mentioned address. Representatives from KSM Engineering and Testing (KSM hereinafter)
conducted the Rebound Hammer test on March 8th, 2022, at approximately 12:00 PM.
Scope of Test:
The completion of this test by KSM serve to document and evaluate the condition of the concrete
slab at the time of the inspection within a reasonable professional engineering probability and
certainty. KSM will select (3) random locations within the slab for Rebound Hamer Testing. All
conclusions or recommendations are based upon testing, observations, or information gathered on-
site prior to completion of this document. If field conditions change or differ than as stated in this
document, it is the responsibility of all parties to contact KSM for additional review. The
compressive strength test results listed below are in accordance with ASTM C805 and based on
the corrected average rebound numbers gathered on site.
Concrete Properties:
The following was provided to KSM by the client.
Design Mix / Strength: 2,500 psi
Headquarters Mailing
11345 U.S. Highway 1 P.O. Box 78-1377
Sebastian, FL. 32958 Sebastian, FL. 32978
Orlando Phone: 772-589-0712
723 Progress Way C.A. # 5693
Sanford, FL. 32771 KSMengineering.net
Proudly Serving Florida since 1990
Page 2 of 2
Information gathered during test:
Date Poured: N/A
Date Tested: March 8th, 2022
Approximate age of concrete: N/A
Description of the test area:
Surface characteristics: Trowel Finish
Curing conditions: Shaded by Framing
Air Temperature: 80o
Orientation of hammer: -90o
Swiss Hammer Information:
James Instruments Inc. Manual Test Hammer Model W-M-250
Serial No. 40401-90280
Calibrated by James Instruments Inc.
3727 N. Kedzie
Chicago, IL. 60618
Test Results:
Location Average Rebound # Approximate Compressive
Strength (PSI)
S.W. Corner 25.6 2,750
Center 24.8 2,630
N.E. Corner 25.6 2,750
Conclusions and Recommendations:
Based upon our review of the field collected data and laboratory testing, within a reasonable
professional engineering certainty, the concrete slab has an approximate compressive strength that
meets or exceeds the required design strength of 2,500 psi.
If you have any questions about this letter, please contact my office.
Regards,
Julie E. Keller, P.E.
President
PE # 68366
3/15/22