HomeMy WebLinkAboutNOAMIAMI•DADE IVIIAMI-DARE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY ANb ECON01MIC RESOURCES (RER) Miami, Florida 33175-2474 BOARD AND CODE ADNIINISTRATION DIVISION T(786)315.2590 F (786) 315-2599 NOTICE OF ACCEPTANCE (NOA) www.mianiidade.eov/economy James Hardie Building Product, Inc. CONCEALED FASTENERS OR ATTACHMENTS 10901 Elm -Avenue ' ARE THE RESPONSIBILITY OF THE Fontana, CA 92337 CONTRACTOR OF RECORD . SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER-Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for .quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ uiay immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is determined by Miami Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code, including the High Velocity Hurricane Zone. DESCRIPTION: "Hardie", "Cem" and "Prevail" Planks and Panels Fiber Cement Siding and Soffit APPROVAL DOCUMENT: Drawing No. PNL, PLK & SOFF, titled "HardiePanel, CemPanel, Prevail Panel; HardiePlank, CemPlank Prevail Lap Siding; HardieSoffit, CemSoffit Panel; Installation Details ' Wood/Metal Stud Construction", sheets 1 through 12 of 12, dated 04/24/2013, prepared by the manufacturer, signed and sealed by Ronald L Ogawa, P.E., bearing the Miami -Dade County Product Control revision stamp with the Notice of Acceptance number and expiration date by the Miami -Dade County Product Control Section. MISSILE IMPACT RATING: Large -and Small Missile Impact Resistant LABELING: A permanent label with the manufacturer's name or logo, Plant City, Florida, and the following statements: "ASTM C 1186 Type A compliant" and "Miami -Dade County Product Control Approved" is to be located on each siding plank or panel and per FBC 1710.9.2 and 1710.9.3 on soffit panels. RE, NEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided -to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA revises NOA # 13-0311.07 and consists of this page 1 and evidence page E-1, as well as appi-oval document mentioned above. The submitted documentation was reviewed by Carlos M. Utrera, P.E. NOA No.15-0122.04 Expiration Date: May 1, 201.7 Approval Date: April 9, 2015 FIL *,9f 361-�5 x -- E James Hardie Building Products, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED A. DRAWINGS "Submitted tinder NOA # 13-0311.07" 1. Drawing No. PNL, PLK & SOFF, titled "HardiePanel, CemPanel, Prevail Panel; HardiePlank, CemPlank Prevail Lap Siding; HardieSoffit, CemSoffit Panel; Installation Details Wood/Metal Stud Construction", sheets 1 through 12 of 12, dated 04/24/2013, prepared by the manufacturer, "signed and sealed by Ronald I.Ogawa, P.E. B. TESTS "Submitted tinder NOA # 13-0311.07" 1. Test reports on 1) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 2) Cyclic Wind Pressure Loading per FBC, TAS 203-94 along with marked -up drawings and installation diagram of HardiePlank, HardieSoffit and HardiePanel, prepared by Intel tek Testing Services NA LTD, Test Report No. 100733361COQ-004, dated 08/24/2012, with revision 1 dated 04/25/2013, signed and sealed by Rick Curkeet, P.E. "Submitted tinder NOA # 02-0729.02" Laboratory Report Test Date Signature 2. ATI-16423-1 PA 202 & 203 03/18/96 A. N. Reeves P.E. 3.. ATI 16423-2 PA 202 & 203 03/18/96 A. N. Reeves P.E. 4. ATI 16423-3 PA 202 & 203 03/18/96 A. N. Reeves P.E. C. CALCULATIONS 1. None. D. QUALITY ASSURANCE 1. Miami -Dade Department of Regulatory and Economic Resources (RER) E. MATERIAL CERTIFICATIONS 1. None. F. STATEMENTS 1. Statement letter of code conformance to the 5 h edition (2014). FBC issued by Ronald I.Ogawa & Associates, Inc., dated 10/26/2014, signed and sealed by Ronald I. Ogawa, P.E. Carlos M. Utrera, P.E. Product Control Exaininer NOA No. 15-0122.04 Expiration Date: May 1, 2017 Approval Date: April 9, 2015 E-1 —WALL l�NG7H PRODUCT DESM PTION SEE Harde.PaneM. CemPsnet®, & Stud Spacing at 16" O.G. DETAIL A Prevail® Panel Sid'mg materials are BE- 1 ` nonasbestos fiber -cement products Fi--i--►I �/ . ,/g^ dick / 5 ply APA rated tested in accordance with ASTM •-1lt , QGA ��� p sheathing in Clde It d meeting 186 Grade , Type A an 9 got• ,r _ accordance with Florida the requirements of the Florida i i i i.� \�•�� i•i;' \ E• .. Bru'id'rtq Code Section Building Code. 23223 NEL DIME -SJPM WAIT. ! Water -resistive Vlldtfl Length Thickness f .� y ��'i'i ` barrier per Florida 4 8,9,10' S115' iElGH Drpr . �! i�fly' Building Code ®�'' �� Setion 14042 DES�G�I PRE_S_S_U RATING �? Pressure X X 4" S.P-F lristalfas6`o�ds Design i cS"$Q!1l�i�d i Wood Studs Wood -76 ..;� __y.� Impact Resistant-- {� HardiePanei, CT ON B� Cempanel, ptanks installed over 518" thick / 5 ply SNP — APA rated plywood sheathing Nails at 1s" 0.C. (typ.) prevail panel 3187 Minimum Edge Distance Siding oft me Sheathing fastener, as described in Note 1 Panel fastener, as described in Note 2 HardiePanel, Cempanel, Prevail Panel Siding Water -;resistive barrier per - Florida Building Code Section 14042 T518" thick / 5 ply APA rated plywood sheathing fastened in accordance with Florida Building Code Section 2=3 2" X 4" S-P-F Wood Studs The wall and soffit frames are to be designed by the Architect or Engineer of Record in compliance with the Florida Building Code. yA�EPANEfl,_CEMPAAkE_L, '_v_��4�^r���-�-�-•"nce, the manufactureris ■ All installation shall be dorms in conformance with this Notice of Accepts installation recommendations, and the applicable sections of the �nU insda talled shall be ■ Wood studs where l•IardiePanel, Cempanel, Prevail Panel Siding designed by an Engineer or Architect Per the Florida Building Code and the requirements of this N.OA M (Abbe 115/8" thick / 5 ply APA rated plywood sheathing shall be attached to the studs in accordance with Florida Building Code Section 2322& d sheathing supported ■ The siding panels shag be Installed over 5/a- thick 15 ply APA rated PIYWOO by a minimum of 2'9C4" S-P-F wood studs spaced a ma)dmum of 1s" O.C. • (Note 21 The siding panel fastener shall be a 2' long, 0.223" head diameter, 0.092" shank diameter, corrosion resistant siding nail; the faStenets shad be spaced at 6" O.C. at panel edges and intermediate studs; the fasteners shall be driven through the 5/8" thick / 5 ply APA rated plywood sheathing into wood studs located at IS- O.C. f • Fasteners shall have a minimum edge distance of 3i8" and a minimum clearance of 2" from , corners. Fax 909-427-0534 Creator. I- Gonzales HARDIEPANUt CEMPANEL, PREVAIL PANEL INSTALLATION DETAILS WOOD STUD CONSTRUCTION .fames Hartle Building Produces, Inc. 10901 Elm Avenue Fontana, CA 92337 VM No A I I PNL-pL"OFF Date: 4rz;i=3 IsNeEr 1 OF 92 Fastener Spacing per Florida 16.QOin, Building Code.Section 2322.3�i p,q ili:VL�D Fastener Spacing per Florida av�i+YtbeFl�iBa Building Code Section 2322.3 .�- • .9y I ` `-• -o STA ssfo�ua� / Cladding Framing / Sheathing FRAMING - • , • -NOMINAL 2" X 4" S-P F WOOD STUDS 16" O.C. FASTENED FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE WITH•3-1/2" 16d COMMON NAILS (2 PER TOP AND NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS) BOTTOM CONNECTION) • THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE WirH THE FLORIDA BUILDING CODE SH�A7HlIV� ■ NOMINAL 5/8" THICK/5 PLY APA RATED PLYWOOD ¢ HARDIEPANEL, CEMPANEL, PREVAIL PANEL SHEATHING FASTENED IN ACCORDANCE WITH FLORIDA INSTALLATION DETAILS WOOD STUD CONSTRUCTION BUILDNG CODE SECTION 2322.3 - _C_I A_D_ K_ Q .fames Hardie Building Products, Inc, ■ THE PANEL IS FASTENED WITH 2" LONG, 0.223" HEAD 10901 Elm Avenue DIAMETER, O.C9Z) SHANK DIAMETER, CORROSION Fontana, CA 92337 RESISTANT SIDING NAILS, PLACE NAILS S" O.C. AT + PANEL EDGES AND INTERMEDIATE STUDS Phone: 909.356-6300 SIZEFSCM No ORNo REV Fax 909-427-0634 A PNL-PLKSOFF 1 Creator E. Gonzales .SCALE 1" = 9-0^ Date:4124/2013 SHEET 2 OF 12 No WALL LENGTH Stud Spacing at 16" O.C. B 4---, l _ 1 _ I WALL. B4-- 1 3/8" Minimum pYTg1.L,6 Sheathing fastener, as described in Note 1. Panel fastener, as described in Note 2 HardiePanel® Siding Water -resistive barrier per Florida Building Code Section 1404.2 PEI No. ?. -o STATE Qmod' Sf ONA' Distance Nails at 6" O.C. (typ.) RDII=PAf�Ei�CEIyiPA�iat,-QR��4pAEL SIDING f1�SJA�ON Di;L7gI1:S ■ All installation shall be done in conformance with this Notice of Acceptance, the manufacturer's installation recommendations, and the applicable sections of the Florida Building Code. Metal studs where HardiePanel, Cempanel, Prevail Panel Siding will be installed shall be designed by an Engineer or Architect per the Florida Building Code and the requirements of thin N.O.A. ■ [Note 11 5/8" thick /5 ply APA rated plywood sheathing shall be attached to metal studs at 6" oc at panel edges and all intermediate supports using a No.8-18, 0.315" head diameter X 1-IW long bugle head screw ■ The siding panels shall be installed over 5/8" thick / 5 ply APA rated plywood sheathing supported by a minimum 20ga, Nominal 3-SZ' X 1-518" Metal C-studs spaced a maximum of 16". ■ [Note 2] The siding panel fastener shall be a minimum No. 8-18, 0.315" head diameter X 1-518" long" ribbed bugle head screw ("or screw shall have at least 3 full threads penetrating.metal framing); the fasteners shall be spaced at 6" O.C. at panel edges and intermediate studs; the fasteners shall be driven through the 5/8" thick IS ply APA rated plywood sheathing into metal studs located at 16" O.C. ■ Fasteners shall have a minimum edge distance of 3/8" and a minimum clearance of 2" fram comers. SEE DETAIL A ti 61W thick 15 ply APA rated plywood sheathing fastened to metal studs as described in Note 1 PRODUCT DESCRIPTION HardiePaneie, CempaneM, & Prevail® Panel Siding materials are nonasbestos fiber -cement products tested in accordance with ASTM C1186 Grade It, Type A and meeting the requirements 01 the Florida Building Code. y PANEL DLM�T_LS_LQNS Water -resistive Width Length Thickness it barrier per Florida 4' 8,9,101 5/16" Building Code Section 1404.2 13ESClz a� Installation Design Pressure toga, M18" X 1-5/8" Metal Studs -104 psf Metal Cstud -� tt HardiePenel, Impact Resistant — panel installed over 518" thick / 5 ply M p g ce , APA rated plywood sheathing Prevvailail PPaanel Siding HARDIEPANEL, CEMPANEL, PREVAIL PANEL S/8"thick / 5 ply APA rated INSTALLATION DETAILS METAL STIED CONSTRUCTION plywood sheathing fastened James Hardie Building Products, lnm to metal studs as described _ 10901 Sim Avenue in Note I. gap a Fontana, CA 92337 20ga, 3-5/8" X 1-&811.Metal C-stud phone: 9094W-6300 sIM FSCM No OWS N° The wail and soffit frames are to be designed Fax 909-427-0634 A PNL-PLK SOFF by the Architect or Engineer of Record in compliance with the Florida Building Code. Creator, E. Gonzales SCALE' 112" =1'-o" Date: 4124/2013 sH 3 OF • T 6.00in. . • ffi�y�;gwdlke6cFlSoar�s �Ac=Ptww No !'--Q'31 T By produa FA1I!�G ■ -518" X 1-b/8" STEEL 16" O.C. NOMINAL 20 GAUGE 3 FASTENED WITH 518" WAFER HEAD SCREWS (2 PER TOP AND BOTTOM CONNECTION) THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE WITH THE FLORIDA BUILDING CODE S_fiE�1TIi3G NOMINAL 518" THICK / 5 PLY APA RATED PLYWOOD SHEATHING TO METAL STUDS AT 6" OC AT PANEL EDGES AND ALL INTERMEDIATE SUPPORTS USING A NO.8-18, o.315° HEAD DIAMETER X 1-1/4' LONG BUGLE HEAD SCREW CLADDING THE PANEL IS FASTENED WITH NO.8-18, 0.315" HEAD DIAMETERX 1-518' LONG CORROSION RESISTANT RIBBED BUGLE HEAD SCREWS (SCREW SHALL HAVI=AT LEAST 3 FULL THREADS PENETRATING THE METAL FRAMING), PLACE SCREWS 6" O.C. AT PANEL EDGES AND INTERMEDIATE STUDS Cladding Framing I• II I I Sheati7ing II I•I II I I I II'II II•I� '���t�/mil/iii��i l I I � ��� SF • + o. 121 I I ' ,e `• STATE OF I • � FLO R1�4 =' 'yam-�'� 1 S OVAL FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE -P t NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS) 11! HARDIEPANE.L, CEMPANEL, PREVAIL PANEL INSTALLATION DETAILS METAL STUD CONSTRUCTION James Hardie Building Products, Inc. 10901 Elm Avenue • Fontana, CA 92337 DWC3 NO RE phone: 909-356-6300 SIZE, FSCM No 1 pNL-PLKSOFF Fax 909427-0834 A Creator. F. Gonzales SCALE 1"=1'-0" Date:412412013 SHEET 4 OF 12 • WALL HEIGHT 1 an B Fi 1 3/01 Minimum Edge Distance .D_FTAi4A x LENGTH -Sheathing fastener, as described in Note 1 Mails at 161- O.C. (typ.) Siding fastener, as described in Note 2 HardiePlank, Cemplank, Prevail Lap Siding 3 // Water -resistive barrier per Florida Building Code Section 1404.2 " 5/8" thick 15 ply APA rated ----�' plywood sheathing fastened .in accordance with Florida Building Code Section 2322.3 2" X 4" S-P-F Wood Studs The wall and soffit frames are to be designed 'by the Architect or Engineer of Record in r.mmnitarrrnvAth the Florida Building Code. S10NAN- SEE DETAIL A ` 5/8" thick 15 ply APA (` fsreftorlda d plywood sheathing in accordance with Building Code �g0_�UG3 DiZsS3oPria�u HardiePlanemplankd!), & Prevail® Plank Lap Siding materials are nonasbestos fiber -cement products tested in accordance with ASTM C1186 Grade it, Type meeting the requirements of the Florida Building Code. Section 2=3 1�� r:_U_( MSIQNS Wates4es9stive Width Length Thickness \ barrier per Florida 59-112" 12' $116 , BuWaV Code Section 14042 p9JGN PF,ES_SUFRF...RAT1NG 2 X 4" S-p-F installation Design Pressure Wood Studs Wood Studs -92 psf impact Resistant— S�C7�0 Planks installed over 5/8" thick / 5 ply � Lap Siding 1-1/4" 4au X 5116" APA rated plywood sheathing thick starter strip tD_I�P_I�attc�c_irL�NKLPJiYA_ �4W�S>IALNGJN��At-I-qTa-o�`>I-aA � All installation shall be done in conformance with this Notice of Acceptance, the manufacturer's installation recommendations, and the applicable sections of the Florida Building Code - Will be installed shall be designed by an Engineer or Architect per the Florida Building Code and the requirements of this N.OA ■ [Note 1] 5/8" thick ! 5 ply APA rated plywood sheathing shall be attached to the studs in accordance with Florida Building Code Section 2322.3. ■ Planks shall be applied horizontally commencing from the bottom course of the wall with 1-114" wide laps at the top of the plank such that the exposure area of each plank is 5 8A 1W vertically. _ [Note 2] The siding fastener shall be a 2-1/Z long, 0.223" head diameter, 0.092" shank diameter, corrosion -resistant siding nail; The siding is fastened S 8-1/4" O.C. vertically and 16" O. hin horizontally, fastens fasteners are driven into wood studs thr uugh 4n fram thheply Abo om edgpA rated plywood the overlapping plank, are placed in the overlapping area approximately = Vertical joints shall be placed over studs. od sheathing supported by a The planks shall be installed over 5/8 thick / 5 ply APA rated plywood minimum of 2"X4' S-P-F wood studs spaced a maximum of 16" O.C. ■ Fasteners shall have a minimum edge distance of 31W. HARDIEPLAXK, CEMPLANK, PREVAIL LAP SIDING INSTALLATION DETAILS WOOD STUD CONSTRUCTION James Hardie Build'mg Products, I'no. 10901 Elm Avenue Fontana, CA 92337 GC: A I I PNL-PLK-SOFF Creator. E. Gonzales IsCALE 112" -1--o" Date: 4/24/2013 SHEET 5 OF 12 Fastener Spacing per Florida Building Code Section 2322.3 • •� �• Fastener Spacing per Florida Building Code Section 2322-3 0.75n asaww0yiwVd&dwflb t >hMEMSCA& Acwpft= NO T � Frodu�tCoead 5S.251n. Fl2�► 1NG ■ NOMINAL 2" X 4" S-P-F WOOD STUDS 1S- O.C. FASTENED WITH 3=1/2" 16c1 COMMON NAILS (2 PER TOP AND BOTTOM CONNECTION THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE WITH THE FLORIDA BUILDING CODE SH TH NG ■ NOMINAL 5/8" THICK / 5 PLY APA RATED PLYWOOD SHEATHING FASTENED IN ACCORDANCE WITH FLORIDA BUILDING CODE SECTION 2322.3 �LADD�G ' ■ PLANKS,OVERLAP 1-1/4" ■ THE EXPOSURE IS s8-1/4" IN THE PLANKS ARE FACE NAILED WITH 2-1/2° LONG, 0?23" HEAD DIAMETER, 0.092" SHANK DIAMETER, CORROSION RESISTANT SIDING NAILS, -PLACED 3/4" UP FROM THE BOTTOM EDGE OF THE PLANK AT EACH STUD LOCATION —16 in. 0 Cladding Framing Sheathing pROMCr REVISED �osgpi,riog 21 wid►fc lE7 " cat � � � , No. 1 IN STATE OF . FPS••......-= ����'QJ �01�AL ti ,, 'FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION ANDlUriY�►i�l 1rY1LOAD ARE NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS) HARDIEPLANK, CEMPLANK, PREVAIL LAP SIDING INSTALLATION DETAILS WOOD STUD CONSTRUCTION James Hardie Building Products, Inc. 10901 Elm Avenue Fontana, CA 9=7 IZE FSCM NO Dvva NO fA PNL-PLK-SOFF 1 creator E.Gonzales ISCAu 1"=11-0" 1 Date:4124)2013 ISNEEr 6OF12 WALL HEIlGM i B B at 16' 3/4" Minimum DETAIL ei do "Orift i C- 1rVALL LENGTH SEE P1�OD_ DISC !PT' DETAILA HardiePlankO, CemplankO, and W thick / 5 ply APA Prevail® Plank Lap Siding materials _....._- ------- .__._---,.,- _.._.__ .�........ / '� rated pWocd are nonasbestos fiber -cement ' sheathing fastened products tested In accordance with ASTM C1186 Grade I!, Type A and to ts1el studs as meeting the requirements of the ���ii'ihri�•. described in Note 1 Florida Building Code. 's C0 wi* ifivFuffm S 10�40 �1 I _ Yv Water resistive "1 barrier per Florida .L DIMEPISLONS, Bvad'mg Code Width Length Thickness Sedlon 14042 S 9.1/2" 12' —$y ;r'tndnrdrGveedl ; i w !{ i i' 20ga, 3-518" X 1-S/8" . DESIGN PRESSURE RATING k�Hardleftnk, lC-sfirdInstallation Design Pressure blAlF` Metal Studs .92 psf ... .__mplanlc, Prevrail ......'.•\apSiding Impact Resistant- 16" O.C. '�.E _X 1s" Planks installed over 5/8" thick / 5 ply Distance Nails at (typ)-��� 1 1/4 tall 5/ thick starter strip APA rated plywood sheathing Sheathing fastener, as described in Note 1 Siding fastener, as described in Note 2 HardiePlank, Cemplank, Prevail Lap Siding Water resistive barrier per Florida Building Code Section 1404.2 5/8" thick 15 ply APA rated plywood sheathing fastened to metal studs as described in Note 1 20ga, 3-5/8" X 1-8/8" Metal C-stud The wall and soffit frames are to be designed by the Architect or Engineer of Record in compliance with the Florida Building Code. FiARD1FpLANation shall be I�CEMPLANK. PRE1/AIL LqP $ID1NG_INS_%gLLA'FIQTd DETAU S ■ An installdone in conformance with this Notice of Acceptance, the manufacturer's installation recommendations, and the applicable sections of the Florida Building Code. ■ Metal studs where HardiePlank, Cemplank, Prevail Lap Siding will be installed shall be designed by an Engineer or Architect per the Florida Building Code and the requirements of this N.OA • ENote 1] 5/8" thick / 5 ply APA rated plywood sheathing shall be attached to metal studs at 6"oc at panel edges and all intermediate supports using a No.8-18, 0.315" head dtameterx 1-1/4" long bugle head screw ■ Planks shall be applied horizontally commencing from the bottom course of the wall with 1-1W wide laps at the top of the plank such that the exposure area of each plank is S 8-1/4" vertically. ■ jNote 21 The siding fastener shall be a minimum No. 8-18, 0.315" head diameter X 2-1/4" long{ bugle head screw over metal studs (`or screw shall have at least 3 full threads penetrating metal framing); The siding is fastened.-9 8.1/4" O.C. vertically and 16" O.C. horizontally; fasteners are driven into metal studs through 5/8" thick 16 ply APA rated plywood sheathing, fasteners are placed in the overlapping area apprbximately 3/4" from the bottom edge of the overlapping plank, ■ Vertical joints shall be placed over studs. ■ The planks shall be installed over 5/8" thick 15 ply APA rated plywood sheathing supported by a minimum 20ga, Nominal 3-5/8" X 1.8/8" Metal C-studs spaced a maximum of 16" O.C. ■ Fasteners shall have a minimum edge distance of 30. 0.75,11 .Fgyl�r • NOMINAL 20 GAUGE 3-5/B" X 1-6/8" STEEL Sl-UUS IV' O,C. FASTENED WITH 516" LONG RIBBED BUGLE HEAD SCREWS (2 PER TOP AND BOTTOM CONNECTION) ■ THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE WITH THE FLORIDA BUILDING CODE sNEAs ■ NOMINAL 50 THICK / 5 PLY APA RATED PLYWOOD SHEATHING TO METAL STUDS AT V OC AT -PANEL EDGES AND ALL INTERMEDIATE SUPPORTS USING A NO.8-18, 0.315" HEAD DIAMETER X 1-114" LONG BUGLE HEAD SCREW QLADDIAIG ■ FLANKS OVERLAP 1-1/4° • THE EXPOSURE IS :9 8-1/4" ■ THE PLANKS ARE FASTENED WITH NO. $-18, 0.315" HEAD DIAMETER X 2-1/4' LONG CORROSION - RESISTANT RIBBED BUGLE HEAD SCREWS (SCREW SHALL HAVE AT LEAST 3 FULL THREADS PENETRATING THE METAL FRAMING), PLACED 3/4" UP FROM THE BOTTOM EDGE OF THE PLANK AT EACH ATI rn I nr:A-nnM FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION D GRAVITY LOAD NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS r - l HARDIEPLANK, CEMPLANK, PREVAIL LAP SIDING INSTALLATION DETAILS METAL STUD CONSTRUCTION James Hardie Building ProdUets, Jna _ 10901 Elm Avenue • 1 - m Fontana, CA 92337 Creator E. Gonzales PNL-PLK-SOFF 1. = T-0" I Date: 4/2412011 8OF12 WALL WALL LENGTH Stud Spacing at 16" O.C. I 3/8" Minimum Nails at 4" O.C. Distance offt'fastener, as ascribed in Note 1 HardieSoffit, Cemsoffrt Mirlimum 2" X 4" S-P-F Wood Studs The wall and soffit frames are to be designed by the Architect or Engineer of Record in compliance with the Florida Building Code. SEE E NALMT .DEscj2iP71_10 HardieSof M & CemsoffM materials are DETAIL A nonasbestos fiber -cement products tested in i 1� accordance with ASTM C1186 Grade 11, Type A and meeting the requirements of the Florida Building Code. S_O_FffTi]� SIGNS_ 2" X 4" S-P-F Width Length Thickness Wood Studs g! 114" rAe" A"J_G_N.j&F_SSUJ(13AT1NG HardieSoffit, Installation Design Pressure Cemsoffit Wood Studs -70 psf EGAW, �GTJont�Jg �� n itYP•�ReDl1C� ODIlG?aEYLSED o`� •"C •e o � tee. ek ;ea N0. 4 2� > Cobe -0! A U exeptasoe No 1so �G!�s � STATE OF �eProa+,aceeeroif `�4,cF• k%RA3JSsOEn__T, EMSOF_FI7k4MMLAASIA-4A JMDET.A" = All installation shall be done in conformance with this Notice of Acceptance, the manufacturer's installation recommendations, and the applicable sections of the Florida Building Code. = Wood studs where HardieSoffit, CemsoffitWll be installed shall be designed by an Engineer or Architect per the Florida Building Code and the requirements of this N.OA The soffit shall be installed over minimum 2 X4 S-P-F wood studs spaced a maximum of 16' O.C. ■ DNote 11 The soffit fastener shall be a 2 long, 0.223" head diameter, 0.092" shank diameter, corrosion resistant siding nail; the fasteners shall be spaced at 4" O.C. at panel edges and intermediate studs; the fasteners shall be driven into wood studs looted at 16" O.C. = Fasteners shall have a minimum edge distance of 3/8- and a minimum clearance of 2" from comers. HARDIESOFFIT, CEMSOFFIT PANEL INSTALLATION DETAILS WOOD STUD CONSTRUCTION James Hardie Building Products, Inc. 10901 Sim Avenue Fontana, CA 92337 DM NO PNL PLK-SOFF Creator. E. Gonzales IsGALE 12-= t'-o- 1 Date:4424 MS 9OF12 • 4.001n- s cagpl7' crib the F10CAS ffi C01mpbyiaS wish the F1 wida • 17 n EM—MNQ NOMINAL 2" X 4" S-P-F WOOD STUDS 16" O.C. FASTENED WITH 3-1/2" 16d COMMON NAILS (2 PER TOP AND BOTTOM CONNECTION) THE WALL. AND SOFFIT FRAMES ARE TO BE DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE WITH THE FLORIDA BUILDING CODE CL.ADD).�IG THE SOFFIT IS FASTENED WITH 20 LONG, 0223" HEAD DIAMETER, 0.092" SHANK DIAMETER, CORROSION RESISTANT SIDING NAILS, PLACE NAILS 41 O.C. AT PANEL EDGES AND INTERMEDIATE STUDS / Cladding Framing - GA N0. Vh21 STATE OF FOR METALAND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS) I HARDIESOFFIT, CEMSOFFIT PANEL INSTALLATION DETAILS WOOD STUD CONSTRUCTION James Hardie Building Products, Inc. _ 10901 Elm Avenue tt Fontana, CA 92337. Shane: 909-356.000 517E F901,1 No DM NO RE Fax 909-427-0634 A PNL-PLK-SOFF 1 Creator. E. Gonzales SCnu: 1"=1'-0." Date: 4r24/2013 SHIMT 10 OF 12 WALL LENGTH Stud Spading.at 16" O.C. SEE DETAILA i ; I•i i 10 I , i I Metal 0-stud WALL OGHT 1 r-laroieSortlt, Ae" Cemsoffit '� i I i'; ;•I �.1 Li i S CTI N Nails at 6" O.C. (typ.) wr Minimu,n —Q' V."^V* UCT OWL"Cwn as COwO by whb tbo FhCida AC=PtMx1M (3�C3rl•G�% E. IEP-IO_D_U_CJ��SC91P"�ON HardeSoffa &� CemsoffitO materials are nonasbestos fiber -cement products tested in accordance with ASTM C1186 Grade 11, Type A and meeting the requirements of the Florida Building Code. sQ� PJMEN LO v rdth Lenp Thickness 4, $, Y11 DESIGN PRESSURE ELTT t3G. installation Design Pressure Metal Studs-N.Wf_- TATE OF p�,ane cao�d, eao P:oelxt Co.+enot <E, PO,=OR 1 B P .y�to 6.00in. 16.00in, Cladding Framing r • T - 6.00I in. MeDucirIzEnsw adw, .t Code ais x�+8 vri!>! i�o Yr�a�ias j�aiiirri�i.�. ACCCIPIUM"WO In . Ado • F�oR���`'' c� �3 Fsts, 0 e FR,0.NI_ING- ■ NOMINAL 20 GAUGE 3-5/8" X 1-5/8"STEEL STUDS 1W O.C. FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE FASTENED WITH 518° WAFER HEAD SCREWS (2 PER TOP NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESIS LOADS) AND BOTTOM CONNECTION) ■ THE WALLAND SOFFIT FRAMES ARE TO BE DESIGNED BY THE ARCHITECT OR ENGINEER OF RECORD IN COMPLIANCE WITH THE FLORIDA BUILDING CODE HARDIESOFFIT, CEMSOFFIT PANEL CLADDING THE SOFFIT IS FASTENED WITH NO.8-18, 0.315" HEAD INSTALLATION DETAILS METAL STUD CONSTRUCTION DIAMETER 1-1/4" LONG CORROSION RESISTANT RIBBED BUGLE HEAD SCREWS (SCREW SHALL HAVE AT LEAST 3 .lames Hardie Building Products, Inc, FULL THREADS PENETRATING THE METAL FRAMING), PLACE 10901 Elm Avenue SCREWS 6" O.C, AT PANEL EDGES AND INTERMEDIATE � — o Fontana, CA 92337 - STUDS 0M NO RSf Phone: 909-356-6 300 SIZE rscM No Fax 909-427-0634 A PNL-PLK-SOFF 1 Creator. E. Gonzales saN.s �" = 9'-0" Date. •at24�20 ►3 12 OF i 2