HomeMy WebLinkAboutRizzo Residence SealedREVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEG-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952 8.295kW PV SYSTEMCODES AND STANDARDS2 SOUTHEAST JUAREZ LANE,PORT ST. LUCIE, FL 34952RIZZO RESIDENCEVICINITY MAPSHEET INDEXG-01COVER SHEETPROJECT DESCRIPTION:OWNERHOUSE PHOTOA-01ROOF PLANS-01MODULE LAYOUTS-02ATTACHMENT DETAILS-02.1E-01ELECTRICAL LINE DIAGRAME-02WIRING CALCULATIONSE-03SYSTEM LABELINGDS-01-06DATA SHEETSSHEET SHEET DESCRITIONCOVER SHEETA-00NOTES AND DESCRIPTIONELECTRICAL CERTIFICATION:STRUCTURAL CERTIFICATION:DESIGN CRITERIA:WIND SPEED (ULT): 170 MPHWIND SPEED (ASD): 132 MPHRISK CATEGORY:IIEXPOSURE:CPROJECT SITESS-01.1ARTIAL RESSURE AND MODULES EXOSURETITAN SOLAR525 W BASELINE RD,MESA, AZ 85210(855) 729-7652INSTALLERCastillo Engineering Services LLC620 N. Wymore Road, Suite 250, Maitland, FL 32751TEL: (407) 289-2575Ermocrates E. CastilloLicense#: FL PE 52590ENGINEERRIZZO, LAWRENCE21x395 HANWHA: Q. PEAK DUO ML-G10+ (395W) MODULESROOF MOUNTED SOLAR PHOTOVOLTAIC MODULESEQUIPMENT SUMMARY21 HANWHA: Q. PEAK DUO ML-G10+ (395W) MODULES01 SOLAREDGE TECHNOLOGY: SE7600H-US INVERTER21 SOLAREDGE POWER P401 OPTIMIZERSGOVERNING CODES :FLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)FLORIDA PLUMBING CODE, 7TH EDITION 2020 (FPC)FLORIDA BUILDING CODE, 7TH EDITION 2020 (FBC)FLORIDA MECHANICAL CODE, 7TH EDITION 2020 (FMC)NATIONAL ELECTRICAL CODE 2017 (NEC)ASCE 7-16FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020 (FFPC)RACKING: K2 CROSSRAIL 48-XL - RAILATTACHMENT: SPLICE FOOT XPROJECT SITEI ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFY THATTHE PV ELECTRICAL SYSTEM AND ELECTRICALCOMPONENTS ARE DESIGNED AND APPROVED USINGTHE STANDARDS CONTAINED IN THE MOST RECENTVERSION OF THE FLORIDA BUILDING CODE. FBC 107,THE NEC 2017, AND THOSE SET FORTH BY THEFLORIDA SOLAR ENERGY CENTER CERTIFICATION.I ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFYTHAT THE INSTALLATION OF THE MODULES IS INCOMPLIANCE WITH FBC: RESIDENTIAL 2020 7th ED.,CHAPTER 3. BUILDING STRUCTURE WILL SAFELYACCOMMODATE WIND LATERAL AND UPLIFTFORCES, AND EQUIPMENT DEAD LOADS.SYSTEM SIZE:8.295 kW DC STCARRAY AREA #1:316.81 SQ FT.ARRAY AREA #2:126.73 SQ FT.STRUCTURE CALCULATION
System Description This system is a grid-tied, PV system, with PV generation consisting of 21x395HANWHA: Q. PEAK DUO ML-G10+ (395W) Modules with a combined STC rated dcoutput power of 8,295W. The modules are connected into 01 SOLAREDGETECHNOLOGY: SE7600H-US Inverter. The inverter has electronic maximumpower point tracking to maximize energy captured by the PV modules. Theinverter also has an internal ground fault detection and interruption device that isset to disconnect the array in the event that a ground fault that exceeds oneampere should occur. The inverter has DC and AC disconnect integrated systemand labels are provided as required by the National Electrical CodeWhen the sun is shining, power from the PV array is fed into the inverter,where it is converted from DC to AC. The inverter output is then used tocontribute to the power requirements of the occupancy. If PV power meets therequirements of the loads of the occupancy, any remaining PV power is sold backto the utility. When utility power is available, but PV power is not available,building loads are supplied by the utility.The inverter meets the requirements of IEEE 1547 and UL 1741.Figure 1: PV System Block DiagramCentralized AC toDC InverterPV ModulesPoint ofUtilityConnectionUtility MeterInverterJunctionBoxOptimizerSection..............Elevation ...........Detail ................Detail ................(Enlarged Plan)Keyed Notes ..........Ground Terminal .....Grounding Point/rod....Solar Panel ......... orCombiner Box ..........AC Disconnect ..........Main DistributionPanel ......................Fuse ......................Overcurrent Breaker ..Inverter ....................Transformer .............Automatic ...............Transfer SwitchXX-XXXX-XXXX-XXXX-XX1CBACDMDP Sheet where section is located Detail ID Letter Sheet where section is located Detail ID Letter Sheet where section is located Detail ID Letter Sheet where section is locatedArea to be enlargedKeyed note designationon applicable sheetATS00Module with SourceCircuit numberVent, Attic fan(Roof obstruction)PV Roof AttachmentTrussesConduitFire AccessAC Alternating CurrentAPPROX ApproximateAWG American Wire GaugeCB Combiner BoxDC Direct CurrentACD AC DisconnectDISC Disconnect(E) ExistingEL ElevationEQ EqualJB Junction BoxMCB Main Combiner BoxMFR ManufacturerMIN MinimumMISC Miscellaneous(N) NewOCPD OverCurrent Protection DevicePOCC Point Of Common CouplingPV PhotovoltaicSF Squarefoot/feetSTC Standard Test ConditionsTBD To Be DeterminedTYP TypicalUNO Unless Noted OtherwiseVIF Verify In FieldWP Weather ProofBatteryBATUtility meterUMGPGeneration PanelMDPMain Distribution PanelSoladeckSDNAVD North American Vertical datumMicrogrid Interconnect DeviceMIDREVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEA-00CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952NOTES ANDDESCRIPTIONSymbols:Abbreviations:74"41.1"RAILS IN THISPOSITION UNOFALL PROTECTION:ANCHORAGES USED FOR ATTACHMENT OF PERSONAL FALL ARREST EQUIPMENTMUST BE INDEPENDENT OF ANY ANCHORAGE BEING USED TO SUPPORT ORSUSPEND PLATFORMS, AND CAPABLE OF SUPPORTING AT LEAST 5,000 POUNDSPER EMPLOYEE ATTACHED, OR MUST BE DESIGNED AND USED AS FOLLOWS:·AS PART OF A COMPLETE PERSONAL FALL ARREST SYSTEM WHICHMAINTAINS A SAFETY FACTOR OF AT LEAST TWO.·UNDER THE SUPERVISION OF A QUALIFIED PERSONADDITIONAL INFORMATION·29 CFR 1926 SUBPART M, FALL PROTECTION. OSHA STANDARD.·1926.502, FALL PROTECTION SYSTEMS CRITERIA AND PRACTICES···1926.502(D)(15)ALLOWABLE/DESIGN PRESSUREPSFDOWN PRESSURE75UPLIFT PRESSURE, 2 RAILS55HANWHA: Q. PEAKDUO ML-G10+ (395W)MODULESFOR BOTH ROOF:
85'-0"56'-4"96'-5"43'-11"15'-3"UMINVACDMDP17'-4"21'-8"16'-3"1'-5"JBREVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEA-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952ROOF PLANA-01SCALE: 1/8" = 1'-0"1ROOF PLAN WITH FIRE SETBACKSAND PROPERTY LINESROOF #1(06) HANWHA: Q. PEAK DUOML-G10+ (395W) MODULES(N) (21) SOLAREDGEPOWER P401 OPTIMIZERSROOF #2(15) HANWHA: Q. PEAK DUOML-G10+ (395W) MODULESFIRE ACCESS AND PATHWAYSAS PER NFPA 1,11.12.2- FIRE SETBACK - 3 FT- ZONING SETBACK - 2 FT3'-0" FIRE SETBACK1'-6" FIRE SETBACK1'-6" FIRE SETBACK1'-6" FIRE SETBACK1'-6" FIRE SETBACK1'-6" FIRE SETBACK1'-6" FIRE SETBACK 1-STORYHOUSE(N) JUNCTION BOX(N) (01) SOLAREDGE TECHNOLOGY:SE7600H-US INVERTER(E) SERVICE POINT ANDUTILITY METERING(E) MAIN SERVICE DISCONNECT/MAIN DISTRIBUTION PANEL(N) ALTERNATIVE POWER SOURCEAC DISCONNECT/RAPID SHUTDOWNJUAREZ LN,ALL MODULES TO BE INSTALLED AT LEAST 2FT AWAY FROM ALL THE ROOF EDGESEXISTINGDRIVEWAY3/4" EMT OR EQUIVALENTCONDUIT RUN
36'-6"58'-6"4'-0"TYP.REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952MODULE LAYOUTS-01SCALE: 1/8" = 1'-0"1(E) BACK YARD
MODULE LAYOUTGENERAL INSTALLATION PLAN NOTES:1) ROOF ATTACHMENTS TO SYP TRUSSES SHALL BE INSTALLED ASSHOWN IN SHEET S-02 AND AS FOLLOWS FOR EACH WIND ZONE:WINDZONESNON - EXPOSED MODULESEDGE / EXPOSED MODULESSPANCANTILEVERSPANCANTILEVERZONE 12' - 0"0' - 8"2' - 0"0' - 8"ZONE 1'XXXXZONE 2e2' - 0"0' - 8"N/AN/AZONE 2nXXXXZONE 2r2' - 0"0' - 8"2' - 0"0' - 8"ZONE 3e2' - 0"0' - 8"N/AN/AZONE 3rXXXXMODULE TYPE, DIMENSIONS & WEIGHTNUMBER OF MODULES = 21 MODULESMODULE TYPE = HANWHA: Q. PEAK DUO ML-G10+ (395W) MODULESMODULE WEIGHT = 42.99 LBS / 19.5 KG.MODULE DIMENSIONS = 74"x 41.1" = 21.12 SFUNIT WEIGHT OF ARRAY = 2.04 PSFARRAY AREA & ROOF AREA CALC'SROOFROOF TYPEARRAYAREA(sq.Ft.)ROOFAREA(Sq. Ft.)ROOFAREACOVEREDBY ARRAY(%)TILTAZIMUTHTRUSSSIZETRUSSSPACING#1ASPHALT SHINGLE316.81333.0695.1218.4°270°2"X4"24" o.c.#2ASPHALT SHINGLE126.73734.5617.2518.4°180°2"X4"24" o.c.SEE SHEET S-02.1 FOR SUPPORTING CALCULATIONS.2) EXISTING RESIDENTIAL BUILDING IS AN ASPHALT SHINGLEROOF WITH MEAN ROOF HEIGHT OF 15 FT AND SYP 2"X4" ROOFTRUSSES SPACED 24" O.C. EXISTING ROOF SLOPE FOR SOLARSYSTEM RETROFIT IS 18.4 DEGREES. CONTRACTOR TO FIELDVERIFY AND SHALL REPORT TO THE ENGINEER IF ANYDISCREPANCIES EXIST BETWEEN PLANS AND IN FIELDCONDITIONS.3) FIRE SETBACK TO BE 3' FROM RIDGES AND EDGES, AND 18" EACHWAY FROM HIPS AND VALLEYS PER NFPA 1,11.12.24) THE EXISTING ROOF AND STRUCTURE WILL NOT BE ADVERSLYAFFECTED BY THE ADDITIONAL LOADS IMPOSED BY THE SOLARSYSTEM.* I CERTIFY THAT THE INSTALLATION OF THE MODULES IS INCOMPLIANCE WITH FBC: RESIDENTIAL 2020 7TH ED., CHAPTER 3.BUILDING STRUCTURE WILL SAFELY ACCOMMODATE WIND LATERALAND UPLIFT FORCES AND EQUIPMENT DEAD LOADS. *ROOF #1TILT - 18.4°AZIM. - 270°LEGEND- WIND ZONE 1 (TYP)- WIND ZONE 2e (TYP)- WIND ZONE 2n (TYP)- WIND ZONE 2r (TYP)- WIND ZONE 3r (TYP)- WIND ZONE 3e (TYP)ROOF #1(06) HANWHA: Q. PEAK DUOML-G10+ (395W) MODULES(N) (21) SOLAREDGEPOWER P401 OPTIMIZERSROOF #2(15) HANWHA: Q. PEAK DUO ML-G10+(395W) MODULESROOF #2TILT - 18.4°AZIM. - 180°(E) FRONT YARD
(84) PV ROOF ATTACHMENT@ 24" O.C. MAX.(SEE SHEET S-02 FORATTACHMENT DETAIL)(SEE SHEET S-01.1 FOR PARTIALPRESSURE OF THE MODULE)
4'-0"TYP.7'-2"7'-0"6'-9"6'-11"6'-8"4'-7"6'-7"6'-11"6'-10"P7P1P2P3P4P5P6P8P9P10P11P12P13REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-01.1CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952PARTIAL PRESSURE AND MODULES EXPOSURES-01.1SCALE: 1/8" = 1'-0"1ARTIAL RESSURE ANDMODULES EXOSURELEGEND- NON- EXPOSED MODULE- MIN. MODULE EDGE DISTANCE LINE- EDGE MODULE- MODULE EXPOSURE LINE- EXPOSED MODULE- WIND ZONE 1 (TYP)- WIND ZONE 2e (TYP)- WIND ZONE 2n (TYP)- WIND ZONE 2r (TYP)- WIND ZONE 3r (TYP)- WIND ZONE 3e (TYP)NOTE : PARTIAL PRESSURES OF THE WIND ZONES ONALL MODULES HAVE BEEN VERIFIED AND ARE WITHINTHE ALLOWABLE PER THE MANUFACTURERSPECIFICATION, INSTALLER SHOULD FOLLOW THELAYOUT TO AVOID HIGHER ZONAL PARTIALPRESSURES. ANY CHANGES IN LAYOUT SHOULD BEREPORTED BACK TO THE ENGINEER OF RECORD.2h2DISTANCE : 0' - 8"0.5hDISTANCE : 7' - 6"- MISSING MODULEALLOWABLE MODULE UPLIFT PRESSURE 2 RAILS: 55 PSF2h20.5hROOF #1(06) HANWHA: Q. PEAK DUOML-G10+ (395W) MODULESROOF #2(15) HANWHA: Q. PEAK DUO ML-G10+(395W) MODULESFOR NON-EXPOSED MODULES(E) FRONT YARD
(E) BACK YARD
4"REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952ATTACHMENT DETAIL2ATTACHMENT DETAIL (ENLARGED SECTION VIEW)S-02SCALE: 6" = 1'-0"h2PV MODULESEE (2/S-02) FORENLARGED VIEW(E) ROOF SHEATHING2"x4" TRUSSES @ 24" OCATTACHMENT DETAILS-02SCALE: 1" = 1'-0"1(E) ASPHALT SHINGLE ROOFGROUNDING MID/END CLAMPPV MODULEK2 SPLICE FOOT X2"x4" TRUSSES @ 24" OCK2 FLEXFLASH BUTYLT-BOLT & HEX NUT SETM5 X 60 LAG SCREWSAT EACH ATTACHMENT POINTINTO EXISTING FRAMING(2"X4") TRUSS SPANNERS FORMISSED TRUSS ATTACHMENT(IF REQUIRED)K2 CROSSRAIL 48-XL - RAIL
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMES-02.1CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952STRUCTURECALCULATION
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952ELECTRICALLINE DIAGRAM1ELECTRICAL LINE DIAGRAME-01SCALE: NTSG=GGG~GGNL2L1L1L2NGNL2L1G-+G-+G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-(N) JUNCTION BOX600 V, NEMA 3RUL LISTED-+-+G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-G+-+-+-SOLAR ARRAY (8.295 kW-DC STC)(21) HANWHA: Q. PEAK DUO ML-G10+ (395W) MODULES(01) STRING OF 11 MODULES CONNECTED TO MPPT #1(01) STRING OF 10 MODULES CONNECTED TO MPPT #2(N) INVERTER:SOLAREDGE TECHNOLOGY: SE7600H-USOUTPUT: 240 VAC, 32A99% CEC WEIGHTED EFFICIENCYNEMA 3R, UL LISTED, INTERNAL GFDIWITH INTEGRATED DC DISCONNECTG+-+-+-(2) #10 AWG USE-2/PV WIRE + RED(2) #10 AWG USE-2/PV WIRE - BLACK#6 BARE CU WIRE PROTECTED PER NEC 250.64(B)INTERCONNECTION120% RULE - NEC 705.12(B)(2)(3)(b)UTILITY FEED + SOLAR BACKFEED150A + 40A = 190ABUSS RATING x 120%200A x 120% = 240APV MODULEGROUNDING SYSTEMSOLAREDGE POWER OPTIMIZER P401NOTE:1. SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THEREQUIREMENTS OF THE NEC 2017, AND THOSE SET FORTH BY THEFLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDINGMAXIMUM NUMBER OF MODULE STRINGS, MAXIMUM NUMBER OFMODULES PER STRING, MAXIMUM OUTPUT, MODULEMANUFACTURER AND MODEL NUMBER, INVERTER MANUFACTURERAND MODEL NUMBER, AS APPLICABLE.2. THE PV BACKFED BREAKER IS AT THE END OF THE BUSBAR ANDTHERE IS NO LUG FED SUB PANEL.TO UTILITY GRID(E) MAIN SERVICE DISCONNECT/MAIN DISTRIBUTION PANEL,200A RATED, 240VEXISTING GROUNDINGELECTRODE SYSTEML2L1L2L1GL2L1L2L1L2L1L2L1L1L2NL1L2NN(E) MAIN BREAKER150A/2P,240V.L2L1NGL2L1NGBI-DIRECTIONALSERVICE POINT AND UTILITYMETERING1-PHASE, 240VL1L2N40A/2P(N) ALTERNATIVE POWERSOURCE AC DISCONNECT/RAPID SHUTDOWN: 240V, 60AMP RATED,NEMA 3R, UL LISTEDLOCKABLE & NON FUSIBLE(2) #10 AWG THWN-2 + RED(2) #10 AWG THWN-2 - BLACKEGC #10 AWG THWN-2IN 3/4" EMT OR EQUIVALENTCONDUIT RUNUSE METAL RACEWAYS FOR ANY DCCIRCUITS ENTERING BUILDING PRIOR TOINVERTER DC DISCONNECTING MEANSPER NEC 690.31(3) #8 AWG THWN-2(1) #10 AWG THWN-2 GNDIN 3/4", EMT OR EQUIVALENT,CONDUIT RUN
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952WIRING CALCULATIONSNUMBER OF CURRENTCARRYING CONDUCTORS INEMT4-67-910-20PERCENT OFVALUES.80.70.50INVERTER SPECIFICATIONSMANUFACTURER / MODEL #SOLAREDGE TECHNOLOGY SE7600H-USNOMINAL AC POWER7.6KWNOMINAL OUTPUT VOLTAGE240 VACNOMINAL OUTPUT CURRENT32AI ERMOCRATES CASTILLO PE# 52590 AN ENGINEERLICENSED PURSUANT TO CHAPTER 471, CERTIFYTHAT THE PV ELECTRICAL SYSTEM AND ELECTRICALCOMPONENTS ARE DESIGNED AND APPROVED USINGTHE STANDARDS CONTAINED IN THE MOST RECENTVERSION OF THE FLORIDA BUILDING CODE. FBC 107,THE NEC 2017, AND THOSE SET FORTH BY THEFLORIDA SOLAR ENERGY CENTER CERTIFICATION.DC PHOTOVOLTAIC POWER SOURCE TO BE INSTALLEDAT INVERTER PER NEC 690.53 & 690.54OPERATING CURRENTOPERATING VOLTAGE400V15AMAX INPUT CURRENT OF INVETERMAXIMUM SYSTEM VOLTAGE20A480V1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION.2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. THE TERMINALS ARE RATED FOR 75 DEGREES C.3.) THE WIRES ARE SIZED ACCORDING TO NEC 110.14 .4.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.5.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.6.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS.7.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.8.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.9.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION.10.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.11.) UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE.12.) MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.13.) RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.14.) CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE 310.10 (D).15.) CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).16.) ALL CONDUITS TO BE INSTALLED A MIN OF 7/8" ABOVE THE ROOF SURFACE.DC CONDUCTOR AMPACITY CALCULATIONS:ARRAY TO INVERTEREXPECTED WIRE TEMP (In Celsius)33°TEMP. CORRECTION PER TABLE 310.15(B)(2)(a)0.96NO. OF CURRENT CARRYING CONDUCTORS4CONDUIT FILL CORRECTION PER NEC TABLE 310.15(B)(3)(a)0.80CIRCUIT CONDUCTOR SIZE10 AWGCIRCUIT CONDUCTOR AMPACITY40AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B)18.751.25 X OUTPUT OF OPTIMIZERDERATED AMPACITY OF CIRCUIT CONDUCTOR30.72ATEMP. CORRECTION PER TABLE 310.15(B)(2)(a) XCONDUIT FILL CORRECTION PER NEC TABLE 310.15(B)(3)(a) X CIRCUITCONDUCTOR AMPACITYResult should be greater than (18.75A) otherwise increase the size of the conductor and itsampacityAC CONDUCTOR AMPACITY CALCULATIONSINVERTER TO MAIN SERVICE PANELNo. OF INVERTER1EXPECTED WIRE TEMP (In Celsius)33°TEMP. CORRECTION PER TABLE 310.15(B)(2)(a)0.96NO. OF CURRENT CARRYING CONDUCTORS3CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a)1CIRCUIT CONDUCTOR SIZE8AWGCIRCUIT CONDUCTOR AMPACITY55AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B)40A1.25 X MAX INVERTER OUTPUT CURRENTDERATED AMPACITY OF CIRCUIT CONDUCTOR52.8ATEMP. CORRECTION PER TABLE 310.15(B)(2)(a) XCONDUIT FILL CORRECTION PER NEC TABLE 310.15(B)(3)(a) X CIRCUITCONDUCTOR AMPACITYResult should be greater than (40A) otherwise increase the size of the conductor and itsampacitySOLAR MODULE SPECIFICATIONSMANUFACTURER / MODEL #HANWHA Q. PEAK DUO ML-G10+(395W) MODULEVMP36.88IMP10.71VOC45.27ISC11.10MODULE DIMENSION74"L x 41.1"W x 1.25"D (In Inch)
UMINVACDMDPREVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEE-03CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952SYSTEM LABELINGLABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC690.54)WARNINGELECTRIC SHOCK HAZARDLABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.13(B))TERMINALS ON BOTH LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONPHOTOVOLTAIC SYSTEM AC DISCONNECTRATED AC OPERATING CURRENT 32 AMPSAC NOMINAL OPERATING VOLTAGE 240 VOLTS! WARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVOLTAIC SYSTEMLABEL LOCATION:POINT OF INTERCONNECTION(PER CODE: NEC 705.12(B)(2)(3)(b))!LABEL LOCATION:DC DISCONNECT, INVERTER(PER CODE: NEC690.53)INVERTERRAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL LOCATION:AC DISCONNECT(PER CODE: NEC690.56(C)(3))AVA2015480MAXIMUM SYSTEM VOLTAGE(VOC)MAXIMUM CIRCUIT CURRENT(Isc)MAXIMUM RATED OUTPUT OFDC TO DC CONVERTER (Idc)WARNINGIN CASE OF EMERGENCY, CONTACT:TITAN SOLARPH. NO.: (855) 729-7652TURN RAPID SHUTDOWNSWITCH TO THE "OFF" POSITION TOSHUT DOWN PV SYSTEMAND REDUCESHOCK HAZARDIN THE ARRAYSOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRICPV PANELSCAUTION!LABEL LOCATION:MAIN SERVICE DISCONNECT / MAIN DISTRIBUTION PANEL, PV DISCONNECTLOCATED NO MORE THAN 3FT (1M) FROM THE SERVICE DISCONNECT(TEXT HEIGHT SHOULD BE A MINIMUM OF 3/8")(PER CODE: NEC 690.56(B), NEC 705.10, NFPA 1, 11.12.2.1)2 SOUTHEAST JUAREZ LANE, PORT ST. LUCIE, FL 34952POWER TO THIS BUILDINGSUPPLIED FROM MULTIPLE SOURCES EMERGENCY RESPONDER:THIS SOLAR PV SYSTEM IS EQUIPPEDWITH RAPID SHUTDOWN.TURN RAPID SHUTDOWN SWITCH TO THE ''OFF''POSITION TO SHUTDOWN ENTIRE PV SYSTEMSERVICE POINT ANDUTILITY METERINGMAIN SERVICE DISCONNECT/MAIN DISTRIBUTION PANELALTERNATIVE POWER SOURCE ACDISCONNECT/ RAPID SHUTDOWNINVERTERPV SOLAR ARRAYON ROOFWARNING:POWER SOURCE OUTPUT CONNECTION DONOT RELOCATE THIS OVERCURRENT DEVICELABEL LOCATION:POINT OF INTERCONNECTION(PER CODE: NEC 705.12(B)(2)(3)(b))LABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION(PER CODE: NEC 690.56(C)(1)(a), IFC 1204.5.1!!LABEL LOCATION:MAIN DISCONNECT(PER CODE: NFPA - 1, 11.12.2.1.5)ADHESIVE FASTENED SIGNS:· THE LABEL SHALL BE VISIBLE, REFLECTIVE AND SUITABLE FORTHE ENVIRONMENT WHERE IT IS INSTALLED [NFPA 1, 11.12.2.1]· WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].· ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT [IFC 605.11.1.3]
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-01CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-02CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-03CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-04CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-05CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952DATA SHEET
REVSHEET NAMESHEET SIZESHEET NUMBERRIZZO RESIDENCE PROJECT INSTALLERSignature with SealANSI B11" X 17"DATEDESCRIPTIONREVISIONSPROJECT NAMEDS-06CASTILLO ENGINEERINGSERVICES, LLCCOA # 28345620 N. WYMORE ROAD,SUITE 250,MAITLAND, FL 32751TEL: (407) 289-2575ERMOCRATES E. CASTILLO - FL PE 52590COPYRIGHTED BYCASTILLO ENGINEERINGSERVICES, LLC2 SOUTHEAST JUAREZ LANE,
PORT ST. LUCIE, FL 34952DATA SHEET