In-Place Density Test Report
Client:OASIS POOLS, LLC UES Technician:Mark Rogers
PO Box 650256
Vero Beach, FL 32965
Date Tested:03/22/2022
Project:Oasis Pools LLC
Various Locations, , TBD County, FL
Type of Test:
Area Tested:10527 Oakbridge Court, Ft. Pierce Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Final Grade
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northeast corner of pool 0-1 ft 114.2 11.2 111.5 10.5 98 Pass
2 Northwest corner of pool 0-1 ft 114.2 11.2 112.2 10.6 98 Pass
3 Southwest corner of pool 0-1 ft 114.2 11.2 111.6 10.9 98 Pass
4 Southeast corner of pool 0-1 ft 114.2 11.2 110.7 10.3 97 Pass
5 Northside of pool 0-1 ft 114.2 11.2 112.1 10.4 98 Pass
Remarks:SW corner 1-2', 2-3', 3-4', 4-5', 5-6' HCP=60+, > 95% Compaction, PASS. HCP tests are empirically correlated to the
relative density of the soil.
Permit: 21-10481
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Alex Albandoz, P.E.
STATE OF FLORIDA
Professional Engineer No. 92555
This item has been digitally signed and sealed by Alex Albandoz,
P.E. on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.