In-Place Density Test Report
Client:GHO HOMES CORPORATION UES Technician:Mark Rogers
590 NW Mercantile Place
Port St. Lucie, FL 34986
Date Tested:03/24/2022
Project:GHO SCATTERED LOTS
Various Locations, , TBD County, FL
Type of Test:
Area Tested:9412 Meadowood Drive, PSL - House
Pad
Field:ASTM D-6938 Nuclear Gauge Method
Material:Backfill Laboratory:ASTM D1557 Modified Proctor
Reference Datum:0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Test
No.Location of Test Range
Maximum
Density
(pcf)
Optimum
Moisture
(%)
Field Dry
Density
(pcf)
Field
Moisture
(%)
Soil
Compaction
(%)
Pass
or
Fail
1 Northeast corner of pad 0-1 ft 121.2 10.2 119.2 9.8 98 Pass
2 Southwest corner of pad 0-1 ft 121.2 10.2 118.9 10.2 98 Pass
3 Center of pad 0-1 ft 121.2 10.2 118.1 10.3 97 Pass
Remarks:Permit: 21100776
Reviewed By
GFA International, Inc
FBPE Registry No.4930
Alex Albandoz, P.E.
STATE OF FLORIDA
Professional Engineer No. 92555
This item has been digitally signed and sealed by Alex Albandoz,
P.E. on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the signature
must be verified on any electronic copies.