.11i1�i'�li'61NEERING 1���1F�C..
PROFESSIONAL STRUCTURAL CONSULTANTS
850 NW Federal Hwy, Suite 172, Stuart, FL 34994
Voice: (772)223-9883
Cell: (772)215-4080
March 10, 2022
Mr. Bill LaPrade
c/o The Glass Professionals
3570 SE Dixie Hwy
Stuart, FL 34997
Re: Window Replacement - Nivarro Residence, 9940S. Ocean Dr., Unit # 508, Jensen
Beach, FL 34957
Dear Mr.LaPrade;
I have reviewed the required wind load requirements for the replacement window at the above
referenced location. I have prepared the following report for your use.
The replacement window is PGT SH5000 (Single Hung 5500) with NOA No. 20-0401.03. The
provided allowable design pressures are +70 psf and -I 10 psf.
The window has a masonry opening of 37.75" x 50.625" or 1,911.1 sq. inches or 13.3 square
feet. The applied required design pressures for a 10 square foot (conservative) opening (per the
attached Wind Load Calculator) are hi -lighted in the table. The required applied design
pressures are +/- 59.1 psf.
This window is more than adequate to withstand the expected pressures and meets or exceeds the
requirements of the 2020 Florida Building Code (FBQ 6"' Edition and ASCE 7-16. If you
have any questions or concerns, or if I can be of any future service, please do not hesitate to
contact me.
Respectfully submitted,
(51� �M-
T. Stiles Peet. P.E., S.E.
ES AFDigitally signed
C'%
``�5•� by Timothy
* No. aszoo ':* : Stiles Peet
_ * �= Date:
��•• STATE OF
I'Z0R\'QP.'��` 2022.03.10
i'FSS'O'NA;E?G�� 10:44:49-05'00'
P:\2022\22-019 GLASSPRO GENERAL (20-061)\22-019.01 NIVARRO\22-019.01 9940 S. OCEAN DR WINDOW CERT.doc
3110/22, 9:36 AM
CADDtools Design Pressure results
ASCE 7-16 Wind load Program (30.5 Part 3: Building Wall Components and Cladding)
Wall Components and Cladding (Mean Roof Height h > 6o ft)
Project: NAVARRO
Prepared by: TSP of SEG, INC.
E-mail:
Input:
ASCE 7-16 Strength Design Load & Allowable Stress Design
Wind Speed = 165 mph
Building Exposure = D (Flat Unobstructed areas)
Internal Pressure Coefficient GCpi = 0.18 Enclosed Building
Kzt = 1.00
Kd = 0.85
Ke=1.00
Mean Roof Height =150 ft
Output:
Velocity Pressure Exposure Coefficient "Kz max." = 1.54
Per Table 26.10-1, page 268
LRFD uses wind speed Vult = 165 mph
Velocity Pressure (qh LRFD) = 91.23 psf = .00256*Kz*Kzt*Kd*Ke *VA 2 lb/ft^2
Per eQ.30.3-1, page 335
ASD uses wind speed Vasd1= 128 mph
Velocity Pressure (qh ASD) = 54.74 psf = .002 Kz*Kzt Kd*Ke *VA 2*o.61b/ft^2
LRFD (Load Resists ce
ASD (Allowable Stress
(Design)
Per Figure 30.6-1, Page
Factor Design)
8
TributaryCoefficients
Area
Positive
Zone
4& 5
Negative
Center
Zone 4
Ne ativ
Cor er
Zo e 5
Positive
Zone
4& 5
Negative
Center
Zone 4
Negativ
Co
e 5
External Pressure
Positiv Negative Negativ
Sq Feet
psf
psf
f
psf
psf
p f
GCp Center Corner
10 ft2
98.5
-98.5
-180.
59.i
-59.1
- 8.4
0.90 -0.90 -1.80
20 ft2
98.5
-98.5
-180.6
9.1
-59.i
o8.4
0.90 -0.90 -1.80
5o tt�
90•7
-93.3L
-159.9 111
•4
-95.9 10.81
-0.84 -1.57
100a
84.8
-89.4
-144.1
50.9
-53.6
-86.5 0.75 -0.80 -1.40
20o ft2
79•0
-85.5
-128.4
47.4
-51.3
-77.1 0.69 -0.76 -1.23
50o ft2
71.2
-80.3
-io7.7
42.7
-48.2
-64.6 0.60 -0.70 -i.00
Least Width = 85 ft a = 8.5 ft (Zone 5)
lo% of least width but not less than 3 ft.
Presented by CADDtools.com
hftps://caddtools.com/CTcalculatel6.php 1/2