HomeMy WebLinkAboutAPPROVED, Generac 50 amp Smart Managemnet ModuleSmart Management
Modules (SMM)
GENERAL"
GENERAC�"- ACCESSORIES
Model 006873-0
C &us
LISTED
DESCRIPTION
Generacs Smart Powe• Management System is designed to optimize the performance of a standby generator. The system can consist of up to 8 individual
Smart Management Modules (SMM). Unlike other load management systems that depend on another control device, the SMM modules are actually self -
aware and operate autonomously.
Frequency is the true measure of generator engine performance and does not need to factor in increased ambient temperatures, elevation changes or
generator fuel type. The modules monitor the frequency (Hz) of the power being produced by Generac's standby generators and if t falls below a certain
threshold, the module will automatically follow a power management algorithm to ensure that the generator is not overloaded.
The modules can be set to a load priority between 1-8 or be set in a lock out only mode for loads that just simply do not need to run in an outage, therefore
reducing the necessary size of the generator for a more cost effective solution.
SMM SPECIFICATIONS
GENERAC
Smart Management Modules (SMM)
W1
Model
006873-0
_---
Height (in/mm)
Ht
6.17/156.8
H2
2.36/60
Width (in/mm)
Wt
7.06/179.4
W2
4.72/120
Depth (in/MT)
3.7/94
Weight (lbs/kilos)
2.06/0-94
Shipping Weight (lbs/kilos)
2.44/1.11
UPC Code
696471068733
H1
SMM Controls (located behind the cover of the module)
Dimensions and UPC
I
LED ON = LOAD CONNECTED
LED FLASH 1S = LOAD SHED
PRIORITY
LOCKOUT
LOAD ON
LED FLASH 3S = 30 MIN LOCKOUT
b
GENERATOR
LED FLASH 6S = GEN LOAD LOCKOUT
3 7
.-
LED OFF = NO MODULE POWER
O
®
O
O
TEST
d
LOCKOUT
DISABLED
Priority Dial (A) — Se's module priority.
Lockout Switcn (B) — Prevents 'oad from operating when system is operating under generator power.
Test Button (C) — Disaoles contactor output for a specified time.
LED (0) — Provides .module status with easy viewing through the external viewing window
located in the upper right comer of the module.
Generac Power Systems. Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com