HomeMy WebLinkAboutAPPROVED, Theresa Polhemus_03-12-2022_PLANSET (1)VICINITY MAPSITE MAP (N.T.S)A-00SITE MAP &VICINITY MAPTHERESA POLHEMUSNEW GRID-INTERACTIVE PHOTOVOLTAIC SYSTEM WITH BATTERY STORAGE SYSTEMDC SYSTEM SIZE (14.52KW)33°C0°C0 PSF170MPH (ASCE 7-16)IIDWIND FLOW MAPSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029GOVERNING CODESFLORIDA RESIDENTIAL CODE, 7TH EDITION 2020 (FRC)FLORIDA BUILDING CODE, 7TH EDITION 2020 (FBC)FLORIDA FIRE PREVENTION CODE, 7TH EDITION 2020 (FFPC)FLORIDA EXISTING BUILDING CODE, 7TH EDITION 2020 (FBC EX)SITE MAP & VICINITY MAPA - 00A - 01S - 01ELECTRICAL LINE DIAGRAMWIRING CALCULATIONSSYSTEM LABELINGMODULE DATASHEETE - 01E - 02E - 03STRUCTURAL ATTACHMENT DETAILINVERTER DATASHEETCOMBINER DATASHEETDS - 01DS - 02DS - 03DS - 06S - 02SHEET INDEXSHEET NO.SHEET NAMEROOF PLAN & MODULESARRAY LAYOUTSITE DETAILSASHRAE EXTREME LOWASHRAE 2% HIGHGROUND SNOW LOADWIND SPEEDRISK CATEGORYWIND EXPOSURE CATEGORYRACKING DATASHEETATTACHMENT DATASHEET13.86 KWSYSTEM SIZE :14.52 KW DC STC57.64 A(44) ENPHASE IQ7X-96-2-US MICROINVERTERSDC RATING OF SYSTEMAC RATING OF SYSTEMAC OUTPUT CURRENTNO. OF MODULESNO. OF INVERTERSARRAY STRINGINGDESCRIPTIONNEW GRID-INTERACTIVE PHOTOVOLTAICSYSTEM WITH BATTERY STORAGESYSTEM DETAILS(44) PANASONIC VBHN330SA17 330W SOLARMODULES(1) BRANCH OF 11 MODULESDS - 07(2) BRANCHES OF 12 MODULESNATIONAL ELECTRIC CODE, NEC 2017 CODE BOOK, NFPA 70FPLUTILITYNO. OF BATTERY(2) ENPHASE ENCHARGE-10-1P-NA(1) BRANCH OF 9 MODULESBATTERY DATASHEETSMART SWITCH DATASHEETDS - 04DS - 05MSSPOHIO STS INDIAN RIVER DR187'-2"64'-10"220'-2"75'-4"24'-6"83'-9"3'-7"
17'ROOF 1ROOF 2ROOF 3ROOF 4ROOF 5DRIVEWAY
PV ARRAY18" SETBACK3' SETBACK(E) METER MAIN COMBO(OUTSIDE HOUSE)(E) SUB SERVICE PANEL(CRITACAL LOAD PANEL)(INSIDE HOUSE)This item has been electronically signed and sealed by Vincent Mwumvaneza using a Digital Signature and Date.Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Exp:02/28/2023 STRUCTURAL ONLY
A-01 & MODULESROOF PLANMODULE TYPE, DIMENSIONS & WEIGHTSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029I CERTIFY THAT THE INSTALLATION OF THE MODULES IS INCOMPLIANCE WITH FBC: RESIDENTIAL CHAPTER 3.BUILDINGSTRUCTURE WILL SAFELY ACCOMMODATE LATERAL AND UPLIFTWIND LOADS, AND EQUIPMENT DEAD LOADS. *GENERAL INSTALLATION PLAN NOTES:1) ROOF ATTACHMENTS TO METAL SEAMS SHALL BE INSTALLEDAS SHOWN IN SHEET S-01 AND AS FOLLOWS FOR EACH WINDZONE:.WIND ZONE 1: MAX SPAN 4'-0" O.C.WIND ZONE 2: MAX SPAN 4'-0" O.C.WIND ZONE 3: MAX SPAN 2'-0" O.C.2) EXISTING RESIDENTIAL BUILDING METAL 26 GAUGE ROOFWITH MEAN ROOF HEIGHT 15 FT AND METAL SEAMS SPACED AT11" O.C.CONTRACTOR TO FIELD VERIFY AND SHALL REPORT TO THEENGINEER IF ANY DISCREPANCIES EXIST BETWEEN PLANSAND IN FIELD CONDITIONS.LEGENDSUMACDPMMSP- UTILITY METERJB- AC DISCONNECT- PRODUCTION METER- MAIN SERVICE PANEL- VENT, ATTIC FAN (ROOF OBSTRUCTION)- JUNCTION BOXINV- INVERTER- CONDUIT- STRING TAG- FIRE SETBACKNUMBER OF MODULES = 44 MODULESMODULE TYPE = PANASONIC VBHN330SA17 330W SOLAR MODULESWEIGHT = 40.81 LBS / 18.5 KG.MODULE DIMENSIONS = 62.6" X 41.5" = 18.04 SFNUMBER OF INVERTER = 44 MICROINVERTERSINVERTER TYPE = ENPHASE IQ7X-96-2-US MICROINVERTERSDC SYSTEM SIZE: 14.52 KWAC SYSTEM SIZE: 13.86 KWNOTES:1. LOCATION OF JUNCTION BOX(ES), ACDISCONNECTS(S), AC COMBINER PANEL(S),AND OTHER ELECTRICAL EQUIPMENT(S)RELEVANT TO PV INSTALLATION SUBJECT TOCHANGE BASED ON SITE CONDITIONS.2. SETBACKS AT RIDGES CAN BE REDUCED TO18 INCHES IN COMPLIANCE WITH FBC R 324.6.2:TOTAL PLAN VIEW AREA = 2905 SQFTTOTAL PV AREA = 44(62.6 IN)(41.5 IN)/(144 IN^2) = 793.8 SQFT( 793.8 SQFT/ 2905 SQFT)100 = 27.33 %TOTAL PV AREA POPULATES 27.33 % OF TOTALPLAN VIEW AREA AND IS WITHIN THE 33%REQUIREMENT.M- METER MAIN COMBO1- MODULE STRING2- MODULE STRING3- MODULE STRING4- MODULE STRING1BI- BACKUP INTERFERNCEBAT- BATTERYCP- COMBINER PANELSWH- SMART WATER HEATERUSD- UTILITY SERVICE DISCONNECTSS- SMART SWITCHSSP- SUB SERVICE PANELROOF 1ROOF 3ROOF 4ROOF 5PV ARRAY18" SETBACK3' SETBACKMSSPSSBATT(N) ENPHASE SMARTSWITCH(N) 2-ENCHARGE-10 BATTERYBATT(E) METER MAIN COMBO(OUTSIDE HOUSE)(E) SUB SERVICE PANEL(CRITACAL LOAD PANEL) (INSIDEHOUSE)(E) FRONT YARD(E) BACK YARDCPACD(N) AC DISCONNECT(NON-FUSIBLE)(N) COMBINER PANEL(OUTSIDE HOUSE)JBCONDUIT RUN11111111122222222222233333333333344444444444ROOF ACCESS POINTROOF ACCESS POINTROOF ACCESS POINTROOF 2This item has been electronically signed and sealed by Vincent Mwumvaneza using a Digital Signature and Date.Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Exp:02/28/2023 STRUCTURAL ONLY
S-01ARRAYLAYOUT(ROOF #1)ROOF DESCRIPTION:SHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029MODULES - 9ROOF TILT - 18°ROOF AZIMUTH - 360°SEAM SPACING - @11" O.C.LEGENDS- VENT, ATTIC FAN (ROOF OBSTRUCTION)- PV ROOF ATTACHMENT- RAFTERS / TRUSSES- RAILS- FIRE SETBACKWIND LOAD INFORMATION:THIS SYSTEM HAS BEEN DESIGN TO MEETTHE REQUIREMENTS OF THE 7TH EDITION OFTHE FLORIDA BUILDING CODE AND USED THE FOLLOWING DESIGN PARAMETERS: ULTIMATE WIND SPEED: 170 MPHEXPOSURE CATEGORY: DRISK CATEGORY: IIMEAN ROOF HEIGHT: 15ROOF SLOPE: 7°-20°- WIND ZONE 1- WIND ZONE 1'WIND ZONE 2- WIND ZONE (2)- WIND ZONE (2r)- WIND ZONE (2e)- WIND ZONE (2n)WIND ZONE 3- WIND ZONE (3)- WIND ZONE (3r)- WIND ZONE (3e)- METAL SEAMWIND ZONE 1(ROOF #2)MODULES -24ROOF TILT - 18°ROOF AZIMUTH - 180°SEAM SPACING - @11" O.C.(ROOF #3)MODULES -3ROOF TILT - 18°ROOF AZIMUTH - 90°SEAM SPACING - @11" O.C.(ROOF #4)MODULES -5ROOF TILT - 18°ROOF AZIMUTH - 180°SEAM SPACING - @11" O.C.(ROOF #5)MODULES -3ROOF TILT - 18°ROOF AZIMUTH - 270°SEAM SPACING - @11" O.C.SEAM LOCATIONS ARE APPROXIMATE.ACTUAL LOCATIONS MAY DIFFER ANDCONTRACTOR MAY NEED TO ADJUST MOUNTLOCATIONS. IN NO CASE SHALL THE MOUNTSPACING EXCEED "MAX. MOUNT SPACING"25'-7"3'-11"13'-6"4'-2"27'-2"23'-6"28'-7"23'-6"28'-10"17'-5"16'-11"24'-11"28'-2"17'-6"4'-4"17'-5"1
6
'
-
1
1
"17'-5"25'SOLAR MODULE18" SETBACK3' SETBACKROOF #1ROOF #2ROOF #3ROOF #4ROOF #521'-7"This item has been electronically signed and sealed by Vincent Mwumvaneza using a Digital Signature and Date.Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Exp:02/28/2023 STRUCTURAL ONLY
PHOTOVOLTAIC MODULE GENERAL NOTES:1. APPLICABLE CODE: 2020 FLORIDA BUILDING CODE 7th ED. & ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES2. BOLT DIAMETER AND EMBEDMENT LENGTHS ARE DESIGNED PER NDS(2012)REQUIREMENTS. ALL BOLT CAPACITIES ARE BASED ON A WOOD ROOF TRUSS AS EMBEDMENT MATERIAL.3. ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLERESIDENTIAL ROOFS, CONSIDERING FROM A 7° TO A MAXIMUM 27° (2/12 TO AMAXIMUM 6/12 PITCH) ROOF IN SCHEDULE. ALL RESIDENTIAL ROOFS SHALL NOTEXCEED 30'-0" MEAN ROOF HEIGHT.4. ROOF SEALANTS SHALL CONFIRM TO ASTM C920 AND ASTM 6511.5. THIS SHEET REFLECTS STRUCTURAL CONNECTIONS ONLY. REFER TOMANUFACTURERS' MANUAL FOR ALL ARCHITECTURAL, MECHANICAL,ELECTRICAL, AND SOLAR SPECS.6. ALL ALUMINUM COMPONENTS SHALL BE ANODIZED ALUMINUM 6105-T5 UNLESSOTHERWISE NOTED.7. LAG BOLTS SHALL BE ASTM A276 STAINLESS STEEL UNLESS OTHERWISE NOTED.8. ALL RAILING AND MODULES SHALL BE INSTALLED PERMANUFACTURERS' INSTRUCTIONS.9. I CERTIFY THAT THE INSTALLATION OF THE MODULES IS IN COMPLIANCEWITH FBC:BUILDING CHAPTER 16 AND FBC:RESIDENTIAL CHAPTER 3.BUILDING STRUCTURE WILL SAFELY ACCOMMODATE CALCULATEDWIND LATERAL AND UPLIFT FORCES, AND EQUIPMENT DEAD LOADS.S-02STRUCTURAL ATTACHMENTDETAILSSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029STRUCTURAL ATTACHMENT DETAILSS-5 PROTEA BRACKETMETAL ROOFS-5 PROTEA BRACKETSOLAR MODULESOLAR MODULEMETAL ROOFIRONRIDGE L-FOOTIRONRIDGE L-FOOTIRONRIDGE XR10IRONRIDGE XR10This item has been electronically signed and sealed by Vincent Mwumvaneza using a Digital Signature and Date.Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. Exp:02/28/2023 STRUCTURAL ONLY
NOTE:1. SUBJECT PV SYSTEMS HAS BEEN DESIGNED TO MEET THEREQUIREMENTS OF THE NEC 2017, NFPA 70 AND THOSE SET FORTH BYTHE FLORIDA SOLAR ENERGY CENTER CERTIFICATION, INCLUDINGMAXIMUM NUMBER OF MODULE STRINGS, MAXIMUM NUMBER OFMODULES PER STRING, MAXIMUM OUTPUT, MODULE MANUFACTURERAND MODEL NUMBER, INVERTER MANUFACTURER AND MODELNUMBER, AS APPLICABLE.2. PROVIDE TAP BOX IN COMPLIANCE WITH 312.8 IF PANEL GUTTERSPACE IS INADEQUATE.E-01ELECTRICALLINE DIAGRAMSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029SOLAR ARRAY (14.52KW-DC STC)(44) PANASONIC VBHN330SA17 330W SOLAR MODULES(2) BRANCHES OF 12 MODULES(1) BRANCH OF 11 MODULES(1) BRANCH OF 9 MODULESL2L1(N) ENPHASE ENCHARGE 10(N) ENPHASE ENPOWERSMART SWITCHL2L1L2L1L1NGL1L2L1L2L1L1 L2 N(E) SUB SERVICE PANEL /CRITICAL LOAD PANEL125A, 240V RATED (INSIDE HOUSE)(3) #4 AWG THWN-2(1) #8 AWG THWN-2 GND IN 1" IMC, RMC, FMC, LFMC,PVC, HDPE, NUCC, RTRC,LFNC, FMT, ENT OR EMTCONDUIT RUN(1) #8 AWG THWN-2 - RED(1) #8 AWG THWN-2 - BLACK(1) #10 AWG THWN-2 GNDIN 3/4" IMC, RMC, FMC, LFMC,PVC, HDPE, NUCC, RTRC,LFNC, FMT, ENT OR EMTCONDUIT RUN(3) # 3 AWG THWN-2(1) #8 AWG THWN-2 GND IN 1-1/4" IMC, RMC, FMC, LFMC,PVC, HDPE, NUCC, RTRC,LFNC, FMT, ENT OR EMTCONDUIT RUNL2L1L2L1NL2L1L1L280A/2P40A/2P125A/2PFORGENERATOR(OPTIONAL)100A/2PL1L2WIRELESSCOMMUNICATIONGL2L1NGL2L1NGNO2NC2G
NO1NC1TO UTILITY GRIDL1 L2 NBI-DIRECTIONALUTILITY METER1-PHASE, 240V(OUTSIDE HOUSE)L1 L2 N(E) MAIN SERVICE PANEL,200A RATED, 240V.(OUTSIDE HOUSE)L2L1L2L1L2L1NGL2L1L2L1L2L1L1 L2 NEXISTING GROUNDING200A/2P(E) MAIN BREAKER200A/2P, 240V(3) #4 AWG THWN-2(1) #8 AWG THWN-2 GND IN 1" IMC, RMC, FMC, LFMC,PVC, HDPE, NUCC, RTRC,LFNC, FMT, ENT OR EMTCONDUIT RUNL2L2FUSEFUSENOTE: ALL LOADS OF EXISTINGSERVICE PANEL & THEIRRESPECTIVE BREAKERSNEEDS TO BE MOVED TOBACKUP ELECTRICAL PANELBEFORE PV INSTALLATION. NONEW LOADS MAY BE PLACEDON THE EXISTING SERVICEPANEL AS IT ISDECOMISSIONED IN THISINTERCONNECTIONARRANGEMENT.(3) # 3 AWG THWN-2(1) #8 AWG THWN-2 GND IN 1-1/4" IMC, RMC, FMC, LFMC,PVC, HDPE, NUCC, RTRC,LFNC, FMT, ENT OR EMTCONDUIT RUN(N)100A/2PL2L1NG15A20A/2PL2L1GN G20A/2PL2L120A/2PL2L120A/2PL2L1(N) 125A ENPHASE IQ COMBINER 3(X-IQ-AM1-240-3) [WITH UPTO (4)2-POLE BREAKERS AND ENVOYCOMMUNICATION GATEWAY](N)JUNCTION BOX600 V, NEMA 3RUL LISTED(4) #10 AWG THWN-2 - RED(4) #10 AWG THWN-2 - BLACK(1) #10 AWG THWN-2 GNDIN 3/4" IMC, RMC, FMC, LFMC,PVC, HDPE, NUCC, RTRC,LFNC, FMT, ENT OR EMTCONDUIT RUNQ CABLESENPHASE IQ7X-96-2-USMICROINVERTERSPV MODULESL2L1(N) ENPHASE ENCHARGE 10GPV SHED(N) AC DISCONNECT:240V, 100AMP, UNFUSEDNEMA 3R, UL LISTED10A/1PMUST BE ACCESSIBLE TOQUALIFIED UTILITYPERSONNEL, BE LOCKABLEAND BE A VISIBLE-BREAKSWITCH
E-02WIRINGCALCULATIONSSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029ELECTRICAL NOTES1. ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, ANDLABELED FOR ITS APPLICATION.2. ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90DEGREE C WET ENVIRONMENT.THE TERMINALS ARE RATED FOR75 DEGREE C.3. CONDUCTOR TERMINATION AND SPLICING AS PER NEC 110.144. WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPSSHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE ASPOSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.5. WORKING CLEARANCES AROUND ALL NEW AND EXISTINGELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.6. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLECODES AND STANDARDS.7. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITSARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEMACCORDINGLY.8. ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELEDAND READILY VISIBLE.9. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULEFRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIPMANUFACTURER'S INSTRUCTION.10. MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPERG.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.11. THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE .12. UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALLPHOTOVOLTAIC SYSTEM COMPONENTS LOCATED AT THE SERVICEENTRANCE.13. MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.14. RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.15. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED ASSUNLIGHT RESISTANT PER NEC ARTICLE 300.6 (C) (1) AND ARTICLE310.10 (D).16. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLEFOR USE IN WET LOCATIONS PER NEC ARTICLE 310.10 (C).ELECTRICAL CALCULATIONS:1.CURRENT CARRYING CONDUCTOR(A)BEFORE IQ COMBINER PANELAMBIENT TEMPERATURE = 33°CCONDUIT INSTALLED AT MINIMUM DISTANCE OF 7/8 INCHES ABOVE ROOF .....NEC 310.15(B)(3)(c)TEMPERATURE DERATE FACTOR - 0.96 ...NEC 310.15(B)(2)(a)GROUPING FACTOR - 0.7...NEC 310.15(B)(3)(a)CONDUCTOR AMPACITY= (INV O/P CURRENT ) x 1.25 / A.T.F / G.F ...NEC 690.8(B)= [(12 x 1.31) x 1.25] / 0.96 / 0.7= 29.24 ASELECTED CONDUCTOR - #10 THWN-2 ...NEC 310.15(B)(16)(B)AFTER IQ COMBINER PANELTEMPERATURE DERATE FACTOR - 0.96GROUPING FACTOR - 1 CONDUCTOR AMPACITY=(TOTAL INV O/P CURRENT) x 1.25 / 0.96 / 1 ...NEC 690.8(B)=[(44x 1.31) x 1.25] /0.96 / 1=75.05 ASELECTED CONDUCTOR - #4 THWN-2 ...NEC 310.15(B)(16)2.PV OVER CURRENT PROTECTION ..NEC 690.9(B)=TOTAL INVERTER O/P CURRENT x 1.25=(44 x 1.31) x 1.25 = 72.05 ASELECTED OCPD = 80ASELECTED EQUIPMENT GROUND CONDUCTOR (EGC) = #8 THWN-2 ... NEC 250.122(A)INVERTER SPECIFICATIONSMANUFACTURERENPHASEMODEL NO. IQ7X-92-2-USMAX DC INPUT VOLTAGE79.5 VMAX OUTPUT POWER315 VANOMINAL AC OUTPUT VOLTAGE240 VNOMINAL AC OUTPUT CURRENT1.31 AMODULE SPECIFICATIONMODEL NO.PANASONICVBHN330SA17 330WPEAK POWER330WRATED VOLTAGE (Vmpp)58 VRATED CURRENT (Impp)5.70 AOPEN CIRCUIT VOLTAGE (Voc)69.7 VSHORT CIRCUIT CURRENT (Isc)6.07 ABATTERY SPECIFICATIONMODEL NO.ENPHASEMODEL NO.ENCHARGE-10CAPACITY58 VMAX. CONT. POWER OUTPUT3.84 KVAMAXIMUM OUTPUT CURRENT16 ANOMINAL OPERATING VOLTAGE240 V
E-03SHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029SYSTEMLABELINGWARNINGELECTRIC SHOCK HAZARD!DO NOT TOUCH TERMINALSTERMINALS ON BOTH LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONPHOTOVOLTAIC SYSTEM AC DISCONNECTRATED AC OPERATING CURRENT 57.64 AMPSAC NOMINAL OPERATING VOLTAGE 240 VOLTSWARNINGNOMINAL OPERATING AC VOLTAGE -NOMINAL OPERATING AC FREQUENCY-MAXIMUM AC POWER-MAXIMUM AC CURRENT-MAXIMUM OVERCURRENT DEVICE RATINGFOR AC MODULE PROTECTION PER CIRCUIT-2403151.3120VVA 60 HzAAINVERTER OUTPUT CONNECTION DO NOTRELOCATE THIS OVERCURRENT DEVICEPHOTOVOLTAIC SYSTEMEQUIPPED WITH RAPIDWARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVOLTAIC SYSTEMWARNING PHOTOVOLTAICPOWER SOURCE!855-335-2469EMERGENCY CONTACTWARNING!INVERTER OUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNING!DEDICATED SOLAR PANELS DONOT CONNECT ANY OTHER LOADSSHUTDOWNSOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWNLABEL LOCATION:AC DISCONNECT, POINT OF INTERCONNECTION, COMBINER PANEL(PER CODE: NEC 690.13(B))LABEL LOCATION:AC DISCONNECT, INVERTER(PER CODE: NEC 690.54)LABEL LOCATION:CONDUIT RUNWAY(PER CODE: NEC690.31(G)(3)(4))LABEL LOCATION:MAIN SERVICE DISCONNECT(NEC 705.12(B)(3-4) & NEC 690.59)ADHESIVE FASTENED SIGNS:·ANSI Z535.4-2011 PRODUCT SAFETY SIGNS AND LABELS, PROVIDESGUIDELINES FOR SUITABLE FONT SIZES, WORDS, COLORS, SYMBOLS, ANDLOCATION REQUIREMENTS FOR LABELS. NEC 110.21(B)(1)·THE LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THEENVIRONMENT INVOLVED. NEC 110.21(B)(3)·ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLYADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT. IFC 605.11.1.3LABEL LOCATION:COMBINER PANEL, AC DISCONNECT(PER CODE: NEC 690.52)LABEL LOCATION:POINT OF INTERCONNECTION, MAIN SERVICE DISCONNECT(PER CODE: NEC 705.12 (B)(2)(c))[Not required if panelboard is rated not less than sum of ampere ratingsof all overcurrent devices supplying it]DATA PER PANELLABEL LOCATION:AC DISCONNECT, DC DISCONNECT, POINT OFINTERCONNECTION(PER CODE: NEC 690.56(C)(3))IFC 605.11.3.1(1) & 690.56(C)(1)(a) Label for PV Systems thatShut down the array and the conductors leaving the arrayLABEL PLACEMENT: BATTERY
DS-01DATASHEETMODULESHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029
DS-02DATASHEETINVERTERSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029
DS-03DATASHEETCOMBINERSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029
DS-04DATASHEETBATTERYSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029
DS-05DATASHEETSMART SWITCHSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029
DS-06DATASHEETRACKINGSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029
DS-07DATASHEETATTACHMENTSHEET NUMBERSHEET NAMEDESCRIPTIONREV
REVISIONS
DATEPERMIT DEVELOPEROPH03/12/2022DESIGNERREVIEWERDATETHERESA POLHEMUS
11001 S INDIAN RIVER DR,
FORT PIERCE, FL 34982
ENGG.ENGINEER OF RECORDPHONE: 855-335-24695344 9TH ST, ZEPHYRHILLS FL 33541LICENSE# EC13010029