HomeMy WebLinkAboutLetter - Attachment To Post Tension SlabWieder inn 11718 SE Federal Hwy.. #373 Hobe Sound, FL 33455 (772) 546-5823 Cell: (772) 618-3437 Fax: (772) 545-3734 E-mail: awieder@wiederengineering.com July 19, 2018 Mark Corson MA Corson & Associates, Inc 1121 SE Ocean Blvd. Stuart, FL 34996 RE: Seiber Residence Regency Island Dunes Condominium Penthouse PH2 & PH3 South Hutchinson Island, FL Subject: Attachment to Post Tension Slab To whom it may concern: The exist structural slab is a post tension slab. Attachment to slab can be made by the use of pins as long as the pin length is 3/4" or less. This allows for fastener penetration that is less than the minimum cover requirements for post tension cables and therefore should not have any conflict. Use of a Hilti PAF - X-ZF 0.138" diameter x 3/4" long pin (or equal) has a allowable tensile capacity of 60 Ibs per pin. Spacing of and number of pins shall be such that the load per pin is maintained at less than the capacity indicated. It is recommended that in all connection locations 2 pins should be used with a minimum spacing of not less than 1 1/2' for redundancy where possible. Wieder Engineering also recommends that ceiling framing be spaced at 16" on center supporting'/2' thick drywall boards. Do not hesitate to contact my office should you have any questions. Wieder `Engineering; Inc. Allen Wieder, PE, SECB FL 43444 E:\WorM5s\Seiber Condo - Mark CorsonTin Attachment to Slab Letter Rev i.wpd