HomeMy WebLinkAboutAPPROVED, ENERGY CALCS & MANUAL J - 270 CAMINO DEL RIOFORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: WYNNE THE WINDSOR IMPACT Builder Name: WYNNE DEVELOPMENT Street: THE WINDSOR Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: Owner: Jurisdiction: Design Location: Ft_, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. Wall Type41432.0 sgft.) Insulation Area 2. Single family or multiple family Detached a. Concrete Block - Int Insul, Exterior R=4.1 1224.00 ft2 3. Number of units, if multiple family 1 b. Frame - Wood, Adjacent c. NIA R=11.0 208.00 ft2 R= ft' 4. Number of Bedrooms 3 d. NIA R= ft2 5. Is this a worst case? Yes 11. Ceiling Types (1783.0 sgft.) Insulation Area a. Under Attic (Vented) R=30.0 1753.00 ft' 6. Conditioned floor area above grade (ft2) 1753 b. Knee Wall (Vented) R=19.0 $0.00 ft2 Conditioned floor area below grade (ft') 0 c. NIA R= ft2 7. Windows(151,4 sgft.) Description Area 12. Ducts R ft2 a. U-Factor: Sgl, U=1.02 111.36 ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 195 SHGC: SHGC=0.29 b. U-Factor: Sgl, U=1.11 40.00 ft' 13. Cooling systems kBtufhr Efficiency SHGC: SHGC=0.27 a. Central Unit 34.8 SEER:15.00 c. U-Factor: NIA ft2 SHGC: Area Weighted Average Overhang Depth: 4,850 ft. 14. Heating systems kBtulhr Efficiency Area Weighted Average SHGC: 0.285 a. Electric Heat Pump 34.8 HSPF:8.50 8. Skylights Area c. U-Factor:(AVG) NIA ft2 15. Hot water systems SHGC(AVG): NIA a. Electric Cap: 40 gallons 9. Floor Types (1753.0 sgft.) Insulation Area EF:0.970 a. Slab -On -Grade Edge Insulation R=0.0 1753.00 ft' b. Conservation features b. N/A R= ft2 None c. NIA R= ft' 16. Credits None Total Proposed Modified Loads: 49.38 Glass/Floor Area: 0.0$6 PASS Total Baseline Loads: 50.69 I hereby certify that the plans and specifications covered by Review of the plans and ES this calculation are in compliance with the Florida Energy specifications covered by this Code. calculation indicates compliance with the Florida Energy Code. PREPARED BY: Before construction is completed DATE: 1-12-2021 this building will be inspected for compliance with Section 553.908 � Ab I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code. ._ Q�WIS BUILDING OFFICIAL: DATE:OWNER/Qt ' DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (111402.4.1.2). 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: WYNNE THE WINDSOR IMP Bedrooms: 3 Address Type: Street Address Building Type: User Conditioned Area: 1753 Lot # Owner Name: Total Stories: i Block/Subdivision: # of Units: 1 Worst Case: Yes PlatBook: Builder Name: WYNNE DEVELOPMENT Rotate Angle: 180 Street: THE WINDSOR Permit Office: ST. LUCIE COUNTY Cross Ventilation: No County: St. Lucie Jurisdiction: Whole House Fan: No City, State, Zip: FT. PIERCE , Family Type: Detached FL , New/Existing: New (From Plans) Comment: CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1753 14024 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfI ID Finished Cooled Heated 1 MASTER BEDROO 224 1792 No 0 1 1 Yes Yes Yes 2 WIC 63 504 No 0 1 No Yes Yes 3 MASTER BATH 56 448 No 0 1 Yes Yes Yes 4 M. BATH 61 488 No 0 1 Yes Yes Yes 5 LAUDRY 36 288 No 0 1 No Yes Yes 6 BEDROOM 2 180 1440 No 0 1 1 Yes Yes Yes 7 DINING/GREAT R 588 4704 No 2 1 Yes Yes Yes 8 KITCHEN 209 1672 Yes 0 1 Yes Yes Yes 9 BATH 50 400 No 0 1 Yes Yes Yes 10 HALL 25 200 No 0 1 No Yes Yes 11 FOYER 92 736 No 0 1 Yes Yes Yes 12 BEDROOM 3 169 1352 No 0 1 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulatio MASTER BEDRO 37 ft 0 224 ft- _-__ 0 1 0 2 Slab -On -Grade Edge Insulatio WIC 1 ft 0 63 ft' ---- 0 1 0 3 Slab -On -Grade Edge Insulatio MASTER BATH 8 ft 0 56 ft' ---- 0 1 0 4 Slab -On -Grade Edge Insulatio M. BATH 7 It 0 61 ft' ---- 0 1 0 5SIab-On-Grade Edge Insulatio LAUDRY 1 ft 0 36 ft' ---- 0 1 0 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpel 6 Slab -On -Grade Edge Insulatio BEDROOM 2 12 ft 0 180 ft' ____ 0 1 0 7 Slab -On -Grade Edge Insulatio DINING/GREAT 50 it 0 588 ft' ___ 0 1 0 8 Slab -On -Grade Edge Insulatio KITCHEN lift 0 209 ft' ____ 0 1 0 9 Slab -On -Grade Edge Insulatio BATH 5 ft 0 50 ft' ____ 0 1 0 10SIab-On-Grade Edge Insulatio HALL i ft 0 25 ft' ____ 0 1 0 11SIab-On-Grade Edge Insulatio FOYER 9 ft 0 92 ft' ____ 0 1 0 12SIab-On-Grade Edge Insulatio BEDROOM 3 14 ft 0 169 ft' ___ 0 1 0 ROOF / Roof Gable Roof Red Solar SA Emilt Emit Deck Pitch V # Type Materials Area Area Color Bart Absor. Tested Tested Insul. (deg) 1 Hip Metal 1847 ft2 0 W Light N 0.6 No 0.9 No 0 18.4 ATTIC / `� # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 150 1753 ft' N N CEILING # Ceiling Type Space R-Value Ins Type . Area - Framing Free Truss Type 1 Under Attic (Vented) MASTER BEDRO 30 Blown 224 ft' 0.1 Wood _ 2 Under Attic (Vented) WIC 30 Blown 63 ft' 0.1 Wood 3 Under Attic (Vented) MASTER BATH 30 Blown 56 ft' 0.1 Wood 4 Under Attic (Vented) M. BATH 30 Blown 61 ft' 0.1 Wood _ 5 Under Attic (Vented) LAUDRY 30 Blown 36ft' 0.1 Wood _ 6 Under Attic (Vented) BEDROOM 2 30 Blown 180 ft' 0.1 Wood 7 Under Attic (Vented) DINING/GREAT 30 Blown 588 ft' 0.1 Wood 8 Under Attic (Vented) KITCHEN 30 Blown 209112 0.1 Wood 9 Under Attic (Vented) BATH 30 Blown 50 ft' 0.1 Wood _ 10 Under Attic (Vented) HALL 30 Blown 25 ft' 0.1 Wood 11 Under Attic (Vented) FOYER 30 Blown 92 ft' 0.1 Wood 12 Under Attic (Vented) BEDROOM 30 Blown 169 ft2 0.1 Wood 13 Knee Wall (Vented) DINING/GREAT 19 Blown 30 ft' 0.11 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below _ 1 NE=>SW Exterior Concrete Block- Int InsMASTER BE 4.1 16 0 8 0 128.0 ft2 0 0 0.3 0 _ 2 SW=>NE Exterior Concrete Block - Int InsMASTER BE 4.1 7 0 8 0 56.0 it' 0 0 0.3 0 3 NW=>SE Exterior Concrete Block - Int InsMASTER BE 4.1 14 0 8 0 112.0 ft' 0 0 0.3 0 1/12/2021 1:15 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 6 FORM R405-2020 INPUT SUMMARY CHECKI IST RIPPORT WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below _ 4 NE=>SW Exterior Concrete Block - Int InsMASTER BA 4.1 8 0 8 0 64.0 ft2 0 0 0.3 0 _ 5 NE=>SW Exterior Concrete Block - Int Insul M. BATH 4.1 7 0 8 0 56.0 ft' 0 0 0.3 0 -6 NE=>SW Exterior Concrete Block - Int Ins&EDROOM 2 4.1 12 0 8 0 96.0 ft- 0 0 0.3 0 7 SW=>NE Exterior Concrete Block- Int Ins(DINING/GRE 4.1 30 0 8 0 240.0 ft2 0 0 0.3 0 _ 8 NW=>SE Exterior Concrete Block -Int Ins(iIINING/GRE 4.1 20 0 8 0 160.0 ft- 0 0 0.3 0 9 SW=>NE Exterior Concrete Block - Int InsulKITCHEN 4.1 11 0 8 0 88.0 ft2 0 0 0.3 0 10 NE=>SW Exterior Concrete Block - Int Insul BATH 4.1 5 0 8 0 40.0 ft2 0 0 0.3 0 _ 11 SE=>NW Exterior Concrete Block - Int Insul FOYER 4.1 8 0 8 0 64.0 ft2 0 0 0.3 0 _ 12 SW=>NE Exterior Concrete Block - Int Insul FOYER 4.1 1 0 8 0 8.0 W 0 0 0.3 0 _ 13 NE=>SW Exterior Concrete Block - Int InsBIEDROOM 3 4.1 13 0 8 0 104.0 ft2 0 0 0.3 0 _ 14 SW=>NE Exterior Concrete Block - Int InsSEDROOM 3 4.1 1 0 8 0 8.0 ft2 0 0 0.3 0 15 N=>S Garage Frame - Wood BEDROOM 3 11 26 8 208.0 ft2 0.23 0.3 0 DOORS # Ornt Door Type Space Storms U-Value Width Height Area Ft In Ft In i SE=>NW Insulated FOYER None .39 3 3 6 8 21.7 ft2 WINDOWS Orientation shown is the entered orientation => chan ed to Worst Case. / Wall Overhang V # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 NW=>SE 3 Metal Low-E Single Yes 1.02 0.29 Y 32.4 ft2 1 ft 0 in 1 ft 41n Drapes/blinds Exterior 5 2 NE=>SW 5 Metal Low-E Single Yes 1.02 0.29 Y 6.9 ft2 1 ft 0 in 1 ft 4 in None None _ 3 NE=>SW 6 Metal Low-E Single Yes 1.02 0.29 Y 16.2 ft2 1 ft 0 in 1 ft 4 in None None _ 4 SW=>NE 7 Metal Low-E Single Yes 1.02 0.29 Y 39.8 ft- 1 ft 0 in 1 ft 4 in None None 5 NW=>SE 8 Metal Low-E Single Yes 1.11 0.27 Y 40.0 ft2 8 ft 0In 1 ft 4 in None None 6 NE=>SW 13 Metal Low-E Single Yes 1.02 0.29 Y 16.2 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5 GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 806 ft2 806 ft2 26 ft 8 ft 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000254 1168.7 64.12 120.37 .0902 5 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split Singl HSPF:8.5 34.8 kStulhr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split Sing[ SEER: 15 34.8 kStu/hr cfm 0.85 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.97 40 gal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Carl # Company Name System Model # Collector Model # Area Volume FEF None None ft2 DUCTS / ---- Supply---- --- Return --- Air CFM 25 CFM25 HVAC # V # Location R-Value Area Location Area Leakage Type Handier TOT OUT ON RLF Heat Cool 1 Attic 6 195 ft2 Attic 55 ft2 Default Leakage Attic (Default) (Default) 1 1 TEMPERATURES Programable Thermostat: N Ceiling Fans: Conlin [[ ]]Jan ((�� Feb Healing [XI Jan [X1 Feb [[ ]]Mar [XI Mar r A r [ AApr [ ] Ma [7c� Jun D0 Jul ] [ ] Jun [ ] Jul Xl Au E ] Aug Se 4 ] Sep Oct Nov Dec € Venting [[ II Jan [[ ]] Feb [[�X]] Mar [[ May 1 [ 1 Jun [)Jul [ 1 Aug f 1 Sep Oct Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD) PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft. 0 ft2 0 ft 0.3 MASTER BEDROO Default(8 lbs/sq.ft. ft2 ft 0.3 WIC Default(8 lbs/sq.ft. ft2 ft 0.3 MASTER BATH Default(8 lbs/sq.ft. ft2 ft 0.3 M. BATH Default(8 lbs/sq.ft. ft2 ft 0.3 LAUDRY Default(8 lbs/sq.ft. ft2 ft 0.3 BEDROOM 2 Default(8 lbs/sq.ft. ft2 ft 0.3 DINING/GREAT R Default(8 lbs/sq.ft. ft2 ft 0.3 KITCHEN 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft. ft' ft 0.3 BATH Default(8 lbs/sq.ft. ft' ft 0.3 HALL Default(8 lbs/sq.ft. ft' ft 0.3 FOYER Default(8 lbs/s.ft. ft' ft 0.3 BEDROOM 3 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 6 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a Project Name: WYNNE THE W INDSOR IMPACT Builder Name: WYNNE DEVELOPMENT Street: THE W INDSOR Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: Owner: Jurisdiction: U w Design Location: FL, Fort Pierce COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be Installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier, not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/aftic The air barier in any dropped ceiling/soffit shall be aligned with The Insulation in any dropped ceiling/soffit the insulation and any gaps In the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be Insulated by completely filling the cavity sealed. with a material having a thermal resistance of R3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including Insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity Insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous Insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth In unvented crawl spaces shall be covered with Where provided instead of floor insulation, Insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Bads in narrow cavities shall be out to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures Installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Baa Insulation shall be out neatly to fit around wiring and plumbing in exterior walls, or Insulation that on installation readily conforms to available space shall extend beh'nd p'ninn and wiring Exterior walls adjacent to showers and tubs shall Shower/tub The air barrier Installed at exterior walls adjacent to showers and on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition, inspection or log wars snan be in accoroance with the provisions or Icc-4u0. 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 97 The lower the EnergyPerformance Index, the more efficient the home. 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area (fI) 7. Windows" Descdption a. U-Factor: Sgl, U=1.02 SHGC: SHGC=0.29 b. U-Factor: Sgl, U=1.11 SHGC: SHGC=0.27 c. U-Factor: N/A SHGC: d. U-Factor: N/A SHGC: Area Weighted Average Overhang Depth: Area Weighted Average SHGC: 8. Skylights Description a. U-FBctor(AVG): N/A SHGC(AVG): N/A THE WINDSOR, FT. PIERCE, FL, New (From Plans) 10. Wall Type and Insulation Detached a. Concrete Block - Int Insul, Exterior b. Frame- Wood, Adjacent c. N/A 3 d. N/A Yes 11. Ceiling Type and Insulation level a. Under Attic (Vented) 1753 b. Knee Wall (Vented) Area c. N/A 111.36 ft' 12. Ducts, location 8 insulation level a. Sup: Attic, Ret: Attic, AH: Attic 40.00 ft' 13. Cooling systems ft' a. Central Unit ft' 2.850 ft. 0.285 Area ft° 9. Floor Types Insulation Area a. Slab -On -Grade Edge Insulation R=0.0 1763.00 ft' b. N/A R= ft' c. N/A R= ft' 14. Heating systems a. Electric Heat Pump 15. Hot water systems a. Electric b. Conservation features None Credits (Performance method) I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. \ �� Builder Signature: �.. Date: Address of New Home: a`10 Cg��tla 125� �.� City/FL Zip: `RSN.-, 3%-ka-5a Insulation Area R=4.1 1224.00 ft- R=11.0 208,00 ft' R= ft' R= ft- Insulation Area R=30.0 1763.00 ft' R=19.0 30.00 ft' R= ft. R ft- 6 195 kBtu/hr Efficiency 34.8 SEER:15.00 kBtu/hr Efficiency 34.8 HSPF:8.50 Cap: 40 gallons EF: 0.97 None *Note: This is not a Building Energy Rating. if your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For Information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 1/12/2021 1:15 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 a Project Summary o wrightsofk Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 ftre:772-466-6799 Fax T72466-6796 Email: OUICKCALCS@AOL.COM Project• • For: WYNNE DEVELOPMENT THE W INDSOR, FT. PIERCE, FL Notes: Design Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Insidedb 70 OF Insidedb 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 21542 Btuh Structure 16420 Btuh Ducts 6191 Btuh Ducts 9337 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipmentload 27734 Btuh Use manufacturers data n Rate/swingg multipplier Equipmenlsensibleload 0.95 Infiltration 24470 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2495 Btuh Ducts 2546 Btuh Central vent (0 cfm) 0 Btuh Heatingg Cooling (none) Area (ft) 1753 1753 Equipment latent load 5041 Btuh Uolume(fN) 16478 16478 Air changes/hour 0.38 0.20 Equipment Total Load ((Sen+Lat) 29511 Btuh EquivAVF (cfm) 104 55 Req. total capacity at 0.70 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIERAIR CONDITIONING Trade CARRIERAIRCONDITIONING Model 25HBC536KO30 Cond 25HBC536KO30 AHRI ref 7914585 Coil FX4DN((B,F)037 AHRI ref 7914585 Efficiency 8.5 HSPF Efficiency 12.0 EER,15 SEER Heating Input Sensible cooling 24360 Btuh Heating output 34600 Btuh@47°F Latentcooling 10440 Btuh Temperature rise 27 OF Total cooling 34800 Btuh Actual air flow 1160 Cfm Actual airflow 1160 cfim Airflowfactor 0.042 cfm/Btuh Airflowfactor 0.045 cfn tuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point= 36 OF Backup: Input=7 kW, Output=23009 Btuh, 100AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed. •` - wrr9titsoft- 2021-Jarv1213:18:18 �y •r ^•^•^—+�^�r RigM-SdteO Umersa1201919.021 RSW8101 Page �•M ...DocrnertslWngitsafl FNAC\WYNNE-THE WINDSOR.Rp Calc=M18 Frort Door faces: N wrightsoft" Right-.1® Worksheet Job: Entire House Data: QUICK CALCS, INC. By. 317 ST. LUCIE LN, Fr. PIERCE, FL 34946 Plow: 772466-6799 Fax 772466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Enbre House BEDROOM 2 Exposed all 207.6 ft 41.0 ft 3 Room height 9.4 ft d 9.4 it hwV=l 4 5 Room dimensions Room area 1753.D IF 14.0 x 20.0 ft 280.0 ft' Ty Construction number U-value (BtahAF--°F) Or HTM (BtuW) Area OF) or perimeter (ft) Load (BWh) Area OF) or perimeter (ft) Load (BWh) Heat Cool Grass NIPS Heat Cool Gross NrP/S Heat Cool 6 V[ It-GG 13A-4= lWom 4A5-2om 0.143 1270 0.770 n In n 4.00 35.56 21.56 2.55 34.77 19.31 C49 15 38 596 0 0 2386 533 815 1517 522 730 66 0 0 66 0 0 263 0 0 167 0 0 11 W� VL 13A-0ars 13A4ars 0.143 0.143 ne a 4.00 4.00 2.55 2.55 27 141 27 100 106 400 68 255 0 0 0 0 0 0 0 0 1ACiom 1270 a 35.56 87.06 20 1 711 1741 0 0 0 0 D 11DO 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0 w 13A4ocs 0.143 w 4.00 2.55 27 27 106 68 0 0 0 0 Vf/ t-G 13AA= 0.143 s 4.00 2.55 536 530 2121 1349 188 188 753 479 1Aclom 1270 s 35.56 34.77 6 6 213 209 0 0 0 0 13A4= 0.143 w 4.00 2.55 320 255 1022 649 132 108 432 275 1A-cl m 1ACiom 1270 1270 w w 35.56 35.66 54.53 54.53 12 12 1 1 415 427 636 654 12 12 1 1 415 427 636 654 4A5-2om 12C-0sx 0770 0.091 w 21.56 255 45.63 128 41 254 2 254 880 647 1862 326 0 0 0 0 0 0 0 0 P C F 16A-30md 22A-tpl 0.032 0.989 - - 0.90 27.69 2.32 0.00 1753 1763 1753 208 1571 5748 4067 0 280 280 280 41 251 1135 650 0 6 c)AED e"rsion 397 488 Envelope bwlgain 19331 15285 36761 3349 12 a) InlilOation 3211 905 729 205 b) Roomventilation 0 0 0 0 13 Internal gaiw O=panb@ 230 1 230 0 0 Applianoestother 0 0 Subtttal(lines 6 to 13) 21542 16420 4405 3554 Less external loci 0 0 0 0 Less transfer 0 0 0 0 Redistibuton 0 0 0 0 14 Subtotal 21542 16420 4405 3554 15 Ductloads 29% 57% 6191 9337 29% 57% 12661 2021 room bad 27734 25757 5671 5575 Arrequired(dm) 1160 237 25Total Calculations approved bvACCA to meet all requirements of Manual J 8th Ed wr7 F!tw� rt- 2021-Jan�1213:18:18 Aftk"'""' '^'^^`^�O`• - Rigt4SULVUriwrsa1201919.021RSU08107 ...Dow rts\Wdgttwft HVADWYNNE-THEWINDSOR.np Calc=tvtl8 Frord Doorlaces: N Page1 r wrightsoft° Right -A Worksheet Job: Entire House Date: ey QUICK CALCS, INC. 317 ST LUCIE LN., FT. PIERCE, FL 34946 Phore: 772466-6799 Fax 772-466-6796 Email: OUICKCALCS@AOL.COM 1 Room name WIC MASTER BATH 2 Dpomdwall 0 It 9.0 ft 3 Room height 9.4 ft hea abol 9.4 ft heaGwol 4 5 Room dimensions Room area 7.0 x 9.0 ft 63.0 ff 7.0 x 9.0 t 63.0 1f Ty Conshidon number U-value (BWhtF--'F) Or HTM (BWh4f) Area OF) or perimeter (ft) Load (BWh) Area (it) or perimeter (ft) Load (BWh) Heat Cool Gros WP5 Heat Cool Gross NIPS Heat Cool 6 V�1 I-G 13A4oca 1Aoiom 0.143 1270 n n 4.00 35.56 2.65 34.77 0 0 0 0 0 0 0 0 0 0 0 0 0 - 0 0 o �G 4P5-2om 0,770 n 21.56 19.31 0 0 0 0 0 0 0 - 0 11 W t�/ IL-G 13A4os 1344as 0.143 0A43 ne a 4.00 4.00 2.55 2.55 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Ac1om 1270 a 35.56 -10.92 87.06 0 0 0 0 0 0 0 0 D 11DO 0.390 a 11.31 0 0 0 0 0 0 0 0 W 13A4ow 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 �/ LG 13A4ocs 0.143 s 4.00 2.55 0 0 0 0 85 -85 339 215 1Aciom 1270 s 35.56 34.77 0 0 0 0 0 0 0 0 VII 13A4as w 0 0 0 0 0 0 0 0 1Aclom tAolom 1270 1270 1270 w w 5.56 35.56 35.56 4.53 54.53 54.53 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 21.56 45.63 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 2.55 128 0 0 0 0 0 0 0 0 C 16A30md 0.032 - 0.90 2.32 63 63 56 146 63 63 56 146 F 22A-tpl 0.989 - 27.69 0.00 63 0 0 0 63 9 249 0 6 c)AED exwrsion -10 -28 Enwlope losagain 56 136 $44 334 42 a) Infiltration 0 0 160 45 b) Roomvenfilation 0 0 0 0 13 Intemalgains: Oowpants@ 230 0 0 0 0 ApplianceNother 0 0 Subtotal(lines 6to 13) 56 136 804 379 Les exemal load 0 0 0 0 Less transfer 0 0 0 0 Redistibuton 0 0 0 0 14 Subtotal 56 136 804 379 15 Duct loads 29% 57% 16 77 29% 57% 231 216 Total room bad 73 214 1036 595 Airrequired(chm) 3 10 43 27 Calculatlons approved byACCA to meet all requirements of Manual J 8th Ed. c -rk- wr19tr+�oft^ 2021-Jao-1213:18:18 A&A Righ-SuteO Udwrsa1201919.021 RSU08101 Page t ..,Doamerts\WdgFbDft NAQWYNNE-THEWINDSOR.np Calc=WB From Ooorfaces: N +� wrghtsoft° Right-JO Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., Fr. PIERCE, FL 34946 Ptone:772-466-6799 Fax 772466-6796 Email: QUICKCALCSc(AOL.COM 1 Room name MBATH KITCHEN 2 ENeosedvall 8.0 It 8.0 ft 3 Room height 9.4 ft heaVrool 9.4 It heaVmol 4 5 Room dimensions Room area 7.0 x 8.0 ft 56.0 IF 1.0 x 172.0 ft 172.0 f? Ty Construction U-value Or HTM Area OF) Load Area (f?) Load number (Bluh/IF--°Fj (Btuhv) or perimeter (ft) (Btuh) or perimeter (ft) (BWh) Heat Cool Gross NIPS Heat Cool Gross N/P/S Heat Cool 6 VLG13A4ocs 0.143 n 4.00 2.55 0 0 0 0 0 0 0 -0 1Aclom 1270 n 3556 34.77 0 0 0 0 0 0 0 0 G 4A5-2om 0.770 n 21.56 19.31 0 0 0 0 0 0 0 0 w 13AAccs 0.143 ne 4.00 2.55 0 0 0 0 0 0 0 0 11 13A4ars 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0 1Ao1om 1270 a 35.66 87.06 0 0 0 0 0 0 0 0 D 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0 w 13A4as 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11/ 13A4<xe 0.143 s 4.00 2.55 76 69 2T7 176 0 0 0 0 �G 1"lorn 1270 s 35.56 34.77 6 6 213 209 0 0 0 0 Vtl 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0 -13A-4ocs �I�G 1Aolm 1270 w 35.56 54.53 0 0 0 0 0 0 0 0 1Aclw 1270 w 35.56 54.63 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 21.56 45.63 0 0 0 0 0 0 0 0 P 12C-Ow 0.091 2,55 126 0 0 0 0 75 75 192 96 C 16A-30md 0.032 - 0.90 2.32 56 56 50 130 172 172 154 399 F 22A-tpl 0.989 - 27.69 0.00 56 8 222 0 172 8 222 0 6 c)AED excursion -38 -34 Envelope loss/gain 762 477 1 567 462 12 a) Infiltration 142 40 0 0 b) Roommantlarton 0 0 0 0 13 Internal gains: Oceupana@ 230 0 0 6 0 Applianoesrother 0 0 Subtotal (lines 6 to 13) 904 517 667 462 Less c*nal load 0 0 0 0 Less transfer 0 0 0 0 Redistnbuton 0 0 0 0 14 Subtotal 904 617 567 462 15 Ductloads 29% 57% 260 294 29% 57A 1631 263 Total room load 1164 811 730 7235 Air required(cfm) 49 37 31 33 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wel9ft r9 - 2021-Jan1213:18:18 Right-Sute@Unversa1201914.021 RSU08101 Page 3 ...Dowrerts\Wngttroft HVAC\WYNNE-THEWINDSORnp Laic=NU8 FrontDoorfaces: N wrightsoft, Right-M Worksheet Job: Entire House Data: QUICK CALCS, INC. By. 317 ST. LUCIE UN., Fr. PIERCE, FL 34946 Phoe:772-466-6799 Fax: 772466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH BEDROOM2 2 EVosedwdll 5.0 ft 42.6 ft 3 Room height 9A It heaV=1 9A ft heaNmol 4 5 Room dimensions Room area 9.0 x 5.0 it 45.0 ft' 1.0 x 204,0 ft 204.0 IF Ty COnshVCtion U-value Or HTM Area (ft-) Load Area (" Load number (BNh4P--9 (BWINP) or perimeter (ft) (BNh) or perimeter (ft) (BWh) Heat Cool Gros N/P/S Heat Cool Gros N/P/S Heat Cool 6 13A4ow 1Actan 4A5-2om 0.143 1270 0.770 n n n 4.00 35M 21.56 2.55 34.77 19.31 47 0 0 47 0 0 188 0 0 120 0 0 132 0 0 132 0 0 527 0 0 335 0 0 11 W 13A-4ocs 13A4ocs 0.143 0.143 ne a 4.00 4.00 2.55 2.65 0 0 0 0 0 0 0 0 27 85 27 65 106 259 68 164 1Aclom 11DO 13A4acs 1270 0.390 0.143 a a se 35.56 10.92 4.00 87.06 11.31 2.55 0 0 0 0 0 0 0 0 0 0 0 0 20 0 27 1 0 27 711 0 106 1741 0 68 W G 13A4as 0.143 s 4.00 2.55 0 0 0 0 132 132 527 335 1Ao1om 1270 s 35.56 34.77 0 0 0 0 0 0 0 0 13A4ocs 0.143 w 4.00 2.65 0 0 0 0 0 0 0 0 1Aciom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0 G 1Aclom 1270 w 35.66 54.53 0 0 0 0 0 0 0 0 P 4A5-20m 12C-Ow 0.770 0.091 w 21.56 2.55 45.63 128 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C F 16A-30md 22A-tpI 0.032 0.989 - 0.90 27.69 2.32 0.00 45 45 45 5 40 138 104 0 204 204 204 43 183 1179 473 0 6 c)AED exarsion -17 -99 Envelope loss(gain 367 207 3599 3085 12 a) Infiltration 89 25 758 214 b) Roomeantlation 0 0 0 0 13 Internal gains: Oowpants@ 230 0 0 0 0 Appliancessiother 0 0 Subtotal (lines6 to 13) 456 232 43571 3299 Less Werral load 0 0 0 0 Lessbansfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 456 232 4357 3299 15 Ductloads 29% 57% 131 132 29% 57% 1252 1876 Total room load 687 364 5609 5175 Air required(dm) 25 i6 235 233 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rid- wrJsftt rt- 202 1 -Jan-1 2 13:18:18 A ^^ RigitSuLD Uriversel 201919.021 RSU08101 Page ...Doa rWWrigftsoft HVACWYNNE-THE WINDSOR.np Cale =MJ8 Front Door faces:N wrightsoft Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By 317 ST. LUCIE LN, Fr. PIERCE, FL 34946 Phone:772-466-6799 Fax: 772466-6796 Email: QUICKCALCS@,AOL.COM 1 Room name ENTRY LAUNDRY 2 Exposedwall 18.0It 13.0It 3 Room height 9.4 A heaVcool 9.4 t heaV000l 4 5 Room dimensions Room area 1.0 x 92.0 fl 92.0 IF 7.0 x 6.0 t 42.0 ff Ty Cork"on U-value Or HTM Area (ft) Load Area (It) Load number (BNh/IF--°F) (BWh4F) or perimeter (fl) (Bah) or perimeter (fl) (Btuh) Heat Cool Gross NIPS Heat Cool Gross NIPS Heat Cool 6 Vrl 13A4c<s 0.143 n 4.00 2.55 0 0 0 0 0 0 0 0 II---GG 1Aaiom 4AS2om 1270 0.770 n n 35.66 21.56 34.77 19.31 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W % 11 13.A4ocs 13AAc s 0.143 0.143 ne a 4.00 4.00 2.55 2.55 0 56 0 35 0 142 0 90 0 0 0 0 0 0 0 0 1Ao1om 1270 a 35.66 87.06 0 0 0 0 0 0 0 0 F-G �D 1100 13A4ocs 0.390 0.143 a so 10.92 4.00 11.31 2.55 21 0 21 0 229 0 236 0 0 0 0 0 0 0 0 0 W 13AAa 1Ao1cm 0.143 1270 a s 4.00 35.56 2.55 34.77 0 0 0 0 0 0 0 0 56 0 56 0 226 0 144 0 M4A 1Ao1om 0.143 1270 w w 4.00 35.56 2.66 54.53 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1Aciom 1270 w 35.56 54.53 0 0 0 0 0 0 0 0 4A5-2om 0.770 w 21.56 45.63 0 0 0 0 0 0 0 0 P 12C-0av 0.091 - 2.55 128 113 113 287 145 66 66 168 84 C 16A30md 0.032 - 0.90 2.32 92 92 82 213 42 42 38 97 F 22A-pN 0.989 - 27.69 0.00 92 18 498 0 42 13 360 0 6 c)AEDexairsion 49 -24 Envelopelor4galn 1239 637 1 7911 301 12 a) Infiltration 107 30 107 30 b) Rcomvenfilaton 0 0 0 0 13 Intemalgains: Oooupants@ 230 0 0 0 0 Applianws(other 0 0 Subtoal(lines6t)13) 1346 667 898 331 Lea external load 0 0 0 0 Leahans<er 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1346 667 898 331 15 Ductloads 29% 57% 387 379 29% 57% 258 188 Total room load 1733 1017 1156 520 Air required(cfm) 72 47 48 23 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. wrl9hisofR^ 2021-JaM213:18:18 .9-A RigHTHE WINDSOR.rLprwl 919.021R6U0810 Page5 .-DoamaHs\WdgrGrofl HVAC\WYNNE-THE WINDSOR.np Calc=M18 Froth Dooraces:N +� wrightsoft' Right-J® Worksheet Jo" Entire House Date: QUICK CALCS, INC. By. 317 ST. LUGE LN.,Fr. PIERCE, FL 34946 P1ore: 772466-6799 Fax 77240"796 Emil: OUICKCALCS@AOL.COM 1 Room name GREATIDWING Room7 2 Elpomdmil 50.0 ft 13.0 It 3 Room height 9.4 ft heaVmol 9.4 ft heetkrol 4 Room dimensions 1.0 x 567A It 13.0 x 13.0 ft 5 Room area 567.0 IN 169.0 ft' Ty Construction U-value or ATM Area Load Arn number (BtuhAF-9 (BWhAS) or perimeter (ft) (BWh) or perimeter (ft) (Btuh) Heat Ccol Gross N/P)S Heat Cool Grore N)P5 Heat Cool 6 13A4= 0.143 n -400 2,65 - 282 - 244 978 622 - 122 -107 429 -.273. "IW W - 1270 n 35.56 34.77 - - - 0 0 0 - ' 0 15 - 0 533 ' 522 4A5-2om 0.770 n 21.56 19.31 38 0 816 730 0 0 0 - 0 W 13A4om 0.143 ne 4.00 2.65 0 0 0 0 0 0 0 0 11 VII - 13A-0as - 0.143 a 4.00 HE 0 0 0 0 - 0 0 0 0 L _GG AActam 1270 a 35.56 87.06 0 0 0 0 0 0 .0 0 11DO - 0.390 a 10.92 - -- 1121 0 0 0 -.0 - 0 - 0 -0 -.0 -- 0 W 13A4ao; 0.143 se 4.00 2,55 0 0 0 0 0 0 0 lq/ 134-flocs 0.143 s 4A - 0 `2.65 0 0 0 0 0 0 '.0 "0 �C 1Ac1am 1270 s - 35M 34.77 0 0 0 0 0 - 0 ` 0 0 lq/ 1"1M w 4A0 2.63 180 140 580 375 0 0 0 0 1Ao1om 1270 1270 w 35M 54.53 0 0 0 0 0 0 0 0 1Ao1am 1270 w 3556 54.53 0 0 0 0 0 0 0 0 `�I-CGC 4A5.2om 0.770 w 21M 45.63 41 2 880 1862 0 0 0 0 P 12C-Osv 0A91 - 2.55 128 0 0 0- 0 0 - 0 - 0 0 C 16A-30md OD32 - 0.90 2.32 567 567 508 1315 169 169 151 392 F 22A-tp1 02% - 27.89 0.00 667 50 1385 0 169 13 360 -0 6 c)AED exmrsim 307 -100 Envelope bWgaln 6154 5210 1474 1086 12 a) InAlhatron 889 251 231 65 b) Roomventladon 0 0 0 0 13 Intemil gales: O-Panls@ 230 0 0 1 230 Appliancestother 0 0 Submal(lires6to13) 6043 5461 1705 1381 Lessexamalload 0 0 0 0 Lesstransfer 0 0 0 0 Redishlbuton 0 0 0 0 14 Subtotal 6D43 6461 1705 1381 15 Dualoads 29% 57% 1737 3105 29% 57% 490 766 Total room load 7780 8566 2195 2167 Alr required(dm) 325 386 92 98 CalCuldons approved byACCAto meet all requirements of Manual J 8th Ed. -*- wrl htsaaTt' ...IPogAa9.021 R r 2021-h1213:18:18 Dowr6WdglsoftNACWYNNE-THEWINDSOR.W Calc=M6 FrortWorfaoss:N Page wrightsoft. Duct System Summary Job:Y rY Data: Entire House By. QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phore:772-466-6799 Fac 772466-6796 Email: OUICKCALCS@AOL.COM Project Information For: WYNNE DEVELOPMENT THE W INDSOR, FT. PIERCE, FL External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest fiction rate Actual airflow Total effective length (TEL) Heating 0 in H2O 0 in H2O 0 in H2O 0.000 / 0.000 in H2O 0 in/100ft 1160 cfin Oft Supply Branch Detail Table Cooling 0 in H2O 0 in H2O 0 in H2O 0.000 /0.000 in H2O 0 in/100ft 1160 cfin Name Design (Btuh) Htg (Cfm) Clg (Cfm) Design FIR Diam (in) H x W (in) Duct Mall Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 364 25 16 0 0 Ox0 ShMt 0 0 BEDROOM c 2788 119 126 0 0 OxO ShMt 0 0 BEDROOM2 h 2587 117 117 0 0 OxO ShMt 0 0 BEDROOM2-A h 2587 117 117 0 0 Ox0 ShMt 0 0 BEDROON-A C 2788 119 126 0 0 OxO ShMt 0 0 ENTRY h 1047 72 47 0 0 OXO ShMt 0 0 GREATIDINING c 2855 108 129 0 0 OxO ShMt 0 0 GREAVDINING-A C 2855 108 129 0 0 OxO ShMt 0 0 GREAT(DINING-B c 2855 108 129 0 0 Ox0 ShMt 0 0 KITCHEN c 725 31 33 0 0 OxO ShMt 0 0 LAUNDRY h 520 48 23 0 0 Ox0 ShMt 0 0 M. BATH h 811 49 37 0 0 OxO ShMt 0 0 MASTERBATH h 595 43 27 0 0 OxO ShMt 0 0 Room7 C 2167 92 98 0 0 OXO ShMt 0 0 wlc c 214 3 10 0 0 Ox0 ShMt 0 0 Return Branch Detail Table Name Grille Size (in) I Htg (cfm) Cig MITI) TEL (ft) Design FIR Veloc (fpm) Diam (in) HxW (in) Stud/Joist Opening (in) Duct Mat Trunk rb1 Ox 0 1160 1160 0 0 0 0 Ox 0 ShMt * wrightsoft- 2021Jan1213:1899 A ,.,.�•, Mwad.,.,.,,.,, Riglt-SULODUversa1201919.021 RSU08101 Page ..,Do a rts\Wrig"mft HVACWYNNE-THEWINDSORnp Calc=MJB FroNDoorhces:N