This letter serves as my response to comments:
Structural
M
1. C&C negative design pressures referenced in section 3 on sheet S 1.01 appear too low. They
also do not match any other referenced DP for roof or wall zones on same sheet please
clarify.
Response: S1.01 Section 3 C&C design pressures revised.
2. Roof Zone 3 DP requirements noted on sheet S1.01 are too low, per table R302.2(2). Please
address this.
Response: S1.01 Roof Zone 3 Uplift revised.
Single Family Residence
1. Roof product design pressures submitted on Product Approval affidavit do not meet DP
required in table.
Response: See attached Product Approval schedule.
2. Sliding glass doors shown on plans not included on product approval affidavit.
Response: See attached Product Approval schedule.
1
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www.abdesigngroup.com
A R C H I T E C T S
Design
Groupin�.
N
3. Window mullions shown on plans not included on product approval affidavit.
Response: See attached Product Approval schedule.
4. Please include 2 sets of manufacturer's installation specs for elevator.
Response: See attached elevator specifications.