HomeMy WebLinkAboutNOA Single Hung WindowDEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES .(RER) . BOARD AND CODE ADMINISTRATION DIVISION Z2,0 NOTICE OF ACCEPTANCE (NOA) REVUE MIAMI-DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175-2474 TT (786) 315-2590 F (786) 315-2599 CGI Windows and Doors, Inc. CODE C®Mp 3780 W -104" Street LIANCE Hialeah, FL-33018 ST. LUCK COUNTY SCOPE: RCCC This NOA is being issued under the applicable rules and regulations govbrning the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to. have this product.or material tested for quality assurance purposes.. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance if it is determined by Miami -Dade County Product Control Section that this product or material fails.to'meet the requirements of the applicable building code. This product is approved as described herein and has been designed to comply with the Florida Building Code, including the High Velocity Hurricane Zone. DESCRIPTION: Series "Sentinel 110"iluminum Sing, -e Iungt� ow L.M.I. APPROVAL DOCUMENT: Drawing No. S11110-LM-NOA, titled "Series 110 Alum. Single Hung Window (LM)", sheets 1 through 9 of 9, dated 07/02/20, with revision A dated 07/07/20, prepared by manufacturer, signed and sealed by Anthony Lynn Miller, P.E., bearing the Miami -Dade County Product Control Revision stamp with the Notice of Acceptance number and expiration date by the Miami -Dade County Product Control Section. MISSILE IMPACT RATING: Large and Small Missile Impact Resistant. LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state, model/series, and following statement: ,'Miami -Dade County Product Control Approved", unless otherwise noted herein. RENEWAL -of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be -available for inspection at the job site at the request of the Building Official. This. NOA revises and renews NOA# 17-1018.08 and consists of this page 1 and evidLae j2y E-3, E-4 and E-5, as well as approval document mentioned above. The submitted documentation was reviewed by Manuel Perez, P.E. NOA No. 20-0722.09 Expiration Date: September 22, 2025 Approval Date: September 10, 2020 9/1/20' , Page 1 CGI Windows and Doors, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 1. EVIDENCE SUBMITTED UNDER PREVIOUS NOA's A. DRAWINGS 1. Manufacturer's die drawings and sections. (Submitted under NOA No. 10-0510. 11) 2. Drawing No W10-03, titled "Series Sentinel 110 Alum S.H. Wdw. (L.M.I./S.M.I.)", sheets 1 through 9 of 9, dated 02/02/10, with revision D dated 09/29/17, prepared by Al-Farooq Corporation, signed and sealed by Javad Ahmad, P.E. (Submitted under NOA No.17--1018.08) B. TESTS 1. Test reports on: 1) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 2) Large Missile Impact Test per FBC, TAS -201-94 3) Cyclic Wind Pressure Loading per FBC, TAS 203-94 along with -marked -up drawings and installation diagram of a series 7500 PVC fixed window, to qualify DuPont "Butacite" PVB interlayer, Duraseal® and Super Spacer(D insulating glass spacer, prepared by Certified Test Laboratories, Test Report No. CTLA-3056 WA, dated 03/03/15, signed and sealed by Ramesh C. Patel, P.E. (Submitted under NOA No.15-0512.09) 2. Test reports on: 1) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 2) Large Missile Impact Testper FBC, TAS 201-94 3) Cyclic Wind Pressure Loading per FBC, TAS 203-94 along with marked -up drawings and installation diagram of a series 7400 PVC project out window, to qualify DuPont "Butacite" PVB interlayer, Duraseal(b and Super Spacer® insulating glass spacer, prepared by Certified Test Laboratories, Test Report No. CTLA-3056 WB, dated 03/03/15, signed_ and sealed by Ramesh C. -Patel, P.E, (Submitted under NOA No.15-0512.09) 3. Test reports on: 1) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94 2) Large Missile Impact Test per FBC, TAS 201-94 3) Cyclic Wind Pressure Loading per FBC, TAS" 203-94 along with marked -up drawings and installation diagram of a series 23 8 aluminum fixed window, to qualify DuPont "Butacite"-PVB interlayer, Duraseal® and Super Spacer® insulating glass spacer, prepared by Certified Test Laboratories, Test Report No. CTLA-3056 WC, dated 04/16/15,. signed and sealed by Ramesh C. Patel, P.E. (Submitted under NOA No.15-0512.09) Manuel Perez, P Product Control Ex .! NOA No. 20 0E722,Expiration Date: September Approval Date: September 10, 2U E-1 1. EVIDENCE` SUBMITTED UNDER PREVIOUS NOA's (CONTINUED) B. TESTS (CONTINUED) 4. Test reports on: -1)Air Infiltration Test, per FBC, TAS 202-94 " 2) Uniform Static Air, Pressure Test, Loading per FBC TAS 202-94 ' 3) Water Resistance Test, -per FBC, TAS 202-94 ` 4) Large Missile Impact Test per FBC, TAS_ 201-94 5), Cyclic Wind Pressure Loading per FBC, TAS 203-9+ 6) Forced Entry Test,per FBC 2411.3.2.1; TAS 202-94 along with marked -up drawings and installation diagram of a series "Sentinel" aluminum single hung window; prepared by Hurricane Test Laboratory, LLC; Test Report No. HTL-0080-0101-10; dated 02/03/10, signed and sealed by Vinu J. . Abraham, P.E. (Submitted under NOA No. 10-0510.11) C. CALCULATIONS 1. Anchor verification calculations and structural analysis, complying with FBC 611 Edition (2017), dated 09/29/17, prepared by Al-Farooq Corporation, signed and sealedby Javad Ahmad, P.E. (Submitted under NOA No.17-1018.08) 2. Glazing complies with ASTM E1300-09 D. QUALITY ASSURANCE 1. Miami -Dade Department of Regulatory and Economic Resources (RER). E. MATERIAL CERTIFICATIONS 1. Notice of Acceptance No. 14-0916.11 issued to Kuraray America, Inc. ^for their . "SentryGlas® (Clear and White) Glass Interlayers" dated, 06/25/15,.expiring.on 07/04/18. 2. Notice of Acceptance No. 16=11I7.01 issued to Kuraray America, Inc. for their "Trosifol@ Ultraclear, Clear and Color PVB Glass Interlayers" dated 01/19/171 expiring. on 07/08/19. 3. . Notice of Acceptance No. 17-0712.03 issued to Eastman Chemical Company.(MA) for their,"Saflex CP - Saflex and Saflex. HP, Composite Glass Interlayers, with -PET Core" dated 09/07/17, expiring on'12/11/18. 4. ' Notice of Acceptance No. 17-0712:05 issued to Eastman Chemical Company (MA) for their"Saflex Clear and Color Glass. Interlayers" dated 09/07/17, expiring on 05/21/21: IM12 Manuel Pei Product Control E: NOA No.-201 Expiration Date: September:: Approval Date: September CGI Windows and Doors, Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 1.. EVIDENCE .SUBMITTED UNDER PREVIOUS'NOV (CONTINUED) F. STATEMENTS -1. Statement letter of conformance, complying with FBC 511 Edition -(2014), and of no financial interest, dated 08/26/14, issued by Al-Farooq Corporation; signed and sealed by Javad Ahmad, P.E. . (Submitted under NOA No. 17-1018. 09) 2. Laboratory compliance letter for Test Report No. HTL-0080-0101-10, issued by Hurricane Test Laboratory, LLC, dated February 03, 2010, signed and sealed. by Vinu I Abraham, P.E. (Submitted under NOA No:10-0510.11) , 3. Test Proposal for the qualification of Butacite® PVB glass interlayer byDupont as well as Duraseal® and Super Spacer® Standard warm -edge flexible insulating glass spacers, dated December 16, 20,14, issued by RER, Product Control Section, signed by Jaime Gasconj Supervisor. (Submitted under NOA No.15-051210) G. OTHERS J. Notice of Acceptance No..15-0512.10, issued to CGI Windows &. Doors for their Series "S'entinel 110" Aluminum Single Hung Window - L.M.I., approved. on 08/06/15 and - expiring on 09/22/20. Manue Product Control F NOA7No. 2Q -Expiration Date: September Approval Date: September .2. NEW EVIDENCE SUBMITTED A. DRAWINGS 1. Drawing No SH110-LM-N0A, titled "Series .110.Alurn Single Hung Window (LM)", . sheets 1 through 9 of 9,. dated 07/02/20, with revision -A dated-07/07/20, prepared by manufacturer, signed and sealed by Anthony Lynn Miller, P.E. B. TESTS 1. Test reports on: 1) Air Infiltration Test, per FBC, TAS 202-94 2) Uniform Static Air Pressure Test, Loading per FBC, TAS 202-94 3) Water Resistance Test, per:FBC, TAS 202-94 4) Large Missile Impact Test per FBC,. TAS 201-94 5) Cyclic Wind Pressure Loading per FBC,`TAS 203-94 6): Forced Entry Test, per ASTM F588 and TAS 202-94 along with marked -up drawings and installation diagram of all PGT Industries, Inc. CGI Windows, and Doors,. Inc., representative units listed below and tested to qualify Dowsil 791 and Dowsil 983 silicones, per Proposal #19=1155TP, prepared by Fenestration Testing Laboratory, Inc., Test Reports No.: PGT .Industries, Inc. test specimens: FTL-7897, PGT PW5520 PVC Fixed Window(unit 6 in proposal), dated 09/,03/14 FTL-20-2107.1, PGT'SGD780 Aluminum Sliding Glass Door (unit 7 in proposal) FTL-20-2107.2, PGT CA740 Alum. Outswing Casement Window (unit 8 in proposal) FTL-20-2107.3, PGT PW7620A Aluminum Fixed Window (unit 9 in proposal) and FTL-20-2107.4, PGTPW7620A Aluminum Fixed Window -(unit 10 in proposal) all dated 07/13/20 and signed and sealed by Idalihis Ortega,. P.E. . CGI Windows -and Doors Inc. test specimens:. FTL-20-2108.1, CGI SH3.60 Aluminum Single Hung Window (unit .1 in proposal) FTL-20-2108.2, CGI CA238 Alum. Outswing.Casement Window (unit 2 in proposal). FTL-20-2108.3, CGI SGD560 Aluminum Sliding Glass. Door {unit 3 in proposal) FTL-20-2108.4, CGI PW4.10 Aluminum. Fixed Window,(unit 4 in proposal) .and FTL-20-2108.5, CGI SH360 Aluminum Single.Hung Window '(unit 5 in proposal) all dated 08/24/20 and signed and sealed by Idahnis Ortega, RE. C. CALCULATIONS . 1. Anchor verification calculations and structural' analysis, complying with FBC 71' Edition (2020), dated 07/11/20, prepared by manufacturer,. signed and sealed by Anthony Lynn Miller, P.E. Manuel'Perez, P. Product Control Ex er :. NOA No. 2 0722.09 Expiration Date: September:: 2, 2 Approval Date:, September 10, 2020 E-4 CGI Windows and Doors, Inc. . NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED 2. NEW EVIDENCE SUBMITTED (CONTINUED). D. QUALITY ASSURANCE 1., Miami -Dade Department of Regulatory and Economic Resources (RER) E. MATERIAL CERTIFICATIONS 1. Notice of Acceptance No. 18-0715.11 issued to Kuraray America, Inc. for their "Kuraray SentryGlas® XtraTM (SGXT"� Clear Glass Interaayet" dated 05/23/19, .expiring on 05/23/24. 2. Notice of Acceptance No. 19-0305.02 issued to Kuraray America,. Inc... for their "Trosifol® Ultraclear, Clear and Color PVB Glass Interlayers" dated 05/09/19, expiring on `01/08/24. 3.- Notice of Acceptance No. 18-0301.06.issued to Eastman Chemical Company (MA) for their "Saflex CP Saflex and Saflex HP Composite Glass Interlayers with PET Core" dated 05/t7/18, expiring on 12/11/23. 4: Notice of Acceptance No. 17-0712.05 issued to Eastman Chemical Company (MA) for their "Saflex Clear and Color Glass Interlayers" dated 09/07/17, expiring on 05/21/21. F. STATEMENTS 1. Statement letter of conformance, complying with FBC, 61h Edition (2017) and the FBC 71h Edition (2020), dated July 16, 2020, issued by manufacturer, signed and sealed by Anthony Lynn Miller, P.E. 2. Statement letter of no financial interest, dated July 16, 2020, issued by manufacturer, signed and sealed by Anthony Lynn Miller, P.E. 3.. Proposal No. 19-1155 TP issued by the Product Control Section, dated January 10, 2020, signed by Ishaq Chanda, P.E. 4. Notification of Successor Engineer for manufacturer's NOA document per Section 61G15-27.001 of the Florida Administrative Code; notifying original engineer that the successor engineer is assuming full professional and legal responsibility for all engineering documents pertaining to this NOA, dated July 16, 2020, signed and sealed by Anthony Lynn Miller, P.E. 5. Proposal No.;19-1155 TP issued by the Product Control Section, dated January 10, 2020, -signed by Ishaq Chanda, P.E. G. OTHERS 1. Notice of Acceptance No. 17-1018.08, issued to CGI Windows. & Doors for their Series "Sentinel 11 0"Aluminuih Single Hung Window - L.M.I., approved on 12/21/17 and expiring on 09/22/20. Manuel.'Pe Product Control E NOA.No. 20 Expiration Date: September Approval Date: September 'E-5 1 47 7/16' 1 1/2' MAX. SERIES_ SENTINEL 110 ALUMINUM SINGLE HUNG WINDOW LARGE & SMALL MISSILE (LM & SM) DESIGN LOAD RATINGS FOR THESE WINDOWS TO BE AS PER CHARTS SHOWN ON SHEET 2. D.L.O. (FIX. LITE) 20 9/16- ** MAX. Al HEAD/SILL u u 11 II II II ram- - u '� u B J u �I 11 47 7/16' U.LU. (VLNI) 50 1/4' EQUAL FRAME APPROVAL APPLIES TO SINGLE UNITS OR SIDE BY SIDE COMBINATIONS OF S.H./S.H. OR SINGLE HUNG WINDOW WITH OTHER MIAMI—DADE COUNTY APPROVED WINDOWS USING MIAMI—DADE COUNTY APPROVED MULLIONS IN BETWEEN. LOWER DESIGN. PRESSURE FROM WINDOWS OR MULLION APPROVAL WILL APPLY TO ENTIRE SYSTEM. THIS PRODUCT HAS BEEN DESIGNED AND TESTED TO COMPLY WITH THE REQUIREMENTS OF THE 2017 (6TH EDITION) AND 2020 (7TH EDITION) FLORIDA BUILDING CODE INCLUDING HIGH VELOCITY HURRICANE ZONE (HVHZ). 1BY OR 2BY WOOD BUCKS & BUCK FASTENERS BY OTHERS, MUST BE DESIGNED AND INSTALLED ADEQUATELY, TO TRANSFER APPLIED PRODUCT LOADS TO THE BUILDING STRUCTURE. - ANCHORS SHALL BE CORROSION RESISTANT, SPACED AS SHOWN ON DETAILS AND INSTALLED PER MANUF'S INSTRUCTIONS. SPECIFIED EMBEDMENT TO BASED MATERIAL SHALL BE BEYOND -WALL DRESSING OR STUCCO. A LOAD DURATION INCREASE IS USED IN DESIGN OF,ANCHORS INTO WOOD ONLY. ALL SHIMS TO BE HIGH IMPACT, NON-•METAWC AND NON —COMPRESSIBLE MATERIALS INCLUDING BUT NOT LIMITED TO STEEL/METAL SCREWS, THAT COME INTO CONTACT WITH OTHER DISSIMILAR MATERIALS SHALL MEET -THE REQUIREMENTS OF THE 2017/2020 FLORIDA BLDG. CODE.& ADOPTED STANDARDS. THIS PRODUCT APPROVAL IS GENERIC AND DOES NOT PROVIDE INFORMATION FOR A SITE SPECIFIC PROJECT, i.e. LIFE SAFETY OF THIS PRODUCT, ADEQUACY OF STRUCTURE RECEIVING THIS PRODUCT AND SEALING AROUND OPENING FOR WATER INFILTRATION RESISTANCE, ETC. CONDITIONS NOT SHOWN IN THIS DRAWING ARE TO BE ANALYZED SEPARATELY, AND TO BE REVIEWED BY BUILDING OFFICIAL. FALSE MUNTINS (SURFACE APPI FIN FRAME - �c *CENTER ANCHOR REQUIRED WHEN SPACING EXCEEDS 20 9/16" LAMINATED GLASS INSULATING LAM. GLASS SMALL MISSILE IMPACT LARGE MISSILE IMPACT .z z U PRODUCT REVISED as complying with the. Florida. Building Code REVISED FOR 2020 FBC, ADDED ANCHOR TYPE, BACKBEDDING & REFORMATTED -JR- 07/07/20 N Y w O y . ul N a1o0 K 0 Z K Z O In Z a N O V ' O M01. U) W V V o K O ZZ un�o0 N �1 zWo S aN LL O a�Z j ul z Q e N w C1 Z to T. laaVS Vl'atl 2 N p O Li W ohm z A3� 9 ar-o Q to. W E3g�N Z W 3�� 0 .> Un=� UmSm W aill —a0 sauaS ``111111111 r��' N�c NSE 4,1,�1�� No.58705• '�•.� a : S A/6�61 �� •�\• A. LYNN MILLER, RE P.E.# 58705 0M0Z cmiu�o I y O !D { `y rn m m yny �z o w HEIGHT D0 m 6o N S Zo �z ei 3� 3 O z Z n x x C v D HEIGHT C D r r • m � f C p Z 22 m FLANGE DIMS. O r8-1/4" r• .m. MIN. � D.LO. , O VENT m r BUCK DIM. LENGTH (L) . 'V W�� m yl A N W m m W N •° W N ,D tM; � 0 N V W Ir W. m tlRR � N' I� N N m m N m m N m lD N m m N m Oo N m •• pj C tl p� EE m • PP �•l 0 0 0 o c e o o c o o c c c c c c c c e c c e c o c v r6 J V U U J J U Ili J�� U N W fVn N IVn N Vi N N IVII N IVII U IYI N IJn N lJn N�� M D D O' O C b O G O U G G C G, C O G O R U v oS0000�00000�S0000Sa0000SSo���� b o b c b b o c c o c b o bb b b o iii �i � �i i°n �i N � u inii �i r1°n u rnii � eT -in o b b o c b o b b b-b b ,�'n b o bb b c c c c o b b b b b v j R tD m U •.' N iO•. � Y R W � N � (��(��jj tl N • m m : � ?: b ltl '� o c o b o 0 0 yy V a � VV a o o Big 0 0 pv a oo c c o 0 o v y� m O mm O O mm mm O G O v a' \�`0— dImpactResistant a°�'�°°` �\ ��CS q'' Windows &Doors 1070 ECEHNOLOGY DRIVE m •c x O e WERE SiMGEFT•. N. VENICE, FL 34275 p� �� = ••.yQ 941 480-1600 CGI WINDOWS AND. INC. i ) •0la c _ 3780 W 104TH STREET �.n m r>; AN m: r= HIALEAH,FL33018 REGISTRATION 029296 9 mm •'1 5t3_rr • a 2 : { _ (305) 5934 590 o ° •mA;:'SERIES 110 ALUM. SINGLE HUNG WINDOW(LM) 07/02/20CD o,F�"'�^.\\ ` o DESIGN LOADS pm JENS ROSOWSKI ° ro N o SH110 "SENTINEL" r 2 OF 9 . oz . SH110-LM-NOA -A tNil to m .075' Saflex CP With PET Core .075" Saflex CP With PEr Care By 'Eastman Chemical Co. By 'Eastman Chemical Co.' .090" Saflex Clear And Color Glass he .090" Saflex Clear And Color Glass By 'Eastman Chemical Co.' g4—D9 g By 'Eastman Chemical Co.' - 0" SentryGlasO 090' SentryGlos® PRODUCT REVISED ! 'Kumray America, Inc,' By 'Kuraray America, Inc. 09 c Iying with the Florida 1/B' ANNEA 0' Trosifol PVB 'Kuraray Ameica, Inc.' 1/8' HEAT STREN'D GLAS .090" Trosifol PVB' By 'Kuraray Ameica, Inc.' Building Code NOA-No. 20-0722.09 - Ex Iratlon Date• 9/22/2025 ANNEALED CLASS 1/B" HEAT STREN'D GLASS pp.. FSn ICONE, - Mia4pade ProducYCo trol 5899, GE 1200 DOW CORNING 791, 953 & 995 z g mGE 1200 DOW CORNING 791, 899, 983 & 995TYPES ADDED BACKBEDDING M1 - JR - 07/07/20 EB ab GLASS TYPE 'A' GLASS TYPE 'B' m o O - 5/16- OVERALL LAM. GLASS 5/16- OVERALL LAM: GLASS m a)o0 OOf ¢O (L.M.I & S.M.I.) (L.M.I & S.M.I.) z z - z z0 W _j . 0 Oz a.. 5 0 uMOiQ r/1 - .075" Saflex CP With PET Coro _ .075" Saftex CP With PET Core 'Eastman _ ¢ z aN - By 'Eastman Chemical Co. By Chemical Co. w o (0 9M0 w 1 /8' ANNEALED GLAJLED 090" Saflex Clear And Color Glass 1/8' HEAT STREN'D GLASS g .090' Saflex Ciear •.And Color Glass 'Eastman a I z °�' j . -'Eastman Chemical Co.' - S By Chemical CO.' - _ tL - 1/4' AIR ' SentryGlas�- 1/4' AIR SPACE 090' SentryGlas® 'Kuramy i - _ O 'Kuraray America, Inc.' By America; Inc.' o Z1/8" ,. ANNE" Trosifol PVB 1/8" HEAT STREN'D .090- Trosifol PV13 - 'Kuraray y G g MOR 'w 00 TEMPERED G'Kuramy Ameica, Inc.' OR TEMPERED- GLASS- By Ameica, Inc.'• ail 0 xW ANNEALED GL+.,SS 1/8HEAT STREN'D GLASS A "'¢ QoiEL SILICONE: O `4 U) � GEE1122000 z GE 1200 DOW CORNING 791, z = W toDOW CORNING 791, W 899, 983.& 995 M1 899, 983 & 995 (V7 w(0 rn Bill rosa0 saaa5 XL EDGE SPACER - XL EDGE SPACERST. STEEL 13Y'CARDINAL' ST. STEEL BY'CARDINAL'OR OR , • BY 'QUANEX' P7 O DDURRASEAL BY 'QUANEX' ��NY LYNDURASEAL �` ........ORiEg SUPER SPACER BY 'QUANEX' [�7 - 1 SUPER SPACER BY 'QUANEX' 'Al' GLASS TYPE 'BI' GLASS TYPE 0.70' OVERALL INSUL LAM. GLASS 0.70" OVERALL INSUL LAM. GLASS •-D _ (L.M.I & S.M.I.) (L.M.I & S.M.I.) 0'• �SE20;' ' i�(Q •'•.FLORID P;.•'• \�� . S/ONAL 0,, A LJNN RIIL%Bk. P.E. FOR INSULATED GLASS INSTALLATIONS ABOVE 30' IN THE HVHZ, OR FOR SAFETY GLAZING APPLICATIONS PER THE FBC, THE OUTBOARD LITE (CAP) MUST BE TEMPERED. P.E#58705 1BY FOR SPACING W D BUCK •.' I 9 0 4 0 0 SWEEP LOCK OPTIONAL TO EGRESS LOCK AT SILL TYPICAL ANCHORS SEE ELEV. FOR SPACING 4 WOOD BUCKS AND METAL STRUCTURE NOT BY CGI WOW. MUST SUSTAIN LOADS IMPOSED BY GLAZING SYSTEM AND TRANSFER THEM TO THE BUILDING STRUCTURE. O I 14 1 '• Q .. •�. de ° a.. ' ••d •' ! I a EDGE DISi.-• .a •• m 8 EDGE •• v j s • ''• .• • 9 .' TYPICAL ANCHOI • DIST. ... ••' a TYPICAL DHORS I • SEE ELEV. FOR SPACING 3Y 11mic SEE 'w wnnn a FORS CING / j I MIAA11-DADE COUNTY APPROVED I MUWON & MUWON ANCHORS _ II SEE SEPARATE NOA m n�EDG DIST. TYPICAL ANCHORS TYPICAL ANCHORS -SEE ELEV. 'SEE ELEV. FOR SPACING FOR SPACING ICAL ANCHORS: SEE ELEV. FOR SPACING 1 /4" DIA. TAPCON BY 'ffW' (Fu=125 KSI, Fy-100 .KSI) 1/4" DIA. ULTRACON BY-'ELCO' (Fu=177 KSI, Fy-155 KSI) 1 /4" DIA. ULTRACON+ BY 'DEWALT' (FU-164 KSI, Fy=148 KSI INTO 2BY WOOD BUCKS OR WOOD STRUCTURES 1-3/8" MIN. PENETRATION INTO WOOD THRU 1 BY BUCKS INTO CONC. OR BLOCKS 1-1/4" MIN. EMBED INTO CONCRETE (HEAD/SILL/JAMBS) 1' 1/4" MIN. EMBED INTO BLOCKS (JAMBS) DIRECTLY INTO CONCRETE OR BLOCKS 1-1/4" MIN. EMBED INTO CONCRETE (HEAD/SILL/JAMBS) 1-1/4" MIN. EMBED INTO BLOCKS (JAMBS) #14.SMS OR SELF DRILLING SCREWS (Fu-74 KSI, Fy=57 KSI) INTO MIAMI-DADE COUNTY APPROVED MULLIONS OR INTO METAL STRUCTURES (HEAD/SILL/JAMBS) (3) THREADS MIN. PENETRATION BEYOND SUBSTRATE ALUMINUM : 1/8" THK. MIN. (6063-T5 MIN. STEEL 1/8" THK. MIN: (Fy = 36 KSI MIN. (STEEL IN CONTACT WITH ALUMINUM TO BE PLATED OR PAINTED) TYPICAL EDGE DISTANCE INTO CONCRETE AND MASONRY = 2-71/2" MIN. INTO WOOD STRUCTURE = 1" MIN. INTO METAL STRUCTURE ='3/4" MIN. WOOD AT HEAD, SILL OR JAMBS 5G=0.55 MIN. CO)CRETE AT HEAD, SILL. OR JAMBS fc = 3000 PSI MIN. C-9q HOLLOW/FILLED BLOCK AT JAMBS fm - 2000 PSI MIN. JCT REVISED flyingwith the Florida , C.d. _ M1am1-pace Produc YM"trol ADDED ANCHOR TYPE, - JR - 07/07/20 0 •d a it o O J N 3rOp O O N u z Y,0 ZO w � d C5 ~ ca =.ii L . ux Rip W LSZ L S v 7 aN lajr o (7 'JMO adz j x lL W O y U J � o K 0 v m o! y ? Tn C xO U) raa45 WgF Pru W U. 0 0 Ln =o o p w 0 Zgxg w z o UmS 5-! •osgp T--s ``711\11111 11l�!!i .. Ny LYNIV 41 No.. 5 J8705' • fr ST E6 F 810NAL 1' y_y A LYNN MILLER, P.E P.E# 58705 MAX. FOR SPACING METAL STRUCTURE o^E_ DIST. TYPICAL ANCI c ~. 0 1 BY WOOD BUCKS ' 4 1 O 1 LN14.X 1° FH. SMS. EXTERIOR FLANGE & FLANGE ADAPTOR FRAME. SHIMS - —"' SEE ELEV. _ • SPACING ' �.> FLANGE ADAPTOR FRAME PRODUCT REVISED as Complying with the Florida BuildingCodNOA-No. 20-0722.09 Ez Iratlon Date• 9/22/ ByOBam OISf. )13Y A - �ade ProducrCo trol t• .o El. ai -414" MAX. a o — WOOD ANCHORS O nW �I INTALLAnON DETAILS SHOWN ON PAGES 4 AND 5 APPLY TO BOTH FLANGE FRAME AND FLANGE ADAPTOR FRAMES. Y S �11cII11 O aloe O �. G11 # 2 Z pZ�o, 0 u D Wvvo K O Z y �ZWv 'aN K o>� JMO LL Z S y = Lu J O A O't A G ? 7354S - •y oy ca O' p�C yxoQ) _ W inw Z 3 o SLL .1 W rn o 0 w Z g U I` a n Un2.! fWA L+• l/l all. •asap 4 6 4cEY.. ;. Qom':'' •.F� -; a{ : No. 58705 G gip. �Gtb:'w� �O� . STf TE FORIO (V s TONAL IEr:�`�. A LYNN MILLER, P.E. P.E.# 58705 TYPICAL ANCHORS - - - - 1BY FOR SPACING FOR PAC - METAL EQUAL LEG FRAME WOOD BUCK STRUCTURE - - . ' .. .' 50GE*'PI7- ' - o w �.• �. `. d - •' d V a. n •• d .. < • a EDGE TYPICAL ANCHORS x� DIST. SEE ELEV. �� _______ __ _._ __ _ ________, • , I ' 'a d,. . {, a e d • • _ FOR SPACING m� rn c �r EDGE DIST I 1 I MIAMI-DADE COUNTY APPROVED 1 I � MUWON . MUWON ANCHORS � I •,1 . .. '• -•..' - snB.DIST. \ oo EDGE 30 � o x ^ �I SEE SEPARATE NOA II —EEDGE I .. PRODUCT REVISED as eomplying with the Florida . M3 � - E1 O N L-_______ _-_--_-_-___ � - _ Building Code ES I ---- - NOA-No. 20-0722.09 Ex Han pate • 9/22/2025 -11 jl II M2 rn _ T7TYPICAL ANCHORS- TYPICAL ANCHORS Y S5 SEE ELEV. .SEE ELEV. By: Y �i. ' II II III TYPICAL ANCHORS SEE ELEV. FOR SPACING MIAMI-DADE COUNTY FOR SPACING Mlam ado Produgt'Co trot FOR SPACING _ APPROVED MULLION do MULLION ANCHORS ANCHORS o f .I M9 1/4- BUCK WIDTH BUCK WIDTH SEE SEPARATE NOA BUCK WIDTH , SHIMSiy c D1 a a N ¢ SWEEP LOCK 1 OPTIONAL TO I I EGRESS LOCK AT SILL _ o ?3 p •naa © ES M3 c• I 1 ZK Z y Z. j • �p EDGE I I L > Y ^ O F W o E4 LJ DIST. `° d o N (m 0'1 u wO m .d #14 XI FF1. SMS. 0 co j 1 F3 EB i x o z _ ( c0 EQUAL LEG FRAME CAN BE INSTALLED DIRECTLY :? [ N Z -j 1aa45 INTO WOOD, CONCRETE OR METAL STRUCTURES O y 0 Li? .J 2 o'. 1 WITHOUT THE NEED OF A .WOOD BUCK. c `�' o o z. I- 2 3/8- MIN. o i j�j� c1�._ ♦♦ _- O N alil •�sa0 sauag . 1 i I I11/!// a. 2 3 8' MIN. _ ` : " < 1 •,e• •d.. �, mg ♦♦♦♦ •' jI° a • YYY1111 Y LYNN N _ d• TYCHO •8 I PICAL ANRS \♦♦,<�ON ��Cn�SF Ci 14 . \ ♦ ♦ .' P. ., • e .. I I SEE ELEV. FOR SPACING Q-; ••,'A E2 �- ♦♦; ..� No.58705 ,x WHEN USED THE MIN. WOOD BUCK' '• DEPTH SHALL BE 2%". THE USE OF 10 ''• 4T r �`� - •. r. a DEEPER OR BEVELED WOODBUCKS IS 0E TYP,AN�HORS PERMITTED.�` \♦♦♦ •'' _ . I SEE ELLICAL• f l l 1 I l l 113Y FOR SPACING - A LYNN MILLER, RE WOOD BUCK P.E.# 58705 m M oo v7 1/2' MIN. N n N EXTERIOR - 3� A OPTIONAL ...... _— J VENT HEIGHT �cm v O mn BUCK HEIGHT m NNNO o0 f D.L.OPG. N v m -- II II L 8 Via€ z� m v�{ Z r x gz m E2 p{„F 1/2' MIN. 1/4' MAX, Z o 1/4' MAY - GAP Sz v a - GAP - _C e y0 c !�m m A Z oil i Z LaV7. 5 G7 O c m � 0 J O m I mm i � N OOy N � N 0 Z .'Ll to 0 O m O v � c a td v c v � o � x m O ' H z Revision:OImpaCt Resistant PREPARED BY.A LYNN MILLER 3 m' m x m m Windows & Doors 1070 TECHNOLOGY DRIVE m 5 x O e ^ 0 `����a,,. �• ,r , WERESMONGER' N. VENICE, FL 34275 �3 Z 3 "Cr, T pj •'•�%`y% CGI WINDOWS AND DOORS. INC. (941)480.1600 D o o mQ 3780 W 104TH STREET z 'HIALEAH. FL 33018 ° 0 �•,?. REGISTRATION #29296 y. m P m '{ 3 - •Z ' O > a� O : _ (305) 593-659D mF _y.A +d� ei N SC �; = m :o O c _ SERIES 110 ALUM. SINGLE HUNG WINDOW (LM) 0 07/02/20 m M ' �_ ,� N oki to C" FIN DETAILS . e m JENS ROSOWSKI ° N N r C %G��'' 0 IN ; SH110 "SENTINEL" y 7 OF 9 02 SH110-LM-NOA 1TE6T PART / QUANTITY DESCRIPTION M&TRRIAL MANP./SUPPLIM/REMARKS El CGI-100 1 FRAME HEAD 6063-Te - E2 CGI. 101 1 FRAME SILL 6063-T6 - E3 CGI-102 2 FRAME JAMB 6063-T6 - E4 CGI-103 1 MEETING RAIL 6063-T6 - E5 CGI-104 1 LOCK RAIL 6063-T6 - E6 CGI-105 1 HANDLE RAIL 6063-T6 - E7 CGI-106 2 SASH RAIL - 6063-T6 - EB CGI-107 AS READ. 5/16" GLAZING BEAD 6063-T5 E9 CGI-10B AS READ. 0.700" GLAZING BEAD 6063-T5 - E10 CGI-109 AS READ. FRONT FLANGE ADAPTOR 6063-TG - E11 CGI-110 AS REQD. NAIL FIN ADAPTOR 6063-T5 - E12 CGI-135 1 FLANGE FRAME HEAD 6063-T6 - E13 CGI-136 2 FLANGE FRAME JAMB 6063-T6 - E14 CGI-137 1 FLANGE FRAME SILL 6063-T6 - E17 CGI-605 OPTIONAL 'SCREEN FRAME -6063-T5 - M1 6GI-382V AS REQD. GLAZING BULB VINYL (DUROMETER 75-80 SHORE A) PVC - M2 CGI-111" OPTIONAL SCREW COVER - PVC PROTOTYPE OR EQUIV. M3 CGI=112 AS RE OD. EQUAL LEG COVER/SHIM, 3" LONG AT ANCHOR LOCATIONS PVC - M9 SUPER BOOST 2/ WDW. SPIRAL BALANCE - BSI OR EQUN. M10 - 2/ WDW. BLOCK/TACKLE BALANCE - BSI OR EQUIV. M11 W23201NG AS REQD. PILE WITH CENTER FIN WOOL ULTRAFAB OR EQUIV. M12 CGI-129 1/ WDW. EGRESS�LOCK ALUM. SULLIVAN M13 CGI-131 2/ WDW. HANDLE RAIL END CAP NYLON" M&M M14 " E26018WN - -D BULB-T SLOT PVC ULTRAFAB OR EQUIV. M15 CGI-133 4/ WDW. SASH GUIDE(SPIRAL BALANCE) NYLON M&M , M16 CGI-130 2/ WDW. SASH TOP GUIDE(SPIRAL BALANCE NYLON M&M M17• A30730401-32 - 1/ WDW. CAM LOCK - ZINC TRUTH'OR EQUIV. M18 .CGI-132 2/ WDW. SASH STOP, 2" LONG PVC PROTOTYPE OR EQUIV. M19 - - 2/ LITE' - SETTING BLOCK - - EPDM - DUROMETER 85±5 SHORE A M20 CGI-125 2/ WDW. SASH CAM (B/T BALANCE) - NYLON. M&M M21 - 2/ WDW. B/T BALANCE TAKE OUT CUP - BSI OR EQUIV. M22 146-6 2/ WDW. WEEP COVER NYLON AMESBURY OR EQUN M23 CGI-134 - SILL SPACER PVC PROTOTYPE OR EQUIV. S2 - 2 OR 3/CORNER $ 10 X 1 1/4" LG. PHL PH. SMS ST/ST. ASSEMBLY SCREW - - S4 - 4/ WDW. $ 8 X 1/2" PH. "SMS. ST/ST BALANCE BRACKET SCREW - - S5 - 2/ WDW. 6 X -1" LG. FH. SMS Sr/Sr.SPIRAL B. ASSEMBLY - - S6 2/ LOCK # 6 X 1/2" LG. FH. SMS. ® CGI-133 & CAM LOCK - - Q , o � .Aea uaJ ro O m aiup 0_ O Z } ^ O W Z dp . O Z LL 0 uMOlp w=W� w Um w Z KU Ss U, Z 0M0 IL 6- 2i O 2 y Z w J O CD N O N ff K Z N (q iaa45 OC oRoW 3o J K w Z�m. tp'O <ym Q w ~ IZ_I-- E c 3�LLm $ $ y LL .O 0 Z w !/I �. n J �3 mgo Vi U M 2 m to aliU •asap seises `�L111111111j � � .. ' LICENSE •. �� No.58705 G' C) . �E F u ' \(lu YO&iAL ''/Ili i I I111�` A LYNN MILLER, P.E. P.E.# 58705 zsos oss zsos .ohs 1.550 1.880 sz s2 � 1.245 .745 ._0�6: OBS .745 TYP. L015 E72 1.015 et O50 kt1 PRODUCT REVISED as complying with the Florida code FLANGE FRAME HEAD FLUSH FRAME HEAD NAIL FIN ADAPTER ..20-0722.09 NDA-No. -1.583 1.583 1007 -+ . Expiration Date•- 9/22/2025 �-t , t L-O�. Mlam4ade ProducMq trol• 745 _ . 065 TYP.. 065 TYP. 065 2.113 TYP. 1.368 I 3.675 1.429 - 3.175 3.175 1.015 - VENT TOP CORNER z 1.429 .065 • .500 1.220-_ E4 MEETINGRAIL FRAME TOP CORNER ' 1.000IF - .500 2.50s n O '^ail e14 O FLANGE FRAME SILL FLUSH FRAME SILL .1.043 > 12 N o 00 F v O .W d = .500 - 1.301 1.301 1.788 _ m O o in Z m ❑ ur�0 (o F.065 - 085 TYR .. .065 O65 TYP. 065 TYP. S2 U U d 51 a z ^ W o sZs 7 O .. 'oN 9M0 rn 2.440 2 440 1.015 I i a o Z j = o `o (3 a in � 0 w o r0 1.015. 1.015 O LOCK RAIL I FRAME BOTTOM CORNER VENT BOTTOM CORNER w C7 0 O J-js .. 2.195� • .745 .745 W 2.048 eta 2.346. O - o z °D y o E' 3�"0 ¢ O Z 0 F Z w FLANGE FRAME JAMB FLUSH FRAME JAMB 1.892 065 1.043TYP: Z o 0' 3.490 -, � o.705 W o 45050 .050TYP. 7YP 31L S2 1.015 11111111i,64 e6p1Y LYI�N� .,. HAND RAIL \ .•' LIGENS /C�� ..745 .665 .875 O 5/15" GLAZING BEAD O .700" GLAZING BEAD . �1.450 ,180�.�G ��` _ .� : No. 587D5 ^_ -0 - �T •• S E F CUB: ���SS'•F<OR10P.••�G��� 1.395 r L-P..180 1.449 .293 .050� .080 �- .550 .050 '/,, 01VAL.1E��`� .065 1.413 u3 FRAME COVER 0FLUSH SCREW COVER O SASH RAIL Et0 FLANGE ADAPTOR aLYP.E#6B705 PE