Loading...
HomeMy WebLinkAboutST LUCIE DRAWINGS.pdfELECTRICAL SERVICE PORT ST. LUCIE, FLORIDASPECIFICATION GRADE GROUNDING TYPE, NEMA TYPE 5-20.2. ALL PANELS AND DISCONNECTS SHALL BE LABELED REGARDING LOADS DIRECTORIES. LABEL EACH CIRCUIT WITH ACTUAL ROOM NUMBERS OR CONTAIN ADEQUATE INFORMATION TO BE COPIED AND USED AS PANEL LOADS SERVED. THE PANEL SCHEDULES SHOWN ON THE PLANS DO NOT 1. PROVIDE EACH BRANCH CIRCUIT PANEL WITH A DIRECTORY INDICATING ROOM NAMES SERVED, SUCH AS "RECPT 109, 110, 111".SERVED AND WHERE SERVED FROM.4. LABEL EACH POWER JUNCTION BOX WITH AN INDELIBLE MARKER 3. USE ENGRAVED PLAQUES FOR LABELING LARGE EQUIPMENT.INDICATING THE CIRCUIT NUMBERS CONTAINED WITHIN.SECTION 16195 - ELECTRICAL IDENTIFICATION3. OUTDOOR BELOW GRADE PULL BOXES SHALL BE NON-METALLIC OPEN-BOTTOM WITH NON-METALLIC NON-TRAFFIC RATED COVER, BROOKS OR EQUAL. DO NOT MAKE SPLICES IN BELOW GRADE PULL BOXES.THE LAST JUNCTION BOX.AND MOISTURE RESISTANT, TYPE THWN WITH A 600 VOLT RATING. HOMERUN FOR CIRCUITS LONGER THAN FIFTY FEET AS MEASURED FROM 7. WIRING DEVICES SHALL BE 20 AMP RATED, 120V HEAVY DUTY 4. PVC CONDUIT SHALL BE USED UNDERGROUND AND OUTDOORS ONLY. UNLESS INDICATED OTHERWISE. PVC IS APPROVED WITHIN CONCRETE WALLS.2. OUTDOOR DEVICE BOXES SHALL BE CAST FS TYPE WITH GASKETED COVERS, 5. WIRE SHALL BE COPPER UNLESS NOTED OTHERWISE ON THE PLANS, HEAT 6. MINIMUM WIRE SIZE IS #12 FOR POWER CIRCUITS. RUN #10 MINIMUM SECTION 16050 - ELECTRICAL BASIC MATERIALS AND METHODSELECTRICAL SPECIFICATIONS8. FOR DEVICES LOCATED ON OPPOSITE SIDES OF A FIRE RATED WALL,SPACE DEVICES NOT LESS THAN 24 INCHES APART.PRIOR TO ORDERING MATERIALS OR ROUGH-IN.REQUIREMENTS. IF THERE ARE INCONSISTENSISTIES, GET CLARIFICATION.ORDERING MATERIALS. CHECK VOLT/AMP RATINGS, AND MOUNTING/TRIM WORKING CLEARANCES AND FIRE RATINGS. VERIFY EQUIPMENT RATINGS PRIOR TO5. COORDINATE THE INSTALLATION WITH OTHER TRADES TO MAINTAIN PROPERAT BID TIME, THEN BE SPECIFIC IN EXCLUDING THEM.PRESENCE OF THE OWNER.INCLUDE ALL MATERIAL AND LABOR FOR A COMPLETE INSTALLATION.SPECIFICALLY NOTED ON THE PLANS TO BE RECONNECTED OR REUSED.FEE AND OTHER REQUIREMENTS IN THE BID. IF THESE FEES ARE NOT AVAILABLE6. CONTACT THE UTILITY COMPANIES PRIOR TO BID AND INCLUDE THEIR4. VISIT THE JOBSITE PRIOR TO BID AND EXAMINE THE EXISTING CONDITIONS.2. ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECT, EXCEPT WHERE 3. ALL SYSTEMS SHALL BE TESTED FOR PERFORMANCE VERIFICATION IN THE 1. ALL WORK AND EQUIPMENT SHALL BE IN COMPLIANCE WITH THE FOLLOWING CODES AND STANDARDS:SECTION 16010 - ELECTRICAL GENERAL PROVISIONSPVC ABOVE GROUND INDOORS IS PERMITTED TO THE FIRST BOX OR PANELUNLESS NOTED OTHERWISE.B. NATIONAL ELECTRICAL CODE, 2017C. NATIONAL FIRE ALARM CODE, CURRENT EDITION.A. FLORIDA BUILDING CODE 20201. ALL WIRING METHODS AND MATERIALS ALLOWED BY THE N.E.C. ARE APPROVED. LIMITED TO ANGLE FRAMING, EQUIPMENT SUPPORTS,12. DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL PLANS FOR DIMENSIONS.11. ALL BARE METAL SURFACES SHALL BE PRIMED AND PAINTED TO PREVENT ANY RUST, INCLUDING BUT NOT MOUNTING HARDWARE, ETC.13. ALL RACEWAYS SHALL HAVE A GREEN GROUNDING14. ALL NEW BREAKERS IN EXISTING PANELS SHALL15. CONTRACTOR SHALL FIRESTOP ALL NEW AND20. SURGE PROTECTION SHALL BE PROVIDED ON ALL16. EC SHALL FURNISH AND INSTALL EXPANSION JOINTS17. COORDINATE ALL MECHANICAL LOADS, VOLTAGES AND18. EC MAY INSTALL MULTIPLE CIRCUITS INDICATED ON22. NO SPLICES SHALL BE PERMITED IN UNDERGROUND/6. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND GENERAL CONTRACTOR ON REQUIREMENTS FOR STRUCTURAL SUPPORT AND FRAMING FOR ALL ELECTRICAL EQUIPMENT AND SYSTEMS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND VERIFYING STRUCTURAL SUPPORT AND FRAMING.7. THE SIZE, LOCATION, WEIGHT, AND NEC ARTICLE 110/384 REQUIRED SERVICE CLEARANCES OF EQUIPMENT INSTALLED UNDER DIVISION 16 ELECTRICAL SHALL BE COORDINATED WITH ALL OTHER TRADES.8. WHERE CROWDED LOCATIONS EXIST OR WHERE THERE IS A POSSIBILITY OF CONFLICT BETWEEN TRADES, CONTRACTOR SHALL MAKE COMPOSITE DRAWINGS SHOWING THE EXACT LOCATION OF DUCTS, CONDUIT AND EQUIPMENT. DRAWINGS SHALL BE BASED ON FIELD MEASUREMENTS AND, AFTER CONSULTATION AND AGREEMENT BETWEEN THE TRADES, SHALL BE APPROVED BY THE ARCHITECT BEFORE INSTALLATION OF THE WORK.9. ELECTRICAL CONTRACTOR IS TO PROVIDE PULL STRINGS IN ALL EMPTY CONDUIT AND RACEWAYS WITH10. ALL RACEWAY TERMINATION'S SHALL HAVE BUSHINGS AND BE GROUNDED WHERE RACEWAY IS METAL. LABELING TAGS AT EACH END.5. CONTRACTOR SHALL NOT CONCEAL ANY WORK UNTIL INSPECTED BY ELECTRICAL INSPECTOR AND/OR ARCHITECT/ENGINEER. CONTRACTOR SHALL NOTIFY A/E OF A SCHEDULED INSPECTION TIME WITHIN 72 HOURS. CONTRACTORS SHALL NOT CONCEAL WORK UNTIL APPROVED. SPECIFICATIONS FOR REQUIREMENTS.1. ALL WORK SHALL COMPLY WITH CODES AND STANDARDS LISTED IN THE SPECIFICATIONS.2. THE DRAWINGS ARE DIAGRAMATIC AND THE OMISSION OF AN ITEM NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM DOES NOT RELIEVE THE CONTRACTOR FROM FURNISHING AND INSTALLING THAT ITEM.3. NOTIFY ARCHITECT/ ENGINEER OF ANY CONFLICTS PRIOR TO PURCHASING EQUIPMENT AND PRIOR TO CUTTING4. PRIOR TO BID, COORDINATE ALL ELECTRICAL WORK WITH MECHANICAL WORK AND OTHER TRADES. SEE OPENING. GENERAL NOTES: CABLES ENTERING/ EXITING BUILDINGS THAT CONNECT TO FLUSH IN-GRADE PULL BOXES WITHOUT PRIOR WRITTEN APPROVAL BY OWNER. ELECTRICAL EQUIPMENT. RESPONSIBLE FOR VERIFYING CONDUIT FILL AND AT ALL LOCATIONS WHERE BUILDING EXPANSION JOINTS LOCATIONS WITH MECHANICAL CONTRACTOR AND MAKE NECESSARY ADJUSTMENTS WITHOUT EXTRA CHARGES. PANEL SCHEDULE IN A SINGLE CONDUIT. EC SHALL BE CONDUCTOR DERATING. ARE USED. HIGHEST RATED BREAKER IN THAT PANEL. APPROVED FIRESTOP SYSTEM RATED FOR THE AND INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S INSTRUCTIONS. HAVE AN AIC RATING EQUAL TO OR GREATER THAN THE EXISTING ELECTRICAL PENETRATIONS IN FIRE RATED PARTITIONS (WALLS, FLOORS OR CEILINGS) WITH AN APPLICATION. FIRESTOP SYSTEM SHALL BE UL LISTED CONDUCTOR.19. ANY REDUCTION IN CABLE SIZE TO FIT ON LUGS IS THE RESPONSIBILITY OF THE CONTRACTOR IF CALLED FOR ON THE DRAWINGS OR NOT.SECTION 16120 - WIRES AND CABLES21. ALL WIRE AND CONDUIT SIZES SHOWN ARE BASED ON THE LENGTH OF THE ASSUMED ROUTING OF THE WIRE AND CONDUIT AND VOLTAGE DROP COMPLIANCE. CONTRACTOR SHALL VERIFY THE WIRE AND CONDUIT SIZE BASED ON THE ACTUAL LENGTH OF THE ROUTE AND ADJUST AS REQUIRED MEETING ALL REQUIRED VOLTAGE DROPS.THAT MAY REASONABLY BE EXPECTED TO REMAIN IN PLACE SHALL BE DETERMINE EQUIPMENT EXPECTED TO REMAIN IN PLACE, PRIOR TO COMPLETION OF THIS PROJECT. MEET WITH THE OWNER/USER TO PROTECTED DURING CONSTRUCTION AND SHALL BE OPERATIONAL AT SECTION 16030 - ELECTRICAL DEMOLITIONDURING CONSTRUCTION, UNLESS OTHERWISE INDICATED ON THE PLANS.1. REMOVE AND DISPOSE OF ALL MATERIALS ABANDONED OR DEMOLISHED 2. EXISTING CIRCUITS, SUCH AS THOSE FEEDING HVAC, AND OTHER SYSTEMS BEGINNING DEMOLITION.4. AC, MC, BX CABLES PERMITTED AS ALLOWED BY LOCAL CODE. 2. ALL MAINS AND FEEDERS ARE TO RUN THE ENTIRE LENGTH INCONTINUOUS PIECES WITHOUT JOINTS OR SPLICES. JOINTS INBRANCH CIRCUITS SHALL OCCUR ONLY AT OUTLETS AND JBOXES WITH NO SPLICES OR TAPS IN CONDUITS.1. LIGHTING AND RECEPTACLE, BRANCH MOTOR POWER AND PANELFEEDERS CIRCUITS SHALL HAVE TYPE THHN/THWN/MTWINSULATION BUILDING WIRE. ALL CONDUCTORS INSTALLED INDAMP OR WET LOCATIONS OR UNDER GRADE SHALL HAVEINSULATION MEETING NEC. ALL WIRING INSTALLED INHIGH-TEMPERATURE AREAS SHALL HAVE TYPE AVA INSULATION.3. PHASE COLORS PER ELECTRICAL STANDARDS.400A/3P400A/3P600A/3P600A/3P600A/3P600A/3P400A/3P1200A/3P1200A3P3P400A/KGENERATOR1600A/3PMAIN BREAKEREXISTING MAIN DISTRIBUTION PANEL"MDP"(UTILITY POWER)#2 BREAKERGENERATOR#1 BREAKEREXISTING MAIN EMERGENCY DISTRIBUTION PANEL"EMDP"(GENERATOR POWER)NEW EMERGENCY DISTRIBUTIONCENTER1200A, 480V, 3 PHASE, 4WNEMA N1, MBO, LOAD BREAKWITH NO OVERCURRENT PROTECTIONNEW MTSBYPASSUTILITYPOSITIONBYPASSGENERATORPOSITIONATS BYPASS600A, 480V,4P,4WNEMA N1, NF, DTSSNEW ATSNORMALEMERGENCYATS BYPASS400A, 480V,4P,4WNEMA N1, NF, DTSSNEW MTSBYPASSPOSITIONNORMALPOSITIONATS BYPASS600A, 480V,4P,4WNEMA N1, NF, DTSSSWAP OUTEXISTING FORNEW ATS1200A3PCAMLOCK RECEPTACLELOAD BANK DOCKINGNEWCAMLOCK RECEPTACLEPORTABLE GENERATORNEWDOCKING STATIONLOAD DISTRIBUTIONPANELEXISTING1200A, 480V,3 PH,3W,N3R,MLO2-2"C EACH WITH 4-#3/0 W/#3GUNDERGROUND2-2"C EACH WITH 4-#3/0 W/#3GUNDERGROUND2-2"C EACH WITH 4-#3/0 W/#3GUNDERGROUND2-2"C EACH WITH 4-#3/0 W/#3GUNDERGROUND2-2"C EACH WITH 4-#3/0 W/#3GUNDERGROUND2-2"C EACH WITH 4-#3/0 W/#3GUNDERGROUNDLOAD4-3 1/2"C EACH WITH 4-600KCM AND #3/0GRENOVATION RISER 1200A, 480V,3 PH,3W,N3R,MLO3-3 1/2"C EACH WITH 4-600KCMAND #3/0G400A/3P11111FIELD CHANGESKAG3/22/22