HomeMy WebLinkAboutEngineering Component & Cladding Pressure Calculator98205 | 44628-6842361111 | Page 1/4 Date: March 8th, 2022 ASCE 7 Components & Cladding Wall Pressure Calculator Prepared For: Newman Windows & Doors 16140 E. Cornwall Dr. loxahatchee FL Project: Matay Project Address: 5159 N A1A #714 Hutchinson Island Florida 03/08/2022 Box for Engineer Seal Only-Original Rqd for Permit & Use ** See below for sealing engineer. ** This document has been signed by one of the following engineers. Refer to name in stamp for applicable engineer. C/A 9885 | Frank Bennardo PE 0046549 | Richard Neet, PE 86488 The following has been considered in determining allowable stress design (ASD) wall opening pressures for the above-referenced location. Contractor-Provided Input: ASCE: ASCE 7-16 (2020 FBC 7th ED, 2018 IBC) Wind Velocity: 170 MPH Exposure Category: D Kd: 0.85 Kzt: 1 Minimum Building Dimension: 50FT Mean Roof Height: 80FT Lowest Installation Elevation: 0FT ROOF SLOPE: SLOPED (>=10°) Number Of Openings: 7 Shutter: NO Mark: 1 Height Of Opening: 37 IN Width Of Opening: 35 IN Zone: 4 Mark: 2A Height Of Opening: 36 IN Width Of Opening: 35 IN Zone: 4 Mark: 2B Height Of Opening: 35 IN Width Of Opening: 35 IN Zone: 4 Mark: 3A Height Of Opening: 36 IN Width Of Opening: 35 IN Zone: 4 Mark: 3B Height Of Opening: 36 IN Width Of Opening: 35 IN Zone: 4 Mark: 3C Height Of Opening: 36 IN Width Of Opening: 35 IN Results: Based on the above, the following ASD design pressures apply for the opening marks which shall correspond with contractor-supplied building layout: a: 5 FT Mark: 1 Wall Positive Pressure: 56.2PSF Wall Negative Pressure: -56.2PSF Mark: 2A Wall Positive Pressure: 56.2PSF Wall Negative Pressure: -56.2PSF Mark: 2B Wall Positive Pressure: 56.2PSF Wall Negative Pressure: -56.2PSF Mark: 3A Wall Positive Pressure: 56.2PSF Wall Negative Pressure: -56.2PSF Mark: 3B Wall Positive Pressure: 56.2PSF Wall Negative Pressure: -56.2PSF Mark: 3C Wall Positive Pressure: 56.2PSF Wall Negative Pressure: -56.2PSF Mark: 4 Wall Positive Pressure: 51.1PSF Wall Negative Pressure: -53PSF 401 West Atlantic Avenue, R10 Unit #219, Delray Beach, FL 33444 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com NOTE: This digitally sealed file is being provided in an unlocked format at the building departments request. Please review any changes/markups to ensure integrity of the source document to prevent fraud 98205 | 44628-6842361111 | Page 2/4 Zone: 4 Mark: 4 Height Of Opening: 79 IN Width Of Opening: 105 IN Zone: 4 401 West Atlantic Avenue, R10 Unit #219, Delray Beach, FL 33444 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com 98205 | 44628-6842361111 | Page 3/4 Design pressure results are in accordance with the Building & ASCE 7 codes listed above for an ENCLOSED structure only (Gcpi=+-0.18). Results are based on contractor-supplied data and are not field verified by this office. Inputs shall be verified by others prior to permit & use. Contractor has consented that they have consulted with this firm to submit accurate data. Selection of all components & their respective approvals shall be by others and are to be within the ASD design pressure limitations stated herein. Results only valid with original or verifiable digital seal by a licensed PE of this firm. For more information on any of the terms listed herein, or to use a wind pressure design tool, visit EngineeringExpress.com/Wind. See Following Page(s) for Layout and Dimensional Figures. 401 West Atlantic Avenue, R10 Unit #219, Delray Beach, FL 33444 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com 98205 | 44628-6842361111 | Page 4/4 Powered by TCPDF (www.tcpdf.org) 401 West Atlantic Avenue, R10 Unit #219, Delray Beach, FL 33444 (954) 354-0660 | (866) 396-9999 Team@EngineeringExpress.com | EngineeringExpress.com