HomeMy WebLinkAboutTrussL '
ENGINEERING COVER SHEET
i
Professional of Record: Not Specified
Permit Number: Miscellaneous:
The information in this box is for administrative purposes only and is not part of this engineering review.
Truss Fabricator: Spec Truss
Customer: Jack Early
Job Reference: Early Res
Location: 10851 S Ocean Drive Lot#109
Job Number: 190990
Date: 3/4/2021
Notes: Please see individual truss design
drawings for load criteria, applicable codes,
specific loading and ITW BCG View
version number.
Roof TCL
20
Floor TCL
50 Building Code: FBC 7th Ed. 2020 Res.
Roof TCDL
20
Floor TCD
15 Wind: 170 MPH ASCE 7-10 Residential - CAT II Exposure: C
Roof BCL
0
Floor BCL
0
Roof BCD
10
Floor BCD
5
Non Concurrent Load: 10
Page
ID
I Seq.Num.
Page
I ID
I Seq.Num.
Page
ID
I Seq.Num.
1
Al
1339479
339509
339385
339377
339380
2
5
8
11
1 A2
AG1
1-1J5
AA
1339464
339401
339396
339393
3
6
9
12
1 A3
EJ5
1-1J513
1 J3
1339517
339381
339387
1339379
4
A4
7
EJ5A
10
J1
13
J3A
C a r I G. Forbes 1000 S. Dixie HWY W.
P E# 2 0 6 9 9 Pompano Beach FI 33060
A Professional Engineer's Seal affixed to this index sheet indicates the acceptance of professional
Engineering responsibilities for individual truss components fabricated in accordance with the
listed and attached Truss Specification Sheets. Determination as to the suitability of these
individual truss components for any structure is the responsibility of the Building Designer, as
defined in ANSI/TPI 1-2002 , Section 2.2 Permanent files of the original Truss Specification Sheet
are maintained by Carl G. Forbes P.E. #20699. Questions regarding this Index Sheet and/or the
attached Specification Sheets may be directed to the truss fabricator listed above or Carl G.
Forbes P.E. #20699 Phone: 561-686-4000
iCommand by Alpine, an ITW Company
Page 1 of 1
RECEIVED
MAR 17 2021
Qermitting Department
St. Lucie Ccuryt-
Date: 3/4/2021
ST_ENGCOVERSHEET
Truss Label: Al Ply: 1 Job Number: 190990
Qty: 2 Early Res /Jack Early /Early Res
Wgt: 98.0 Ibs 03/04/2021
7 3.11/9, 8'
/// 1 5X4
\\\1.SX4=4X10(**)(!1
=2.5X4 =JAO =L.OM
SFN, T PLATE REQ.
II ut/4T 21'8-1 /2"
227'
7'
SEAT PLATE REQ.
Loading Criteria (psf)
Wind Criteria
Snow Criteria (Pg,Pf!n PSF)
Defl/CS1 Criteria
♦ Maximum Reactions (Ibs)
TCLL: 50.00
Wind Std: ASCE 7-16
Pg: NA Ct: NA CAT: NA
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TCDL: 15.00
Speed: 170 mph
Pf: NA Ce: NA
VERT(LL): 0.243 G 999 360
Loc R+ / R- / Rh / Rw / U / RL
A 1688 /- /- /611 /708 /150
BCLL: 0.00
Enclosure: Closed
Lu: NA Cs: NA
VERT(CL): 0.385 G 658 240
BCDL: 5.00
Risk Category: II
Snow Duration: NA
HORZ(LL): -0.092 G - -
H 1557 /- /- /546 /670 /-
Des Ld: 70.00
EXP: C Kzt: NA
HORZ L 0.157 G - -
(T )
Wind reactions based on MWFRS
Building Code:
NCBCLL: 10.00
Mean Height: 25.00 ft
Creep Factor: 2.0
p
A Brg Width = Min Req = 2.8
Soffit: 2.00
TCDL: 7.0 psf
FBC 7th Ed. 2020 Res.
Max TC CSI: 0.901
9.5
H Brg Width = 9.5 Min Req = 1.8
Load Duration: 1.00
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
TPI Std: 2014
Max BC CSI: 0.741
Bearings A & H are a rigid surface.
Bearings A & H require a seat plate.
Spacing: 24.0 "
C&C Dist a: 3.00 ft
Rep Fac: Yes
Max Web CSI: 0.279
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: not in 4.50 ft
FT/RT:10(0)/10(0)
Mfg Specified Camber.
Chords Tens.Comp. Chords Tens. Comp.
GCpi: 0.18
Plate Type(s):
VIEW Ver: 20.02.o0A.1020.21
A- B 137 -508 E - F 1037 -2051
B - C 948 -2214 F - G 1035 -2398
Wind Duration: 1.33
WAVE
Lumber
C - D 936 -1846 G - H 1094 -2539
Top chord: 2x4 SP SS;
D - E 1113 -2198
Bot chord: 2x4 SP #1; B2 2x4 SP SS;
Webs: 2x4 SP #2;
Lt Slider: 2x6 SP #2; block length = 1.833'
Maximum Bot Chord Forces Per Ply (Ibs)
Rt Slider: 2x6 SP #2; block length = 1.833'
Chords Tens.Comp. Chords Tens. Comp.
A- K 1821 -634 J -1 2198 -821
Plating Notes
K- J 2198 -821 I - H 2O32 -738
(1) - plates so marked were sized using 0% Fabrication
Tolerance, 0 degrees Rotational Tolerance, and/or
zero Positioning Tolerance.
Maximum Web Forces Per Ply (Ibs)
(**) 2 plate(s) require special positioning. Refer to
Webs Tens.Comp. Webs Tens. Comp.
A - B 1037 -2045 E - I 239 -595
scaled plate plot details for special positioning
requirements.
C - K 782 -243 I - F 629 -174
Wind
K-D 365 -892
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Additional Notes
Calculated vertical live load deflection is 0.08" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.13" at X = 0-
0- 0.
Calculated horizontal live load deflection is 0.09"
Calculated horizontal total load deflection is 0.16"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U353 live and U207 total load.
Carl G. Forbes
PE#20699
-WARNING" READ AND FOLLOWALL NOTES ON THIS DRAWING!
"*IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handlingshipping, installing and bracing. , Refer to and follow the latest edition of BCSI (Building
Component Safety Information, b TPI an SBCA) r safety practices prior to performing these functions. Installers shall provide temporary p
bracing per BCSI.. Unless noted oytherwise, top chord shall have properly attached structural sheathin4 and bottom chord shall have a properly
attacheo rigid ceiling Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10,
as applicable. Apply plates to each face of truss and position as shown above and on the Join Details, unless noted otherwise. Refer to SPEC
drawings 160A-Z for standard plate positions. us AWUSS
Pk 155D555Woo
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing, any failure to build the fax: nsaa577[ie
truss in conformance with ANSI PI 1, or for handling, shipping,, mstalla ion and bracin of trusses. A seal on this drawing or cover pa e
listing this drawintq indicates acceptance of professional enc �sneering responsibility solely or the design shown. The suitability and use ofris
drawing for any s ructure is the responsibility of the BuildinggDesigner per ANSI/T I 1 Sec.2. Page 1
For more information see these web sites: Alpine: al ineitw.com TPI: t inst.or ; SBCA: sbcindust .com; ICC: iccsafe.or ; AWC: awc.or —�--
Truss Label: A2 Ply: 1 Job Number: 190990
j Qty: 2 Early Res /Jack Early /Early Res
Wgt: 107.8 Ibs 03/04/2021
i 9'
S 5X57/ 1.5X4
D E
47" i9'
=6X5
F
=2.5X4 III1.5X4 =H0308 1111.5X4 =2.5X4
SF-9T PLATE REQ.
1IIE_ 21'8-1/2"
22'7"
SEAT PLATE REQ.
Loading Criteria (psf)
Wind Criteria
Snow Criteria (Pg,Pf in PSF)
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 50.00
Wind Std: ASCE 7-16
Pg: NA Ct: NA CAT: NA
PP Deflection in loc Udefl U#
Gravity
Non -Gravity
TCDL: 15.00
Speed: 170 mph
Pf: NA Ce: NA
VERT(LL): 0.579 J 438 360
Loc R+ / R- / Rh
/ Rw / U / RL
A 1771 /- P
/622 /715 /192
BCLL: 0.00
Enclosure: Closed
Lu: NA Cs: NA
VERT(CL): 0.965 J 262 240
BCDL: 5.00
Risk Category: II
Snow Duration: NA
HORZ(LL): -0.196 G - -
1 1634 /- /-
/552 1669 /-
Des 70.00
EXP: C Kzt: NA
HORZ TL 0.327 G - -
( )
Wind reactions based on
MWFRS
Building Code:
CLLd*
NCBCLL: 10.00
Mean Height: 25.00 ft
Creep Factor: 2.0
A Br Width = 11.0
9
Min Re 2.1
q =
Soffit: 2.00
TCDL: 7.0 psf
FBC 7th Ed. 2020 Res.
Max TC CSI: 0.864
1 Brg Width = 9.5
Min Req = 1.9
Load Duration: 1.00
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
TPI Std: 2014
Max BC CSI: 0.891
Bearings A & I are a rigid surface.
Bearings A & I require a seat plate.
Spacing: 24.0 "
C&C Dist a: 3.00 ft
Rep Fac: Yes
Max Web CSI: 0.785
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: not in 9.00 ft
FT/RT:10(0)/10(0)
Mfg Specified Camber:
Chords Tens.Comp.
Chords Tens. Comp.
GCpi: 0.18
Plate Type(s):
VIEW Ver:20.02.00A.1020.21
A-B 125 -690
B - C 976 -2370
C - D 967 - 2164
E-F 979 -1936
F - G 1006 -2261
G - H 1037 - 2527
Wind Duration:1.33
WAVE HS
Lumber
Top chord: 2x4 SP SS;
D - E 859 -1635
H - I 1154 -2737
Bot chord: 2x4 SP SS;
Webs: 2x4 SP #2; W2 2x4 SP SS;
Lt Slider: 2x6 SP #2; block length = 1.833'
Maximum Bot Chord Forces Per Ply (Ibs)
Rt Slider: 2x6 SP #2; block length = 1.833'
Chords Tens.Comp.
Chords Tens. Comp.
A - N 1963 -695
L - K 1936 -605
Loading
Truss passed check for 20 psf additional bottom chord
N - M 1862 - 577
K - J 1920 - 599
live load in areas with 42"-high x 24"-wide clearance.
M - L 1936 -605
J -1 2218 -800
Wind
Maximum Web Forces Per Ply (Ibs)
Wind loads based on MWFRS with additional C&C
Webs Tens.Comp.
Webs Tens. Comp.
A - B 890 - 2035
O - E 360 - 976
member design.
Wind loading based on both gable and hip roof types.
C - N 196 -278
K - F 500 -187
D - O 730 -176
J - G 333 - 581
Additional Notes
O - M 229 -64
Calculated vertical live load deflection is 0.12" at X = 0-0-0.
Calculated vertical total load deflection is 0.20" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.20"
Calculated horizontal total load deflection is 0.33"
Allowable vertical deflection ratios are L/360 live and U240 total load.
Calculated vertical deflection ratios are L/224 live and U136 total load.
Carl G. Forbes
PE#20699
**WARNING** READ AND FOLLOW ALL NOTES ON THIS DRAW NGI
"IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handling shipping, installing and bracing. , Refer to and follow the latest edition of BCSI (Building
Component Safety Information, bY TPI an� SBCA) r saty practices prior to performing these functions. Installers shall rovide temporary
bottom have
bracing er BCSI., Unless noted otherwise, top chord shall have roperattached structural sheathin and chord shall
id Locations shown for lateral respaint of webs shall have bracinfq installed per BCSI sections
a pro erly
B3, B7 or Bg10,
attacheyri ceillnp. permanent
as applicabgle. Apply to each face, of truss and position as shown above and on the Join Details, unless noted otherwise.
Refer to
SPEC I RUSS
Oates
drawings 160A-Z for standard plate positions.
us Trsuss
Alpine, a division of ITW Buildin Com onents GroupInc. shall not be responsible for an deviation from this drawing,an failure to build the
P a
bracin trusses. A thi
36490
VH 166U68734W
`^� i66ll6"xe
truss in conformance with ANSI PI 1 or for handlig, shipping, installation and of seal on rawin or cover pa
listing this drawin indicates acceptance en Pneering responsibili��r solelyorthe design shown. The suitabilify and use MIS
of professional
drawing for any structure is the responsibility of the BuildinggDesigner per ANSI/TP1 1 Sec.2.
For more information see these web sites: Alpine: alpineitw.com; TPI: tpinst.org; SBCA: sbcindustry.com; ICC: iccsafe.org;
AWC: awc.org
P19e
—2 2
Truss Label: A3 Ply: 1 Job Number: 190990
s Qty: 2 Early Res /Jack Early /Early Res
Wgt: 112.0 Ibs 03/04/2021
Loading Criteria (psf)
TCLL: 50.00
TCDL: 15.00
BCLL: 0.00
BCDL: 5.00
Des Ld: 70.00
NCBCLL: 10.00
Soffit: 2.00
Load Duration: 1.00
Spacing: 24.0 "
1 r1" '
a4x4
aU5E C-4X5
12 6 92X4� H 103X7
p
T goH0508 C 195X5
C
o
03X4e J®3X4
8'
—M6(rC6) A K-5X8(C51
a2X4(C6 �2X4(C%
iUM -5 8M
_eJin
PLATE REQ.
i 7'3-12"
Wind Criteria
Wind Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.33
Lumber
Top chord: 2x4 SP SS; T2 2x6 SP M-26;
Bot chord: 2x4 SP SS; B2 2x6 SP M-26;
Webs: 2x4 SP #2;
Lt Slider: 2x6 SP #2; block length = 1.833'
Rt Slider: 2x6 SP #2; block length = 1.833'
Loading
Truss passed check for 20 psf additional bottom chord
live load in areas with 42"-high x 24"-wide clearance.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Sid: 2014
Rep Fac: Varies by Ld Case
FT/RT:10(0)110(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is 0.07" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.09" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.10"
Calculated horizontal total load deflection is 0.16"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U397 live and U292 total load.
SEAT PLATE REQ.
21'8-12"
83-12' 73-12" —j
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.236 L 999 360
VERT(CL): 0.362 L 700 240
HORZ(LL): -0.096 D - -
HORZ(TL): 0.153 D - -
Creep Factor: 2.0
Max TC CSI: 0.899
Max BC CSI: 0.476
Max Web CSI: 0.740
Mfg Specified Camber:
VIEW Ver: 20.02.00A.1020.21
Carl G. Forbes
PE#20699
7'3.11T
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
A 1814 /- A 1613
/719 /238
K 1671 A A /543
/673 /-
Wind reactions based on MWFRS
A Brg Width = 11.0 Min Req = 2.1
K Brg Width = 9.5 Min Req = 2.0
Bearings A & K are a rigid surface.
Bearings A & K require a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords
Tens. Comp.
A - B 233 - 532 F - G
592 - 362
B - C 955 -2424 G - H
970 -1988
C - D 969 -2241 H - I
1118 -2531
D - E 1002 -2069 I - J
1208 -2930
E - F 601 - 329 J - K
1196 - 3050
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - M 1979 - 644 L - K 2580 - 948
M - L 1985 - 643
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A - B 1100 -2295 L - H 1078 -406
D-M 310 0 L-I 523 -1033
E - G 1480 - 2601
**WARNING** READ AND FOLLOW ALL NOTES ON THIS DRAWING[
**IMPORTANT"* FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handlin shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
Component Safety Information, bv TPI and SBCA) for safety practices prior to performing these functions. Installers shall provide temporary
bracing per BCSI. Unless noted otherwise, top chord shall have properly attached structural sheathing) and bottom chord shall have a properly ��♦�'%
attachetl ri id ceiling Locations shown for permanent lateral restraint of webs shall have bracing insta led per BCSI sec ions B3, B7 or B'10,
as applicabgle. Apply plates to each face of truss and position as shown above and on the Join f Details, unless noted otherwise. Refer to SPEC truss
drawings 160A-Z for standard plate positions. us Truss
PH MUM=
Alpine, a division of ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing, any failure to build the TAX: JUD6373CIB
truss in conformance with ANSIQ PI 1, or for handling, shipping,, installation and bracing of trusses. A seal on this drawingg or cover page
listing this drawing indicates acceptance of professional en shipping,
responsibili��yr solely -for the design shown. The suitabiliC and use of pate
drawing for any structure is the responsibility of the BuildinggDesigner per ANSI/TPI 1 Sec.2. Dann
Truss Label: A4. Ply: 1 Job Number: 190990
Qty: 9 Early Res /Jack Early /Early Res
Wgt: 116.2 Ibs 03/04/2021
ling Criteria (psf)
_. 50.00
L: 15.00
L: 0.00
L: 5.00
Ld: 70.00
CLL: 10.00
t: 2.00
1 Duration: 1.00
:ing: 24.0 "
11'3-112"
F.AX4
11'3-1/2" -'
SEA'[ PLATE REQ, SEAT PLATE REQ.
-1f4T 21'8-1/2"
r 7' + 8'3-1/2" 'I' 7'3-1/2"j
- 22.7"
l —MAJ2"
Wind Criteria
Wnd Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.33
Lumber
Top chord: 2x4 SP SS; T2 2x6 SP M-26;
Bot chord: 2x4 SP #1; B2 2x6 SP #2;
Webs: 2x4 SP #2;
Lt Slider: 2x6 SP #2; block length = 1.833'
Rt Slider: 2x6 SP #2; block length = 1.833'
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Snow Criteria (Pg,Pf 1n PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Varies by Ld Case
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
The maximum horizontal reaction is 2147#
Calculated vertical live load deflection is 0.07" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.11" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.11"
Calculated horizontal total load deflection is 0.19"
Allowable vertical deflection ratios are L/360 live and U240 total load.
Calculated vertical deflection ratios are L/428 live and U265 total load.
***** BEARING ANALOG MODIFIED! *****
8' -i- 73-1/2" �I
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.244 L 999 360
VERT(CL): 0.437 L 580 240
HORZ(LL): -0.108 H - -
HORZ(TL): 0.193 H - -
Creep Factor: 2.0
Max TC CSI: 0.779
Max BC CSI: 0.605
Max Web CSI: 0.597
Mfg Specified Camber:
20.02.00A.1020.21
Carl G. Forbes
PE#20699
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
A 1702 /- /2147 /614 /712 /816
K 1576 /- /2147 /541 /662 /816
Wind reactions based on MWFRS
A Brg Width = 11.0 Min Req = 2.0
K Brg Width = 9.5 Min Req = 1.9
Bearings A & K are a rigid surface.
Bearings A & K require a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 76 - 563 F - G 372 -178
B - C 1009 - 2256 G - H 914 -1788
C - D 977 -2031 H - I 1071 -2264
D - E 941 -1850 I - J 1172 - 2690
E - F 453 -150 J - K 1159 - 2807
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - M 137 - 501 L - K 450 - 209
M - L 234 - 397
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A - B 973 - 2057 E - G 1220 - 2112
C - M 371 -581 L - H 1196 -431
D-M 615 -218 L-I 575 -1249
`"WARNING- READ AND FOLLOW ALL NOTES ON THIS DRAWING!
"*IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handlin shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
Component Safety Information, by TPI an SBCA) fo'r safety practices prior to performing these functions. Installers shall provide temporary
bracing per BCSI.. Unless noted otherwise, top chord shall have properyattached structural sheathing and bottom chord shall have a properly
attacheo rigid ceilm Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10,
as applicable. Apply Plates to each face of truss and position as shown above and on the Join Details, unless noted otherwise. Refer to SPEC
drawings 160A-Z for s andard plate positions. us fr uss
Pit P6U69660W
Alpine, a division of ITW Buildin Components Group Inc. shall not be responsible for any deviation from this drawing, any failure to build the i4x: ts6a6s1a6ie
truss in conformance with ANSI/gfP1 1, or for handling, shipping, installation, and bracin of trusses. A seal on this drawln or cover pa e
listing this drawin, indicates acceptance of professional en Pneering responsibility solelyorthe design shown. The suitability and use oflhis
drawing for any structure is the responsibility of the Building gDesigner per ANSI/TPI 1 Sec.2. Pa e 4
For more information see these web sites: Alpine: alpiineitw.com; TPI: t inst.or ; SBCA: sbcindust .com: ICC: iccsafe.or ; AWC: awc.or —9—
Truss Label: AG Ply: 1 Job Number: 190990 I
Qty: 2 Early Res /Jack Early /Early Res
Wgt: 120.4 Ibs 03/04/2021
fi
12
12'7"
:s 7X10 III 1.5X4[11 ]
C D
1111.5X4 =6X10
E F
1111.5X4 --4X4[10]=H0508=3X4[16] 1111.5X4
ST PLATE REQ.
III 21'8-1/2"
Loading Criteria (psf)
Wind Criteria
TCLL: 50.00
Wind Std: ASCE 7-16
TCDL: 15.00
Speed: 170 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 5.00
Risk Category: II
EXP: C Kzt: NA
D
Des Ld: 70.00
Mean Height: 25.00 ft
NCBCLL: 10.00
TCDL: 7.0 psf
Soffit: 2.00
BCDL: 3.0 psf
Load Duration: 1.00
MWFRS Parallel Dist: 0 to h/2
Spacing: 24.0 "
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.33
Lumber
Top chord: 2x4 SP SS; T3 2x4 SP #1;
Bot chord: 2x6 SP M-26;
Webs: 2x4 SP #2;
Lt Slider: 2x4 SP #2; block length = 1.500'
Special Loads
--(Lumber Dur.Fac.=1.00 / Plate Dur.Fac =1.00)
TC: From 134 pIf at 0.00 to 134 pIf at 5.00
TC: From 67 pIf at 5.00 to 67 ph' at 17.58
TC: From 134 pIf at 17.58 to 134 pIf at 22.58
BC: From 10 pIf at 0.00 to 10 pIf at 5.03
BC: From 5 ph' at 5.03 to 5 pIf at 17.55
BC: From 10 pIf at 17.55 to 10 pIf at 22.58
TC: 269 lb Conc. Load at 5.03,17.55
TC: 203lb Conc. Load at 7.06, 9.06,11.06,11.52
13.52,15.52
BC: 107 lb Conc. Load at 5.03,17.55
BC: 42 lb Conc. Load at 7.06, 9.06,11.06,11.52
13.52,15.52
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Varies by Ld Case
FT/RT:10(0)/10(0)
Plate Type(s):
Plate Shift Table
JT Plate Lateral Chord JT Plate Lateral Chord
No Size Shift Bite No Size Shift Bite
[10] 4X4 1.25 R 1.25 [11] 1.5X4 S 2.25
[16] 3X4 2.50 R 1.25
Wind
Wind loads and reactions based on MWFRS.
Wind loading based on both gable and hip roof types.
227'
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.242 E 999 360
VERT(CL): 0.350 E 728 240
HORZ(LL): 0.040 H - -
HORZ(TL): 0.059 C - -
Creep Factor: 2.0
Max TC CSI: 0.827
Max BC CSI: 0.672
Max Web CSI: 0.659
Mfg Specified Camber:
Ver: 20.02.00A.1020.21
Additional Notes
Calculated vertical live load deflection is 0.03" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.04" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.04"
Calculated horizontal total load deflection is 0.06"
Allowable vertical deflection ratios are U360 live and U240 tot
Calculated vertical deflection ratios are U1036 live and U685
Carl G. Forbes
PE#20699
5' 'I
°4X8(A8R)
M
SEAT PLATE REQ.
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ /R- /Rh /Rw /U /RL
A 2389 /- /- /- /1314 /-
M 2173 /- P P /1194 P
Wind reactions based on MWFRS
A Brg Width =11.0 Min Req = 2.0
M Brg Width = 9.5 Min Req = 1.8
Bearings A & G are a rigid surface.
Bearings A & G require a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 1003 -1759 D - E 2851 -4869
B - C 1891 -3311 E - F 2822 -4826
C - D 2818 -4819 F - G 2362 -4152
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp
I-lbad. 2849 -1631 J -1 4869 -2851
rl�
L - K 2831 -1617 I - H 3620 - 2064
K - J 4869 -2851 H - G 3605 - 2059
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp
A - B 995 -1832 E - I 497 - 745
C - L 249 - 364 I - F 1648 - 885
C - K 2432 -1401 H - F 322 - 89
K - D 568 - 873
"*WARNING- READ AND FOLLOW ALL NOTES ON THIS DRAWING[
-IMPORTANT" FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handling shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
Component Safety Information, by TPI an c7 SBCA) r safety practices prior to performing these functions. Installers shall provide temporary
bracing per BCSI., Unless noted otherwise, top chord shall have proper)v attached structural sheathing and bottom chord shall have a properly
attachetl ri id ceilm . Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B'10,
as applicable. App�y elates to each face, of truss and position as shown above and on the Join Details, unless noted otherwise. Refer to SPEC Russ
drawings 160A-Z for s andard plate positions. us muss
Alpine, a division of ITW Building rn onents GroupInc. shall not be responsible for an deviation from this drawing,an failure to build the Pll 15696966000
truss in conformance with ANSI/fPI 1 P or for handling, shipping, installattion, and bracing of trusses. A seal on thirawin or cover page M 166D6873418
9. PPingr. t9y P g
listing this drawin indicates acceptance of professional en lneering responsibilitty� sole) gfor the design shown. The swtab111 and use of this
drawing for any sigructure is the responsibility of the BuildinggDesigner per ANSI/TPI 1 S c.2. Penn A
Truss Label: EJ5 Ply: 1 Job Number: 190990 I
Qty: 15 Early Res /Jack Early /Early Res
Wgt: 19.6 Ibs 03/04/2021
ling Criteria (psf)
_. 50.00
L: 15.00
L: 0.00
L: 5.00
Ld: 70.00
CLL: 10.00
t: 2.00
1 Duration: 1.00
;inn: 24.0 "
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x4 SP #2;
Webs: 2x6 SP #2;
12
6
B
1111.5X4
=2X4(A1
a A
F
II 1.5X4E
g
10-1/ AT PLATE REQ.
Wind Criteria
Wind Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.33
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
�— 1-6-1/2" —1 3'5-1/2"
5'
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Yes
FT/RT:10(0)/10(0)
Plate Type(s):
WAVE
Additional Notes
Calculated vertical live load deflection is 0.05" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.06" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.03"
Calculated horizontal total load deflection is 0.03"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U794 live and U600 total load.
C
A
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.046 E 397 360
VERT(CL): 0.057 E 320 240
HORZ(LL): -0.026 C - -
HORZ(TL): 0.029 C - -
Creep Factor: 2.0
Max TC CSI: 0.440
Max BC CSI: 0.194
Max Web CSI: 0.054
Mfg Specified Camber:
20.02.00A.1020.21
Carl G. Forbes
PE#20699
♦ Maximum Reactions (Ibs)
Gravity
Loc R+ / R- / Rh
Non -Gravity
/Rw /U /RL
F 519 /- /- /247 /123 /206
D 42 A3 A /16 /20 /-
C 203 /- /- /82 /150 A
Wind reactions based on MWFRS
F Brg Width = 11.0 Min Req = 1.5
D Brg Width = 1.5 Min Req = -
C Brg Width = 1.5 Min Req = -
Bearing F is a rigid surface.
Bearing F requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 119 -171 B-C 91 -123
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-E 173 -59 E-D 0 0
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
B-E 219 -479
**WARNING— READ AND FOLLOWALL NOTES ON THIS DRAWINGI
**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handlin shipping, installing and bracing. , Refer to and follow the latest edition of BCSI (Building
Component Safety Information, by TPI an tl SBCA) fo'r safety practices prior to performing these functions. Installers shall provide temporary
bracing per BCSI. Unless noted otherwise, top chord shall have proper)% attached structural sheathing and bottom chord shall have a properly ���
attached rigid ceiling Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10,
as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise. Refer to SPEC 1�RUSS
drawings 160A-Z for standard plate positions. us Truss
Alpine, a division of ITW Buildin Com onents Group Inc. shall not be res onsible for an deviation from this drawing,an failure to build the F (561)MIGuo
p' p p r% y y EM: 1506373419
truss in conformance with ANSIIgfPI 1, or for handling, shipping,, installs ion and bracin of trusses. A seal on this drawing or cover page
listing this drawing indicates acceptance of professional engineering responsibilit��rr solely or the design shown. The suitability and use of [his
drawing for any structure is the responsibility of the Building -Designer per ANSI/TP1 1 Sec.2. P8 e
For more information see these web sites: Alpine: al ineitw.com; TPI: t inst.or ; SBCA: sbcindust .com: [CC: iccsafe.o ; AWC: awc.or Ene 6 6
Truss Label: EJ5A Ply: 1 Job Number: 190990 I
Qty: 1 Early Res /Jack Early /Early Res
Wgt: 23.8 Ibs 03/04/2021
D
T12
ill 1.5X4C
T
6
a
v
0
_
N 1111.5X4 B
=2X4(A1)
E
I
I
A
¢.
—3X4
1
1111 5X4
H 1111.5X4
g
10-1/2' AT PLATE REQ.
4,5„
'1' "
Loading Criteria (psf)
Wind Criteria
TCLL: 50.00
Wind Std: ASCE 7-16
TCDL: 15.00
Speed: 170 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 5.00
Risk Category: II
EXP: C Kzt: NA
Des Ld: 70.00
D
Mean Height: 25.00 ft
NCBCLL: 10.00
TCDL: 7.0 psf
Soffit: 2.00
BCDL: 3.0 psf
Load Duration: 1.00
MWFRS Parallel Dist: 0 to h/2
Spacing: 24.0 "
C&C Dist a: 3.00 It
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.33
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x4 SP #2;
Webs: 2x6 SP #2; W2 2x4 SP #2;
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Yes
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is 0.04" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.05" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.03"
Calculated horizontal total load deflection is 0.04"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U815 live and U593 total load.
5' _i
Def11CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.038 H 407 360
VERT(CL): 0.047 H 332 240
HORZ(LL): -0.031 C - -
HORZ(TL): 0.034 C - -
Creep Factor: 2.0
Max TC CSI: 0.427
Max BC CSI: 0.195
Max Web CSI: 0.063
Mfg Specified Camber:
VIEW Ver: 20.02.00A.1020.21
Carl G. Forbes
PE#20699
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
H 487 /- /- /232 /116 /206
E 56 /- /- /24 /43 /-
D 198 /- /- /88 /134 /-
Wind reactions based on MWFRS
H Brg Width = 11.0 Min Req = 1.5
E Brg Width = 1.5 Min Req = -
D Big Width = 1.5 Min Req = -
Bearing H is a rigid surface.
Bearing H requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 44 -173 C - D 89 -64
B-C 42 -147
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-H 167 -28 G-E 0 0
H - F 28 - 25
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B - H 224 -455 G - F 39 -21
G-C 32 -30
—WARNING- READ AND FOLLOW ALL NOTES ON THIS DRAWING!
"*IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handlin shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
Component Safety Information, bY TPI an SBCA) fo'r safety practices prior to performing these functions. Installers shall provide temporary
bracing per BCSI. Unless noted otherwise, top chord shall have properattached structural sheathing and bottom chord shall have a properly
attached ri id ce!lin Locations shown for permanent lateral restraint of webs shall have bracin installed per BCSI sections B3, B7 or B10,
as applicable. Apply plates to each face, of truss and position as shown above and on the Joinf Details, unless noted otherwise. Refer to SPEC Russ
drawings 16OA-Z for standard plate positions. US TRUSS
Alpine, a division of ITW Buildin �Com onents Group Inc. shall not be responsible for an deviation from this drawing, an failure to build the PR (5606864000
P gg P P P Y 9 Y PAX: 156D6973618
truss in conformance with ANSI PI 1, or for handling, shipping,, installation and bracingof trusses. A seal on this drawin or cover pa e
listing this drawing indicates acceptance of professional enpmeering responsibilitt%� sol lyfor the design shown. The suitability and use of Phis
drawing for any structure is the responsibility of the Building -Designer per ANSIITP1 1 ec.2. Pa G' %
For more information see these web sites: Alpine: al ineitw.com; TPI: t inst.or ; SBCA: sbcindust .com; ICC: !ccsafe.or AWC: awc.or g
Truss Label: HJ5 Ply: 1 Job Number: 190990
Qty: 3 Early Res /Jack Early /Early Res
Wgt: 32.2 Ibs 03/04/2021
ling Criteria (psf)
_. 50.00
L: 15.00
L: 0.00
L: 5.00
Ld: 70.00
CLL: 10.00
t: 2.00
1 Duration: 1.00
;ina: 24.0 "
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x6 SP #2;
Webs: 2x6 SP #2;
Special Loads
4-V4"
11.. III1.5X4(**) E
1L _Z 1/8" SEAT PLATE REQ.
f 1'11-771/8" -�-
7'0-1/8"
Wind Criteria
Wnd Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 fit
Loc. from endwall: Any
GCpi: 0.18
Wnd Duration: 1.33
---(Lumber Dur.Fac.=1.00 / Plate Dur.Fac =1.00)
TC: From 2 plf at 0.00 to 2 pif at 7.01
BC: From 2 plf at 0.00 to 2 plf at 7.01
TC: 266 lb Conc. Load at 1.41
TC: 146 lb Conc. Load at 4.24
BC: 9 lb Conc. Load at 1.41
BC: -9 lb Conc. Load at 4.24
Plating Notes
(**) 1 plate(s) require special positioning. Refer to
scaled plate plot details for special positioning
requirements.
Wind
Wind loads and reactions based on MWFRS.
Wind loading based on both gable and hip roof types.
5'0-1/4"
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Varies by Ld Case
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is 0.02" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.02" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.01"
Calculated horizontal total load deflection is 0.01"
Allowable vertical deflection ratios are L/360 live and U240 total load.
Calculated vertical deflection ratios are U2469 live and U3027 total load.
C
Deb/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.019 E 999 360
VERT(CL): 0.020 E 999 240
HORZ(LL): -0.007 B - -
HORZ(TL): 0.007 B - -
Creep Factor: 2.0
Max TC CSI: 0.476
Max BC CSI: 0.097
Max Web CSI: 0.040
Mfg Specified Camber:
20.02.00A.1020.21
Carl G. Forbes
PE#20699
i
1
♦ Maximum Reactions (Ibs)
Gravity
Loc R+ / R- / Rh
Non -Gravity
/Rw /U /RL
F 401 /- /- /- /197 /-
D 66 /-5 A A /32 A
C 65 A A A /40 /-
Wind reactions based on MWFRS
F Brg Width =15.6 Min Req = 1.5
D Brg Width =1.5 Min Req = -
C Brg Width = 1.5 Min Req = -
Bearing F is a rigid surface.
Bearing F requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 99 -45 B-C 28 -38
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-E 13 -24 E-D 0 0
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
B - E 189 - 371
**WARNING** READ AND FOLLOWALL NOTES ON THIS DRAWINGI
-IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
quire extreme care in fabricating, handlin shiipping, installing and bracing. , Refer to and follow the latest edition of BCSI (Building
t Safety Information, by TPI an SBCA) toF sa ety practices pnor to pertormmg these functions. Installers shall provide temporary
BCSI. Unless noted otherwise, top chord shall have ropedy attached structural sheathing and bottom chord shall have a pro erly
ceiling Locations shown for permanent lateral res�raint of webs shall have bracing installed per BCSI sections B3, B7 or Bel O,
e. Apply plates to each face of truss and position as shown above and on the JoinT Details, unless noted otherwise. Refer to
60A-Z for standard plate positions.
a division of
any
not be responsible for any deviation from this drawing, any failure to build the
g,, installation, and bracingof trusses; A seal on this drawing or cover page
enng responsibilit�yr solely -for the design shown. The swtabili and use of this
3ignerperANSI/TPI1 Sec.2.
SPEC I RUSS
us TRuss
PH (5606866880
PA%: 150687308
Truss Label: HJ5B Ply: 1 Job Number: 190990
Qty: 1 Early Res /Jack Early /Early Res
Wgt: 37.1 Ibs 03/04/2021
H 1111.5X4(**)
1L 2 1�EAT PLATE REQ.
Loading Criteria (psf)
TCLL: 50.00
TCDL: 15.00
BCLL: 0.00
BCDL: 5.00
Des Ld: 70.00
NCBCLL: 10.00
Soffit: 2.00
Load Duration: 1.00
Spacing: 24.0 "
Wind Criteria
Wind Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00It
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 It
Loc. from endwall: Any
GCpi: 0.18
Wind Duration:1.33
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x6 SP #2;
Webs: 2x6 SP #2; W2 2x4 SP #2;
Special Loads
--(Lumber Dur.Fac.=1.00 / Plate Dur.Fac.=1.00)
TC: From 2 plf at 0.00 to 2 plf at 7.01
BC: From 2 pif at 0.00 to 2 plf at 7.01
TC: 266 lb Conc. Load at 1.41
TC: 146 lb Conc. Load at 4.24
BC: 9 lb Conc. Load at 1.41
BC: -9 lb Conc. Load at 4.24
Plating Notes
(**) 1 plate(s) require special positioning. Refer to
scaled plate plot details for special positioning
requirements.
Wind
Wind loads and reactions based on MWFRS.
Wind loading based on both gable and hip roof types.
6'0-1/8" 1- 1'
7'0-1/8" -i
Snow Criteria (Pg,Pr in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Varies by Ld Case
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is 0.02" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.02" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.01"
Calculated horizontal total load deflection is 0.02"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U2287 live and U3610 total load.
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): -0.025 F 999 360
VERT(CL): 0.029 F 999 240
HORZ(LL): -0.014 C - -
HORZ(TL): 0.015 C - -
Creep Factor: 2.0
Max TC CSI: 0.389
Max BC CSI: 0.066
Max Web CSI: 0.088
Mfg Specified Camber:
VIEW Ver: 20.02.00A.1020.21
Carl G. Forbes
PE#20699
T
I
♦ Maximum Reactions (Ibs)
Gravity
Loc R+ / R- / Rh
Non -Gravity
/Rw /U /RL
1 384 A /- /- /188 P
E 74 /- /- A /56 P
D 70 P /- /- /24 P
Wind reactions based on MWFRS
I Brg Width = 15.6 Min Req = 1.5
E Brg Width =1.5 Min Req = -
D Brg Width = 1.5 Min Req = -
Bearing I is a rigid surface.
Bearing I requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 47 - 57 C - D 23 - 8
B - C 60 - 69
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp,
A-H 57 -51 G-E 0 0
H - F 35 - 36
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B - H 179 - 356 G - F 52 - 37
G-C 20 -55
-WARNING** READ AND FOLLOW ALL NOTES ON THIS DRAWING!
**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
quire extreme care in fabricating, handling9 shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
t Safety Information, by TPI an SBCA) for safety practices prior to performing these functions. Installers shall provide temporary
BCSI. Unless noted otherwise, top chord shall have proper)Y attached structural sheathing and bottom chord shall have a properly
id ceilm Locations shown for permanent lateral restraint of webs shall have bracin insta-Iled per BCSI sections B3, B7 or B10,
e. Apply plates to each face of truss and position as shown above and on the Join
f Details, unless noted otherwise. kefer to
of
any
not be responsible for any deviation from this drawing, any failure to build the
ig,, installation and bracing of trusses. A seal on this drawinq or cover pa e
:ering responsibili(� solely for the design shown. The suitability and use of this
signer per ANSI/TPI1 Sec.2.
SPEC? RUSS
US TRUSS
Pk (5696866000
FAX: rAD68784I8
Truss Label: j 1 Ply: 1 Job Number: 190990
Qty: 6 Early Res /Jack Early /Early Res
Wgt: 4.2 Ibs 03/04/2021
ling Criteria (psf)
_. 50.00
L: 15.00
L: 0.00
L: 5.00
Ld: 70.00
CLL: 10.00
t: 2.00
1 Duration: 1.00
:ing: 24.0 "
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x4 SP #2;
Wind
Wind Criteria
Wnd Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration:1.33
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
12
6
B
2XA4(A1 �-
1
r
I
4-1/4"
C
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Yes
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is -0.00" at X = 1- 0- 0.
Calculated vertical total load deflection is -0.00" at X = 1- 0- 0.
Calculated horizontal live load deflection is 0.00"
Calculated horizontal total load deflection is 0.00"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U1206776 live and U1206776 total loa
d.
***** BEARING ANALOG MODIFIEDI
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.000 - - 360
VERT(CL): 0.000 - - 240
HORZ(LL): 0.000 - -
HORZ(TL): 0.000 - -
Creep Factor: 2.0
Max TC CSI: 0.083
Max BC CSI: 0.011
Max Web CSI: 0.000
Mfg Specified Camber:
20.02.00A.1020.21
Carl G. Forbes
PE#20699
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ /R- /Rh /Rw /U /RL
C 5 /- /126 /5 /- /75
B 133 /- /126 /69 /47 /49
Wind reactions based on MWFRS
C Brg Width =1.5
B Brg Width = 1.5
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-B 171 -45
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-C 52 -126
**WARNING** READ AND FOLLOW ALL NOTES ON THIS DRAW NGI
"*IMPORTANT"* FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
quire extreme care in fabricating, handling,shipping, installing and bracing. , Refer to and follow the latest edition of BCSI (Building
t Safety Information, by TPI an� SBCA) fsafy practices prior to performing these functions. Installers shall provide temporary
BCSI. Unless noted otherwise, top chord shall have propenr\ attached structural sheathing and bottom chord shall have a propperly
ceilin Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10,
e. Apply plates to each face of truss and position as shown above and on the Join Details, unless noted otherwise. Refer to
60A-Z for standard plate positions.
Of
deviation from this drawing, any failure to build the
of trusses. A seal on this drawingor cover pagge
or the design shown. The suitability and use of this
SPEC A RUSS
US TRUSS
M (560686,000
FAX 156D6570415
Page 10
Truss Label: J 1 A Ply: 1 Job Number: 190990
Qty: 2 Early Res /Jack Early /Early Res
' Wqt: 4.2 Ibs 03/04/2021
Loading Criteria (psf)
TCLL: 50.00
TCDL: 15.00
BCLL: 0.00
BCDL: 5.00
Des Ld: 70.00
NCBCLL: 10.00
Soffit: 2.00
Load Duration: 1.00
Spacing: 24.0 "
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x4 SP #2;
Wind Criteria
Wind Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.33
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
12
6
B
2XA4(A1 d.
r
0
4-1/4"
C
Snow Criteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Yes
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is -0.00" at X = 1- 0- 0.
Calculated vertical total load deflection is -0.00" at X = 1-0-0.
Calculated horizontal live load deflection is 0.00"
Calculated horizontal total load deflection is 0.00"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U1206799 live and U1206799 total loa
d.
— BEARING ANALOG MODIFIEDI
Defl/CSI Criteria
PP Deflection in loc Udefl U#
VERT(LL): 0.000 - . - 360
VERT(CL): 0.000 - - 240
HORZ(LL): 0.000 - - -
HORZ(TL): 0.000 - - -
Creep Factor: 2.0
Max TC CSI: 0.083
Max BC CSI: 0.011
Max Web CSI: 0.000
Mfg Specified Camber:
VIEW Ver:20.02.00A.1020.21
Carl G. Forbes
PE#20699
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ /R- /Rh /Rw /U /RL
C 5 A 1126 /5 /- [75
B 133 A /126 /69 /47 /49
Wind reactions based on MWFRS
C Brg Width = 1.5
B Brg Width = 1.5
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-B 171 -45
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-C 52 -126
—WARNING— READ AND FOLLOW ALL NOTES ON THIS DRAW]NGI
`"IMPORTANT" FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
quire extreme care in fabricating handling shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
t Safety Information, by TPI and'SBCA) fo'r safety practices prior to performing these functions. Installers shall provide temporary
��BCSI., Unless noted otherwise, top chord sh II have 1p�roper) attached structural sheathing and bottom chord shall have a pros) erly
Ile LAID& plates to each face Of truss and position as shown above and onvthe Join Details, unless noted otherwise B7Refer to '
of
from this drawing, any failure to build the
s; A seal on this drawi .g or cover page
;ign shown. The suitabitiry and use of this
`Aft'___
SPECI RUSS
us 4Russ
M I546P6=0
Fa MWS73413
any
Page 11
Truss Label: J3
Ply: 1
Job Number: 190990
Qty: 6
Early Res /Jack Early /Early Res
'
Wgt: 14.0 Ibs
03/04/2021
12 C
6�
T
III1.5X4 B
0
2XI(A1) HB 1'5-1/2"
:-
1
F D
III 1.5X4 E
PLATE REQ.
i 10-1/2PEAT
1'6-1/2" 1'5-1/2"
�-— 3' j
Loading Criteria (psf)
Wind Criteria
Snow Criteria (Pg,Pf in PSF)
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 50.00
Wind Std: ASCE 7-16
Pg: NA Ct: NA CAT: NA
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TCDL: 15.00
Speed: 170 mph
Pf: NA Ce: NA
VERT(LL): 0.019 E 983 360
Loc R+ / R- / Rh / Rw / U / RL
F 443 /- /- /229 /93 /123
BCLL: 0.00
Enclosure: Closed
Lu: NA Cs: NA
VERT(CL): 0.029 E 635 240
BCDL: 5.00
Risk Category: II
Snow Duration: NA
HORZ(LL): -0.010 C - -
D - /47 /- /17 /31 /-
Des Ld: 70.00
EXP: C Kzt: NA
HORZ(TL): 0.015 C - -
C 73 /-36 A /12 /65 /-
Building Code:
NCBCLL: 10.00
Mean Height: 25.00 It
Creep Factor: 2.0
p
Wind reactions based on MWFRS
Soffit: 2.00
TCDL: 7.0 psf
FBC 7th Ed. 2020 Res.
Max TC CSI: 0.239
F Brg Width = 11.0 Min Req = 1.5
Load Duration: 1.00
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
TPI Std: 2014
Max BC CSI: 0.176
D Brg Width = 1.5 Min Req = -
C Brg Width = 1.5 Min Req = -
S Spacing: 24.0 "
p g:
C&C Dist a: 3.00 ft
Rep Fac: Yes
Max Web CSI: 0.025
Bearing F is a rigid surface.
Loc. from endwall: Any
FT/RT:10(0)/10(0)
Mfg Specified Camber:
Bearing F requires a seat plate.
GCpi: 0.18
Plate Type(s):
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.33
WAVE
VIEW Ver: 20.02.00A.1020.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A - B 104 - 95 B - C 33 - 73
Top chord: 2x4 SP #2;
Bot chord: 2x4 SP #2;
Webs: 2x6 SP #2;
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-E 109 -44 E-D 0 0
Wind
Wind loads based on MWFRS with additional C&C
member design.
Maximum Web Forces Per Ply (Ibs)
Wind loading based on both gable and hip roof types.
Webs Tens.Comp.
Additional Notes
B - E 128 -335
Calculated vertical live load deflection is 0.02" at X = 0- 0- 0.
Calculated vertical total load deflection is 0.03" at X = 0- 0- 0.
Calculated horizontal live load deflection is 0.01"
Calculated horizontal total load deflection is 0.02"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U1967 live and U1271 total load.
Carl G. Forbes
PE*20699
-WARNING** READ AND FOLLOWALL NOTES ON THIS DRAWNG!
**IMPORTANT"* FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
Trusses require extreme care in fabricating, handlin shipping, installing and bracing. , Refer to and follow the latest edition of BCSI (Building
Component Safety Information, b TPI an r7 SBCA) fo'r safety practices no to performing these functions. Installers shall provide temporary
bracing BCSI.. Unless top chord shall have a�tached structural sheathing and bottom chord shall have a properly
per noted oytherwise, properP%
attachetl ri id ceilin Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10,
as applicable. App7oy plates to each face, of truss and position as shown above and on the Joint Details, unless noted otherwise.
Fkefer to SPEC RUSS
fkuss
drawings 160A-Z for standard plate positions. us
Alpine, a division of ITW Buildin Com onents Group Inc. shall not be responsible for an deviation from this drawing, an failure to build the PH 1%Ud963418
p p P P Y 9d Y i0.% 99D69fl6i9
trusses; A this drawing e
truss in conformance with ANSI PI 1, or for handling, shipping,, installation and bracing of seal on or cover pa
listing this drawing indicates acceptance emmneenng responsibility solely -for the design shown. The suitabilify and use of fnis
of professional
drawing for any structure is the responsibility of the Building -Designer per ANSI/T I 1 Sec.2.
For more information see these web sites: Alpine: al ineitw.com� TPI: t inst.or : SBCA: sbcindust .com; ICC: iccsafe.or
Pa a 12
- AWC: awc.or g
Truss Label: J3A Ply: 1 Job Number: 190990
Qty: 2 Early Res /Jack Early /Early Res
Wgt: 9.8 Ibs 03/04/2021
iding Criteria (psf)
_L: 50.00
DL: 15.00
LL: 0.00
DL: 5.00
i Ld: 70.00
BCLL: 10.00
fit: 2.00
id Duration: 1.00
icing: 24.0 "
Lumber
Top chord: 2x4 SP #2;
Bot chord: 2x4 SP #2;
4
Wind Criteria
Wnd Std: ASCE 7-16
Speed: 170 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 25.00 ft
TCDL: 7.0 psf
BCDL: 3.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: Any
GCpi: 0.18
Wind Duration: 1.33
Wind
Wind loads based on MWFRS with additional C&C
member design.
Wind loading based on both gable and hip roof types.
12 B
2X4(A'
SEAT PLATE REQ.
Snow Crteria (Pg,Pf in PSF)
Pg: NA Ct: NA CAT: NA
Pf: NA Ce: NA
Lu: NA Cs: NA
Snow Duration: NA
Building Code:
FBC 7th Ed. 2020 Res.
TPI Std: 2014
Rep Fac: Yes
FT/RT:10(0)/10(0)
Plate Type(s):
Additional Notes
Calculated vertical live load deflection is 0.00" at X = 0- 6- 5.
Calculated vertical total load deflection is 0.01" at X = 0- 6- 5.
Calculated horizontal live load deflection is 0.00"
Calculated horizontal total load deflection is 0.00"
Allowable vertical deflection ratios are U360 live and U240 total load.
Calculated vertical deflection ratios are U7380 live and U5006 total load.
3'
Defl/CSI Criteria
PP Deflection in Icc Udefl U#
VERT(LL): NA
VERT(CL): NA
HORZ(LL): 0.003 C -
HORZ(TL): 0.005 C -
Creep Factor: 2.0
Max TC CSI: 0.284
Max BC CSI: 0.160
Max Web CSI: 0.000
Mfg Specified Camber:
Ver: 20.02.00A.1020.21
Carl G. Forbes
PE#20699
T
11-T
0
1
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ /R- /Rh /Rw /U /RL
A 226 /- /- /90 /59 /123
C 44 /- /- /24 /11 /-
B 167 /- /- /74 /111 /-
Wind reactions based on MWFRS
A Brg Width = 9.5 Min Req = 1.5
C Brg Width =1.5 Min Req = -
B Brg Width = 1.5 Min Req = -
Bearing A is a rigid surface.
Bearing A requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A - B 75 -77
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-C 0 0
**WARNING** READ AND FOLLOW ALL NOTES ON THIS DRAWING!
**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS
quire extreme care in fabricating, handling shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building
t Safety Information, b TPI and SBCA) F safety ractices prior to performing these functions. Installers shall provide temporary
BCSI. Unless noted o�herwise, top chord shall Me Pr roper attached structural sheathing and bottom chord shall have a pro pperly
id ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10,
e. AD[& Dlates to each face of truss and position as shown above and on the Join f Details, unless noted otherwise. Refer to
a division of
not be responsible for any deviation from this drawing, any failure to build the
in
stallation nstalls ionand bracing of trusses. A seal on this drawing or cover page
enng responsibility solely -for the design shown. The suitability and use of this
signer per ANSlfrPll Sec.2.
SPEC I RUSS
us TRUSS
M (560E96100
FAk MONO
any
Page 13