HomeMy WebLinkAboutLetter - Response To Plan Review CommentsArchitectonic Inc
March 22, 2018
St. Lucie County
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Re: Crull Services Inc_
1937 N Old Dixie Hwy
Permit# 1706-0646
RECEIVED
APR 03 2018
ST. Lucie County, Permitting
Please be advised that the following items are in response to plan review comments for the above referenced
project dated 8/1/2017
I. You will need separate sex ADA restrooms per section 403.2 FPC 2014.
Response: See Warehouse Sheet #1
2. You will need a service sink per table 403.1.
Response: See Warehouse Sheet #1
3, You will need a hi to drinking fountain per table 403.1.
Response: See Warehouse Sheet #1
4. Total occupant load for both buildings are over 15 the exemption of not being required to have these items do
not apply to these buildings per section 403.2 and exemptions foot note F and G under table 403.1 of the FPC
2014.
Response: See Warehouse Sheet #1
tG®F F LOR�O
%�bSE:.
��1ec ��' u mittgeCd,
, r nsa9�l9 �'ti
THESE PLAINS AND P'LL PROPOSED WORK
ARE SUBJECT TO ANY CORRECTIONS -
REQUIRED BY FIELD INSPECTORS THAT:
1 1 � MAY BE, NECES6 ARl' III ORDEI a TO..,a��
6-1 •. • r
tH 1L AF ft I C00ES
41 806 Delaware Avenue Tel: 772 460 7751 www.architectonicinc.com
Fort Pierce, Florida 34950 Fax: 772 460 4244 • . FL Reg #AA26003348 1 of 1
Energy`COnservatlon'
r �r
ive,Date:!June,30, 2015
Compliance Option t
Check List
Applications for compliance with the Florida Building Code, Energy Conservation shall
include:
❑ This Checklist
❑ An Input report generated from the software just after completing compliance
calculations without any further changes
❑ The full compliance report generated by the software that contains the project
summary, complaince summary, certifications and detailed component compliance
reports
❑ Boxes appropriately checked in the Miscellanous report generated by the software at
the end of the compliance report
9/27/2017
sir
tt't aeS 0'&1®d"
.•
E IV
ea
N 0982 ate'
a
•a n e.i w
1. 0:� SATE OF
e �
®p�Qc4P@bPRa�Ot
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Page 1 of 13
PROJECT SUMMARY
Short Desc:
Crull Services
Description:
Crull Services Office
Owner:
Crull Services
Addressl:
1937 Old Dixie Hwy.
City:
Fort Pierce
Address2:
State:
FL
Zip:
34946
Type:
Office
Class:
New Finished building
Jurisdiction:
ST LUCIE COUNTY, ST LUCIE COUNTY, FL (661000)
Conditioned Area:
1016 SF
Conditioned & UnConditioned Area:
1016 SF
No of Stories:
1
Area entered from Plans
0 SF
Permit No:
0
Max Tonnage
3
If different, write in:
Compliance Summary
Component Design. Criteria Result
Gross Energy Cost (in $) 649.0 717.0 PASSED
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT--',
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
PASSES
PASSES
No Entry
PASSES
No Entry
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
Compliance Report
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 2 of 13
r
r
.i
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By: Eric J S ob�ooda, PE 2 Building Official:
Date: !
Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify (*) that the system design is in compliance with the Florida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: Reg No:
Mechanical Designer: Reg No:
Plumbing Designer: Reg No:
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
.r
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 3 of 13
Project: Crull Services
Title: Crull Services Office
Type: Office
(WEA File: DAYTONABEACH.TMY)
Building End Uses
1) Proposed 2) Baseline
Total 41.80 54.10
$649 $844
ELECTRICITY(MBtulkWhl$)
41.80
54.10
12226
15836
$649
$844
AREA LIGHTS
11.70
11.70
3415
3423
$181
$182
MISC EQUIPMT
15.20
15.20
4465
4465
$237
$238
PUMPS & MISC
0.10
0.10
22
24
$1
$1
SPACE COOL
12.50
11.50
3653
3372
$194
$180
SPACE HEAT
0.70
1.70
205
490
$11
$26
VENT FANS
1.60
13.90
466
4062
$25
$217
Credits Applied: None PASSES
Passing Criteria = 717
Design (including any credits) = 649
Passing requires Proposed Building cost to be at most 85% of
Baseline cost. This Proposed Building is at 76.9%
i
EnergyGauge Summit0 Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 4 of 13 r
4
Project: Crull Services
Title: Crull Services Office
Type: Office
(WEA File: DAYTONABEACH.TMY)
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
Ext Light 1 Main entries Yes 30.00 6.0 180 120
Ext Light 2 Walkways more that 10 feet Yes 0.20 1,200.0 240 120
wide
Tradable Surfaces: 240 (W) Allowance for Tradable: 1122 (W) PASSES
All External Lighting: 240 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
Project: Crull Services
Title: Crull Services Office
Type: Office
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description Area Design Min Compli-
ID (sq.ft) CP CP ance
Pr0Zo1Sp1 17 Office - Enclosed 1,016 4 1 PASSES,
PASSES
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 5 of 13
Project: Crull Services
Title: Crull Services Office
Type: Office
(WEA File: DAYTONABEACH.TMY)
System Report Compliance
PrOSyl System 1
Variable refrigerant Flow No. of Units
System
1
Component Category
Capacity Design Eff
Design IPLV Comp-
Eff Criteria
IPLV Criteria liance
Cooling System VRF Air Conditioners Air
36000 14.30 13.00
8.00 PASSES
Cooled 0 to 65000 Btu/h
Cooling Capacity
Heating System Heat Pumps Air Cooled
36000 3.14 2.25
PASSES
(Heating Mode) < 65000
Btu/h Cooling Capacity
Air Handling Air Handler (Supply) -
1600 0.10 0.82
PASSES
System -Supply Constant Volume
PASSES
Plant Compliance
Description Installed Size Design Min Design
No Eff Eff IPLV
Min Category Comp
IPLV liance
None
Project: Crull Services
Title: Crull Services Office
Type: Office
(WEA File: DAYTONABEACH.TMY)
Water Heater Compliance
Description Type
Category Design
Min Design Max Comp
Eff
Eff Loss Loss liance
Water Heater 1 Electric water heater <= 12 [kW] 0.98
0.97 PASSES
PASSES =41
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software, Effective Date: June 30, 2015
9/27/2017 Page 6 of 13
r
�I
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] .SF.F]
None
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 7 of 13
Mandatory Requirements (as applicable) Mandatory requirements compiled by US Department
of Energy and Pacific Northwest National Laboratory.'`,
Adopted with permission -
Topic Section Component Description Yes N/A Ex -
Air Leakage
Air Leakage
Air Leakage
Air Leakage
Air Leakage
Fenestration
Fenestration
Fenestration
Insulation
Insulation
Insulation
Insulation
Insulation
Insulation
'1=
Insulation
Insulation
Insulation
Insulation
Insulation
9/27/2017
l:4uz.4."i,l:4uz.4.z tnveiope
i ne owiamg envelope contains a continuous air
U
U
U
barrier that is sealed in an approved manner and
either constructed or tested in an approved
manner. Air barrier penetrations are sealed in an
approved manner.
C402.4.3,C402.4.4 Envelope
Factory -built fenestration and doors are labeled as
meeting air leakage requirements.
C402.4.7 Envelope
Vestibules are installed on all building entrances.
Doors have self -closing devices.
C402.4.1.1 Envelope
All sources of air leakage in the building thermal
envelope are sealed, caulked, gasketed, weather
stripped or wrapped with moisture
vapor -permeable wrapping material to minimize
air leakage.
C402.4.6 Envelope
Weatherseals installed on all loading dock cargo
doors.
C402.4.8 Envelope
Recessed luminaires in thermal envelope to limit
infiltration and be IC rated and labeled. Seal
between interior finish and luminaire housing.
C303.1.3 Envelope
Fenestration products rated in accordance with
❑
❑
0
NFRC.
C303.1.3 Envelope
Fenestration products are certified as to
performance labels or certificates provided.
C402.2.7 Envelope
U-factor of opaque doors associated with the
building thermal envelope meets requirements.
C303.2 Envelope
Below -grade wall insulation installed per
❑
El
0
manufacturer's instructions.
C303.2 Envelope
Slab edge insulation installed per manufacturer's
instructions.
C402.2.6 Envelope
Slab edge insulation depth/length. Slab insulation
extending away from building is covered by
pavement or >= 10 inches of soil.
C403.2.7,C408.2.8,C Envelope
Exterior insulation protected against damage,
sunlight, moisture, wind, landscaping and'
equipment maintenance activities.
C402.4.2.1 Envelope
Roof R-value. For some ceiling systems,
verification may need to occur during Framing
Inspection.
C303.2 Envelope
Roof insulation installed per manufacturer's
0
11
instructions. Blown or poured loose -fill insulation
is installed only where the roof slope is < 3 in 12.
C402.2.1 Envelope
Skylight curbs are insulated to the level of roofs
with insulation above deck or R-5.
.C402.2.1.1 Envelope
High-albedo roofs satisfy one of the following:
❑
❑
0
3-year-aged solar reflectance >= 0.55 and thermal
emittance >= 0.75, 3-year-aged solar reflectance
index >= 64.0, initial year solar reflectance >_
0.70 and thermal emittance >= 0.75, or initial year
solar
C303.2 Envelope
Above -grade wall insulation installed per
manufacturer's instructions.
C3012 Envelope
Floor insulation installed per manufacturer's
11
El0
instructions.
C303.1 Envelope
Building envelope insulation is labeled with
R-value or insulation certificate providing R-value
and other relevant data.
t`
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Page 8 of 13
Insulation C303.2.1 Envelope
Exterior insulation is protected from damage with
a protective material. Verification for exposed
foundation insulation may need to occur during
Foundation Inspection.
Insulation C402.2.1 Envelope
Insulation intended to meet the roof insulation
requirements cannot be installed on top of a
suspended ceiling. Mark this requirement
compliant if insulation is installed accordingly.
Controls C405.2.4 Exterior Lighting
Automatic lighting controls for exterior lighting
installed.
Wattage C405.6 Exterior Lighting
Exterior grounds lighting over 100 W provides >60
❑
❑
Im/W unless on motion sensor or fixture is exempt
from scope of code or from external LPD.
Wattage C405.6.2 Exterior Lighting
Exterior lighting power is consistent with what is
shown on the approved lighting plans,
demonstrating proposed watts are less than or
equal to allowed watts.
Controls C405.2.2.1 Interior Lighting
Automatic controls to shut off all building lighting
installed in all buildings.
Controls C405.2.1.1 Interior Lighting
Independent lighting controls installed per
approved lighting plans and all manual controls
readily accessible and visible to occupants.
Controls C405.2.1.2 Interior Lighting
Lighting controls installed to uniformly reduce the
lighting load by at least 50%.
Controls C405.2.2.3 Interior Lighting
Daylight zones provided with individual controls
that control the lights independent of general area
lighting.
Controls C405.2.3 Interior Lighting
Sleeping units have at least one master switch at
❑
0
the main entry door that controls wired luminaires
and switched receptacles.
Controls C405.2.2.2 Interior Lighting
Occupancy sensors installed in required spaces.
Controls C405.2.2.3 Interior Lighting
Primary sidelighted areas are equipped with
required lighting controls.
Controls C405.2.2.3 Interior Lighting
Enclosed spaces with daylight area under
skylights and rooftop monitors are equipped with
required lighting controls.
Controls C405.2.3 Interior Lighting
Separate lighting control devices for specific uses
installed per approved lighting plans.
Controls C405.3 Interior Lighting
Fluorescent luminaires within odd numbered lamp
configurations that are with 10 feet center to
center (if recess mounted) or are within 1 foot
edge to edge (if pendant or surface mounted)
shall be tandem wired.
Wattage C405.4 Interior Lighting
Exit signs do not exceed 5 watts per face.
0
0
❑
Wattage C405.2.3 Interior Lighting
Additional interior lighting power allowed for
❑
special functions per the approved lighting plans
and is automatically controlled and separated from
general lighting.
Wattage C405.5.2 Interior Lighting
Interior installed lamp and fixture lighting power is
consistent with what is shown on the approved
lighting plans, demonstrating proposed watts are
HVAC C403.2.4.5 Mechanical
less than or equal to allowed watts.
Freeze protection and snowrice melting system
sensors for future connection to controls.
HVAC C403.2.3 Mechanical
HVAC equipment efficiency verified.
Air Leakage C402.4.5.1 Envelope
Stair and elevator shaft vents have motorized
dampers that automatically close.
Air Leakage C402.4.5.2 Envelope
Outdoor air and exhaust systems have motorized
dampers that automatically shut when not in use
and meet maximum leakage rates. Check gravity
dampers where allowed.
HVAC C403.2.5.1 Mechanical
Demand control ventilation provided for spaces
0
El
El
>500 ft2 and >25 people/1000 ft2 occupant
density and served by systems with air side
economizer, auto modulating outside air damper
control, or design airflow >3,000 cfm.
9/27/2017
1
EnergyGauge Summit@ Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
Page 9 of 13
HVAC
C403.2.8.1
Mechanical
Piping Insulation exposed to weather. is protected
from damage (due to sun, moisture, wind, etc.).-
HVAC
C403.2.7
Mechanical
HVAC ducts and plenums insulated. Where ducts
or plenums are installed in or under a slab,
verification may need to occur during Foundation
.
Inspection.
HVAC
C403.2.8
Mechanical
Thermally ineffective panel surfaces of sensible
heating panels have insulation >= R-3.5.
_
HVAC
C403.2.7
Mechanical
Ducts and plenums sealed based on static
pressure and location.
HVAC
C408.2.2.1
Mechanical
Air outlets and zone terminal devices have means
for air balancing.
HVAC
C403.2.6
Mechanical
Exhaust air energy recovery on systems meeting
Table C403.2.6
HVAC
C403.2.11
Mechanical
Unenclosed spaces that are heated use only
radiant heat.
HVAC
C403.2.4.1
Mechanical
Heating and cooling to each zone is controlled by
a thermostat control.
HVAC
C403.2.4.2
Mechanical
Thermostatic controls have a 5 °F deadband.
❑
❑
❑
HVAC
C403.2.4.2
Mechanical
Temperature controls have setpoint overlap
restrictions.
HVAC
C403.2.4.3
Mechanical
Each zone equipped with setback controls using
automatic time clock or programmable control
system.
.HVAC
C403.2.4.3
Mechanical
Automatic Controls: Setback to 55°F (heat) and
85°F (cool); 7-day clock, 2-hour occupant
override, 10-hour backup
SYSTEM —SPECIFIC
C404.3
Mechanical
Temperature controls installed on service water
❑
heating systems (110 OF for dwelling units and
lavatories in public restrooms and 90 OF for other
occupancies.)
SYSTEM —SPECIFIC
C404.4
Mechanical
Automatic time switches installed to automatically
❑
0
El
switch off the recirculating hot-water system or
heat trace.
SYSTEM —SPECIFIC
C404.2
Mechanical
Heat traps installed on non -circulating storage
water tanks.
SYSTEM
C403.2.3
Mechanical
PTAC and PTHP with sleeves 16 in. by 42 in.
—SPECIFIC
labeled for replacement only as per Footnote b to
Table C403.2.3(3).
SYSTEM —SPECIFIC
C403.4.2'
Mechanical
VAV fan >= 7.5 hp are driven by mechanical or
electrical variable speed drive, or driven by
vane -axial with variable speed blades, or operate
with motor demand <=30% design kW at 50%
design flow- calculations required
SYSTEM —SPECIFIC
C403.2.8
Mechanical
HVAC piping insulation thickness. Where piping is
❑
❑
installed in or under a slab, verification may need
to occur during Foundation Inspection.
SYSTEM —SPECIFIC
C403.2.7.1.3
Mechanical
Ductwork operating >3 in. water column requires
air leakage testing.
SYSTEM
C403.3.1,C403.3.1.1 Mechanical
Air economizers provided where required, meet
—SPECIFIC
the requirements for design capacity, control
signal, ventilation controls, high -limit shut-off,
integrated economizer control, and provide a
means to relieve excess outside air during
operation.
SYSTEM —SPECIFIC
C403.3.1,C403.4.1
Mechanical
Water economizers provided where required,
❑
❑
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM —SPECIFIC
C403.4.1.4
Mechanical
Economizer operation will not increase heating
energy use during normal operation.
SYSTEM —SPECIFIC
C403.4.5
Mechanical
Zone controls can limit simultaneous heating and
cooling and sequence heating and cooling to each
zone.
SYSTEM —SPECIFIC
C403.4.3.1
Mechanical
Three -pipe hydronic systems using a common
1
return for hot and chilled water are not used.
EnergyGauge SummM Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017
Page 10 of 13
�^ .
J
SYSTEM C403.4.3.2
Mechanical Two -pipe hydronic systems using a common
—SPECIFIC
distribution system have controls to allow a
deadband > 15 OF, allow operation in one mode
for at least 4 hrs before changeover, and have
rest controls to limit heating and cooling supply
temperature to <=30 OF.
SYSTEM C403.4.3.3.1
Mechanical Hydronic heat pump systems connected to a
—SPECIFIC
common water loop meet heat rejection and heat
addition requirements.
SYSTEM C408.2.2.2
Mechanical HVAC hydronic heating and cooling coils have
—SPECIFIC
means to balance and have pressure test
connections.
SYSTEM C403.2.10.1
Mechanical HVAC fan systems at design conditions do not
El❑
❑
—SPECIFIC
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM —SPECIFIC C403.2.10.2
Mechanical HVAC fan motors not larger than allowable limits.
SYSTEM C403.4.2
Mechanical VAV fan motors >=7.5 hp to be driven by variable
—SPECIFIC
speed drive, have a vane -axial fan with variable
pitch blades, or have controls to limit fan motor
demand.
SYSTEM C403.4.2.1
Mechanical VAV fans have static pressure sensors positioned
—SPECIFIC
so setpoint <=1/3 total design pressure.
SYSTEM C403.4.2.2
Mechanical Reset static pressure setpoint for DDC controlled
❑
13
—SPECIFIC
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM C403.4.5.4
Mechanical Multiple zone HVAC systems have supply air
—SPECIFIC
temperature reset controls.
SYSTEM C403.4.3.4
Mechanical Hydronic systems greater than 300,000 Btu/h
❑
0
El
—SPECIFIC
designed for variable fluid flow.
SYSTEM C403.4.3.5
Mechanical Reduce flow in pumping systems >10 hp to
—SPECIFIC
multiple chillers or boilers when others are shut
down.
SYSTEM C403.4.3.4
Mechanical Temperature reset by representative building
—SPECIFIC
loads in pumping systems for chiller and boiler
systems >300,000 Btu/h.
SYSTEM C403.4.3.3.3
Mechanical Two -position automatic valve interlocked to shut
—SPECIFIC
off water flow when hydronic heat pump with
pumping system >10 hp is off.
SYSTEM C403.4.4
Mechanical Fan systems with motors >=7.5 hp associated
El❑
—SPECIFIC
with heat rejection equipment to have capability to
operate at 2/3 of full -speed and auto speed
controls to control the leaving fluid temperature or.
condensing temp/pressure of heat rejection
device.
SYSTEM C403.4.6
Mechanical Condenser heat recovery system that can heat
❑
—SPECIFIC
water to 85 OF or provide 60% of peak heat
rejection is installed for preheating of service hot
water in 2417 facility, water cooled systems reject
>6 MMBtu, SHW load >=1 MMBtu.
SYSTEM SPECIFIC C403.4.7
Mechanical Hot gas bypass limited to:
—
<=240 kBtu/h — 50%
>240 kBtu/h — 25%
SYSTEM C404.2
Mechanical Service water heating equipment meets efficiency
—SPECIFIC
requirements.
SYSTEM C403.2.4.2
Mechanical Heating and cooling to each zone is controlled by
i
—SPECIFIC
a thermostat control. Minimum one humidity
control device per installed
humidification/dehumidification system.
SYSTEM —SPECIFIC C403.2.4.3.3
Mechanical Systems include optimum start controls.
13
0
❑
SYSTEM C403.2.4.1.1
Mechanical Heat pump controls prevent supplemental electric
0
—SPECIFIC
resistance heat from coming on when not needed.
SYSTEM —SPECIFIC C404.3
Mechanical Public lavatory faucet water temperature < 1107.
SYSTEM —SPECIFIC C404.5
Mechanical All piping in circulating system insulated
SYSTEM —SPECIFIC C404.5
Mechanical First 8 ft of outlet piping is insulated
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant. Software. Effective Date: June 30, 2015
9/27/2017 Page 11 of 13
SYSTEM —SPECIFIC C404.5 Mechanical
All heat traced or externally heated piping
insulated
~
SYSTEM —SPECIFIC C404.6 Mechanical
Controls are installed that limit the operation of a
recirculation pump installed to maintain
temperature of a storage tank.
SYSTEM —SPECIFIC C404.7.1 Mechanical
Pool heaters are equipped with on/off switch and
no continuously burning pilot light.
SYSTEM —SPECIFIC C404.7.3 Mechanical
Vapor retardant pool covers1are provided for
heated pools and permanently installed spas.
SYSTEM SPECIFIC C404.7.2 Mechanical
Time switches are installed on1` all pool heaters and
pumps.
SYSTEM —SPECIFIC C403.2.3 Mechanical
Centrifugal fan open -circuit cooling towers having
combined rated capacity — 1100 gpm meets
Testing C408.2.3.2 Mechanical
minimum efficiency requirement: > 38.2 gpm/hp.
HVAC control systems have been tested to ensure
proper operation, calibration and adjustment of
controls.
Mandatory Additional C406 Project
Efficient HVAC performance, efficient lighting
13❑
13
system, or on -site supply of renewable energy
consistent with what is shown the iapproved plans.
Insulation C402.2.8 Project
Bottom surface of floor structures incorporating
radiant heating insulated to > R-3. I
To be checked=during Plan` Review"
'Plan
^
Review C103.2 Envelope
Plans and/or specifications provide all information
�4❑�0
with which compliance can be determined for the
building envelope and document where
exceptions to the standard are claimed.
Plan Review C103.2 Exterior Lighting Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the exterior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided shoul
Plan Review C103.2 Interior Lighting
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the interior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided shoul
Plan Review C103.2 Mechanical
Plans, specifications, and/or calculations pro ide
all information with which compliance can be
determined for the mechanical systems and
equipment and document where exceptions to the
standard are claimed. Load calculations per
acceptable engineering st
Plan Review C103.2 Mechanical
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the service water heating systems
and equipment and document where exceptions
to the standard are claimed. Hot water system
sized per manufact
Plan Review C406 Project
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the additional energy efficiency
package options.
Plan Review C402.3.2.2 Envelope
Skylights in office, storage, automotive service,
manufacturing, non -refrigerated warehouse, retail
store, and distribution/sorting area have a
measured haze value> 90 percent unless
designed to exclude direct sunlight.
Y, ��,u� c:necKea;lrosi �ons><ructio:n rr�or to.Issuance ofCertificate.ofAcc"upaney;'.�
Post Construction C408.3 Exterior Lighting Lighting systems have been tested to ensure ��❑ ��
proper calibration, adjustment, programming, and
operation.
Post Construction C408.2.5.1 Interior Lighting Furnished as -built drawings for electric power
systems within 30 days of system acceptance.
EnergyGauge Summit@) Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 12 of 13
-I
1
Post Construction C303.3,C408.2.5.2 Interior Lighting
Furnished O&M instructions for systems and
equipment to the building owner or designated
representative.
Post Construction C408.3 Interior Lighting
Lighting systems have been tested to ensure
❑
proper calibration, adjustment, programming, and
operation.
Post Construction C408.2.5.1 Mechanical
Furnished HVAC as -built drawings submitted
within 90 days of system acceptance.
Post Construction C303.3,C408.2.5.2 Mechanical
Furnished O&M manuals for HVAC systems within
0
90 days of system acceptance.
Post Construction C408.2.5.3 Mechanical
An air and/or hydronic system balancing report is
❑
0
❑
provided for HVAC systems.
Post Construction C408.2.1 Mechanical
Commissioning plan developed by registered
0
El
0
design professional or approved agency.
Post Construction C408.2.4 Mechanical
Preliminary commissioning report completed and
certified by registered design professional or
approved agency.
Post Construction C408.2.5.4 Mechanical
Final commissioning report due to building owner
within 90 days of receipt of certificate of
Post Construction C408.2.3.1 Mechanical
occupancy.
HVAC equipment has been tested to ensure
110
❑
proper operation.
Post Construction C408.2.3.3 Mechanical
Economizers have been tested to ensure proper
operation.
1
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
9/27/2017 Page 13 of 13
Project Name: Crull Services
Project Title: Crull Services Office
Address: 1937 Old Dixie Hwy.
State: FL
Zip: 34946
Owner: Crull Services
EnergyGauge Summit® v5.10
INPUT DATA REPORT
Project Information
Orientation: North
Building Type: Office
Building Classification: New Finished building
No.of Stories: 1
GrossArea: 1016 SF
Zones
No Acronym Description Type
Are�Multiplier
Total Area
�lsfl
[sf]
1 PrOZo 1 Zone 1 CONDITIONED
1016.0 1
1016.0 ❑
Spaces
f No Acronym Description Type Depth Width
Height Multi Total Area
Total Volume
IN [ft]
[ft] plier [sf]
[cf]
9/27/2017
EnergyGauge Summit® v5.10
I&
In Zone: PrOZol
1 PrOZolSpl Zo0Sp1
Office - Enclosed
46.18
22.00
10.00
1 1016.0
10159.6 ❑
Lighting
No Type
Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: PrOZol
In Space: Pr0Zo1Sp1
'
1 Compact Fluorescent General Lighting
1
1115
1115
Occupancy sensor without 4
Daylighting
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance Heat
Dens. R-Value
[ft]
[ft] plier
[sf]
[Btu/hr.
sf. F] Capacity
[Ib/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone: PrOZol
1 PrOZolWal
5/8" stucco 47.00
10.00 1
470.0
North
0.2067 5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
2 PrOZo1Wa2
5/8" stucco 47.00
10.00 1
470.0
South
0.2067 5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
3 PrOZo1Wa3
5/8" stucco 22.00
10.00 1
220.0
East
0.2067 5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
4 PrOZo 1 Wa4
5/8" stucco 22.00
16.00 1
220.0
West
0.2067 5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
9/27/2017
EnergyGauge Summit® v5.10
2
r
Windows
No Description >-L"Iype
Shaded U SHGC
[Btu/hr sf F]
Vis.Tra
NA-7- H (Effec) Multi Total Area
[ft] [ft] plier [Sf]
In Zone: PrOZol
In Wall: East
1 PrOZo1Wa3Wi1 User Defined
In Wall: North
1 PrOZo1Wa1Wil User Defined
No 1.2500 0.82
No 1.2500 0.82
0.76
0.76
3.00 5.00 2
3.00 5.00 4
30.0
60.0
❑
❑
Doors
No Description Type
Shaded? Width H (Effec) Multi
IN [ft] plier
Area
[sf]
Cond. Dens. Heat Cap.
[Btu/hr. A. F] [lb/cf] [Btu/sf. F]
R-Value
[h.sf.FBtu]
In Zone: PrOZol
In Wall: North
1 PrOZo1Wa1Dr1 Solid core flush
(2.25)
No 3.00 7.00
2
21.0 0.3504 0.00 0.00
2.85
❑
Roofs
No Description Type
Width H (Effec) Multi
IN IN plier
Area
[sf]
Tilt
[deg]
Cond. Heat Cap Dens.
[Btu/hr. SE F] [Btu/sf. F] [lb/cf]
R-Value
[h.sf.FBtu]
In Zone: PrOZol
1 PrOZo1Rfl Mtl Bldg Roof/R-30
Batt
22.00 46.18 1
1016.0
0.00
0.0333 2.17 23.52
30.0
❑
Skylights
No Description Type
U SHGC Vis.Trans
[Btu/hr sf F]
W
[ft]
H (Effec) Multiplier Area
IN [sf]
Total Area
[Sf]
9/27/2017
i _ 7 V.
PPW �A
EnergyGauge Summit® v5.10
3 `
4&
. 446 -
jP=on=-
In Roof:
No Description Type
In Zone: PrOZol
1 PrOZo1F11 1 ft. soil, concrete
floor
Floors
Width H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value
[ft] [ft] plier [sf] [Btu/hr. sf. F] [Btu/sf. F] [lb/cf] [h.sf.F/Btu]
22.00 46.18 1 1016.0 0.4284 29.35 110.02 ' 2.33 ❑
Systems
PrOSyl System 1
Variable refrigerant Flow System
No. Of Units 1
Component Category
Capacity Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
36000.00 14.30 8.00
36000.00 3.14
1600.00 0.10
❑
❑
❑
Plant
Equipment Category
Size Inst.No Eff.
IPLV
Li
Water Heaters
W-Heater Description
1 _
Capacit3Cap.Unit
1 [Gal]
UP Rt. Efficiency
12 [kW] 0.9800- [Ef]
EnergyGauge Summit@ v5.10
Loss
[Btu/h] ❑
4
EA -Lighting,
Description
No. of Watts per Area/Len/No. of units Control Type
Luminaires Luminaire [sf/fVNo]
Wattage
[W]
1 Ext Light 1
2 Ext Light 2
Main entries 2 60
Walkways more that 10 feet 2 60
wide
6.00 Photo Sensor control
1260.00 Photo Sensor control
120.00
120.00
Piping
No Type
Operating Insulation
Temperature Conductivity
[F] [ Btu-in/h.sf.F]
Nomonal pipe Insulation
Diameter Thickness
[in] [in]
Is Runout?
Fenestration Used
Glass
LGlass Type No. of Conductance SHGC VLT
Panes [Btu/h.sf.F]
rA1 User Defined 1 1.2500 0.8200 0.7600 ❑
9/27/2017 EnergyGauge Summit® v5.10 5
low
268
Matl268
0.625" stucco
No
0.1302
0.0521
0.4000
16.00
0.2000
❑
42
Mat142
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
269
Mat1269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
12
MatI12
3 in. Insulation
No
10.0000
0.2500
0.0250
2.00
0.2000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
4
Matl4
Steel siding
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
47
Matl47
2 in. Heavyweight concrete
No
0.1670
0.1670
1.0000
140.00
0.2000
❑
Constructs Used
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.Fl [Btu/sf.F] [lb/cf] [h.sf.FBtul
1005 1 ft. soil, concrete floor No No 0.43 29.35 110.02 2.3 ❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
47
2 in. Heavyweight concrete
0.1670
0.000
❑
3
47
2 in. Heavyweight concrete
0.1670
0.000
❑
Simple
Massless Conductance Heat Capacity
Density RValue
No Name
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf] [h.sf.FBtul
1011 5/8" stucco /8"CMU/3/4"ISO No
No 0.21
5.73
34.65 4.8 ❑
BTWN24"oc/.5"
Gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
268
0.625" stucco
0.0521
0.000
❑
2
42
8 in. Lightweight concrete block
0.6670
0.000
❑
3
269
.75" ISO BTWN24" oc '
0.0625
0.000
❑
4
187
GY.D�, OR PLAS BOARD,1/2IN
0.0417
0.000
❑
9/27/2017 EnergyGauge Summit® v5.10 6
No Name Simple
Massless
Conductance
Heat Capacity
Density
RValue
Construct
Construct
[Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1056 Mtl Bldg Roof/R-30 Batt No
No
0.03
2.17
23.52
30.0 ❑
Layer Material
Material
Thickness
Framing
No.
IN
Factor
1 4
Steel siding
0.0313
0.000
❑
2 23
6 in. Insulation
0.5000
0.000
❑
3 12
3 in. Insulation
0.2500
0.000
❑
No Name
Simple Massless Conductance Heat Capacity
Density RValue
Construct Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf] - [h.sf.FBtu]
1058 Solid core flush (2.25)
No Yes 0.35
2.9 ❑
Layer Material Material Thickness Framing
No. [ft] Factor
1 279 Solid core flush (2.25") 0.000
0
9/27/2017
�v
EnergyGauge Summit® v5.10
❑E