Technical Evaluation Report
DIVISION: 23 08 00—COMMISSIONING OF HVAC
THIS DOCUMENT CONTAINS (4) PAGES: THE FIRST PAGE MUST BEAR AN
ORIGINAL SIGNATURE & SEAL OF THE CERTIFYING PE TO BE VALID FOR USE
(Subject to Renew July 1, 2022 or next code cycle change)
REPORT HOLDER:
MITSUBISHI ELECTRIC TRANE US HVAC LLC
1340 SATELLITE BLVD
SUWANEE, GA 30024, USA MITSUBISHI
678-376-2912 1 MEHVAC.COM /_ ELECTRIC
SCOPE OF EVALUATION (compliance with the following codes):
THIS IS A STRUCTURAL (WIND) PERFORMANCE EVALUATION
ONLY. NO ELECTRICAL OR TEMPERATURE PERFORMANCE
RATINGS OR CERTIFICATIONS ARE OFFERED OR IMPLIED
HEREIN.
This Product Evaluation Report is being issued in accordance with the
requirements of the Florida Building Code Seventh Edition (2020)
per FBC Section 104.11.1, FMC 301.15, FBC Building Ch. 16, ASCE-
7-16, FBC Existing Building sections 707.1, 707.2, FBC Building
1522.2, and FBC Residential M1202.1, M1301.1, FS 471.025, including
Broward County Administrative Provisions 107.3.4. This report is also
in accordance with the International Building Code (2012, 2015, &
2018). The product noted on this report has been tested and/or
evaluated as summarized herein.
IN ACCORDANCE WITH THESE CODES EACH OF THESE
REPORTS MUST BEAR THE ORIGINAL SIGNATURE & RAISED
SEAL OF THE EVALUATING ENGINEER.
SUBSTANTIATING DATA:
• Product Evaluation Documents
Substantiating documentation has been submitted to provide this TER
and is summarized in the sections below.
• Structural Engineering Calculations
Structural engineering calculations have been prepared which evaluate
the product based on comparative and/or rational analysis to qualify the
following design criteria:
• Maximum allowable unit panel wind pressure connection
integrity
• Maximum allowable uplift, sliding, & overturning moment
for ground and roof applications
Calculation summary is included in this TER and appears below.
NOTE: No 33% increase in allowable stress has been used in the
design of this product.
INSTALLATION:
The product(s) listed above shall be installed in strict compliance with
this TER & manufacturer -provided model specifications.
The product components shall be of the material specified in the
manufacturer -provided product specifications. All screws must be
installed in accordance with the applicable provisions & anchor
manufacturer's published installation instructions.
LIMITATIONS & CONDITIONS OF USE:
Use of this product shall be in strict accordance with this TER as noted
herein. See final page for complete limitations and conditions of use.
INSTALLATION:
Shall follow manufacturer specifications as well as information provided
herein.
FINISH:
Baked enamel, casing color white ivory.
K: s
Florida Building Code 6th &
7th Editions (2017 & 2020)
International Building Code
(2012, 2016, & 2018)
<. 0
NOTE: THE GRAPHICAL DEPICTIONS IN THIS REPORT ARE FOR
ILLUSTRATIVE PURPOSES ONLY AND MAY DIFFER IN APPEARANCE.
UNIT CASING MATERIAL:
25ga galv. sheet steel equivalent to ASTM A653 CS Cold Rolled Steels.
Removable top & side covers secured with #8 SAE 1016 SMS screws.
Knockouts provided for utility & control connections.
OPTIONS:
This evaluation is valid for all MITSUBISHI models that appear in the table
located on the final page of this report.
STRUCTURAL PERFORMANCE:
Models referenced herein are subject to the following design limitations:
Maximum Rated Wind Pressures*:
± 119 psf Lateral, 94 psf Uplift
Required design wind pressures shall be determined according to the design
pressure guide provided in the appendix or on a site -specific basis in accordance
with ASCE 7 and applicable sections of the building code(s) being referenced in
accordance with ASO methodology.
- Required design pressures shall be less than or equal to the maximum
pressures listed herein.
- *Maximum Rated Wnd Pressures indicate the maximum pressures that all
units listed herein are approved for. Valid for at -grade and rooftop applications.
See limitations herein.
Valid for use inside and outside the High -Velocity Hurricane Zone (HVHZ).
Site -specific wind analysis may produce alternate limitations provided maximum
rated wind pressures stated herein are not exceeded.
VISIT ECALC.10/34959 r
FOR ENGINEER CERTIFIED ORIGINALS
& MORE INFORMATION ABOUT THIS DOCUMENT
OR SCAN THIS OR CODE
VISIT ENGINEERINGEXPRESS.CONi/STORE FOR ■
ADDITIONAL PLANS, REPORTS & RESOURCES IN I
ORIGINAL SIGNATURE AND RAISED SEAL
OR DIGITAL SEAL REQUIRED TO BE VALID PER CODE:
Frank Bennardo, PE, SECB ❑ If Checked, Certifying
ENGINEERING EXPRESS® Engineer and PE #
FL PE#0046549 FLCA #9885 Appear Above
DIGITAL SEAL NOTICE: IF THIS DOCUMENT IS DIGITALLY SIGNED, THIS SHEET IS PART OF A
DIGITALLY SIGNED FILE. IT SHALL REMAIN IN DIGITAL FORMAT, SHALL BE VERIFIED BY
ELECTRONIC MEANS, & PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED. VISIT ECALC.10/DS TO LEARN MORE.
PRINTED DOCUMENT NOTICE: IF THIS DOCUMENT IS PRINTED & DOES NOT CONTAIN AN
ENGINEER'S ORIGINAL SIGNATURE & SEAL, THIS DOCUMENT IS VOID & NOT VALID FOR
USE. PHOTOCOPIES ARE NOT PERMITTED FOR USE.
^.nnvrinht n Fnninearinn Fyn —OF) All RlnhtS RPSBNP.d
The FBC17' Edition (2020) defines APPROVED SOURCE (Section 202) as: "An independent person, firm or corporation, approved by the building official, who is competent and experienced in the application of
engineering principles to materials, methods or systems analyses." Engineering Express® professionals meet the competency requirements as defined in the FBC and can seal their work. Engineering Express® is
regularly engaged in conducting and providing engineering evaluations of single -element and full-scale building systems.
MITSUBISHI M-SERIES SYSTEMS Engineering TER-20-34959
SECTION 2 PRODUCT INSTALLATION
Conder-- "-"
Roof,
structure / substrate
(concrete, steel, see
schedule below)
Mechanical Unit
for illustration purposes.
Tie -down clips for
ground application
in Group IV. See
Tie -Down Strap
and Clip Schedule.
Foot integrated clips
see chart below for
installation anchors
Anchor to Host Structure Schedule
Max
Max
1/8"Min
1/8" Min
Unit
Lateral
Uplift
Concrete
A36
6061-T6
Model
Pressure
Pressure
3,000 psi
Steel
Aluminum
43 psf
0 psf
A, C
N/A
N/A
Group
1,11
119 psf
94 psf
N/A
B
B
Group
43 psf
0 psf
C
N/A
N/A
III, IV
119 psf
94 psf
N/A
B
B
Anchor Types to Host Structure:
A. - 1/4" Dewalt ULTRACON SS4 Anchor embedded 1-3/4" in 3,000 psi concrete.
2-1/2" from edge minimum.
B. - 318" -16 UNC SAE Grade 5 screw minimum 1/2" from edges with nut and
washer specified, for integrated foot installed at roof.
C. - 1/4" Stanley/ Powers Wedge Bolt embedded 2" into 3000 psi concrete, 2"
edge distance minimum.
NA. - NOT APPLICABLE
Tie -Down Strap & Clip Schedule
Unit
Model
Max
Lateral
Pressure
Max
Uplift
Pressure
Tie-
Down
Strap
(qty)
Minimum
WILL (Ibs)
Additional
Tie -Down
Clips Per
Long Side
43 psf
0 psf
N/A
N/A
N/A
Group
89 psf
70 psf
2
500
N/A
I, II
106 psf
84 psf
2
600
N/A
119 psf
94 psf
2
700
N/A
43 psf
0 psf
N/A
N/A
N/A
Group
89 psf
70 psf
2
600
N/A
III
106 psf
84 psf
2
800
N/A
119 psf
94 psf
2
1000
N/A
43 psf
0 psf
N/A
N/A
2
Group
89 psf
70 psf
2
1500
N/A
IV
106 psf
84 psf
2
2000
N/A
119 psf
94 psf
2
2000
N/A
UNIT INTEGRATED FOOT
Equivalent to ASTM A653
galvanized cold rolled steel 0.039"
thick; fasten cabinet using Anchor
from Anchor Schedule to Host
Structure Table and SAE GR5
ASTM-A449 OD V washer & nut to
secure anchor to supporting
structure. (Figure for illustration
purposes)
Tie -down Strap Type:
(for roof applications)
Working Load Limit (WLL)
is strap's manufacturer -
specified per strap, strap
length shall be verified on
site for all cabinets.
NA. - No straps required
TIE -DOWN CLIP
(GROUND APPLICATION)
Miami Tech CUTD 1"wide and any
length ASTM A653 galvanized
steel 0.07" thick for all cabinets tied
down at ground; fasten clip to host
structure using anchor from
Anchor Schedule to Host Structure
Table and (4) #10-16 x 3/8" SS 316
self -drilling screw to fasten clip to
unit. Install at the unit corners with
quantities shown in Tie -down strap
and clip schedule table. For units
in group IV.
ROOF STAND
(BY OTHERS)
STRAPS
(SEE SCHEDULE)
MECHANICAL UNIT
SEE ANCHOR j
SCHEDULEFOR
REQUIREMENT
SUPPORTING STRUCTURES:
METAL STAND.
CONCRETE SLAB.
WALL BRACKET.
METAL CURB.
Note:
Tie -down straps shall be wrapped around unit and roof stand rail, and
shall be tightened using the buckle. Provide two straps per unit.
Straps material shall be high strength webbing and shall be compliant
for exterior grade use if they contain plastic components, per FBC
chapter 26. Select strap from table based on WLL requirements
IN ALL CONDITIONS IT IS THE RESPONSIBILITY OF THE PERMIT HOLDER TO ENSURE THE HOST STRUCTURE IS CAPABLE OF
WITHSTANDING THE RATED GRAVITY, LATERAL, AND UPLIFT FORCES BY SITE -SPECIFIC DESIGN. NO WARRANTY OF ANY KIND,
EXPRESSED OR IMPLIED, IS OFFERED BY ENGINEERING EXPRESS AS TO THE INTEGRITY OF THE HOST STRUCTURE TO CARRY DESIGN
FORCE LOADS INCURRED BY THIS UNIT.
CORP OFC: 160 SW 12TI AVENUE SUITE 106, DEERFIELD BEACH, FLORIDA 33442 Page 2of4
(954) 354-06601(866) 396-99991ENGINEERING EXPRESS.COMITEAM@ENGINEERING EXPRESS. COM
MITSUBISHI M-SERIES SYSTEMS Engineering I TER-20-34959
ELEVATIONS & DIMENSIONS
Cabinet
Model Number
Width
(in)
Depth
(in)
Height
(in)
Weight
(lbs.)
Group I
MUFZ-KJ09/12NAHZ-U*
31.5
11.25
21.63
83
MUZ/Y-GL09/12/15NA-U*
31.5
11.25
21.63
81
MUZ-HM09/12/15/18NA2-U1
31.5
11.25
21.63 1
73-81
MUZ-FS06/09/12NA(H)
31.5
11.25
21.63
81-83
SUZ-KA09/12/15NA2
31.5
11.25
21.63
66-80
MUZ-JP09/12WA
31.5
11.25
21.63
73
MUZ-WR09/12/18NA
31.5
11.25
21.63
73-81
Group II
MUZ/Y-D30/36NA
33.06
13
33.44
126-143
SUZ-KA18/24/30/36NA2
33.06
13
33.44
129
MUZ/Y-GL18/24NA-U1
33.06
13
34.63
119-121
MUZ-HM24NA2-U1
33.06
13
34.63
121
MUZ-FS15/18NA(H)
33.06
13
34.63
124
MXZ-2C20NA2-U1
33.06
13
27.94
126
MUFZ-KJ15/18NAHZ-U1
33.06
13
34.63
124
MUZ-WR24NA
33.06
13
34.63
121
Group
III
MXZ-3C24/30/36NA2-U1
37.41
1 13
31.34
137
SUZ-KA09/12/15/18NAHZ
37.41
13
34.63
129-131
SUZ-KA24NAHZ
37.41
13
37.13
190
MXZ-5C42NA2-U1
37.41
13
41.27
189
MXZ-2C20NAHZ2-U1
37.41
13
41.27
187
MXZ-3C24NAHZ2-U1
37.41
1 13
41.27
189
MXZ-3C30NAHZ2-U1
37.41
13
41.27
189
Group
IV
SUZ-KA30/36NAHZ
41.34
13
52.69
261
MXZ-8C48NAHZ-U1
41.34
13
52.69
276
MXZ-8C48NA2-U1
41.34
13
52.69
269
MXZ-8C60NA2-U1
41.34
13
52.69
309
MXZ-4C36NAHZ-U1
41.34
13
52.69
276
MXZ-5C42NAHZ-U1
41.34
13
52.69
276
-LA
TOP PANEL
GROUP III
... .........
�ui��1111�1IiII��,�IIIIIIIII��uIlhlllllll�l�u. � ',
III!!I1!!f�llllldn8lil!i!i!iiiILIIIV111illll!�II � I�
Illli!IIII�IIi1111111111111IILIIIIIMIN
!11�11
IIIIII�1�1lli�hqI111111111 I�INII
Images for illustration purposes,
Panel Integrity Summary
Panel
Max
Applied
Wind
Pressure
Pressure
Direction
Additional Screws
Needed (pcs)*
Groups
I, II, III
Group
IV
Top
Panel
94 psf
Uplift
NONE
NONE
Panel C
119 psf
Lateral
NONE
NONE
Panel D
119 psf
Lateral
N/A
NONE
Panel A
0 psf
Lateral
NONE
NONE
Panel B
43 psf
Lateral
NONE
NONE
Panel A
89 psf
Lateral
NONE
1
Panel B
89 psf
Lateral
NONE
1
Panel A
119 psf
Lateral
NONE
2
Panel B
119 psf
Lateral
NONE
2
*Additional Screws are required beyond original manufactured cabinet
UNIT PANELS
LI C
C
C
LIMITATIONS & CONDITIONS OF USE: actual units may differ.
Use of this product shall be in strict accordance with this TER as noted herein. 111 ill- -
The supporting host structure shall be designed to resist all superimposed loads as determined by others on a
site specific basis as may be required by the Authority Having Jurisdiction. Host structure conditions which are
not accounted for in this product's respective anchor schedule shall be designed for on a site -specific basis by a
registered professional engineer. No evaluation is offered for the host supporting structure by use of this J_
document; Adjustment factors noted herein and the applicable codes must be considered, where applicable. All
supporting components which are permanently installed shall be protected against corrosion, contamination, and
other such damage at all times. Fasteners must penetrate the supporting members such that the full length of the
threaded portion is embedded within the main member.
This evaluation does not offer any evaluation to meet large missile impact debris requirements which typically are not required for this type
of product.
All of the wind resisting exterior panels, individually meet or exceed their capacity to resist the design wind loads as stated in the calculations
as required by the Codes and standards herein. Due to the indeterminate nature of these units, distortion and deflection cannot be
accurately evaluated, but with diaphragm action of external components and internal stiffeners, the base unit has the capacity to withstand
these forces with individual external parts being contained. Yearly inspections, during equipment maintenance or after named storm, all
screws, cabinet components, clips and anchor bolts are to be verified by the A/C contractor. All damaged cabinet components, loose,
corroded broken tech screws or anchor bolts shall be replaced to ensure structural integrity for hurricane wind forces.
TOP PANEL
TOP PANEL
GROUP
A
i
GROUP II
A'.
i
- i
I
TOP PANEL GROUP VI
0
1II10
Proj. #
Remarks
By
Checked
Date
17.51 11.1
Initial Issue
LAO
FLB
7/30/19
20-34959
2020 FBC
CCB
RVVN
1/25/21
CORP OFC: 160 SW 12T11 AVENUE SUITE 106, DEERFIELD BEACH, FLORIDA 33442 Page 3of4
(954) 354-06601(866) 396-99991ENGINEERINGEXPRESS.COMITEAM@ENGINEERING EXPRESS.COM
MITSUBISHI M-SERIES SYSTEMS
Engineering I TER-20-34959
APPENDIX A: DESIGN WIND PRESSURE GUIDE
Max. Ult.
Wind
Speed
(Vuk)
Max.
of
(Roof
Height)
Exposure
Category
Required Design
Wind Pressures (ASD)
Lateral
Pressure
Uplift
Pressure
140 mph
At -Grade
(0 ft)
C
26 psf
21* psf
D
31 psf
25* psf
100 ft
C
67 psf
53 psf
D
75 psf
59 psf
200 ft
C
76 psf
60 psf
D
84 psf
67 psf
175 mph
At -Grade
(0 ft)
C
40 psf
32* psf
D
49 psf
39* psf
100 ft
C
104 psf
82 psf
D
117 psf
93 psf
200 ft
C
119 psf
94 psf
- --
D
186 mph
At -Grade
(0 ft)
C
46 psf
36* psf
D
55 psf
44* psf
100 ft
C
117 psf
93 psf
D
200 ft
C
D
$
indicates a design wind pressure that is not
approved for use by this evaluation. Seek
additional engineering or contact this office
for design solutions.
UNIT REACTIONS FROM WIND GUIDE
L
N
Example:
U
1
D/2
DIRECTIVE: This design pressure guide is for reference only and shall be approved for
use by the Authority Having Jurisdiction (AHJ). If the design pressures listed in this guide
are not used, required design pressures shall be calculated on a site -specific basis by
others. For site -specific scenarios classified as Exposure Category B, the required design
pressures stated for Exposure Category C in the above guide shall be used or design
pressures shall be calculated separately. For heights and parameters beyond the above
values, consult with an engineer for a site -specific analysis.
The required ASD design pressures listed in the above guide were calculated based on
the parameters listed below. The project design professional or permitting contractor shall
verify that the site -specific conditions are equal to or less than the design parameters
listed below.
*Note: Per the codes and standards referenced herein, uplift is optional for mechanical
equipment at -grade. At the discretion of the AHJ, uplift may be taken as 0 psf or as the
value listed in the guide.
At -Grade (0 ft MRH) Required Design Pressures:
o ASCE 7 "Design Wind Loads: Other Structures"
o Structure Shape = Square, flat terrain
o Height of structure (unit + stand or curb, if used) = 6 ft max.
o Width of unit = 1 ft min., Depth of unit = 1 ft min.
o Uplift Pressure = Lateral Pressure x 1.5 / 1.9 (if considered)
Rooftop (>15 ft MRH) Required Design Pressures:
o ASCE 7 "Design Wind Loads: Other Structures:
Rooftop Structures and Equipment for Buildings"
o Structure Shape = Square, flat terrain
o z = up to 7 ft, where z = height of stand or curb + % unit height
o Lateral GCf= 1.90; Uplift GCf= 1.50
VISIT ECALC.10/FORCES ■0❑
FOR HELP DETERMINING DESIGN
PARAMETERS AND TO SEE MORE EXAMPLES, ❑
OR SCAN THE OR CODE TO THE RIGHT>
DIRECTIVE: This guide is intended for use by a project design professional. Design parameters shall abide all
specifications and limitations stated in this report. Design Professional shall consider all forces, including seismic
and snow loads per governing building codes. Unit reactions obtained from this guide shall be verified by a
registered Professional Engineer. Reactions are applicable for unit -to -host connections only. Sample calculations
are provided below.
Design Parameters:
- Lateral Wind Pressure, Plat
- Uplift Wind Pressure, P_up
- Unit Height, H
- Unit Depth, D
D
- Unit Width, W
- Unit Weight, Wt
- Support Spacing across Depth, sd
- Support Spacing across Width, sw
Unit Reaction Equations:
f
Wit
Long Side (Width x Height):
Short Side (Depth x Height):
- Sliding Force, L= Plat x W x H
Sliding Force, L= Plat x D x H
- Uplift Force, U= P_up x W x D
Uplift Force, U= P—up x W x D
sd
- Total Tension per Long Side =
Total Tension per Short Side =
(LxH/2+Uxsd/2—Wtx0.6xsd/2)/sd
(LxH/2+Uxsd/2—Wtx0.6xsd/2)/sw
A (48" W x 36" D x 42" H), 250 lb net weight unit at wind pressures of 120 psf lateral
and 95 psf uplift, on a 24" wide roof stand,
shall have the following unit reactions:
Long Side (Width x Height)
Short Side (Depth x Height):
1. Sliding Force, L= Plat x W x H
= (120 psf) x (48 in) x (42 in) x (1 in2 / 144 ft2) = 1680 lb
2. Uplift Force, U= P—up x W x D
= (95 psf) x (48 in) x (36 in) x (1 inZ / 144 ft2) = 1140 lb
3. Total Tension per Long Side =
=(LxH/2+Uxsd/2—Wtx0.6xsd/2)/sd
_ ( (1680 lb x 42/2 in) + (1140 lb x 24/2 in) —
(250 lb x 0.6 x 24/2 in) ) / 24 in = 1965 lb
1. Sliding Force, L= Plat x D x H
= (120 psf) x (36 in) x (42 in) x (1 in2/ 144 ft2) = 1260 lb
2. Uplift Force, U= P—up x W x D
= (95 psf) x (48 in) x (36 in) x (1 in2/ 144 ft2) = 1140 lb
3. Total Tension per Short Side =
=(LxH/2+Uxsd/2—Wtx0.6xsd/2)/sw
_ ( (1260 lb x 42/2 in) + (1140 lb x 24/2 in) —
(250 lb x 0.6 x 24/2 in) ) / 48 in = 1046 lb
IN ALL CONDITIONS IT IS THE RESPONSIBILITY OF THE PERMIT HOLDER TO ENSURE THE HOST STRUCTURE IS CAPABLE OF WITHSTANDING THE
RATED GRAVITY, LATERAL, AND UPLIFT FORCES BY SITE -SPECIFIC DESIGN. NO WARRANTY OF ANY KIND, EXPRESSED OR IMPLIED, IS OFFERED
BY ENGINEERING EXPRESS AS TO THE INTEGRITY OF THE HOST STRUCTURE TO CARRY DESIGN FORCE LOADS INCURRED BY THIS UNIT.
CORP OFC: 160 SW 12TH AVENUE SUITE 106, DEERFIELD BEACH, FLORIDA 33442 Page 4of4