HomeMy WebLinkAboutAPPROVED, 3150 NORTH A1A-ELECTRICAL PLANSAUSTEN ENT
ISES INC.
Austen EI ric Inc. &Austen Air Conditioning Inc.
6200 W j 1ST CT
P H IALFAH FiA 33016
Off i c
F
EC 13001529 JC SHAWN CR
CAC 1817770 RICHARD A. CARRY
5 805 8166
30
PROJECT NAME
iara Tower
150 N AlA
Ft Pierce Fl, 34949
21-024
To Elevator Equipment
1 1 /4" C
3#3
14
8 GND
100k AIC 100k AIC TO ELEVATOR EQUIPMENT
100 100
1/2" C
.100 .100 3 # 12
250V 250V 130 130
LLX 3 X 15 15
1 1 /2" C===j
3#2 New Car 1 New Car 2
1#8GND 1/2"C
3#12
EXISTING A/C RISER DIAGRAM
EMDP PNL
1-Carl 125 amp INSIDE MACHINE ROOM OUTSIDE MACHINE ROOM
2- Car 2 125 amp
3- Cab Lt 1 20
4- Cab Lt 2 20 A H U
5- Machine rm a/c 20
NO HEAT
208V 3ph WIRELESS
300A ML O
r�
ACU
1/2"C4#12 THHN 30
215
1 /2" C 4# 12 THHN
1/2�12Gnd
30 n
3 #Cu
1 # �-7
JB LV
f' Conduit Nema 3R
2 # 12 Thhn Cu
1 # 12 Gnd GFCI WP RT RECEPTACLE
I GFCI
ELEVATOR MACHINE ROOM LAYOUT NTS
Existing Ckt to Reuse
Home Pnl ckt 10
411 LED vapor Proof Wrap
Note : This it layout is typical
of both cars. 1 & 2
SINGLE CAB ELEV. PIT NTS
FEED FROM House Pnl CT# 20
4ft LED vapor Proof Wrap
SCOPE OF WORN
1. Replace Main Line Safely Switch
2. Replace Cab Car Safety Switch.
3. Replace GFCI in Hoist way pit.
4. Replace GFCI in Machine room -
5. Replace lights in hoist way pit.
6. A/C connections
JC Shawn
Crow
Digitally signed by
JC Shawn Crow
Date: 2022.02.18
13:58:30-05'00'
AUSTEN ELECTRIC INC.
6200 W 21 ST CT
HIALEAH, FL 33016
305-805-8166
305-805-8190 FAX
EC 13001529
Drawn By: JCSA
Tiara Tower
3150 N A1A
Fort Pierce, FL 34949
21-024
FBC 2020 7th Edition —•—•--- BY OTHERS DATE 12/27/21 E 1
NATIONAL ELECTRIC CODE 2017 REUSE EXISTING NTS
ELEVATORS 1 & 2 N.T.S.
NEW / REPLACE
CONDENSER
AIR HANDLER
MFG: MITSUBISHI
MGF: MITSUBISHI
MUY-GL24NA-U1
MSY-GL24NA-U1
BTU : 22,500
NO HEAT
MAX BREAKER: 20 AMP
MAX BREAKER: 20 AMP
COPPER LINES
CFM : 738
3/8 & 5/8
SEER 20.5
ATTACHED
SEE WIND LOAD CALCULATION
FOR CONDENSER & CONDENSER
STAND MOUNTING BY ENGINEER.
ROC
NOT LESS THEN 12"
1
ROOF LEVEL
FBC 2020 7th Edition
738
CFM
Machine room Layout NTS
3/8" COPPER LIQ. LINE
AHU
�ll ii
II 5/8 COPPER SUC. LINEII II
3/4" PVC DRAIN LINE--))
ACU
ELEVATORS 1 & 2 N.T.S.
U
AIR HANDLER
N.T.S.
WATER LEVEL
MONITORING 3/4 PVC
DEVICE AS PER DRAIN TO ROOF DRAIN
FBCM 307.2.3.1
CONDENSOR LOCATED ON
MOUNTED ON ROOF EXTERIOR WALL
OF MACHINE ROOM ON WALL BRACKET
DUCT SCHEDULE
N/A
OPEN RETURN
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPER
X
SMOKE DAMPER
X
FIRE RATED ROOF / FLOOR
X
FIRE RATED ENCLOSER
X
FIRE STOPPING
X
SMOKE CONTROL
X
ISCOPE OF WORKI
1. INSTALL (1) 2TON MINI
SPLIT SYSTEM IN
ELEVATOR MACHINE
ROOM.
Richard
A Curry
Digitally signed by
Richard A Curry
Date: 2022.02.18
14:06:54-05'00'
AUSTEN A/C INC.
6200 W 21 ST CT
HIALEAH, FL 33016
305-805-8166
305-805-8190 FAX
CAC 1817770
Drawn By: JCSA
Tiara Tower
3150 N A1A
Fort Pierce, FL 34949
21-024
01
DATE 12/27/21 NTS IM 1
FBC 2020 7th Edition
NATIONAL ELECTRIC CODE 2017
Work Location
Machine room
SCOPE OF WOR
1. Replace Main Line Safety Switch,
2. Replace Cab Car Safely Switch.
3. Replace GFCI in Hoist way pit.
4. Replace GFCI in Machine room .
5. Replace lights in hoist way pit.
6. A/C connections
JC Shawn
Crow
Digitally signed
by JC Shawn Crow
Date: 2022.02.18
13:59:09-05'00'
AUSTEN ELECTRIC INC.
6200 W 21 ST CT
HIALEAH, FL 33016
305-805-8166
305-805-8190 FAX
EC 13001529
Drawn By: JCSA
Tiara Tower
3150 N A1A
Fort Pierce, FL 34949
21-024
DATE 12/27/21
�NTS�L-1
Z 1 1