APPROVED, 3150 NORTH A1A-MECHANICAL HEAT CALCULATIONS
Page 1 Commercial Heat Loss and Heat Gain Calculation 2/16/2022 Report Prepared By: Austen Air Conditioning, Inc. For: Tiara Tower 3150 North Al Fort Pierce, FI 34949 Design Conditions: Fort Pierce; Latitude: 27; Time 1:00 PM Indoor: Outdoor. Summer temperature: 75 Summer temperature: 90 Winter temperature: 72 Winter temperature: 42 Relative humidity: 50 Summer grains of moisture: 127 Daily temperature range: 15 Building Component Sensible Latent Total Total Gain Gain Heat Gain Heat Loss (BTUH) (BTUH) (BTUH) (BTUH) Miscellaneous 11,780 0 11,780 0 Ceilings 6,782 0 6,782 11,812 Lights 2,624 0 2,624 0 Door Leakage 290 942 1,232 1,353 Walls 298 0 298 1,617 Doors 79 0 79 198 Infiltration 0 0 0 0 Ventilation 0 0 0 0 People 0 0 0 0 Duct 0 0 0 0 Skylights 0 0 0 0 Partitions 0 0 0 0 Windows 0 0 0 0 Floors 0 0 0 0 Whole Building - All Components 21,853 942 22,795 14,980 (2tons) �RYIp(s•., MICHAELIA DE JESUS ' 4r-. Notary Public -State of Florida Commission # HH 052763 My Comm. Expires Oct 12, 2024 Bonded through National Notary Assn. HVAC-Calc Commercial 4.0 by HVAC Computer Systems Ltd. 888 736-1101 Load calculations are estimates only, actual loads may vary due to weather and construction differences.