Loading...
HomeMy WebLinkAboutSubmital Package Fire Protection PlanADT Commercial 3150 SW 42nd Ave Palm City FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial "-- commercial CRISTELLE CAY MAHI MAHI BUILDING Fire Protection plan 4802 ,Ocean Palms Drive Saint Lucie County, Florida Submittal Package ADT Commercial 3150 SW Ave n Commercial Palm Palm City,, FL. FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial Sprinkler Heads Bulletin 006 June 2021 Reliable Features • cULus Listed as Residential Sprinklers • Push -On cover plate installation • Low water flow requirements Product Description Model RFC Series residential sprinklers are flat cover plate, concealed pendent sprinklers intended for installation in accordance with NFPA 13, NFPA 13R, or NFPA 13D. The sprinklers are cULus Listed as Residential Sprinklers in accordance with UL 199. In addition, Model RFCLL Series sprinklers are cULus Certified for Health Effects to NSF/ANSI standard 61 Annex G (LL) and Australian WaterMark Certified (WMCS). Model RFC30 sprinklers have a 165°F (74°C) temperature rated fusible -link operating element. Model RFC43, RFC49, RFC58, and RFC76 sprinklers are offered with either a 165°F (74°C) or 212°F (100°C) temperature rated fusible -link operating element. Sprinklers with a 165°F (74°C) temperature rating are ordinary temperature classification and are listed for use with a 135°F (57°C) temperature rated cover plate. Sprinklers with a 212OF (100°C) temperature rating are intermediate temperature classification and are listed for use with a 165°F (74°C) temperature rated cover plate. Model RFC Series sprinklers are installed with a Model G5 cover plate. Model G5 cover plates are installed by pushing the cover plate into the cup and turning in the clockwise direction until it is tight against the ceiling. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and RFC49LL sprinklers allow 1/2" (13 mm) of cover plate adjustment. Model RFC58 and RFC76 sprinklers allow 3/4" (19 mm) of cover plate adjustment. Model G5 cover plates are available in a variety of finishes as listed in Table H. Model RFC Series Residential Sprinklers Flat Concealed Pendent Model RFC30 & RFC30LL Model RFC76 cULus Listed i Model RFC43 & RFC43LL Model RFC58 Model G5 Cover Plate Sprinkler Model p Nominal K-Factor gpm/psi"Z (I/min/bar12) Max. Coverage Area ft x ft (m x m) Listings & Approvals Sprinkler Identification Number (SIN) RFC30 3.0(43) 14 x 14 (4.3 x 4.3) cULus RA0611 RFC30LL 3.0(43) 14 x 14 (4.3 x 4.3) cULus, LL, WMCS RA3211 RFC43 4.3(62) 20 x 20 (6.1 x 6.1) cULus RA0612 RFC43LL 4.3(62) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3212 RFCE 4.9�(71) 20,x 20 (6.1x 6.1) cULus RA0616 RFC49LL 4.9(71) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3216 RFC58 5.8(84) 20 x 20 (6.1 x 6.1) cULus RA0613 RFC76 7.6(109) 20 x 20 (6.1 x 6.1) cULus RA0618 cULus: cULus Listed to UL199, Automatic Sprinklers for Fire -Protection Service. LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content). WMCS: Australian WaterMark Certified. www.reliablespdnkler.com Technical Specifications Style: Flat Concealed Pendent Threads:1/2" NPT or ISO 7-1R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating 165°F (74°C) sprinkler 135°F (57°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 199 cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC30LL only) Watermark Certified (RFC30LL only) Model RFC30 & RFC30LL Sprinkler Components and Dimensions i nrea, Body Cup Tower Fusible Lir Deflector (retrac Pin (extent Deflector (extent 1-3/4" (44 mm) +/-1/4" (6 mm) Nominal face of fitting to ceiling Model G5 Cover Plate Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria Bottom View 2-5/16" (68 mm) Cup Dia. ME 3-5/16" (84 mm) Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) Ceiling Table Minimum Flow and Residual Pressure (') Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (I/min) (bar) 12 x 12 9 9.0 (3.6 x 3.6) (34) (0.62) 14x 14 10 11.0 (4.3 x 4.3) (38) (0.76) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Re� b Page 2 of 8 June 2021 www.reliablespdnkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1R1/2 Nominal K-Factor: 4.3 (62 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 199 cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC43LL only) Watermark Certified (RFC43LL only) Bottom View, a a Model RFC43 & RFC43LL Sprinkler Components and Dimensions �. 2-5/16" Threads Threads (58 mm) Cup Dia. Body Cup �` Tower 1-3/4" (44 mm) +/-1/4" (6 mm) 2-5/8" (67 mm) Hole in Ceiling Fusible Link Nominal face of fitting to ceiling 3/16" Deflector (retracted) - (5 mm) Pin (extended) - i i 00GFG0UZ_W ti tf Deflector (extended)—tizcaiir 3-5/16" VCeiling Model G5 Cover Plate (84 mm) Dia. Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria - Minimum Flow and Residual Pressure (1) Max. Coverage Area (2) Ordinary Temperature Intermediate Temperature Flow Pressure Flow Pressure ft. x ft. (m x m) gpm psi gpm psi (I/min) (bar) (I/min) (bar) 15 x 15 12 7.8 12 7.8 (4.6 x 4.6) (45) (0.54) (45) (0.54) 16 x 16 13 9.1 13 9.1 (4.9 x 4.9) (49) (0.63) (49) (0.63) 18 x 18 18 17.5 (5.5 x 5.5) (68) (1.21) 20 x 20 21 23.8 (6.1 x6.1) (79) (1.64) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Rel b Page 3 of 8 June 2021 � www.reliablespdnkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1 R1/2 Nominal K-Factor: 4.9 (71 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications. Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74"C) sprinkler 135°F (57"C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74'C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Cover Plate Finishes Listings and Approvals cULus Listed to UL 199 (See Table H) cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC49LL only) Watermark Certified (RFC49LL oniv) Bottom View ; Model RFC49 & RFC49LL Sprinkler Components and Dimensions �• �l Threads Body Cup Tower Fusible Link Deflector (retracted) Pin (extended) Deflector (extended) - j 2-5/16" (58 mm) Cup Die. 1-3/4" (44 mm) +/-1/4" (6 mm) Nominal face of fitting to ceiling �"",_0?_M Model G5 Cover Plate 3-5/16" (84 mm) Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) Ceiling Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria) .CHI - i Minimum Flow and Residual PressureM Max. Coverage Area (z) Ordinary Temperature Intermediate Temperature Flow Pressure Flow Pressure ft. x ft. (m x m) gpm psi gpm psi (I/min) (bar) (I/min) (bar) 16 x'1`6 13 7.0 ' 13 7.0 (4.9 x 4.9) (49.0) (0.48) (49.0) (0.48) 1:8-x.18 17 12.0 17 12.0 (5.5 x 5.5) (64.3) (0.83) (64.3) (0.83) 20 x 20 20 16.7 21 18.4 (6.1 x6.1) (75.7) (1.15) (79.5) (1.27) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to achieve a mini- mum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 ROOM 4 of 8 June 2021 � www.reliablespdnkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1111/2 Nominal.K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) , Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Chrome Plated Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Ratings Ordinary: 165"F (74°C) sprinkler 135"F (57°C) cover plate Intermediate: 212"F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 199 Bottom View �-; :VVF I Model RFC58 Sprinkler Components and Dimensions �l Threads Body Cup �\ Tower Fusible Link Deflector (retracted) - Pin (extended) - Deflector (extended) 1-7/8" (48 mm) +/- 3/8" (9 mm) Nominal face of fitting to ceiling 0"fiFlG09A Model G5 Cover Plate Model RFC58 Sprinkler Hydraulic Design Criteria 2-5/16" (58 mm) Cup Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16" (5 mm) 3-5/16" (84 mm) IL Ceiling Die. Table Minimum Flow and Residual PressureN Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 16 x 16 16 7.6 (4.9 x 4.9) (60.6) (0.53) 18 x 18 18 9.6 (5.5 x 5.5) (68.1) (0.66) 20 x 20 20 11.9 (6.1 x 6.1) (75.7) (0.82) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Page 5 of 8 June 2021 Reliable www.reliablespdnkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 3/4" NPT or ISO 7-1 R3/4 Nominal K-Factor: 7.6 (109 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Ratings Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model G5 Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 199 Model RFC76 Sprinkler Components and Dimensions Threads Body Cup —� Tower —� Fusible Link Deflector (retracted) Pin (extended) - Deflector (extended) - 1-7/8" (48 mm) +/- 3/8" (9 rr Nominal face of fitting to cei OO6flGO5A Model G5 Cover Plate Bottom View 2-5/16" (58 mm) Cup Dia. 2-5/8" (67 mm) Hole in Ceiling 3/16, (5 mm) 3-5/16" V, (84 mm) Ceiling Dia. Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria �. Minimum Flow and Residual PressureN Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 16 x 16 21 7.6 (4.9 x 4.9) (79.5) (0.52) 18 x 18 24 9.9 (5.5 x 5.5) (90.8) (0.68) 20 x 20 34 20 (6.1 x 6.1) (128.7) (1.4) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Page 6 of 8 June 2021 eliab a www.reliablespdnkler.com Cover Plate FinishesM Standard Finishes Special Application Finishes White Polyester Off White Paint Black Paint Raw Brass Chrome Plated Bright Brass Finished Bronze Black Plated Satin Chrome Stainless Steel Clad(3) Custom Color Paint(2) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Custom color paint is semi -gloss, unless specified otherwise. 3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side. Cover plates are not listed or approved as corrosion resistant. Installation Dimensions Recommended Min. to Min. to Max. Sprinkler Cover Cover Plate Hole Diameter Cover Plate Max. Face Dropped Deflector Cover Plate Model Plate Diameter in Ceiling Adjustment of Fitting to Distance below Temperature Model inch (mm) inch (mm) inch (mm) Ceilings') Ceiling Rating .inch (mm) inch (mm) RFC30, G5 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 135'F RFC30LL (84) (67) (13) (38 to 51) (13 to 25) (57'C) RFC43, 135'F(2) RFC43LL, G5 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 (57'C) RFC49, (84) (67) (13) (38 to 51) (13 to 25) or 165'F(3) RFC49LL I I I (74°C) RFC58, G5 3-5/16 2-5/8 3/4 1-1 /2 to 2-1 /4 1 /4 to 1 131(55F 3C) or 6 RFC76 (84) (67) (19) (38 to 57) (6 to 25) (745* Notes: 1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method prior to installation. A 1/2" x 1/2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing sprinklers. 2. For use with 165'F (74'C) temperature rated sprinklers where the maximum ceiling temperature does not exceed 100'F (38'C). 3. For use with 212'F (100'C) temperature rated sprinklers where the maximum ceiling temperature does not exceed 150'F (66'C). Installation Model RFC series sprinklers are intended to be installed in accordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the requirements of applicable authorities having jurisdiction. Model RFC series sprinklers must not be installed in ceilings with positive pressure in the space above. Ensure that the 4 slots in the cup are open and unobstructed following installation. Model RFC series sprinklers are shipped with a wrench -able protective cap that should remain on the sprinkler until the sprinkler system is placed in service following construction. Model RFC series sprinklers can be installed without removing the wrench -able protective cap using the Model W3 wrench. Alternatively, Model RFC series sprinklers can be installed using the Model FC wrench by temporarily removing the protective cap during installation of the sprinkler. The use of any other wrench to installed Model RFC series sprinklers is not permitted and may damage the sprinkler. Fully insert the Model W3 wrench over the cap until it reaches the bottom of the cup, or the Model FC wrench over the sprinkler until the wrench engages the body. Do not wrench any other part of the sprinkler/cup assembly. The Model W3 and FC wrenches are designed to be turned with a standard 1/2" square drive. Tighten the sprinkler into the fitting after applying a PTFE based thread sealant to the sprinkler's threads. Recommended installation torque for iron pipe fittings is 8 to 18 ft-Ibs (11 to 24 N-m) for 1/2" thread sprinklers and 14 to 20 ft-Ibs (19 to 27 N-m) for 3/4" thread sprinklers. Note: When used with gasketed fittings, follow fitting manufacturer's installation instructions regarding tightening to achieve a leak -free connection. Do not exceed the maximum recommended torque. Exceeding the maximum recommended torque may cause leakage or impairment of the sprinkler. Use care when inserting or removing the wrench from the sprinkler to avoid damage to the sprinkler. Install the cover plate by hand by pushing the cover plate into the cup and turning the cover in the clockwise direction until it is tight against the ceiling. Bulletin 006 June 2021 Page 7 of 8 www.reliablesprinkler.com Model FC For use with Model RFC Series sprinklers without wrench -able cap installed Model W8 High -strength plastic wrench for limited (emergency) use with Model RFC Series sprinklers without wrench -able cap installed. Meets NFPA requirements for sprinkler wrench on premises. Maintenance Model RFC series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by gentle vacuuming. Replace any sprinkler cover plate assembly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non -operation. Guarantee For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, and conditions, visit www.reliablesprinkler.com. Model W3 For use with Model RFC Series sprinklers with wrench -able cap installed Listings and Approvals Listed by Underwriters Laboratories, Inc. and UL Certified for Canada to UL 199, Automatic Sprinklers for Fire -protection Service (cULus). Certified by Underwriters Laboratories, Inc. and Underwriters Laboratories of Canada for Health Effects to NSF/ANSI Standard 61 Annex G (LL) (RFC30LL, RFC43LL, and RFC49LL only). Australian WaterMark Certified (RFC30LL, RFC43LL, and RFC49LL only). Patents Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprinklers are covered by U.S. Patent No. 9,248,327 and U.S. Patent No. 7,275,603. Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are additionally covered by U.S. Patent No. 8,776,903. Ordering Information Specify the following when ordering. Sprinkler • Model (RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, RFC58, RFC76) • Temperature Rating Cover Plate • Model G5 • Temperature Rating • Finish (See Table H) Sprinkler Wrench • Model FC • Model W3 • Model W8 (Limited use) R. Bulletin 006 June 2021 Page 8 of 8 www.reliablespdnkler.com Bulletin 014 August 2021 Model F1 FR56 Sprinkler Types Standard Spray Upright Standard Spray Pendent Conventional Upright/Pendent Vertical Sidewall Horizontal Sidewall Model F1 FR56 Recessed Sprinkler Types Standard Spray Pendent Horizontal Sidewall Model F1 FR56 Concealed Sprinkler Types Standard Spray Pendent Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler Types Standard Spray Upright Standard Spray Pendent Model F1 FR40 Sprinkler Types Standard Spray Pendent Model F1 FR42, F1 FR40, F1 FRXLH & F1 FR28 Recessed Sprinkler Types Standard Spray Pendent Model F1 FR56LL & F1 FR42LL Low Lead Sprinkler Types Standard Spray Pendent with less than 0.25% Lead Con- tent Listing & Approvals The following organizations provide Listings or Approvals for various Model F1 FR series sprinklers. See the Design and Installation table in this Bulletin for information on specific listings and approvals applicable to each sprinkler. 1. Underwriters Laboratories Inc. and Certified for Cana- da (cULus) in accordance with ANSI/UL199. 2. FM Approvals (FM) 3. Loss Prevention Certification Board (LPCB) 4. VdS Schadenverh0tung GmbH (VdS) 5. Underwriters Laboratories Inc. and Underwriters Lab- oratories of Canada Certified for Health Effects to NSF/ ANSI Standard 61 Annex G (ULH) 6. EC Certificate: 0786-CPD-40239 (RA1414), 0786- CPD-40251 (RA1425), 0786-CPD-40252 (RA1475) (EC) 7. WaterMark certified. Certificate Number 23347. (WM) UL Listing Category Sprinklers, Automatic & Open (VNIV) Quick Response Sprinkler Model F1 FR Series Quick Response Glass Bulb Sprinklers r� Ij i.a a � Upright Pendent Conventional Vertical Sidewall Horizontal Sidewall Recessed Pendent/F1 /F2 d le t Recessed Concealed Recessed Horizontal Sidewall Pendent Pendent/FP XLH Upright XLH Pendent XLH Recessed Pendent F1 /F2 Product Description Reliable Model F1 FR series sprinklers are quick -response automatic sprinklers with a glass bulb thermal element. Model F1 FR series sprinklers are Standard Spray sprinklers, with the exception of the Model F1 FR56 Conventional sprinkler which is XLH Recessed an Old-style/Conventional sprinkler. Pendent FP The Model F1 FR Series automatic sprinklers utilize a 3.0 mm frangible glass bulb. These sprinklers have demonstrated response times in laboratory tests which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1 FR Series sprinklers to apply water to a fire faster than standard -response sprinklers of the same tem- perature rating. The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed inside a precisely manufac- tured glass capsule. This glass bulb is specially constructed to provide fast thermal response. 03 c CID aD N O N Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the liquid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflector to distribute the discharging water. Model F1 FIR Series sprinklers provide a wide range of options where quick -response, glass bulb sprinklers are used: • Pendent, recessed pendent, upright, horizontal side - wall, and vertical sidewall deflectors • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 metric), and 5.6 (80 metric) • Flush, recessed, and concealed installations See the Design and Installation Information table in this Bul- letin for information on the approvals and availability of specific Model F1 FIR series sprinkler configurations. Model F1 FIR Recessed Pendent and Recessed Horizontal Sidewall sprinklers are required to be used with Reliable Model F1, F2, or FP recessed escutcheons. See the Recessed Es- cutcheon Data table in this Bulletin for listing and approval infor- mation with each specific Model F1 FIR series sprinkler. Model F1 and F2 recessed escutcheons, shown in Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch (19mm) and 1/2- inch (12.7mm) of adjustment, respectively. Model FP recessed escutcheons, shown in Fig. 2, provide a 1/2-inch (12.7mm) threaded adjustment. Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers are required to be used with Model CCP cover plates. A standard profile Model CCP cover plate is available that provides up to 1/2-inch (12.7mm) of cover plate adjustment. In addition, a low profile Model CCP cover plate is also available that provides up to 5/16-inch (8.Omm) of cover plate adjustment. See the Design and Installation Infor- mation and Listed and Approved Temperature Ratings tables in this Bulletin for further information on approved cover plate options. Application Model F1 FIR Series sprinklers are intended for use in ac- cordance with NFPA 13, FM Property Loss Prevention Data Sheets, and the requirements of the Authority Having Juris- diction. Care must be exercised that the k-factor, tempera- ture rating, deflector style, and sprinkler type are in accor- dance with the requirements of the applicable design and installation standards. In addition, Model F1 FIR Series sprin- klers must be used in accordance with their listings and ap- provals, as well as the information provided in this Bulletin. Installation Glass bulb sprinklers have orange bulb protectors or protec- tive caps to minimize bulb damage during shipping, handling and installation. Reliable sprinkler installation wrenches are designed to install sprinklers with bulb protectors in place. Re- move the bulb protector at the time when the sprinkler system is placed in service for fire protection. Removal of the bulb protec- tor before this time may leave the bulb vulnerable to damage. Remove bulb protectors by undoing the clasp by hand. Do not use tools to remove bulb protectors. Model F1 FIR Series sprinklers must be installed with the Reli- able sprinkler installation wrench identified in the Design and Installation Information table in this Bulletin. Any other wrench may damage the sprinkler. A leak tight sprinkler joint can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do not tighten sprinklers over the maximum recommended installation torque. Exceeding the maximum recommended installation torque may cause leakage or impairment of the sprinkler. Recessed Sprinklers Model F1 FR Series Recessed sprinklers are to be installed as shown in Fig. 1, Fig. 2, or Fig. 3, as applicable to the specific model being installed. The Recessed Escutcheon Data table in the Bulletin identifies the only recessed escutcheons that are permitted to be used with each Model F1 FIR Series Recessed sprinkler. The use of any other recessed escutcheon will void all approvals and negate all warranties. Concealed Sprinklers Model F1 FR Series Concealed Pendent sprinklers are to be installed as shown in Fig. 4 or Fig. 5, as applicable to the selected cover plate. Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers have a facto- ry -installed Model CCP cup. A protective cap is installed at the factory that should remain on the sprinkler until the sprinkler is installed and should then be reinstalled on the sprinkler until the cover plate is installed. The concealed sprinkler assemblies are completed by the installation of a Model CCP push-on/thread- off cover plate assembly. The cover plate and sprinkler cup as- semblies are joined using a cover plate skirt with flexible tabs for threaded engagement. A choice of two Model CCP cover plate assemblies provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover adjustment. Do not install Model F1 FIR Series Concealed Pendent sprinklers in ceilings which have positive pressure in the space above. Model F1 FR Series Concealed Pendent sprinklers require a 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The Model W4 wrench is used to engage the sprinkler wrenching sur- faces and to install the sprinkler in the fitting. Remove the protective cap to install the sprinkler, then reinstall the protective cap until the cover plate is installed. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent dam- age to the sprinkler. Do not wrench any other part of the sprinkler/ cup assembly. Installation is completed by removing the protective cap from the sprinkler and pushing the cover plate onto the cup. Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning the cover plate in the counter clockwise direction. After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impediment to the space above. Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any concealed cover plate/ cup assembly other than the Reliable Model CCP with Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not spe- cifically listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. 2. Technical Data: Sensitivity: Quick -response Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional Maximum Working Pressure: 175 psi (12 bar) -100% Factory tested hydrostatically to 500 psi (34.5 bar) SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar) Design and Installation Information Model Nominal K-factor Nominal Orifice Diameter Deflector/ Orientation Nominal Sprinkler Height Installation Wrench SIN Listings and Approvals Approval Notes US Metric inches mm inches mm Pendent 2.25 57 W2 RA1411 cULus 2 F1 FR28 2.8 40 3/8 10 Recessed Pendent 2.25 57 W4 RA1411 cULus 2 Upright 2.25 57 W2 RA1421 cULus 1,2 F1 FR40 4.0 57 3/8 10 Pendent 2.25 57 W2 RA1418 VdS Recessed Pendent 2.25 57 W4 RA1418 VdS Pendent 2.25 57 W2 RA1413 cULus 2 F1 FR42 4.2 60 7/16 10 Recessed Pendent 2.25 57 W4 RA1413 cULus 2 Upright 2.25 57 W2 RA14231 cULus 1,2 F1 FR42LL 4.2 60 7/16 10 Pendent 2.25 57 W2 RA1410 cULus, ULH Recessed Pendent 2.25 57 W4 RA1410 cULus, ULH F1 FRXLH Pendent 2.25 57 W2 RA1413 cULus 2 Recessed Pendent 2.25 57 W4 RA1413 cULus 2 (F1 FR42 4.2 60 7/16 10 with Pintle) Upright 2.25 57 W2 RA1423 cULus 1,2 cULus, FM, Pendent 2.25 57 W2 RA1414 LPCB, VdS, EC, 1,2,3,4 WM cULus, FM, Recessed Pendent 2.25 57 W4 RA1414 LPCB, VdS, EC, 1,2,3,4 WM F1 FR56 5.6 80 1/2 15 Concealed Pendent 2.25 57 W4 RA1414 cULu� dS,EC, 5,6 cULus, FM, Upright 2.25 57 W2 RA1425 LPCB, VdS, EC, 1,2,3,4 WM "Conventional (Pendent or Upright)" 2.25 57 W2 RA1475 LPCB, VdS, EC, WM 4 Pendent 2.25 57 W2 RA1415 cULus, ULH 1 FlFR56LL 5.6 80 1/2 15 Recessed Pendent 2.25 57 W4 RA1415 cULus, ULH Concealed Pendent 2.25 57 W4 RA1415 cULus, ULH 6 Horizontal Sidewall 2.63 67 W2 RA1435 cULus, FM 1,2,3,7 F1 FR56 5.6 80 1/2 15 Recessed Horizontal Sidewall 2.63 67 W4 RA1435 cULus, FM 8 F1 FR56 5.6 80 1/2 15 Vertical Sidewall (Pen- dent or Upright) 2.25 57 W2 RA1485 cULus, FM, LPCB 1,2,3,9 (') cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating. (2) cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating. (3) Available with FM approved Polyester coating in black or white. (4) Available with LPCB and VdS approved Polyester coating. (5) VdS and EC approvals of the 171 FR56 Concealed Pendent sprinkler are for 155°F (68°C) temperature rated sprinklers only. VdS approved sprinklers must use Norbulb brand glass bulbs with the 1/2-inch (12.7mm) adjustment Model CCP cover plate only. (6) Model F1 FR56 Concealed Pendent and Model F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates, available as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment. (7) cULus Listing of the F1 FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. Minimum to maximum deflector to ceiling distance shall be 4 inches to 12 inches (102mm to 305mm). FM Approval of the F1 FR56 Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (1) cULus Listing and FM Approval of the F1 FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only. (1) The F1 FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. LPCB approval of the F1 FR56 Vertical Sidewall sprinkler is for installation in the Pendent position only. 3. Listed and Approved Temperature Ratings Model Deflector/ Orientation Ordinary Temp. Classification 100*F (38*C) Max. Ambient Temp. Intermediate Temp. Classification 150T (65*C) Max. Ambient Temp. High Temp. Classification 225T (107*C) Max. Ambient Temp. 135°F (57°C) Temp. atin 155°F (68°C) Temp. Rating 175°F (79°C) Temp. Rating 200°F (93°C) Temp. Rating 286°F (141*C) Temp. Rating Orange Bulb Red Bulb Yellow Bulb Green Bulb Blue Bulb Pendent cULus F1 FR28 Recessed Pendent cULus Upright cULus Pendent VdS F1 FR40 Recessed Pendent VdS Pendent cULus F1FR42 Recessed Pendent cULus Upright cULus Pendent cULus, ULH FlFR42LL Recessed Pendent cULus, ULH Pendent cULus F1FRXLH Recessed Pendent cULus Upright cULus Pendent cULus, FM, LPCB, VdS, EC, WM Recessed Pendent cULus, FM, LPCB, VdS, EC, WM F1FR56 Concealed Pendent" cULus, WM cULus,VMS,EC, cULus, WM Upright cULus, FM, LPCB, VdS, EC, WM "Conventional Pendent or Upright)" LPCB, VdS, EC, WM Pendent cULus, ULH FlFR56LL Recessed Pendent - cULus, ULH Concealed Pendent" cULus, ULH Horizontal Sidewall cULus, FM F1FR56 Recessed Horizontal Sidewall cULus, FM F1FR56 Vertical Sidewall (Pen- dent or Upright) cULus, FM, LPCB * Model F1 FR56 Concealed Pendent and F1 FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates. For Ordinary Temperature Classification sprinklers use a 1357 (57°C) temperature rated cover plate. For In- termediate Temperature Classification sprinklers use a 1650F (74°C) temperature rated cover plate. Recessed Escutcheon Data Listed and Approved Recessed Escutcheons Model F1 Model F2 Model FP Deflector/ Model Orientation (Fig.1 & 3) (Fig.1 & 3) (Fig. 2) SIN 3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-inch (12.7mm) adjustment adjustment adjustment F1FR28 Recessed Pendent cULus cULus cULus RA1411 F1FR40 Recessed Pendent VdS VdS VdS RA1418 F1FR42 Recessed Pendent cULus cULus cULus RA1413 FlFR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410 FlFR42XLH Recessed Pendent cULus cULus cULus RA1413 F1FR56 Recessed Pendent cULus, LPCB, VdS, cULus, FM, LPCB, cULus, VdS, EC, WM RA1414 EC, WM VdS, EC, WM FlFR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415 F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435 9 TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS -\ FJ ESCUTCHEONS�� 3/4'T 19mmJ ADJUSTMENT F2 ESCUTCHEON 1/2'T 12.7mm] ADJUSTMENT 2 114" HOLE DIA. ~- [57.2mm] -� 1 15116- DIA [49.2mm] I II II IE. L J� 2 27132' 01A. [72.2mm] 1" X 1/2" REDUCER FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON AT MAXIMUM RECESS = 1 '[25.4mm] AT MINIMUM RECESS = 3/8 [9.5mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 3/4'T l9mm] 7-7-77-7-71 I AT MINIMUM RECESS = 3/8'T9.5mmJ F1 ESCUTCHEON AT MAXIMUM RECESS = 7/8'T22.2mmJ [3.2mmJ AT MINIMUM RECESS = 1-5/8 [41.3mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-1/8'T28.6mm] AT MINIMUM RECESS = 1-5/8'T41.3mm] Fg.1 Model F1 FR56, F1 FR56LL, F1 FR42, F1 FR40, F1 FR42LL, F1 FRXLH & F1 FR28 Recessed Pendent sprinkler with Model F1 or F2 escutcheon I I 1 '" X 1/2" REDUCER 2 5/8" DIA. [66.7mm] HOLE IN CEILING 1 I 2 5/16"" DIA. [58.7mm] CUP L J CEILING FACE OF RTTING 0380 TO FACE OF CEILING DIMENSION _ _ AT MAXIMUM RECESS = 1-1/2 [38mm] AT MINIMUM RECESS = 1 [25.4mm] AT MAXIMUM RECESS = 9/16'[14.3mm] %2 "T 12.7mm] AT MINIMUM RECESS = 1 [25.4mm] ADJUSTMENT ME 3 114" DIA. [82.6mm] Fig. 2 Model F1 FR56, F1 FR56LL, F1 FR42, F1 FR40, F1 FR42LL, F1 FRXLH & F1 FR28 Recessed Pendent sprinkler with Model FP escutcheon 5. FACE OF FITTING TO FACE OF CEILING DIMENSION F1 ESCUTCHEON AT MAXIMUM RECESS = 1 '[25.4mm] AT MINIMUM RECESS = 3/8 [9.5mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 3/4'[19mm] AT MINIMUM RECESS = 3/8'[9.5mm] 2 1/4" HOLE DIA. [57.2mm] 1" X 1/2" REDUCER 1 1 1 1 15/16" DIA. [49.2mm] TURN COLLAR UNTIL TIGHT AGAINST SPRINKLER WRENCH BOSS. F 1/8.. [3.2mm] F1 ESCUTCHEON l M E — 1 3 8"349 AT MAX MU REC SS mmJ AT MINIMUM RECESS = 2-1/16 [[52.4mm] F2 ESCUTCHEON AT MAXIMUM RECESS = 1-5/8 [41.3mm] AT MINIMUM RECESS = 2-1/16'[52.4mm] 4'-12" [101.6mm-304.8mm] 2 27/32" DIA. CEILING TO J [72.2mm] DEFLECTOR 4 \V F1 ESCUTCHEON 3/4[19mm] ADJUSTMENT F2 ESCUTCHEON 1/2'[12.7mm] ADJUSTMENT ascvx RECESSED HSW W/F1 OR F2 ESCUTCHEON (1) FM APPROVED FOR 4" — 6" [101.6MM — 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY. Fig. 3 Model F1 FR56 Recessed Horizontal Sidewall sprinkler with Model F1 or F2 escutcheon 1 " x 112" REDUCING TEE OR ELBOW 2 5116 " DIA — CUP CEILING --' 112 " MAX. COVER ADJUSTMENT COVER PLATE — ASSEMBLY i SPRINKLER ------ +-------- ------ --2 518" DIA. HOLE IN CEILING L_ _J 05 d8 1 112 MAX. i FACE OF FITTING TO FACE OF CEILING " DIMENSION - - - 15116" I r 3 5116 " DIA. CONCEALED. 1 /2" ADJUSTMENT 017FG01A Fig. 4 Model F1 FR56/F1 FR56LL Concealed Pendent sprinklerwith standard depth 1/2-inch (12.7mm) adjustment- Model CCP cover plate 91 1 " x 112 " REDUCING TEE OR ELBOW — — —------+-------- — — — 2 5/8" DIA. 2 5/16 " DIA — i I -- 'i _ J L' . ifHOLE IN CEILING CUP CEILING J —� I ' - 5/16" MAX. COVER ADJUSTMENT 1� j COVER PLATE — ASSEMBLY 3 5/16" DIA. SPRINKLER 1 1/2" MAX. FACE OF FITTING TO FACE OF CEILING DIMENSION 3/4„ CONCEALED, 5/16" ADJUSTMENT 017FGOZA inch (8.Omm) adjustment - Model CCP cover plate Maintenance The Model F1FR Series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gen- tle vacuuming. Replace any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replace- ment of damaged or operated sprinklers. Finishes (1) Standard Finishes Sprinkler Escutcheon Cover late('r Bronze Brass Chrome Chrome Plated Chrome Plated I White Pol ester Coated OAR White Painted Special Application Finishes Sprinkler Escutcheon Cover plateM Electroless Nickel PTFEM Electroless Nickel PTFE Bright Brass Bright Brass(3) Bright Brass Black Plating Black Plated Black Plated Black Paint Black Paint12)161 Black Paint Off White Off White Off White t Satin Chrome Chrome Dull I Chrome Dull (1) Other finishes and colors are available on special order. Consult the fac- tory for details. Custom color painted sprinklers may not retain their UL Corrosion resistance listing. Coverplate custom paint is semi -gloss, unless specified otherwise. (2) cULus Listed only. (1) 200°F (93°C) maximum. (1) cULus listed "corrosion resistance" applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and RA1415 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request. (1) FM Approvals finish as "Polyester coated" applies to SIN Number RA1414, RA1435 and RA1425 in standard black or white. (1) LPCB and VdS Approved finish applies only to RA1425, RA1414, RA1418 (VdS) and RA1475. m cULus listed Corrosion Resistant Material Data Frame: DZR Brass, QM Brass, or Low Lead Brass Deflector: CDA Alloy 220, 260, or 510 Load ScrewlPintle: CDA Alloy 360 or 544 Cup: CDA Alloy 651 or 693 Washer: Nickel Alloy 440 or 360, coated with PTFE Adhesive Tape Bulb: Glass Ordering Information Specify: 1. Sprinkler Model: [F1 FR28][F1 FR40][F1 FR42] [F1 FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL] 2. Sprinkler Deflector/Orientation: [Pendent][Recessed Pendent][Upright][Conventional][Horizontal Sidewall] [Recessed Horizontal Sidewall][Vertical Sidewall] 3. Sprinkler threads: [1/2-inch NPT][ISO7-R1/2] 4. Sprinkler Temperature Rating: [135°F (570C)][155°F (68°C)][175°F (79°C)][200°F (93°C)][286°F (141 °C)] 5. Sprinkler Finish 6. Escutcheon Model: [F1][F2][FP] 7. Escutcheon Finish (where applicable) 8. Cover plate Model: [standard profile CCP 1/2-inch (12.7mm) adjustment][low profile CCP 5/16-inch (8.Omm) adjustment] 9. Cover plate Temperature Rating: [135'F (57'C) for use with Ordinary Temperature sprinklers][165'F (74'C) for use with Intermediate Temperature sprinklers] 10. Cover plate Finish Note: When Model F1 FIR Series Recessed sprinklers are ordered, the sprin- klers and escutcheons are packaged separately. 7. Reliable ... For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many pre- cision -made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles • Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water flow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals • Air maintenance devices • Air compressors • Pressure gauges • Identification signs • Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled (800) 431-1588 Sales Offices Paper Reliabld (800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 08/21 PM 9999970300 Bulletin 135 April 2021 Reliable Features • cULus Listed Residential Sprinklers • Available in pendent and horizontal sidewall orientations • Decorative finishes available, including recessed escutcheons and conical concealed cover plates Product Description Model F1 Res Series sprinklers are residential sprinklers with a 3 mm glass bulb operating element. A variety of K-Factors as well as recessed and conical concealed options are available as detailed in this Bulletin. The F1 Res Series sprinklers are specially engineered for fast thermal response to meet the requirements of UL 1626. They are intended for installation in accordance with NFPA 13, 13R, and 13D. Application The Model F1 Res Series sprinklers cULus Listed Residential sprinklers are intended for use in accordance with NFPA 13, NFPA 13R, or NFPA 13D. The Model F1 Res residential sprinklers are cULus Listed for use in residential occupancies and residential portions of any occupancy, where permitted by NFPA 13, NFPA 13R, or NFPA 13D. For NFPA 13R and NFPA 13D applications, the design flow and pressure shall not be less than the minimum flow and pressure specified in the Listed Design Criteria tables in this Bulletin. For NFPA 13 applications, Residential Sprinkler Summary Model F1 Res Series Glass Bulb Residential Sprinklers cULus Listed Important Note: Model D wrench and Model GFR2 wrench are no longer compatible with this product. Model W2 (non - recessed) and Model W4 (recessed, concealed) are required. J the design density shall be a minimum of 0.1 gpm/sf (4.1 mm/ min), but in no case shall the flow and pressure be less than the minimum flow and pressure specified in the Listed Design Criteria tables in this bulletin. Model F1 Res Series sprinklers are listed for use in wet systems only. Table A Sprinkler Model Sprinkler Identification Number (SIN) Orientation K-Factor gpm/psi11' (Ipm/bar"s) Thread Size NPT or ISO7-1 Installation Options Max. Coverage Area ft x ft (m x m) F1 Res30 R3511 Pendent 3.0(43) 1/2 Pendent or Recessed 16 x16 (4.9 x 4.9) F1 Res49 R3516 Pendent 4.9(71) 1/2 Pendent or Recessed 20 x 20 (6.1 x 6.1) F1 Res58 R3513 Pendent 5.8(84) 1/2 Pendent or Recessed 20 x 20 (6.1 x 6.1) F1 Res76 R7618 Pendent 7.6(109) 3/4 Pendent or Recessed 20 x 20 (6.1 x 6.1) F1 Res30 CCP R3511 Pendent 3.0(43) 1/2 Conical Concealed 14 x 14 (4.3 x 4.3) F1 Res49 CCP R3516 Pendent 4.9(71) 1/2 Conical Concealed 20 x 20 (6.1 x 6.1) F1 Res58 CCP R3513 Pendent 6.8(84) 1/2 Conical Concealed 20 x 20 (6.1 x 6.1) F1 Res76 CCP R7618 Pendent 7.6(109) 3/4 Conical Concealed 20 x 20 (6.1 x 6.1) F1 Res44 NSW) R3531 Horizontal Sidewall 4.4 (63) 1 /2 'Recessed 1 Ei x 20 (4.9 x 6.1) F1 Res44 SWC R3531 Horizontal Sidewall 4.4(63) 1/2 Conical Concealed 16 x 20 (4.9 x 6.1) F1 Res58 HSW R3533 Horizontal Sidewall 5.8(84) 1/2 Recessed 16 x 20 (4.9 x 6.1) F1 Res 58 HSWX RA3533 Horizontal Sidewall 5.8(84) 1/2 Recessed 14 x 26 (4.3 x 7.9) Note: Please note SIN difference between F1 Res58 HSW (R3533) and F1 Res58 HSWX (RA3533). www.reliablesprinkler.com Technical Specifications Finishes Style: Pendent and Recessed Pendent (See Table N) Threads: 1/2" NPT or IS07-1R1/2 Sensitivity -a Nominal K-Factor: 3.0 (43 metric) Fast -response // 'N Max. Working Pressure: 175 psi (12 bar) Temperature Ratings Material Specifications 155°F (68°C) 175-F (79°C) Thermal Sensor: 3 mm glass bulb Recessed Escutcheons Sprinkler Frame: Brass Alloy F2 Recessed Button: Copper Alloy FV Recessed' Sealing Assembly: Nickel Alloy with PTFE Sprinkler Wrenches :u.vrf r -- � •.� �-: "+; Load Screw: Bronze Alloy Model W2 ,, v Deflector: Bronze Alloy Model W4 (Recessed) *Note: Model FV escutcheons are not for use in positively pressurized ceiling plenums. Model F1 Res30 Residential Pendent Sprinkler Components and Installation Dimensions 2-1/4" (57mm *(49D"IA,' of fitting nished eiling (13mm) Threads 4"(6mm) Wrench Flat 0'VH Sealing Assembly2 1/4"03StlfiGlass Bulb(57mm)44mm)Load Screw (6mm) Deflector 1-1/4" (32mm) 2-7/8" (72mm) DIA. Components Dimensions F2 & FV Recessed Escutcheon Installation Model F1 Res30 Residential Pendent Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe Systems') Maximum CoverageArea(') ft. x ft.(m x m) Flow gpm (1/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7) 8 (30) 7.0 (0.48) 1 to 4 inches (25 to 100 mm) 14 x 14 (4.3 x 4.3) 10 (38) 11.0 (0.76) 15 x 15 (4.6 x 4.6) 12 (45) 16.0 (1.1) 16 x 16 (4.9 x 4.9) 13 (49) 18.8 (1.3) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 135 e1 b Page 2 of 15 April 2021 www.reliablesprinkler.com Technical Specifications Finishes Style: Pendent and Recessed Pendent (See Table N) Threads: 1/2" NPT or IS07-1R1/2 Sensitivity Nominal K-Factor: 4.9 (71 metric) Fast -response ^- - - Max. Working Pressure: 175 psi (12 bar) Temperature Ratings M Material Specifications 155°F (68°C) 1750 F (79-C) C) Thermal Sensor: 3 mm glass -bulb Recessed Escutcheons Sprinkler Frame: Brass Alloy Button: Copper Alloy F1 Recessed F2 Recessed Sealing Assembly: Nickel Alloy with PTFE FV Recessed*_;.` Load Screw: Bronze Alloy Sprinkler Wrenches Deflector: Bronze Alloy Model W2 Model W4 (Recessed) *Note: Model FV escutcheons are not for use in positively pressurized ceiling plenums. Model F1 Res49 Residential Pendent Sprinkler Components and Installation Dimensions 2-1/4" (57mm) ace of Ftoceilingfinishedg 2-1/4" (57mm) of F1-156" T(49mrD)DIA. T(49mm)/1 Ttcceilingdg ishe DIA. (16mm) +/- 3/8" (9mm) 0IMI 2-1/4" (57) 1-5/8" (41mm) +/- 3/8" (9mm) 1-1/4" (32mm) 2-7/8" (72mm) DIA. Dimensions F1 Recessed Escutcheon Installation 1/2" (13mm) +/- 1/4"(6mm) 1-3/4'(, 1/4" 2-7/8" (72mm) DIA. F2 & FV Recessed Escutcheon Installation Model F1 Res49 Residential Pendent Sprinkler Hydraulic Design Criteria Mel - Minimum Flow and Residual Pressure in Wet Pipe Systemst') Maximum Coverage Area (2) ft. x ft. (m x m) Flow gpm (I/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7) 13 (49) 7.0 (0.48) 1 to 4 inches (25 to 100 mm) 14 x 14 (4.3 x 4.3) 13 (49) 7.0 (0.48) 16 x 16 (4.9 x 4.9) 13 (49) 7.0 (0.48) 18 x 18 (5.5 x 5.5) 17 (64) 12.0 (0.83) 20 x 20 (6.1 x 6.1) 20 (76) 16.7 (1.15) 12 x 12 (3.7 x 3.7) 15 (57) 9.4 (0.65) 4 to 8 inches (100 to 200 mm) 14 x 14 (4.3 x 4.3) 16(61) 10.7(0.74) 16 x 16 (4.9 x 4.9) 17 (64) 12.0 (0.83) 18 x 18 (5.5 x 5.5) 19 (72) 15.0 (1.03) 20 x 20 (6.1 x 6.1) 22 (83) 20.2 (1.39) Notes: 1. For NFPA 13, installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 135 Rel b Page 3 of 15 April 2021 �v www.reliablesprinkler.com Technical Specifications Finishes Style: Pendent and Recessed Pendent (See Table N) Threads: 1/2" NPT or ISO7-1 R1/2 Sensitivity Nominal K-Factor: 5.8 (84 metric) Fast -response Max. Working Pressure: 175 psi (12 bar) Temperature Ratings 155°F (68°C) Material Specifications 175°F (79°C) Thermal Sensor: 3 mm glass bulb Recessed Escutcheons Sprinkler Frame: Brass Alloy F1 Recessed , Button: Copper Alloy F2 Recessed::.� Sealing Assembly: Nickel Alloy with PTFE FV Recessed*� Load Screw: Bronze Alloy Sprinkler Wrenches ` >- ,"�. '• Deflector: Bronze Alloy Model W2 Model W4 (Recessed) *Note: Model FV escutcheons are not for use in positively pressurized ceiling plenums. Model F1 Res58 Residential Pendent Sprinkler Components and Installation Dimensions 2-1/4" (57mm) 2-1/4" (57mm) 4(49mm) Face of fitting4e(49mm)DIA. Face of fitting to finished to finished ceiling ceiling 5/8" (16mm) 1/2" (13mm) 3/8" (9mm) +/- 1/4" (6mm) l]9- 2-1/4"(57) 1-3/4" (44mm) +/- 1-5/8" (41mm) +/- 1/4" (6mm) 3/8" (9mm) 1-1/4" (32mm) 2-7/8" (72mm) DIA. 2-7/8" (72mm) DIA. Dimensions F1 Recessed Escutcheon Installation F2 8" FV Recessed Escutcheon Installation Model F1 Res58 Residential Pendent Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe Systems(') Maximum Coverage Area" t ft. x ft. (m x m) Flow gpm (1/min) Pressure psi (bar) Deflector to Ceiling Distance 16 x 16 (4.9 x 4.9) 16 (61) 7.6 (0.52) 1 to 4 inches (25 to 100 mm) 18 x 18 (5.5 x 5.5) 19 (72) 10.8 (0.75) 20 x 20 (6.1 x 6.1) 22 (83) 14.4 (1.0) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 135 Re� b�e Page 4 of 15 April 2021 www.rellablesprinkler.com Finishes Technical Specifications (See Table N) Style: Pendent and Recessed Pendent Sensitivity Threads: 3/4" NPT or ISO7-1 R3/4 Nominal K-Factor: 7.6 (109 metric) Fast -response Temperature Ratings Max. Working Pressure: 175 psi (12 bar) 155°F (68°C) Material Specifications 175°F (79°C) i Thermal Sensor: 3 mm glass bulb Recessed Escutcheons Sprinkler Frame: Brass Alloy F1 Recessed F2 Recessed Button: Copper Alloy FV Recessed* Sealing Assembly: Nickel Alloy with PTFE Sprinkler Wrenches Load Screw: Bronze Alloy Model W2 Deflector: Bronze Alloy Model W4 (Recessed) *Note: Model FV escutcheons are not for use in positively pressurized ceiling plenums. Model F1 Res76 Residential Pendent Sprinkler Components and Installation Dimensions maim=t 2-1/4" (57mm) 2-1/4" (57mm) DIA.L of fitting DIA. Face of fitting 1-15/16"nished 1-15/16" to finished (49mm) DIA.eiling (49mm) DIA. ceiling (1 6mm) 1/2" (13mm) 8" (9mm) +/- 1J4" (6mm) O�SYH 2-1/4" (57) I 1-3/4' (44mm) +/- 1-5/ / (41 mm) +/- 1/4" (6mm) 3/8" (9mm) (44mm) 2-7/8" (72mm) DIA. 2-7/8" (72mm) DIA. Dimensions F1 Recessed Escutcheon Installation F2 & FV Recessed Escutcheon Installation Model F1 Res76 Residential Pendent Sprinkler Hydraulic Design Criteria Table Minimum Flow and Residual Pressure in Wet Pipe Systems') Maximum Coverage Area (2) Flow Pressure Deflector to ft. x ft. (m x m) gpm (Ilmin) psi (bar) Ceiling Distance 18 k 18 (5.5 x 5.5) 21 (80) 7.6 (0.52) 1 to 4 inches (25 to 100 mm) 20 x 20 (6.1 x 6.1) 23 (87) 9.2 (0.63) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than'those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 135 Re� e Page 5 of 15 b April 2021 Rem www.reliablesprinkler.com Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 1/2" NPT or IS07-1R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Sensitivity Fast -response Temperature Ratings 155°F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model W4 *Note: Model FP escutcheons and CCP cover plates are not listed for use in positively pressurized ceiling plenums. Model F1 Res30 CCP and FP Recessed Pendent Sprinkler Installation Dimensions 2-5/8" (67mm) 2 5/8" (67mm) DIA. DIA. CCP Recessed Escutcheon Installation 2-5/16" (59mm)DIA. ace of fitting to finished ceiling I i Face of fitting to finished ceiling -1/4" (32mm) 1-1/4" (32mm) I- 1/4" (6mm) �,-,+/- 1/4" (6mm) 15/16"4mm 1" /4" (6m (24mm) +/- 1/4" (6mm) L3-3/16" (78mm) DIA. FP Recessed Escutcheon Installation Model 171 Res30 CCP Pendent & FP Recessed Pendent Sprinkler Hydraulic Design Criteria - Minimum Flow and Residual Pressure In Wet Pipe Systems') Maximum Coverage Area(z) ft. x ft. (m x m) Flow gpm (1/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7) 8 (30) 7.0 (0.48) 1/2 to 1 inch (13 to 25 mm) 14 x 14 (4.3 x 4.3) 11 (38) 13.4 (0.92) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Bulletin 135 Page 6 of 15 April 2021 Reliable www.reliablesprinkler.com Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 1/2" NPT or ISO7-1 R1/2 Nominal K-Factor: 4.9 (71 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Sensitivity Fast -response Temperature Ratings 155-F (68-C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model W4 *Note: Model FP escutcheons and CCP cover plates are not for use in positively pressurized ceiling plenums. Model F1Res49 CCP & FP Recessed Pendent Sprinkler Installation Dimensions maim' CCP Recessed Escutcheon Installation 2-5/8" (67mm) DIA. 2-5/16" (59mm)DIA. ce of fitting o finished ceiling X' (32mm) 114" (6mm) 15l16° ?4mm) 3-3/16" (78mm) FP Recessed Escutcheon Installation Face of fitting to finished ceiling 1-1/4" (32mm) +/- 1/4" (6mm) 1" (25mm) +/- 1/4" (6mm) Model F1 Res49 CCP Pendent and FP Recessed Pendent Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe Systems') Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (1/min) Pressure psi (bar) Deflector to Ceiling Distance 14 x 14 (4.3 x 4.3) 13 (49) 7.0 (0.48) 1/2 to 1 inch (13 to 25 mm) 16 x 16 (4.9 x 4.9) 14 (53) 8.2 (0.57) 18 x 18 (5.5 x 5.5) 18 (68) 13.5 (0.93) 20 x 20 (6.1 x 6.1) 20 (76) 16.7 (1.15) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater, of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Bulletin 135 Re� b Page 7 of 15 April 2021 www.reliablespdnkler.com Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 1/2" NPT or ISO7-1 R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Sensitivity Fast -response Temperature Ratings 155-F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model W4 *Note: Model FP escutcheons and CCP cover plates are not for use in positively pressurized ceiling plenums. Model F1 Res58 CCP and FP Recessed Pendent Sprinkler Installation Dimensions 2-5/8" (67mm) 2-5/8" (67mm)►{ DIA. ��I � DIA. I I CCP Recessed Escutcheon Installation 2-5/16" (59mm)DIA. ce of fitting o finished ceiling I i Face of fitting to finished ceiling /4" (32mm) 1-1/4" (32mm) 1/4" (6mm) 1/4" (6mm) 1 1 25mm) 24mm) 15/16" +/- 1//4" (6mm) L3-3/16" (78mm) DIA. FP Recessed Escutcheon Installation Model F1Res58 CCP Pendent & FP Recessed Pendent Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe Systems0) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (1/min) Pressure psi (bar) Deflector to Ceiling Distance 16 x 16 (4.9 x 4.9) 16 (61) 7.6 (0.52) 1/2 to 1 inch (13 to 25 mm) 18 x 18 (5.5 x 5.5) 19 (72) 10.8 (0.75) 20 x 20 (6.1 x 6.1) 22 (83) 14.4 (1.0) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Bulletin 135 e — Page 8 of 15 April 2021 www.reliablesprinkler.com Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 3/4" NPT or ISO7-1 R3/4 Nominal K-Factor: 7.6 (109 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Sensitivity Fast -response Temperature Ratings 156-F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model W4 *Note: Model FP escutcheons and CCP cover plates are not for use in positively pressurized ceiling plenums. Model F1 Res76 CCP and FP Recessed Pendent Sprinkler Installation Dimensions �• �> 13 G/a,- Ir-7-1 CCP Recessed Escutcheon Installation -5/8" (67mm) DIA. 2-5/16" (59mm)DIA. ace of fitting to finished ceiling -1/4" (32mm) 1- 1/4" (6mm) 15/16" (24mm) L3-3/18" (78mm) DIA. FP Recessed Escutcheon Installation Face of fitting to finished ceiling 1-1/4" (32mm) +/- 1/4" (6mm) 1" (25mm) +/-1/4" (6mm) Model F1 Res76 CCP Pendent & FP Recessed Pendent Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe SystemsM Maximum Coverage Area(2) Flow Pressure Deflector to Ceiling Distance ft. x ft. (m x m) gpm (1/min) psi (bar) 16 x 16 (4.9 x 4.9) 21 (80) 7.6 (0.52) 1/2 o 1 inch (13 to 25 mm) 18 x 18 (5.5 x 5.5) 22 (83) 8.4 (0.58) 20 x 20 (6.1 x 6.1) 25 (95) 10.8 (0.75) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Bulletin 135 a iab Page 9 of 15 April 2021 www.reliablespdnkler.com Technical Specifications Style: Sidewall and Recessed Sidewall Threads: 1/2" NPT or ISO7-1 R1/2 Nominal K-Factor: 4.4 (63 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Sensitivity Fast -response Temperature Ratings 155-F (68°C) 175°F (79°C) Recessed Escutcheons F2 Recessed FV Recessed Sprinkler Wrenches Model W2 Model W4 (Recessed) Model F1Res44 Horizontal Sidewall Sprinkler Installation Dimensions NUOM Face of fitting to finished wall 1-5/8" (41 mm) 3/8" (10mm) +1- 1/4" (6mm) +/- 1/4" (6mm) 2-7/16" (62mm) 5/16" (8mm) Dimensions 2-1/4" 1-15/16" (57mm) (49mm) -- - DIA. DIA. Top of Deflector Down from _ Ceiling to be Either 4" to 6" (100 to 150 mm) or 6" to 12" (150 to 300 mm) Based on Hydraulic Calculations F2 F" FV Recessed Escutcheon Installation Model._F1Res44. Horizontal Sidewall'Sprinkler Hydraulic Design Criteria Table Minimum Flow and Residual Pressure In Wet Pipe SystemsM Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (I/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7) 12 (45) Iv7.5(0.52) 4 to 6 inches (100 to 150 mm) 14 x 14 (4.3 x 4.3) 14-(53) 10:2 (0.70) 15 x 15 (4.6 x 4.6) 15 (57) 11.6 (0.80) Cl:6 x 16(4.9 x 4.9) (16-61)3.3 (0.92) 16 x 1$}(4.9 x 5.5) ljj8 (68) ffl 8(1.16) 16 x 20 (4.9 x 6.1) 23 (87) 27.4 (1.89) 18 x 18 (5.5 x 5.5) 19 (72) 18.7 (1.29) 12 x 12 (3.7 x 3.7) 14 (53) 10.2 (0.7) 6 to 12 inches (150 to 300 mm) 14 x 14 (4.3 x 4.3) 16(61) 13.2(0.91) 15 x 15 (4.6 x 4.6) 16 (61) 13.2 (0.91) 16 x 16 (4.9 x 4.9) 17 (64) 15.0 (1.03) 16 x 18 (4.9 x 5.5) 20 (76) 20.7 (1.43) 16 x 20 (4.9 x 6.1) 23 (87) 27.4 (1.89) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 135 Page 10 of 15 April 2021 Reliable' www.reliablespdnkler.com Technical Specifications Finishes Style: Conical Concealed Sidewall (See Table N) Threads: 1/2" NPT or ISO 7-1 111/2 Sensitivity Nominal K-Factor: 4.4 (63 metric) Fast -response Max. Working Pressure: 175 psi (12 bar) Temperature Ratings _. 155°F (68°C) Material Specifications 175°F (79°C) (1) SWC Thermal Sensor: 3 mm glass -bulb Cover Plates Sprinkler Frame: Brass Alloy SWC Conical Concealed Plate(2) Button: Copper Alloy SWC-2 (Slotted) Conical Concealed Plate (3) Sealing Assembly: Nickel Alloy with PTFE Sprinkler Wrenches _ Load Screw: Bronze Alloy Model W4 Deflector: Bronze Alloy SWC-2 ,t Note: (') Not for installation where the maximum ceiling temperature exceeds 100°F due to cover plate temperature rating. (2) 135°F SWC Conical Concealed Plate for 155°F (68°C) sprinklers (3)135°F SWC-2 (Slotted) Conical Concealed Plate for 175°F (79°C) sprinklers Model F1Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler and Installation Dimensions�i �2-7116° (62mm)� ff" 71/16' (8mm) Dimensions 11 (25mm) 11 (25mm) +/-1/4° (6mm) +/-1/4° (6mm) Face of fitting to finished wall (67mm) (58mm) -- 1 -K - DIA. DIA.) SWC & SWC-2 Concealed Cover Plate Installation Top of Deflector Down 3 5116° from Ceiling to be Either (84mm) 4" to 6° (100mm to 150mm) or 6° to 12° DIA. (150mm to 300mm) Based on Hydraulic Calculations Model F1 Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe SystemsM Maximum Coverage Area (2) ft. x ft. (m x m) Ordinary Temperature Rating 155°F (68°C) Intermediate Temperature Rating 175°F (79°C) Deflector to Ceiling Distance Flow gpm (1/min) Pressure psi (bar) Flow gpm (Urnin) Pressure psi (bar) 12 x 12 (3.7 x 3.7) 13 (49) 8.7 (0.60) 14 (53) 10.2 (0.7) 14 x 14 (4.3 x 4.3) 14 (53) 10.2 (0.7) 14 (53) 10.2 (0.7) 4 to 6 inches (100 to 150 mm) 15 x 15 (4.6 x 4.6) 16 (61) 13.2 (0.91) -- -- 16 x 16 (4.9 x 4.9) 17 (64) 15.0 (1.03) -- _ _ 16 x 18 (5.5 x 5.5) 19(72) 18.7(1.31) -- -- 16 x 20 (4.9 x 6.1) 23 (87) 27.4 (1.89) -- -- 12 x 12 (3.7 x 3.7) 14 (53) 10.2 (0.7) -- -- 6 to 12 inches (150 to 300 mm) 14x14(4.3x4.3) 15(57) 11.7(0.81) -- -- 15 x 15 (4.6 x 4.6) 17 (64) 15.0 (1.03) _ _ _ _ 16 x 16 (4.9 x 4.9) 18 (68) 16.8 (1.16) -- -- 16 x 18 (4.9 x 5.5) 20 (76) 20.7 (1.43) -- -- Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 135 .e1� Page 11 of 15 April2021 �R®aa�b�l�e www.reliablesprinkler.com Technical Specifications Style: Sidewall and Recessed Sidewall Threads: 1 /2" NPT or ISO7-1 R1 /2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Sensitivity Fast -response Temperature Ratings 155"F (68-C) 175°F (79°C) Recessed Escutcheons F2 Recessed FV Recessed Sprinkler Wrenches Model W2 Model W4 (Recessed) Model F1 Res58 Residential Horizontal Sidewall Sprinkler Installation Dimensions 2-7/16" (62mm) Dimensions Face of fitting to finished wall 3/8" (10mm) +/- 1/4" (6mm) ' 2-1/4" 1-15/16" (57mm) DIA. 5/16" (8mm) (49mm) DI -- - A. 1-5/8" (41mm) +/- 1/4" (6mm) Top of Deflector Down from _ Ceiling to be Either 4" to 6" (100 to 150 mm) or 6" to 12" (150 to 300 mm) Based on Hydraulic Calculations F2 & FV Recessed Escutcheon Installation Model F1Res58 Horizontal Sidewall Sprinkler Hydraulic Design Criteria Table Minimum Flow and Residual Pressure in Wet Pipe Systems') Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (1/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7) 16(61) 7.6(0.52) 4 to 6 inches (100 to 150 mm) 14 x 14 (4.3 x 4.3) 18 (68) 9.7 (0.66) 15 x 15 (4.6 x 4.6) 19 (72) 10.7 (0.74) 16 x 16 (4.9 x 4.9) 21 (80) 13.2 (0.91) 16 x 18 (5.5 x 5.5) 25 (95) 18.6 (1.28) 16 x 20 (4.9 x 6.1) 29 (110) 25.0 (1.72) 12 x 12 (3.7 x 3.7) 22 (83) 14.4 (1.0) 6 to 12 inches (150 to 300 mm) 14 x 14 (4.3 x 4.3) 22 (83) 14.4 (1.0) 15 x 15 (4.6 x 4.6) 24 (91) 17.1 (1.18) 16 x 16 (4.9 x 4.9) 26 (98) 20.1 (1.39) 16 x 18 (4.9 x 5.5) 31 (117) 28.6 (1.97) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. Please note SIN difference between F1 Res58 HSW (R3533) and F1 Res58 HSWX (RA3533). Bulletin 135 Page 12 of 15 April 2021 Re_ www.rellablespdnkler.com Finishes Technical Specifications (See Table N) Style: Sidewall and Recessed Sidewall Sensitivity Threads: 1/2" NPT or ISO7-1 R1/2 Fast -response Nominal K-Factor: 5.8 (84 metric) Temperature Ratings Max. Working Pressure: 175 psi (12 bar) 155"F (68°C) 175"F (79°C) Material Specifications Recessed Escutcheon i Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy F2 Recessed FV Recessed R�r ( w ` '� Sprinkler Wrenches Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Model W2 t Load Screw: Bronze Alloy Model W4 (Recessed) Deflector: Bronze Alloy Model F1Res58 HSWX Residential Horizontal Sidewall Sprinkler Installation Dimensions' 2-7/8" (73mm) Dimensions Face of fitting to finished wall 3/8" (10mm) +/-1/4" (6mm) 2-1/4" 1-15/16" (57mm) (49mm) -- - DI A. DIA. 1-7/8" (48mm) +/-1/4" (6mm) F2 & FV Recessed Escutcheon Installation - Top of Deflector Down From Ceiling to be Either 4" to 6" (100 to 150 mm) or 6" to 12" (150 to 300 mm) Based on Hydraulic Calculations Model F1 Res58 HSWX Horizontal Sidewall Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure in Wet Pipe Systems(') Maximum Coverage Area(') ft. x ft. (m x m) Flow gpm (I/min) Pressure psi (bar) Deflector to Ceiling Distance 18 x 20 (5.5 x 6.1) 30 (114) 26.8 (1.85) 4 to 6 inches (100 to 150 mm) 20 x 20 (6.1 x 6.1) 30 (114) 26.8 (1.85) 16 x 22 (4.9 x 6.7) 33 (125) 32.4 (2.23) 16 x 24 (4.9 x 7.3) 38 (144) 42.9 (2.96) 14 x 26 (4.3 x 7.9) 42 (160) 52.4 (3.63) 18 x 20 (5.5 x 6.1) 35 (133) 36.4 (2.51) 6 to 12 inches (150 to 300 mm) 16 x 22 (4.9 x 6.7) 38 (144) 42.9 (2.96) 16 x 24 (4.9 x 7.3) 42 (160) 52.4 (3.61) 14 x 26 (4.3 x 7.9) 46 (174) 62.9 (4.34) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. Please note SIN difference between F1 Res58 HSW (R3533) and F1 Res58 HSWX (RA3533). Bulletin 135 Page 13 of 15 April 2021 eliablc www.reliablespdnkler.com Finishes 15.1411 r"a Standard Finishes Special Application Finishes Sprinkler+' F1, F2. FV, FPM, CCP, SWC (Conical) Sprinkler �'� F1, F2. FV, FP('), CCP, SWC Conical Escutcheons Cover Plates (1) Escutcheons Cover Plates (') Bronze Brass — Bright Brass Bright Brass Bright Brass Chrome Plated Chrome Plated Chrome Plated Satin Chrome Satin Chrome Satin Chrome White White White Paint Black Black Black Paint Polyester(2) Polyester Polyester (2) Polyester — — — Custom Color Custom Color Custom Color Paint Polyester Polyester Electroless Nickel PTFE (2) Notes: (1) Paint or any other coating applied over the factory finish will void all approvals and warranties. (2) cULus Listed Corrosion Resistant. (3) The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring. Installation Models F1 Res sprinklers are to be installed as shown in this bulletin. Model F1, F2, FV, and FP recessed escutcheons are the only recessed escutcheons to be used with Model F1 Res sprinklers. Not all F1 Res sprinklers may be used with all recessed escutcheons offered. Confirm listing of escutcheon type for use with individual sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1 Res sprinklers, use only the Model W2 sprinkler Wrench; for installing Models F1 Res Recessed Pendent, Sidewall, Conical Concealed Pendent (CCP), and Sidewall Concealed (SWC and SWC-2) sprinklers use only the Model W4 sprinkler wrench. Use of wrenches other than those specified may damage these sprinklers. Installation of F1 Res sprinklers in a wall or ceiling will require a hole diameter of 2-1/4" (57 mm) for F1 or F2 recessed escutcheons; or 2-5/8" (67 mm) for FP recessed escutcheons, CCP, SWC, and SWC-2 cover plates. Install F1 Res HSW sprinklers with a ceiling to deflector distance that complies with the hydraulic design criteria tables in this bulletin. The flow arrow on deflector must point away from near wall and "Top" marking must face the ceiling. A 'leak tight" sprinkler joint can be obtained with the following torque: • 1/2" NPT and ISO7-1 R1/2: 8-18 ft-lbs (11 — 24 N-m) • 3/4" NPT and ISO7-1 R3/4: 14-20 ft-lbs (19 — 27 N-m). Do not tighten sprinklers over maximum recommended torque. This may cause leakage or impairment of the sprinklers. Do not install any glass bulb sprinklers where the bulb is cracked or there is a loss of liquid from the bulb. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. Remove this protection at the time the sprinkler system is placed in service. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when protectors are in place. Remove protectors by undoing the clasp by hand. Do not use tools to remove the protectors. Bulletin 135 April 2021 Model W4 Model W4 Wrench Installation The Model W4 wrench includes two sets of jaws. One set of jaws is equivalent to a Model GFR2 wrench and the other set of jaws is equivalent to a Model W1 wrench. Use the smallest of the two sets of jaws that will fit on the sprinkler's wrench flats. The Model W4 wrench is used in conjunction with the installer's nominal 1/2" square drive ratchet and nominal 5" (125mm) long extension (not provided) as shown in Figure 13. Page 14 of 15 www.reliablespdnkler.com Maintenance Reliable Model F1 Res Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25, 13, 13D, and 13R, as well as the requirements of any Authorities Having Jurisdiction. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause improper operation or non -operation. Do not clean sprinklers with soap and water, ammonia liquid or any other cleaning fluids. Remove dust by gentle vacuuming without touching the sprinkler. Replace any sprinkler which has been painted (other than factory applied). Properly installed CCP, SWC, and SWC-2 cover plates will have an air gap that is required for proper operation, do not seal the gap or paint the cover plates. Replace any sprinkler which has been damaged, where cracks are observed in the glass bulb, or when liquid'has been lost from the glass bulb. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Failure to properly maintain sprinklers may result in inadvertent operation or non -operation during a fire event. Listings & Approvals Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) Guarantee For Reliable Automatic Sprinkler Company guarantee, terms, and conditions, visit www.reliablesprinkler.com. Patents For patents applicable to products contained in this technical bulletin, please visit www.r-s.co Ordering Information Specify the following when ordering: Sprinkler • Model (See Table A) • Temperature Rating • Threads (NPT or IS07-1) • Finish (See Table N) Escutcheon or Cover Plate • Model • Finish (See Table N) Sprinkler Wrench • Model W2 (Pendent and HSW) • W4 (Recessed and Concealed) Note: Please note SIN difference between F1 Res58 HSW (R3533) and F1 Res58 HSWX (RA3533). Z a Bulletin 135 Reliable! Page 15 of 15 April 2021 www.reliablespdnk(ercom ADT Commercial 3150 SW 42nd Ave Palm City, FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial Pipe FlameGuard CPVC FIRE SPRINKLER PRODUCTS FG-2-0521 Complete System of Pipe, Fittings & Solvent Cement Corrosion Resistant • Superior Flow • Ease of Installation q Spears® FlameGuard® CPVC Fire Sprinkler Products provide $p{fir .14v" ''r;'� , (V:�. �,,. a cost effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of CPVC FIRE d installation and quick assembly with common tools. CPVC Fire Sprinkler Systems are based on proven products that have been in continuous service for over 40 years.' Spears® FlameGuard® products are approved by UL11, FM® Global, LPCB and Certified by NSF International for potable water use. Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not Sustain Biological Growth Unlike metal systems, FlameGuard® CPVC products never rust, scale or pit and do not sustain biological growth - a cause of Microbiologically Influenced Corrosion (MIC) which can destroy metal fire sprinkler systems from the inside out. Superior Flow Characteristics for Lower Friction Losses The smooth -wall interior surfaces of FlameGuard® CPVC systems result in reduced friction loss over metal systems. The design flow characteristics remain constant throughout the life of the product because there is no interior corrosion in the system due to microbiological activity. Pressure Rated to 175 psi (1.21 Mpa) (1200kpa) a� 150°F (66°C) FlameGuard CPVC Products are produced in combinations of Schedule 40 and Schedule 80 Fitting configurations con -forming toASTM F 438 or F 439 standards and FlameGuard® SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F 442 standards. UL® and FM® Rated working pressure is 175 psi (1.21 Mpa) (1200kpa) @ 150OF (66°C) (LPCB rated to 120°F) (490C). Easy Installation for Lower Costs FlameGuard® CPVC system installations significantly reduce costs over conventional metal piping by virtually eliminating prefabrication. Systems can be fully installed on site using solvent cement joining methods. UL® Listed for U.S. and Canada in NFPA 13, 13R & 13D Systems FlameGuard® CPVC Fire Sprinkler Products are UL® listed for U.S. and Canada applications for Light Hazard occupancies as defined in NFPA 13, Residential occupancies up to and including 4-stories as defined in NFPA 13R, and Residential occupancies for one and two family dwellings and manufactured homes as defined in NFPA 13D. Consult Spears® FlameGuard® CPVC Fire Sprinkler Products Installation Instructions and NFPA Standards for additional applications including air plenum, system risers, concealed, exposed, underground, combustable attic, garage, basement and low pressure dry piping installations. Full Limited Lifetime Warranty FlameGuard® CPVC Fire Sprinkler Products carry a limited lifetime warranty against defects in material or workmanship. Consult Spears® warranty for additional details. ,GHQ N PROGRESSIVEPRODUCTSFROMSPEARS® OLPCB aINNOVATION&TECHNOLOGY k�r oocr Visit our website at www.spearsmfg.com LPS1260 CertlLBCB ref. 293b Spears® FlameGuard® The Leader in Innovative CPVC Fire Sprinkler System Products Pioneer in Molded -in Metal Insert Head Adapters Patent No. 5,437,481 Spears® pioneered the development of the FlameGuard® molded- . in -place metal thread insert for connection of sprinkler heads to CPVC fire sprinkler systems, plus Metal FIPT threaded female adapters for metal -to -plastic transitions. Developed the Special Reinforced (SR) Head Adapters Patent No. 5,582,439 Spears® FlameGuard® continuous improvement program developed the technology to produce a superior patented plastic threaded fitting - the Special Reinforced (SR) Design. This unique design incorporates a patented thermoplastic compression process that equalizes stresses generated by tapered thread joint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Revolutionary Gasket Sealed Head Adapter Choices Patent No. 8,474,472 - 8,297,663 - 7,458,613 a 1 Lead Free • Requires NO Thread Sealants • Eliminates Stress • Prevents Over Tightening • Provides Easy Frame Alignment -> Spears® revolutionary Gasket Sealed Head Adapters feature an elastomer gasket seal at the base of the threads. The gasket Q� seal allows a modified thread design that eliminates radial stress and associated problems typical with tapered thread joint make up. Choose from TorqueSafeTm design with rotating brass thread insert, SofTorqueTm design with Special Reinforced (SR) plastic threads and compressible gasket or QuickTorqueTm with similar features plus brass threads. Full Assortment of Specialty Products & Fitting Configurations Spears® FlameGuard® products provide the specialty fittings needed in today's fire sprinkler systems. The GripLocTm Elbow, Tee, Cap and Coupling and GripLocTm Repair Coupling for quick no -cement repairs; the Adjustable Drop Nipple for fine-tuning to finished ceiling height; and Ringed Head Adapter for ease of locating during installation. Plus a full assortment of fittings including Grooved Coupling Adapters Unions and Flanges sizes 3/4" through 3" TorqueSafe TM, SofTorqueTm & QuickTorqueTm Fittings Lead Free GripLocTm Elbow, Tee, Cap, Coupling & Repair Couplings Lead Free Complete Size Range of CPVC Pipe �`�� "FfamGuarcl° Spears®FlameGuard® CPVC Fire Sprinkler Pipe is available in in sizes 3/4 to 3 ; and conforms to ASTM F 442 standard r: s. .. for SDR 13.5 CPVC pipe.-t�m��uard.us�� . Spears® Solvent Cements & Thread Sealant FlameGuard® products should be installed using Spears® FS-5 One -Step Solvent Cement. For threaded joints, use Spears® BLUE 75— Thread Sealant that has been tested for compatibility with FlameGuard® CPVC Fire Sprinkler Products. Spears® TorqueSafeTM, SofTorque'rm and QuickTorqueTm Gasket Sealed Adapter requires no sealant. Consult sprinkler head manufacturer prior to use. © Copyright 2021 Spears® Manufacturing Company. All Rights Reserved. Printed In the United States ofAmerica 09/18. FG-2-0521 FM Approved and Fully Listed Sprinkler Pipe Wheatland Tube's Schedule 10 and Schedule 40 steel fire sprinkler pipe is FM Approved and UL® and C-UL Listed. Approvals and Specifications Schedule 10 and Schedule 40 meet or exceed the following standards: • ASTM A135, Type E, Grade A (Schedule 10, 1-8 NPS) • ASTM A795, Type E, Grade A (Schedule 40, 1-2 NPS) • ASTM A53, Type E, Grade B (Schedule 40, 2-8 NPS) • ASTM A53, Type F, Grade A (Schedule 40, 1-4 NPS) • NFPA° 13 and NFPA 14 Manufacturing Protocols Schedule 10 and Schedule 40 are subjected to the toughest possible testing protocols to ensure the highest quality and long-lasting performance. PROJECT: CONTRACTOR: Finishes and Coatings All Wheatland black steel fire sprinkler pipe receives a proprietary mill coating to ensure a clean, corrosion -resistant surface that outperforms and outlasts standard lacquer coatings. This coating allows the pipe to be easily painted, without special preparation. Schedule 10 and Schedule 40 can be ordered in black or hot -dip galvanized, to meet FM/UL requirements for dry systems that meet the zinc coating specifications of ASTM A795 or A53. Product Marking Each length of Wheatland fire sprinkler pipe is continuously stenciled to show the manufacturer, type of pipe, grade, size and length. Bar coding is acceptable as a supplementary identification method. DATE: ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE: LOCATIONS: COMMENTS: ❑ BLACK ❑ HOT -DIP GALVANIZED 700`South Dock Street .. e Sharon, PA 16146 1 °'info�wheatland corn wheatland.com V Nheatland T: P 800.257.8182 �a Follow us on'Twitter } ube Fi ADIVISION 'Of F 724,346.7260 f C6)WheatlandTube ZEKELMAN,lNBUSTRIES .. p ; C.5:C�4900 ��-tjb�WEIGHTS AND DIMENSIONS WT./FT. WT./LIFT WT./LIFT WT./LIFT NPS NOMINAL OD NOMINAL ID NOMINAL WALL WT./FT. H2O FILLED PCS./LIFT 21' 24' 25' UL [777-1In r- In -7-1 Wmm I` jbs. 1 1.315 33.4 1.097 27.9 0.109 2.77 1.405 1.814 70 2065 2360 2459 11.4 1,660 42.2 1 442 J: 36.�6 6.109 2.77 1.807 2.514 31 61 2315 2645 2756 7.3 CM) 1.900 48.3 1.682 42.7 0.109 2.77 2.087 3.049 61 2673 3055 3183 5.8 2;375 60.3 2.157 54.8 6.109 2.77� 2.640" 1, 4M2 37 2051 2344 2442 4.7 2% 2.875 73.0 2.635 66.9 0.120 3.05 3.354 5.895 30 2226 2544 2651 3.5 '3 3.50088.9 3.260 82.8 0.120, 3.05 4.336 7.949, 19 1730 P 1977 2060 2.6 C41, 4.500 114.3 4.260 108.2 0.120 3.05 5.619 11.789 19 2242 2562 2669 1.6 5 - 5.563 141.3 ,5.295 - _­ 1-­­ i­­ __ 134,5 _0034 3.40 �� 7�0 17.309 11 13 2124 _ 2427 2529 -­__­,- 1.5 6 6.625 168.3 6.357 161.5 0.134 3.40 9.298 23.038 10 1953 2232 2325 1.0 8 8.625� 219.1 8.249 206.5 0.188 4_ivy.7 16.960' 1i 40.086 7 1� 2493 2849 2968 2.1 . SCHEDULE 40 WEIGHTS AND DIMENSIONS WT./FT. WT./LIFT WT./LIFT WT./LIFT NPS NOMINAL OD NOMINAL ID NOMINAL WALL WT./FT. H2O FILLED PCS./LIFT 21' 24' 25' UL 71 =E'In =7m Cl�) 1.315 33.4 1.049 26.6 0.133 3.38 1.68 2.055 70 2470 2822 2940 1.000 11/4 1.660 42.2 11 1.380 35.1 -0.140 3.56z 2.27 2.922 51 ?431, 2778 2894 1.000 l V2 1.900 48.3 1.610 40.9 0.145 3.68 2.72 3.602 44 2513 2872 2992 1.000 2_' 7 2.375' 60.3 2.067 52.5- �0.1!�4 �3.91 3.66 5.109 24 1845 2108 2196 1.000 2% 2.875 73.0 2.469 62.7 0.203 5.16 5.80 7.871 20 2436 2784 2900 1.000 3 3.500, "88.6 3068 7 .9 Et 0.216 5.49^ 7.58 10.783 13 2069 2365 II 2464 1.000 31/2 4.000 101.6 3.548 90.1 0.226 5.74 9.12 13.400 10 1915 2189 2280 1.000 4, 4.506 A' 114.,3 4,026 1023 0.237 6.02 10.80 ;i 16.311 16 2268 2592 2700 1.000 S 5.563 141.3 5.047 158.2 0.258 6.55 14.63 23.262 7 2151 2458 2560 1.000 6 6.625 !1 -168.3, 7­ 6.065 154.1 0.-280 7,11 18.99 31.498 5 1994 2279 2374 1.000 S.. 8.625 219.1 7.981 202.7 0.322 8.18 28.58 50.240 5 3001 3430 3573 1.000 Calculated using Standard UL CRRfbrmula, UL Fire Protection Directory, Category VIZY The CRRisaratio value used to measure the ability ofa pipe to withstand corrosion. Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0). 8 NPS Schedule 40 is FM Approved but not UL Listed. 700 South Dock Street info@wheatland.com Sharon, 15A 16146 wheatland.com P 800.257.8182 Pollow us on Twitter: F,724.346J260 4� W , heatland-Tu - be (9 C& < APPROVED WFS-081619 Wheatland A DIVISION OF ZEKELMAN INDUSTRIES ADT Commercial 3150 SW 42n1 Ave Palm City, FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial Valves "* Commercial Bulletin 425 August 2020 Reliably Features • Stainless Steel body construction • Factory assembled and tested • Vertical or horizontal installation • Optional mounting bracket Approvals & Listings • Listed by Underwriters Laboratories Inc. and Underwriters Laboratories of Canada (cULus) Product Description The Reliable Residential Riser is UL Listed wet -pipe sprinkler system riser assembly consisting of a stainless steel body, waterflow switch, pressure gage, and drain. Triggering flow for the waterflow switch is 10 gpm (38 LPM). The Residential Riser is intended for use in NFPA 13D and 13R systems, and is offered in 1 ", 1 1/2", and 2" sizes. The product is available with a variety of end configurations (see table A below), and a choice of drain trims including a three position (off/test/drain) valve with several orifice choices. Optional pressure relief valve kits are also available. The Residential Riser can be wall mounted using the cast -in lugs or stud mounted using the optional support bracket (See Fig. 2). Installation The Reliable Residential Riser should be installed in accordance with NFPA 13, NFPA 13D, or NFPA 13R, as well as the requirements of any authorities having jurisdiction. Failure to follow installation instructions may void the warranty and listing of the valve. Connect the riser manifold to the supply piping and system piping using a non -hardening pipe joint compound or joint sealant tape for threaded connections. Ensure proper direction of flow using the flow arrow cast into the manifold. The one -inch (1 ") drain should be piped to a location that will avoid damage to property and injury to personnel. Residential Riser cULus Listed 175psi (12 bar) rated Shown: 2 threaded version with Model TD Test and Drain valve trim, optional Model A Pressure Relief valve kit, and optional locking handle kit (padlock not provided) Maintenance The owner is responsible for maintaining the fire protection system in proper operating condition. Any system maintenance or testing that involves placing a control valve or detection/control system out of service may eliminate the fire protection that is provided by the fire protection system. Notify any required authorities having jurisdiction and implement appropriate precautions prior to proceeding. When required, the Reliable Residential Riser and associated .equipment shall periodically be given a thorough inspection and test. NFPA 25, "Inspection, Testing and Maintenance of Water Based Fire Protection Systems," provides minimum maintenance requirements. Replace any components found to be corroded, damaged, or worn. Increase the frequency of inspections when the valve is exposed to corrosive conditions or chemicals that could impact the valve materials. Table A Nominal Size Available End Connections 1" (25mm) Male or Female NPT 1-1/2" (40mm) Female NPT or Grooved Ends 2" (50mm) Female NPT www.reliablesprinkler.com Residential Riser Basic Assembly with Ball Valve Drain (Shown with Optional Pressure Relief Kit) Water B assure Gauge Press. Relief Manifold Kit (Optional) Body System (i r o 0 C A o (Take Out) 0 10 Supply Drain Water RoJD Drain Valve Water Flow Detector Note: Drain tees are plugged when pressure relief kit is not used. 425FG01A Basic Assembly with Test and Drain Valve (Shown with Optional Pressure Relief Kit) B Water assure Gauge Press. Relief Manifold Kft(Opional)� Body System 0 ' o .o. A " C Drain (Take Out) 0 so Supply Test and Drain Valve Water Flow D Detector Note: Test and Drain valve outlets are plugged when pressure relief kit is not used. Dimensions and Weight 11111111111111111FRI rcM: Basic Assembly with Ball Drain Valve A B C D Weight Manifold Size in in in in Ibs (mm) (mm) (mm) (mm) (kg) Threaded Female 11 8-1/4 2-3/4 7.3 NPT 1 (25) (279) (210) (70) (3.32) Threaded Male NPT 11 8-1/4 2-3/4 7.3 1 (25) 11-1/4 (279) (210) (70) 1 (3.32) Threaded Female 11-1/2 8-1/4 3 8.3 NPT 1-1/2 (40) (286) (292) (210) (76) (3.77) Threaded Female 11-3/4 8-1/4 3-1/4 8.8 NPT 2 (50) (298) (210) (83) (4.00) Grooved Ends 1-1/2 11-1/2 9-1/2 3 8.3 (40) (292) (241) (76) (3.77) Dimensions and Weight - • - Basic Assembly with Test & Drain Valve A B C D Weight Manifold Size in in in in Ibs (mm) (mm) (mm) (mm) (kg) Threaded Female 14-1/2 8-1/4 3-1/4 9.0 NPT 1 (25) (368) (210) (83) (4.09) Threaded Male 14-1/2 8-1/4 3-1/4 9.0 NPT 1 (25) 11-1/2 (368) (210) (83) (4.09) Threaded Female 15 8-1/4 3-1/2 9.7 NPT 1-1/2(40) (292) (381) (210) (89) (4.41) Threaded Female 15-1/2 8-1/4 3-3/4 10.5 NPT 2 (50) (394) (210) (95) (477) Grooved Ends 15 9-1/2 3-1/2 9.7 1-1/2 (40) (381) (241) (89) (4.41) Bulletin 425 August 2020 Page 2 of 4 www.reliablesprinkler.com Support Bracket Mount Recessed or Flush Mounted 2 112' MINIMUM GAP FOR WATER FLOW INDICATOR COVER REMOVAL (TYPICAL ALL MANIFOLDS) STUDS 425FG02A (24 SHOWN) ACCESS PANEL NOT SHOWN OR PROVIDED BRACKETFLUSH WITH FACE OF STUD 2 112' MINIMUM GAP FOR WATER FLOW INDICATOR COVER REMOVAL (TYPICAL ALL MANIFOLDS) If -PLASTIC SPACERS - --_----- -------_F-------------- ------------------------��- - -------- I I I I sruD ' � � :• (2X6 SHOWN) 1- - l --�—„ ur o\ a 425FGOJA ACCESS PANEL NOT SHOWN OR PROVIDED FOR RECESSED INSTALLATION Bulletin 425 e1.�� Page 3 of 4 August 2020 fable www.reliablesprinkler.com Guarantee For Reliable Automatic Sprinkler, Co., Inc. guarantee, terms, and conditions, visit www.reliablesprinkler.com Ordering Information Specify: Reliable Residential Riser Size: [1"] [1-1/2"] [2"] End Connections: See Table A Drain: [Ball Valve] [K2.8 TD] [K4.2 TD] [K5.6 TD] Relief Valve Kit: [175psi] [185psi] Residential Riser Part Number 6A COX Bracket PN 6899190001 (Order Separately) ORPZ(1LZ Riser Manifold Size & End Connections XX Drain Valve YY Pressure Relief Kit Z 00 = 1" Threaded Female NPT 00 = Ball Valve 0 = None 01 = 1" Threaded Female Metric 01 = RASCO Test & Drain (K2.8) 1 = 175 psi (12.1 bar) 02 = 1" Threaded Male NPT 02 = RASCO Test & Drain (K4.2) 2 = 185 psi (12.8 bar) 03 = 1-1/2" Threaded Female NPT 03 = RASCO Test & Drain (K5.6) 04 = 1-1/2" Threaded Female Metric 05 = 1-1/2" Grooved End 06 = 2" Threaded Female NPT 07 = 2" Threaded Female Metric Example: P/N 6AO20RP031 = 1" Threaded Male NPT End Connection with RASCO Test & Drain (K5.6), and 175 psi Pressure Relief Kit. co M 0 0 0) rn rn rn rn rn z ii Bulletin 425 Page 4 of 4 August 2020 Re,�,�.. b�e www.reliablesprinkler.com Bulletin 830 April 2021 Reliably Product Description The Reliable Model RBV series bronze butterfly valves are indicating control valves for fire protection systems. Model RBVT valves have ANSI 131.20.1 NPT threaded end connections and are available in 1" (25 mm), 1-1/4" (32mm), 1-112" (38mm), 2"(51mm), and 2-1/2" (65mm) nominal sizes. The Model RBVG valves have ANSI/AWWA C606 grooved end connections and are available in 1-1/4" (32mm), 1-1/2" (38mm), 2"(51mm), and 2-1/2" (65mm) nominal sizes. The valves are listed for 300 psi (20.7 bar) working pressure. The valves have an integral 10 Amp pre -wired supervisory tamper switch assembly for indoor and outdoor use. The tamper switch signals movement of the valve seal from the full open position. Installation Model RBV series butterfly valves must be installed in accordance with NFPA 13, NFPA 72, FM Global Property Loss Prevention Data Sheets, and the requirements of any authorities having jurisdiction. Failure to follow installation instructions may void the warranty and listing of the valve. Verify compatibility of the valve materials with the water supply and the environment where the valve will be installed prior to installation. The valve can be installed in any orientation on a piping system with standard ASME 61.20.1 NPT threaded (Model BFVT) or ANSI/AWWA C606 grooved (Model BFVG) connections. Install Model BFVT valves by applying PTFE-based thread sealant to the male pipe threads and tightening the threaded connection using a wrench on only the hexagonal wrench -flats of the valve. Over - tightening threaded connections may damage the valve body resulting in leakage. Attached Model BFVG valve using UL Listed or FM Approved grooved couplings. The integral tamper switch assembly consistent of two switches. Switch 1 has dual leads orrthe terminals and is used for connection of the supervisory circuit of a listed fire alarm control panel. RBV Series Bronze Butterfly Valves Threaded end Grooved end Switch 2 has a single lead and is used for connection of the auxiliary equipment. A 14 ga. green wire is connected to the gearbox housing as a ground connection. All unused wires need to be capped with wire nuts and tucked into a junction box. All electrical connections must be in accordance with NFPA 72 and the requirements of any authorities having jurisdiction. End Configuration Options Model End Connections Sizes in (mm) Approvals 1" (25) UL Listed, FM Approved RBVT Threaded 1-1/4" (32), 1-1/2" (38), cULus Listed, FM Approved 2" (51), 2-1/2" (65) RBVG Grooved 1-1/4" (32), 1-1/2" (38), cULus Listed, FM Approved 2" (51), 2-1/2" (65) www.reliablesprinkler.com Technical Specifications Pressure Rating: 300 psi (20.7 bar) End Connections ANSI 131.2O.1 NPT Threads Material Specifications Body: Bronze ASTM 584 C836OO Disc: SS304 Sheet Stamping Handwheel: Ductile Iron ASTM A536 Seat: ASTM D2000 Won Indicator: Powder Metal FDO205 95HT Housing: Forged Brass AS C3771 (Ref. ASTM C377OO) Cover: Forged Brass JIS C3771 (Ref. ASTM C377OO) Listings and Approvals UL Listed - All Sizes cULus Listed - 1-1/4" (32mm), 1-1/2" (38mm), 2" (51mm), 2-1/2" (65mm) FM Approved - All Sizes Model RBVT Bronze Butterfly Valve - Threaded Components and Dimensions C BUTTERFLY VALVE a OPEN� m RBVT R SIZE 300 CWP A Model RBVT Bronze Butterfly Valve - Threaded Dimensions - in. (mm) Table B Valve Size A B C 1 „ 2-1/8 4-15/16 475/8 (54) (125) (118) 1-1/4" 2-5/8 5-1/8 4-5/8 (67) (130) (118) 2-7/8 5-5/8 4-5/8 (73) (142) (118) 2„ 3-1/4 6-1/8 4-5/8 (83) (156) (118) 2-1/2" 4-1/2 6-5/8 4-5/8 (114) (167) (118) Bulletin 830 April 2021 Page 2 of 4 www.reliablespdnkler.com Technical Specifications Listings and Approvals Pressure Rating: cULus Listed 300 psi (20.7 bar) FM Approved End Connections ANSI/AWWA C606 grooves Material Specifications Body: Bronze ASTM 584 C83600 Disc: SS304 Sheet Stamping Handwheel: Ductile Iron ASTM A536 Seat: ASTM D2000 Viton Indicator: Powder Metal FD0205 95HT Housing: Forged Brass JIS C3771 (Ref. ASTM C37700) Cover: Forged Brass JIS C3771 (Ref. ASTM C37700) Model RBVG Bronze Butterfly Valve - Grooved Components and Dimensions Model RBVG Bronze Butterfly Valve - Grooved Dimensions - in. (mm) . - Valve Size A B C 3-7/8 5-3/16 4-5/8 (98) (132) (118) 1-1/2" 4 5-1/2 4-5/8 (102) (139) (118) 2„ 4-1/8 6-1/16 4-5/8 (104) (154) 1 (118) 2-1/2" 4-1/2 6-9/16 4-5/8 (114) (167) (118) Bulletin 830 eliable Page 3 of 4 April 2021 www.reliablesprinkler.com Switch conditions shown to indicate valve in fully open position. Dual Leads Soldered to Switch Tabs Supervised Normally Open Valve Si: TWO LEADS PER TERMINAL BLACK BLA S1 CK OO RED RED WHITE WHITE FIRE ALARM CONTROL PANEL SUPERVISORY CIRCUIT END OR LINE RESISTOR OR NEXT DEVICE m GREEN ACTUATOR CASE GROUND S2: ONE LEAD PER TERMINAL O r� ORANGE VOLTAGE S2 SOURCE 0 ------O YELLOW — I BLUE NOTIFICATION DEVICE (LOAD) Notes: 1. Green wire is provided as ground for the switch housing. 2. Switch rating: 10.1 Amps-125/250VAC-60Hz 3. Actual switch application rating: 10 Amps/115 VAC-60Hz, 0.5 Amps/28 VDC 4. Cap unused leads with wire nuts and tuck into a junction box (not provided). Maintenance The owner is responsible for maintaining the fire protection system in proper operating condition. Any system maintenance or testing that involves placing a control valve out of service will eliminate the fire protection that is provided by the fire protection system. The Reliable Bronze Butterfly valves and associated equipment shall periodically be given a thorough inspection and test. NFPA 25, "Inspection, Testing and Maintenance of Water Based Fire Protection Systems," provides minimum maintenance require- ments. Guarantee For Reliable Automatic Sprinkler Co., Inc. guarantee, terms, and conditions, visit www.reliablesprinkler.com. Bulletin 830 April 2021 Ordering Information Specify the following when ordering: Valve Model • RBVT (threaded) • RBVG (grooved) Valve Size • 1" (25mm) (RBVT only) • 1-1/4" (32mm) • 1-1/2" (38mm) • 2" (51 mm) • 2-1/2" (65mm) 0 co C ti m m rn o) rn VA a Page 4 of 4 www.reliablespdnkler.com ADT Commercial 3150 SW 42nd Ave Palm City, FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial Switches "- commercial SYSTEM SENSOR SSM/SSV Series Alarm Bells System Sensor? SSM and SSV series alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features Reliable Performance.The SSM and SSV series provide loud • A roved for indoor and outdoor use resonant tones. The SSM series operates on 24VDC and are motor PP Low current draw • High dB output • Available in six-inch, eight -inch, and ten -inch sizes • AC and DC models • DC models polarized for use with supervision circuitry • Mount directly to standard four -inch square electrical box indoors • SSM and SSV series come pre -wired Aaencv Listinas 4 U� UDC FM :Q: MEA LISTED O APPO approved 7135-1653:125 54011 C5549 3005255 7135-1651100 331-01-E driven, while the SSV series operates on 120VAC utilizing a vibrating mechanism. Simplified Installation. For indoor use, the SSM and SSV series mount to a standard four -inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used. The SSM and SSV series come pre -wired, to reduce installation time. The SSM series incorporates a polarized electrical design for use with supervision circuitry. SSM/SSV Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 678710" (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi -flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4-square electrical box having a maximum projection of 2'/2 Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA. 'Physical/Operati�g Specifications Operating Temperature Range—31°Fto140°F Operating Voltage SSM series: 24VDC SSV series:120 VAC Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years Electrical Specificati Model ions Gong Diameter (inches) Nominal Voltage Operating Voltage Limit Maximum Current Sound Output (dBA) SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 82 SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1 mA/ FWR-53.5mA 81 SSV120-6 6 Regulated 120VAC 96to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 * Sound output measured at Underwriter Laboratories, as specified in UL464 Information SSM24-6 SSM24-6A Bell, 6, 24VDC, Polarized, 82dBA SSM24-8 SSM24-8A Bell, 8-,24VDC, Polarized, 80dBA SSM24-10 SSM24-1 oA Bell, 10 , 24VDC, Polarized, 81 dBA SSV120-6 SSV120-6A Bell, 6", 120VAC, 85dBA SSV120-8 SSV120-SA Bell, 8-,120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10 , 120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors "STEaI -/ ®2007 5yscem out nor. SENSOR"' 3825OhioAvenue•St.Charles,IL60174 Prod`a,entp duct infionttmchangewithel estwmirsitrysremsensheet. r Phone:800-SENSOR2 • Fax: 630-377-6495 u entpoductinfo nOS-026 -009- h07-#18ersionofthisdatasheec A05-0260-009.10/07•a1882 ADT Commercial 3150 SW 42nd Ave �Qt 1'IRI�I'CIC]� Palm City, FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial Hanger Material All Thread Rod meets following specifications: ASTM A307 Domestic and Import All Thread Rod ASTM A36 Domestic All Thread Rod only ATSM B 633 Domestic and Import Clear Zinc PlatedNellow Zinc Plated ASTM A 153 Domestic and Import Hot Dipped Galvanized ASTM A193-08B Import Stainless Steel T-304 ASTM A193-BB Domestic Stainless Steel T-304 ASTM A193 138M Domestic Stainless Steel T-316 1/2X10 BATRD10 GATRD10 1/2X12 BATRD12 GATRD12 SS4ATRD12 SS6ATRD12 1/2X6 BATRDU GATRDU SS4ATRDU SS6ATRDU 1/4X10 GATRB10 1/4X12 BATRB12 1/4X6 BATRBU GATRBU SS4ATRBU 1X10 GATRG10 1X12 GATRG12 SS4ATRG12 1X6 BATRGU GATRGU SS4ATRGU 3/4X10 BATRF10 GATRF10 3/012 BATRF12 GATRF12 SS4ATRF12 SS6ATRF12 3/4X6 BATRFU GATRFU SS4ATRFU 3/8X10 BATRC10 GATRC10 SS4ATRC10 3/8X12 BATRC12 GATRC12 SS4ATRC12 3/8X12 SS6ATRC12 3/8X3 GATRCM 3/8X6 BATRCU GATRCU SS4ATRCU 3/8X6 SS6ATRCU 5/8X10 BATRE10 GATRE10 5/8X12 BATRE12 GATRE12 SS4ATRE12 5/8X3 SS4ATREM 5/8X6 BATREU GATREU SS4ATREU 7/8X10 BATR7810 GATR7810 7/8X12 BATR7812 GATR7812 SS4ATR7812 SS6ATR7812 7/8X3 SS4ATR78M 7/8X6 BATR78U GATR78U SS4ATR78U Distributed Exclusively by Ferguson and Wolseley Canada © 2014 Ferguson Enterprises, Inc. All Rights Reserved 20348 04/14 Drop -in, Shell -Type Anchors SPECIFIED FOR ANCHORAGE INTO CONCRETE Drop -In, shell -type anchors feature an internally threaded, all -steel shell with expansion cone insert and flush embedment lip. Anchors are manufactured from zinc -plated carbon steel,18-8 stainless steel and 316 stainless steel. Internally Threaded Heavy - Duty Anchoring Systems Depth Charge Stop Drill and RX Drop -in Anchors Ideal for Hollow -Core, Pre -Cast Plank and Post Tension Slabs 94Veppeerj�l !eTMr Sgtop D ll Optimized for use in hollow - core, pre -cast plank and post -tension slabs Lip keeps anchor flush during installation 0 Shallow drilling —fast installation 9 RX Drop -In Anchor See page 81 for kits Anchors should be installed with carbide tipped hammer drill bits made in accordance to ANSI B212.15-1994 specifications. Anchors should be tested to ASTM E488 criteria and listed by ICC-ES. Anchors should also be listed by the following agencies as required by the local building code: UL, FM, City of Los Angeles, California State Fire Marshal and Caltrans. RM Drop -in Anchor RL Drop -in Anchor Coil Thread Anchor Lipped anchor body keeps anchorflush Easy installation El Keeps all rods same length 11 Easy inspection El Available in carbon steel, 18-8 and 316 stainless steel 0 Below surface setting for easy patch work El Quick thread attachment — ideal for 1 sided forming D Use coil rod on job Il 2 diameters (1/2" and 3/4") nwRed Head' Call our toll free number 800.848-5611 or visit our web site for the most current product and technical information at www.itwmdbead.com Multi -Set H Anchors Pumps and heavy piping are common Meets or exceeds U.S. Government G.S.A. Specification A-A-55614 Type 1 applications for larger diameter (Formerly GSA: FF-S-325 Group Vill) Multi -Set Drop -In Anchors. Underwriters Laboratories Factory Mutual Caltrans For the most current approvals/listings visit: www.itw-redhead. Cable tray and strut suspended from com concrete ceilings are ideal Multi -Set applications. In post -tension or hollow -core slabs use the RX-38. ► ► • ► • To set anchor flush with surface. The Multi -Set Anchor is the standard Drill hole to required embedment for pipe -hanging. The RM version has a (see Table on page 69). retainer lip to keep all anchors flush at the surface, keeping all your threaded rod the same length. ao A..'Qro a 2. Clean hole with pressurized air. Expander Slots —allow for easy setting and superior performance P P 3. Drive anchor flush with surface of concrete. Cone Insert —that expands the anchor ' -"' " ��' . when driven with setting tool and hammer a:`4. Ex and anchor with settin tool rovided (see chart P g p18-8 Body —available in zinc -plated steel,Qb stainless steel, and 316 stainless steel 'R°- s T on page 69). Anchor is properly expanded when ;,.a shoulder of setting tool is flush with top of anchor. Easy Depth Inspection —keeps threaded rod drop lengths consistent Retainer Lip —to keep anchor flush with surface For use with threaded rods or headed bolts (supplied by contractor) 01FIRC-hargeTM _ 37 Stop Drill 1RT NUMBER DESCRIPTION FEATURE BENEFITS DRILLING DEPTH 11 Shoulder prevents over drilling. Less likely DCX-138 3/8' Depth Charge Stop Drill 3/4' to hit reinforcing steel or post -tension cable DCX-112 1/2" Depth Charge Stop Drill 1" in concrete nwRed Head' Call our toll free number 800.848-5611 orvhlt our web site for the most current product and technical information at www.itwredhead.com 11 No wasted time or energy drilling deeper than necessary El Prevents anchor from dropping too far into hole below work surface PART NUMBER RT-138 PART NUMBER RTX-138 PART NUMBER RTX-112 IMMI 1 setting tool per master carton For use with RX-38 only. For use with RX-12 only. I (See above for part numbers.) 0 , M1.9, USERTYPE/ BASE CORROSION DROP -IN PART SETTING BOLT SIZE- DRILL BIT THREAD EMBEDMENT QTY/WT QTY/WT APPLICATION MATERIAL RESISTANCE ANCHOR NUMBER TOOL THREADS DIA. DEPTH MIN. HOLE PER BOX PER LEVEL TYPE PART PERINCH In.(mm) In.(mm) DEPTH*** lbs. MASTERCTN NUMBER* In.(mm) lbs.* HVAC/FireSprinkler Solid Low RM RM-14 RT-114 1/4"-20 3/8 (9.5) 3/8 (9.5) 1 (25.4) 100/ 2.6 1000/ 28 Plumber (Pipe -fitter) concrete/ RM-38 RT-138 3/8"-16 1/2' (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/ 3.4 500/ 36 lightweight RM-12 RT-112 1/2"-13 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50/ 5.8 400/ 49 fill deck RM-58 RT-158 5/8"- 11 7/8 (22.2) 1 (25.4) 2-1/2 (63.5) 25/ 7.8 125/ 41 RM-34 RT-134 3/4"-10 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25/11.9 100/49 Hollow -core pre -cast or Post - Low RX IX-31 IX-12 RTX-138 RTX-112 3/8"-16 1/2"-13 1/2 (12.7) 5/8 (15.9) 3/8 (93) 1/2 (12.7) 3/4 (19.1) 1 (25.4) 100/ 3.5 50/ 3.0 1000/ 36 500/ 31 ' tension Solid Medium SRM** SRM-14 RT-114 1/4"-20 3/8 (9.5) 3/8 (9.5) 1 (25.4) 100/ 2.7 1000/ 28 concrete/ 18-8S.S. SRM-38 RT-138 3/8"-16 1/2 (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/3.4 500/36 lightweight SRM-12 RT-112 1/2"-13 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50/ 6.0 400/ 50 fill deck ® SRM-58 RT-158 5/8"-11 7/8 (22.2) 1 (25.4) 2-1/2 (63.5) 25/ 7.9 125/ 42 SRM-34 RT-134 3/4"-10 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25/12.0 100/50 Solid High SSRM** concrete 3165.5. SSRM-12 RT-112 1/2"-13 5/8 (15.9)3/4 (19.1) 2 (50.8) 50/ 6.0 400/50 Concrete Contractor, Solid Low CL-Coil CL-12 RT-112 1/2"-6 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50/ 5.7 400/ 47 General Contractor, concrete Threaded CL-34 RT-134 3/4"-4.5 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25/11.9 100/49 Highway Concrete Cutting/ Solid Low RL RL-14 RT-114 1/4"-20 3/8 (9.5) 3/8 (9.5) 1 (25.4) 100/ 2.6 1000/ 28 Sawing Contractor/ concrete/ (w/o lip) RL-38 RT-138 3/8"-16 1/2 (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/ 3.4 500/ 36 Misc. Metal lightweight RL-12 RT-112 1/2%13 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50/ 5.8 400/ 49 fill deck ® RL-58 RT-158 5/8" -11 7/8 (22.2) 1 (25.4) 2-1/2 (63.5) 25/ 7.8 125/ 41 RL-34 I RT-134 3/4"-10 1 1 (25.4) 1-1/4 (31.8) 1 3-3/16 (81.0) 25/11.9 1 100/49 * 1 setting tool per master carton. ** For continuous extreme low temperature, use stainless steel. ***Embedment is equal to overall length of Drop -In Anchor Part No. Description RX-12 1/2" drop -in using 5/8" drill bit RTX-112 Setting Tool Da-112 Depth Charge Stop Drill /7wRed Head' Call our toll free number 800.848.5611 or visit our web site for the most current product and technical information at www.itwredhead.com Ultimate Tension and Shear Values (Lbs/kN) in Concrete* BOLT DRILL BIT DIA. SIZE In. (mm) In. (mm) MIN. EMBEDMENT DEPTH In. (mm) ANCHOR TYPE TENSION Lbs. kN SHEAR Lbs.NN) fc=2000PSI (13.8 MPa) fc=4000PSI (27.6 MPa) fc=6000PSI (41.4 MPa) fc>2000PSI (f3.8 MPa) 1/4 (6.4) 3/8 (9.5) 1 (25.4) RM, RL orCL-Carbon or SRM-18-8 S.S. or SSRM-316 S.S. 1,680 (7.5) 2,360 (10.5) 2,980 (13.3) 1,080 (4.8) 3/8 (9.5) 1/2 (12.7) 1-5/8 (41.3) 2,980 (13.3) 3,800 (16.9) 6,240 (27.8) 3,160 (14.1) 1/2 (12.7) 5/8 (15.9) 2 (50.8) 3,300 (14.7) 5,840 (26.0) 8,300 (36.9) 4,580 (20.4) 5/8 (15.9) 7/8 (22.2) 2-1/2 (63.5) 5,500 (24.5) 8,640 (38.4) 11,020 (49.0) 7,440 (33.1) 3/4 (19.1) 1 (25.4) 3-3/16 (81.0) 8,280 (36.8) 9,480 (42.2) 12,260 (54.5) 10,480 (46.6) • Allowable values are based upon a 4 to 1 safety factor. Divide by 4 for allowable load values. • For continuous extreme low temperature applications, use stainless steel. Ultimate Tension and Shear Values (Lbs/kN) in , , Lightweight Concrete* BOLT DRILL BIT MINIMUM ANCHOR LIGHTWEIGHT CONCRETE LOWER FLUTE OF STEEL DECK WITH DIA. SIZE EMBEDMENT TYPE fc = 3000 PSI (20.7 MPa) LIGHTWEIGHT CONCRETE FILL In. (mm) In. (mm) DEPTH fc = 3000 PSI (20.7 MPa) In.(mm) TENSION SHEAR TENSION SHEAR Lbs. NN) Lbs. NN) Lbs. NN) Lbs. (kN) 3/8 (9.5) 1/2 (12.7) 1-5/8 (39.7) RM, RL orCL-Carbon or SRM-18-8 S.S. or SSRM-3165.5. 2,035 (9.1) 1,895 (8.4) 3,340 (14.9) 4,420 (19.6) 1/2 (12.7) 5/8 (15.9) 2 (50.8) 2,740 (12.2) 2,750 (12.2) 3,200 (14.2) 4,940 (22.0) 5/8 (15.9) 7/8 (22.2) 2-1/2 (63.5) 4,240 (18.9) 4,465 (19.9) 5,960 (26.5) 5,840 (26.0) 3/4 (19.1) 1 (25.4) 3-3/16 (81.0) 5,330 (23.7) 6,290 (28.0) 8,180 (36.4) 9,120 • Allowable values are based upon a 4 to 1 safety factor. Divide by 4 for allowable load values. Recommended Edge and Spacing Distance Requirements* BOLT DRILL BIT EMBEDMENT ANCHOR EDGE DISTANCE MIN. EDGE SPACING MIN. ALLOWABLE SPACING DIA. SIZE DEPTH TYPE REQUIRED TO DISTANCE AT WHICH REQUIRED TO BETWEEN ANCHORS In. (mm) In. (mm) In. (mm) OBTAIN MAX. LOAD FACTORAPPLIED OBTAIN MAX. LOAD FACTOR APPLIED WORKING LOAD =.80 FOR TENSION WORKING LOAD =.80 FOR TENSION In. (mm) =30 FOR SHEAR In. (mm) =.SS FOR SHEAR In. (mm) In.(mm) 1/4 (6.4) 3/8 (9.5) 1 (25.4) RM, RL 1-3/4 (44.5) 7/8 (22.2) 3-1/2 (88.9) 1-3/4 (44.5) 3/8 (9.5) 1/2 (12.7) 1-5/8 (41.3) 2-7/8 (73.0) 1-7/16 (36.5) 5-11/16 (144.5) 2-7/8 (73.0) orCL-Carbon or SRM-18-8 S.S. or SSRM-316 S.S. 1/2(12.7) 5/8 (15.9) 2 (50.8) 3-1/2 (88.9) 1-3/4 (44.5) 7 (177.8) 3-1/2 (88.9) 5/8(15.9) 7/8(22.2) 2-1/2 (63.5) 4-3/8 (111.1) 2-3/16 (55.6) 8-3/4 (222.3) 4-3/8 (111.1) 3/4(19.1) 1 (25.4) 1 3-3/16 (81.0) 5-5/8 (142.9) 2-13/16 (71.4) 11-3/16 (284.2) 5-5/8 (142.9) • Spacing and edge distances shall be divided by 0.75 when anchors are placed in structural lightweight concrete. Linear Interpolation maybe used forintermediate spacing and edge distances. rrwRed Head' Call our toll free number B00-848-5611 or visit our web sue for the most current product and technical information at www.itwredhead.com Ultimate Tension and Shear Values (Lbs/kN) for RX-series IBO.L(T "and 1"Embedment)* DIA. DRILL BIT EMBEDMENT 2500 PSI (17.2 MPa) CONCRETE 4000 PSI (27.6 MPa) CONCRETE HOLLOW CORE nmm) SIZE In.(mm) TENSION SHEAR TENSION SHEAR TENSION SHEAR In.(mm) Lbs.(kN) Lbs.(kN) Lbs.(kN) lbs.(kN) Lbs.(kN) lbs.(kN) 3/8 (9.5) 1/2 (12.7) 3/4 (19.1) 1,571 (7.0) 2,295 (10.2) 1,987 (8.8) 2,903 (12.9) 1,908 (8.5) 2,401 (10.7) 1/2 (12.7) 5/8 (15.9) 1 (25.4) 2,113 (9.4) 2,585 (11.5) 2,673 (11.9) 3,270 (14.5) 2,462 (11.0) 2,401 (10.7) • The tabulated values are for RX anchors installed at a minimum of 12 diameters on center and minimum edge distance of6 diameters for 100 percent anchor efficiency. Spacing and edge distance maybe reduced to 6 diameters spacing and 3 diameter edge distance provided the values are reduced 50 percent. Linear Interpolation may be used for intermediate spacings and edge margins. • Allowable values are based upon a 4 to I safety factor. Divide by 4 for allowable load values. 0o c c o �soe o0 0 Anchoring Overhead in 3000 PSI 20Guall RXo p-InMetal D�,k Installed in Lightweight Concrete On Metal Deck lower Note Upper Mule ANCHOR DRILL HOLE EMBEDMENT 3000PSI(20.7 MPa)CONCRETE DIAMETER In.(mm) ULTIMATE TENSION LOAD ALLOWABLE WORKING LOAD In.(mm) lbs.(kN) Lbs.(kN) RX-38Drop-In 1/2 (12.7) 3/4 (19.1) Upper Flute 1,410 (6.3) 353 (1.6) Lower Flute 1,206 (5.4) 301 (1.3) • Allowable values are based upon a 4 to 1 safety factor. Divide by 4 for allowable load values. Combined Tension and Shear Loading —for Multi -Set Anchors Allowable loads for anchors subjected to combined shear and tension forces are determined by the following equation: (Ps/Pt)0+ (VsNt)13 S1 Ps = Applied tension load Vs = Applied shear load Pt = Allowable tension load Vt = Allowable shear load ffwRed Head' Call our toll free number 800.848-5611 orvisit our web site for the most current product and technical information at www.itwredhead.com FIGURE 7102 FNW CPVC HANGERS CPVC 2H WRAPAROUND STRAP FEATURES • 3/4" through 2" • Finish: Pre -galvanized • Color: Zinc • Rated for use with CPVC fire sprinkler pipe • Includes (2) ST4.8X25 Self -Tapping Screws REFERENCE CHART U alog Number Pipe Size D A B C E HS FNW7102F 3/4" 1.0501, 2.24" 3.22" 1.181, 1.181, 0.228" FNW7102G ill 1.315" 2.56" 3.54" 1.18" 1.44" 0.228" FNW7102H 1-1/4" 1.660" 315" 4.13" 1-.1811 1.79" 0.226" FNW7102J 1-1/2" 1.900" 3.43" 4.41" 1.18" 2.03" 0.228" FNW7102K 2" 2.375" 3.94" 1.181, 2.50" 0.228" C &us LISTED Max. 5.5' 6- 6.5' 7' 8' FNW.COM 02019 FNW 0619 1339251 We reserve the right to modify or improve the designs or specifications of our products at any time without notice. �s.• V a � �A�ry ou mtm ryry � _ .^e.* �oV A,f to E•.4,} ��vM is I e a Includes flared edges to protect piping Rated for use with CPVC fire sprinkler pipe Includes mounting screw c I Material: Steel Finish: Pregalvanized c&s Part Number, Pipe Size Outer Diameter OD Hole Size HS A B C Hanger Spacing 1070075EG 3/4" 1.050" 7/32" 1 1/4" 2 3/8" 1 3/16" 6' Max 1070100EG 1" 1.315" 7/32" 1 7/16" 2 11/16" 1 3/16" 6' Max 1070125EG 1 1/4" 1.660" 7/32" 1 5/8" 3 1/16" 1 3/16" 7' Max 1070150EG 1 1/2" 1.9001, 7/32" 1 3/4" 35/16" 1 3/16" 7' Max 1070200EG 2" 2.375" 7/32" 1 7/8" 3 11/16" 1 3/16" 8' Max UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC. WARNING nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty. © 2021 nVent All rights reserved nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice. �tL nJent CADDY a e 0 ,.AR AME�W • Includes flared edges to protect piping • Rated for use with CPVC fire sprinkler pipe Includes mounting screws B t I t i � I A Material: Steel Finish: Pregalvanized Part Number Pipe Size Outer Diameter 00 Hole Size HS A B C Hanger Spacing 107005EG3 14'. 131E0. 54(8. / 14'. 8 l i . 1 /416. 6' Max 1070100G3 1. 121E 54(8. / 148. 8148. 1 /416. 6' Max 107018EG3 1 14'. 1Z60. 54(8. " 14'. ! 141. 1 /416. 5' Max 10701EOG3 1 148. 1TOO. 54/8. 5416. / 5416. 1 /416. 5' Max 107080OG3 8. 815E 54(8. " 1E416. / IE416. 1 /416. T Max UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC2 WARNIN3 nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials2lnstruction sheets are available at www2?rico2:om and from your nVent customer service representative2lmproper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and4or void your warranty2 © 8081 nVent All rights reserved nVent, nVent CADDY, nVent GRICO, nVent GRIFLGX and nVent LGNTON are owned by nVent or its global affiliates2 All other trademarks are the property of their respective owners2nVent reserves the right to change specifications.without prior notice2 .t n�ent CADDY The 115 Standard Duty Loop Hanger is ideal for suspending stationary, non -insulated pipelines, including CPVC pipes, in fire sprinkler systems. A knurled insert nut helps simplify vertical adjustments and flared edges on the base (1/2" to 4" sizes) help protect pipes from coming into contact with any sharp edges of the hanger. • Flared edges help prevent any sharp surfaces from coming into contact with the pipe (1/2" to 4" sizes) • Retained insert nut helps ensure the loop hanger and insert nut stay together • Recommended for the suspension of stationary non -insulated pipe lines • Manufactured to use the minimum rod size permitted by NFPA® for fire sprinkler piping • Conforms with Federal Specification WW-H-171 (Type 10), Manufacturers Standardization Society (MSS) SP-58 (Type 101 Material: Steel Finish: Pregalvanized C UL US 6 •MI 1. Part Numbei Pipe Size Outer Diameter OD Rod Size IRS A B C Static Load F Certifications 115005DEG 1/2" 0.840" 3/8" 2 13/16" 1 1/8" 1" 300 tb cULus 1150075EG 3/4" 1.050" 3/8" 3" 1 3/16" -. 15/16" 3001b WLus, FM 1150100EG 1" 1.315" 3/8" 3 1/4" 1 3/8" 15/16" 3001b cULus, FM 1150125EG , 1 1/4" 1.660" r , .,3/8" 3 9/16" ' 1 1/2 .� ' , . 15/16" 3001b cULus, FM 1150150EG 1 1/2" 1.900" 3/8" 3 13/16" 1 5/8" 15/16" 3001b cULus, FM 1150200EG 2" 2.375" 3/8", 4 1/4" 1 7/8" 15/16" 3001b cULus, FM 1150250EG 21/2" 2.875" 3/8" 515/16" 37/16" 2" 5251b cULus, FM 1150300EG 3" 3.500" 3/8" 6 9/16" 3 1/2" . 1 15/16" 525 tb cULus. FM 1150350EG 31/2" 4.000" 3/8" 71/16' 33/4" 115/16" 5851b cULus. FM 1150400EG 4" 4.500" 3/8', 7 9/16" 4' 1 15/16" 650 lb cULus, FM 1150500EG 5" 5.563" 1/2" 913/16" 43/4" 21/4" 1,0001b cULus. FM 1150600EG 6" 6.625" 1/2" 115/16". 65/16" 35/16" 1,0001b cULus, FM 1150800EG 8" 8.625" 1/2" 12 7/8" 6 7/8" 2 7/8" 1.000 lb cULus, FM nJent CADDY FM is a registered certification mark of FM Approvals LLC, LTD. NFPA is a registered trademark of National Fire Protection Association, Inc. UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC. WARNING nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/orvoid your warranty. © 2019 nVent All rights reserved nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice. nJent CADDY • Recommended for suspending vertical steel pipe risers • Slotted holes make assembly easy, eliminating loose hardware • Serrated flange -head bolts eliminate need for wrenches on both bolt and nut • Conforms with Federal Specification WW-H-171 (Type 8), Manufacturers Standardization Society (MSSI SP-58 (Type 81 @01 HS� IF 1 i F 11 Part Nu'm6er` Pipe Size Outer Diameter OD Hole S Size HST A B Static Load F Certifications .r .. ... ,.� to .. _ •-_ .. .... ... .....Tp""I' -14'- o. d 5100800EG 8" 8.625" 11/16" 18 1/4" 2" 2,5001b cULus 5101000EG 10" - 10,.7501" 11/16'' 205/8"' " 2" 2.500lb — 5101200EG 12" 12.750" 11/16"• 22 3/8" 2" 2,7001b — 5101400EG 14", , 14.000!' 241/8" " 2" 2,700t-b - 5101600EG 16" 16.000" 13/16" 27 7/8" 2 1/2" 2,900lb — 5101800EG 18"� , 18.000. E 13/16' „„ „ � 29 13/16" 5102000EG 20" 20.000" 13/16" 32 1/4" 2 1/2" 2,900lb 5102400EG 24" 24.000" 15116"' 361/8"' 3" „ 2,9001b ' �t, A 4 30 a .,6—, r<;.` dr by oaf �u !"A , 1 i `�'reY�.r .qua . u t c' $.. g ''' i N a'��r.r?+,.: E. 510005OHD 1/2" 0.840" 7/16" 8 1/2" 1" 255 lb — 5100100HD i" 1.315' `" 7/16' 9" 1" 2551b 5100125HD 1 1/4" 1.660" 7/16" 9 7/16" 1" 255 lb — 5100150HD _ 1 1/2"'F ' 1 900 ; y `a _ y 7/16" 9 7/8" 1" 255lb- 5100200HD 2" 2.375" 7/16" 101/4" 13/16" 2551b cULus 5100250HDa 21/2" 2.875"1 7/16" 11.. „ 13/16" 390�1b cULus 510030OHD 3" 3.500" 7/16" 113/4" 13/16" 5301b cULus 5100400HD 4' 4.500"'-. 9/16" 13" 1 1/2" 8101b cULus 510050OHD 5" 5.563" 9/16" 141/2" 11/2" 1,1601b cULus 5100600HD 6" 6.625" 9/16" 16" 2" 1.570,1b, cULus " 5100800HO 8" 8.625" 11/16" 18 1/4" 2" 2,5001b cULus ndent CADDY Part Number Pipe Size Outer Diameter OD,,. Hole Size' '.HS '' A B Static Load F Certifications -J-.'�' s� `.,rv9"i+:�3.!.w N:,�.,.a _n- ;.„' 5100050S4 1/2" 0.840" 7/16" 8 1/2" 1" 2551b — 5100075S4 -.° ,' .e ', 3/4" s i 050' -e e 7/16" °9" 1" 2551b 5100100S4 1" 1.315" 7/16" 9" 1" 2551b — 510012554 1 1/4" ` ` 1.660 7/16,a 9.7(16" 1" 2551b', — 5100150S4 1 1/2" 1.900" 7/16" 9 7/8" 1" 2551b — 5700200S4 2" 2.375"° °7/16" - 10 1/4" ° 1 3/161' , ' , 255 lb — 5100250S4 2 1/2" 2.875" 7/16" 11" 1 3/16" 3901b — 510030054 P 3" 3.500'' ' 7/16" 17 3/4" _ 1 3/16,' 530 lb — 5100400S4 4" 4.500" 9/16" 13" 1 1/2" 810 lb — 510050054° ,' 5" ". 5.563"° `• 9/16 141/2" 11/2" 1,160'lb - 5100600S4 6" 6.625" 9/16" 16" 2" 1,570lb — 5100800S4 8', __ 8.625" r11/16" 181/4' 2" 2,5001b° — 5101000S4 10" 10.750" 11/16" 20 5/8" 2" 2.5001b Clamp is fitted for steel pipe and should be installed below a coupling or shear lug, with bolts torqued to recommended value. Slotted holes and bolts for pipe sizes up to 12" only. UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC. WARNING nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty. © 2019 nVent All rights reserved nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice. .t C n�ent CADDY ADT Commercial 3150 SW 42nd Ave C7lmmercicl Palm City, FL. 34990 Tel 772.232.2001 Fax 772.232.2004 www.adt.com/commercial Miscellaneous Material Description Designed for use in difficult sealing applications. It is ideally suited for Anti -Freeze filled sprinkler systems which are more subject to thread leakage than water filled systems. Manufactured to meet MIL Spec AA58092. Thickness is 0.09mm with density of 1.2g/cu cm. Installation Place end of tape on pipe thread 1/8" from end of pipe. 1. Wrap tape around pipe with 70% overlap = 3 layers all the way around the male thread. Stretch tape enough to pull into the thread without causing the thread tape to shred. Overlap back to the starting point. 2. Press tightly on tape and break it. Pipe thread is now ready for joining. 3. Joint should be tightened according to the fitting or device manufacturers' speci- fications. NEVER USE PTFE 02009 Fire Protection Products, Inc (FPPI) PIPE THREAD SEALING TAPE AND PASTE TOGETH- ER. Seal integrity will depend on the quality of the male and female thread, fluid pressure, and the nature of fluid being sealed. The 70% overlap is acceptable under normal water use with fixtures in normal repeated use condi- tion. Higher risk applications may require greater overlap or the use of high density thread sealing tape. ""J f r 0 " Specifications Material: 100% virgin PTFE Size: 1/2" x 520`' 3/4" x.520" � Fire Protection Products, Inc 6241 Yarrow Dr., Suite A, Carlsbad, CA 92011-1541 —1-1—.... ­.. For questions: 1 800 344-1822 • 1 800 344-3775 fax • www.fppi.com Model FPPI-PG Description Model FPPI-PG pressure gauges feature an impact and corrosion resistant case made from ABS (plastic) or powder coated steel. Features phosphor bronze bourdon tube movement with white enameled brass dial face with large numbers for easy reading. Dual scale to 300 PSI/2000Kpa. UUULc Listed (EX26630) and FM Approved. Applications • Fire sprinkler systems • Suitable for all media that will not obstruct the pressure system or attack copper alloy parts Special Features • UL-listed (UL-393), EX26630 • Factory Mutual (FM) approved • Reliable and economical The information contained herein is produced In good faith and is believed to be reliable but is provided for guidance and Information purposes only. FPPI and its agents cannot assume liability or responsibility for results obtained In the use or misuse of its product by persons whose methods and qualifications are outside and beyond our control. it Is the user's responsibility to determine the suitability of, methods of use, preparation prior to use, and appropriate Installation for all products purchased from FPPI. It is the user's sole responsibility to observe and adapt such precautions as may be advisable or necessary for the protection of personnel and property In the handling and use of any of our products. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 + 1 (760) 599-1168 + 1 (800) 344-1822 + 1 (800) 344-3775 FAX 0 2017 Fire Protection Products, Inc. Standard Features Design EN 837-1 & ASME 1340.100 Sizes 4" (100 mm) Accuracy class t &Y3% of span (ASME 640.100 Grade B) The tolerance is reflected in the box associated with the zero mark on the face of the gauge. The value is considered zero when the pointer falls anywhere within this box. Ranges 0/80 psi, retard to 250 psi (air) 0/300 psi (aia/3water, air/water) Working Pressure Steady: 3/ of full scale value Fluctuating: 1/2 of full scale value Short time: full scale value Operating Temperature Ambient: -40OF to 140OF (-40°C to 60°C) Media: 140OF (+60°C) maximum Temperature Error Additional error when temperature of 68°F (20°C) +0.4% for every 18°F (10°C) rising or falling. Percentage of span. P P I Specifications Bourdon Tube Material: copper alloy C-type Pressure Connection Material: copper alloy '/a" NPT lower mount (LM) Movement Copper alloy Dial White aluminum with stop pin; black and red lettering Pointer Black aluminum Case . Black polycarbonate Powder coated steel (Air/Water Gauge only) Window Snap -in clear polycarbonate Item Numbers/Descriptions 11-550-00 Water Gauge 11-551-00 Air Gauge 11-552-00 Air Gauge w/Retard 11-553-00 Air/Water Gauge 11-553-10 Air/Water Gauge w/ Steel Case 11-558-00 Water Gauge, Personalized 11-559-00 Air/Water Gauge, Personalized 11-561-00 Air Gauge w/Retard, Personalized c �L us <&> A G;r— 4 _ LISTED APPRIM �.. Description Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head Cabinets al available in six configurations. Three head, six head, six head ESFR, twelve head, twenty-fou head and thirty-six head. All six styles are manufactured with "knockouts" to accommodate the most common size sprinklers. The shelf is located to allow for the storage of a typical sprinkler head wrench. Each cabinet is finished with a red enamel finish. Each spare head cabinet comes with a hinged door which remains closed to protect the spare sprinklers from the elements and features two holes on the back panel to allow for attachment to most surfaces utilizing the appropriate fasteners. Not intended for exposed or harsh environments. Installation Select the correct Spare Sprinkler Head Cabinet in accordance with the Automatic Sprinkler Systems Handbook. As per the 1989 Edition the correct number of spare sprinkler is as follows: 0-300 sprinklers, not less than 6; 300-1000, not less than 12; 1000 or more, not less than 24. Stock of spare sprinklers shall include all types and ratings installed." Once the correct Spare Sprinkler Head Cabinet has been selected, installation is accomplished by inserting the correct fastener in each of the two holes inside the cabinet, securing the cabinet securely to the wall. The insert the correct number and type of sprinklers in accordance with the "handbook". "Final determination is subject to approval by the AHJ. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 0 2012 Fire Protection Products, Inc. F P P I Specifications Material: Painted Plain Steel Finish: Red enamel Styles: 3 Spare sprinklers,'/z or 3/4 6 Spare sprinklers,'/2 or 3/4 6 Spare, ESFR,'/2, 3/4-or 1" 12 Spare sprinklers'/2 or 3/4 24 Spare sprinklers 36 Spare sprinklers Commercial' Digitally signed Eso? by Jeffrey Collins �, Date:2021.10.12 .......� ...QR.... "'^S.9jANhlfyG�' 14:00:36-04'00' ADT COMMERCIAL 3150 SW 42ND AVE. PALM CITY, FL. 34990 772.232.2001 Job Name 500625593 SP MAHI MAHI CRISTELLE CAY Drawing MAHI MAHI Location PHG Remote Area 1 Contract 500625593 Data File 4TH FLR MAHI MAHI CRISTELLE CAY Area 1.WXF Computer Programs by Hydratec Inc. Revision: 50.5520.727 ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 1 Date HYDRAULIC DESIGN INFORMATION SHEET Name - CRISTELLE CAY Date - 09.14.2021 Location - PHG Building - MAHI MAHI Contractor - ADTC Calculated By - JPC Construction: ( ) Combustible OCCUPANCY - 13R System No. - 1 Contract No. - 500625593 Drawing No. - FP5 (X) Non -Combustible Ceiling Height S Type of Calculation: ( )NFPA 13 Residential (X)NFPA 13R ( )NFPA 13D Y Number of Sprinklers Flowing: ( )l ( )2 (X)4 ( ) S ( ) Other T ( )Specific Ruling Made by Date E M Listed Flow at Start Point - 16 Gpm System Type Listed Pres. at Start Point - 13.3 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction E Domestic Flow Added - Gpm Sprinkler or Nozzle S Additional Flow Added - Gpm Make RELIABLE Model R3531 I Elevation at Highest Outlet - 18'11"Feet Size 1/2 K-Factor 4.4 G Note: Temperature Rating 155 N Calculation Gpm Required 158.726 Psi Required 54.140 At Test Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: A Date of Test - T Time of Test - E Static (Psi) - 62 R Residual (Psi) - 40 Flow (Gpm) - 1000 S Elevation - 0 P Location: P L Source of Information: Y Pump Data: Tank or Reservoir: Rated Cap. Cap. @ Psi Elev. Elev. Other Well Proof Flow Gpm Computer Programs by Hydratec Inc. Revision: 50.5520.727 Water Supply Curve ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 2 Date City Water Supply: Demand: C1 - Static Pressure : 62 D1 - Elevation 17.142 C2 - Residual Pressure: 40 D2 - System Flow : 58.726 C2 - Residual Flow 1000 D2 - System Pressure : 54.140 Hose ( Demand) :100 D3 - System Demand : 158.726 Safety Margin 7.130 150 140 130 P 120 R 110 E 100 S 90 S 80 U 70 C1 R 60 E 50 3 40 30 20 D1 10 100 200 300 400 500 600 700 800 900 FLOW (N " 1.85) C2 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Diagram ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 3 Date 13.2 58.7 58.7 58.7 58.7 101 F 102 E- 103 F 104 F M1 F M2 F RSP4- SPT<- SPB(- TEST 26.6 58.7 58.7 58.7 13.4 105 F 102 T 1 26.6 161 106 <-. 103 16 107 <-- 103 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Fittings Used Summary ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 4 Date Fitting Legend Abbrev. Name '/ % 1 1% 1'/ 2 2'/ 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve. 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Summary - NFPA ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 5 Date SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 62.0 40 1000.0 61.269 158.73 54.14 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 101 38.92 4.4 9.06 13.24 0.05 144 102 39.25 9.58 103 39.58 13.32 104 39.58 19.51 M 1 39.58 24.32 M2 39.58 27.57 RSR4 39.58 30.99 SPT 39.58 31.48 SPB -5.0 50.83 TEST 0.0 54.14 100.0 105 39.25 4.4 9.26 13.39 0.05 144 106 39.58 4.4 13.3 16.05 0.05 196 107 39.58 4.4 13.3 16.05 0.05 256 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 6 500625593 SP MAHI MAHI CRISTELLE CAY Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 101 38.92 4.40 13.24 1 3E 11.475 9.670 150 9.057 to 11.475 -0.143 102 39.25 13.24 1.101 21.145 0.0317 0.670 Vel = 4.46 102 39.25 13.39 1 3E 11.475 12.540 150 9.584 to T 9.563 21.037 -0.143 103 39.58 26.63 1.101 33.577 0.1156 3.882 Vel = 8.97 103 39.58 32.10 1.25 2T 19.046 15.290 150 13.323 to E 4.762 23.808 0.0 104 39.58 58.73 1.394 39.098 0.1582 6.184 Vel = 12.35 104 39.58 0.0 1.5 4E 23.312 35.870 150 19.507 to 23.312 0.0 M 1 39.58 58.73 1.598 59.182 0.0813 4.814 Vel = 9.39 M 1 39.58 0.0 1.5 40.000 150 24.321 to 0.0 M2 39.58 58.73 1.598 40.000 0.0813 3.253 Vel = 9.39 M2 39.58 0.0 2 7E 45.376 67.840 150 27.574 to T 12.965 58.341 0.0 RSR4 39.58 58.73 2.003 126.181 0.0271 3.416 Vel = 5.98 RSR4 39.58 0.0 2 2E 12.307 4.830 120 30.990 to 12.307 0.0 SPT 39.58 58.73 2.157 17.137 0.0285 0.489 Vel = 5.16 SPT 39.58 0.0 4 44.580 120 31.479 to 19.308 SPB -5 58.73 4.26 44.580 0.0010 0.046 Vel = 1.32 SPB -5 0.0 4 4E 63.728 100.000 150 50.833 to G 3.186 98.779 3.136 * * Fixed Loss = 5.302 TEST 0 58.73 4.07 T 31.864 198.779 0.0009 0.171 Vel = 1.45 Zaf 0.0 100.00 Qa = 100.00 TEST 158.73 54.140 K Factor = 21.57 105 39.25 4.40 13.39 1 T 9.563 0.330 150 9.264 to 9.562 0.0 102 39.25 13.39 1.101 9.892 0.0323 0.320 Vel = 4.51 0.0 102 13.39 9.584 K Factor = 4.33 106 39.58 4.40 16.05 1 0.500 150 13.300 to 0.0 103 39.58 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 0.0 103 16.05 13.323 K Factor = 4.40 107 39.58 4.40 16.05 1 0.500 150 13.300 to 0.0 103 39.58 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 0.0 103 16.05 13.323 K Factor = 4.40 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Orfl, , iercia 'Digitally signed by .iN Collins �� No. 53636 /"Jeffrey `t, ' STM1TE Of ( 4� Date•. 2021.10.12 14:00:14-04'00' ADT COMMERCIAL 3150 SW 42ND AVE. PALM CITY, FL. 34990 772.232.2001 Job Name 500625593 SP MAHI MAHI CRISTELLE CAY Drawing MAHI MAHI Location PHG Remote Area 2 Contract 500625593 Data File 4TH FLR MAHI MAHI CRISTELLE CAY Area 2.WXF Computer Programs by Hydratec Inc. Revision: 50.5520.727 ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 1 Date HYDRAULIC DESIGN INFORMATION SHEET Name - CRISTELLE CAY Date - 09.14.2021 Location - PHG Building - MAHI MAHI Contractor - ADTC Calculated By - JPC Construction: ( ) Combustible OCCUPANCY - 13R System No. - 2 Contract No. - 500625593 Drawing No. - FP5 (X) Non -Combustible Ceiling Height S Type of Calculation: ( )NFPA 13 Residential (X)NFPA 13R ( )NFPA 13D Y Number of Sprinklers Flowing: ( )l ( )2 (X)4 ( ) S ( ) Other T ( )Specific Ruling Made by Date E M Listed Flow at Start Point - 16 Gpm System Type Listed Pres. at Start Point - 13.3 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction E Domestic Flow Added - Gpm Sprinkler or Nozzle S Additional Flow Added - Gpm Make RELIABLE Model R3531 I Elevation at Highest Outlet - 18'11"Feet Size 1/2 K-Factor 4.4 G Note: Temperature Rating 155 N Calculation Gpm Required 158.726 Psi Required 54.140 At Test Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: A Date of Test - T Time of Test - E Static (Psi) - 62 R Residual (Psi) - 40 Flow (Gpm) - 1000 S Elevation - 0 P Location: P L Source of Information: Y Pump Data: Tank or Reservoir: Rated Cap. Cap. @ Psi Elev. Elev. Other Well Proof Flow Gpm Computer Programs by Hydratec Inc. Revision: 50.5520.727 Water Supply Curve ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 2 Date City Water Supply: Demand: C1 - Static Pressure : 62 D1 - Elevation 16.999 C2 - Residual Pressure: 40 D2 - System Flow : 62.034 C2 - Residual Flow 1000 D2 - System Pressure 50.560 Hose ( Demand) :100 D3 - System Demand : 162.034 Safety Margin 10.681 150 140 130 P 120 R 110 E 100 S 90 S 80 U 70 C1 R 60 E 50 D2 33 40 30 20 1 D 10 100 200 300 400 500 600 700 800 900 FLOW (N " 1.85) C2 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Diagram ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 3 Date 14.9 29.9 62 62 62 201 F 202 F 203 F 204 F M4 F M3 F RSR4. SPT<-. SPBF- TEST T 141 62 62 62 1 14.$ 29.9 15.1 1 205 *- 203 1 I I 16 1 206 F 207 E- 204 32.1 16 208 F 207 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Fittings Used Summary ADT COMMERCIAL Page 4 500625598 SP MAHI MAHI CRISTELLE CAY Date Fitting Legend Abbrev. Name '/2 '/ 1 1% 1'/ 2 2'/ 3 3Y 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US. Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Summary - NFPA ADT COMMERCIAL Page 5 500625593 SP MAHI MAHI CRISTELLE CAY Date SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 62.0 40 1000.0 61.241 162.03 50.56 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 201 39.25 4.4 11.44 14.88 0.05 144 202 39.58 11.63 203 39.58 12.13 204 39.58 16.35 M4 39.58 21.58 M3 39.58 25.35 RSR4 39.58 27.6 SPT 39.58 28.14 SPB -5.0 47.5 TEST 0.0 50.56 100.0 205 39.25 4.4 11.71 15.06 0.05 144 206 39.25 4.4 13.3 16.05 0.05 196 207 39.25 13.32 208 39.25 4.4 13.3 16.05 0.05 256 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 6 500625593 SP MAHI MAHI CRISTELLE CAY Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 201 39.25 4.40 14.88 1 2E 7.65 0.830 150 11.443 to 7.650 -0.143 202 39.58 14.88 1.101 8.480 0.0394 0.334 Vel = 5.01 202 39.58 0.0 1 E 3.825 8.840 150 11.634 to -3.825 0.0 203 39.58 14.88 1.101 12.665 0.0394 0.499 Vel = 5.01 203 39.58 15.06 1 2E 7.65 12.200 150 12.133 to T 9.563 17.212 0.0 204 39.58 29.94 1.101 29.412 0.1435 4.222 Vel = 10.09 204 39.58 32.09 1.25 E 4.762 15.580 150 16.355 to T 9.523 14.284 0.0 M4 39.58 62.03 1.394 29.864 0.1751 5.228 Vel = 13.04 M4 39.58 0.0 1.25 E 4.762 7.210 150 21.583 to T 9.523 14.284 0.0 M3 39.58 62.03 1.394 21.494 0.1751 3.763 Vel = 13.04 M3 39.58 0.0 2 T 12.965 29.870 150 25.346 to 5E 32.412 45.377 0.0 RSR4 39.58 62.03 2.003 75.247 0.0300 2.254 Vel = 6.32 RSR4 39.58 0.0 2 2E 12.307 4.830 120 27.600 to 12.307 0.0 SPT 39.58 62.03 2.157 17.137 0.0316 0.541 Vel = 5.45 SPT 39.58 0.0 4 44.580 120 28.141 to 19.308 SPB -5 62.03 4.26 44.580 0.0011 0.051 Vel = 1.40 SPB -5 0.0 4 4E 63.728 100.000 150 47.500 to G 3.186 98.779 2.872 * * Fixed Loss = 5.037 TEST 0 62.03 4.07 T 31.864 198.779 0.0009 0.188 Vel = 1.53 Zaf 0.0 100.00 Qa = 100.00 TEST 162.03 50.560 K Factor = 22.79 205 39.25 4.40 15.06 1 E 3.825 0.660 150 11.711 to T 9.563 13.387 -0.143 203 39.58 15.06 1.101 14.047 0.0402 0.565 Vel = 5.08 0.0 203 15.06 12.133 K Factor = 4.32 206 39.25 4.40 16.05 1 0.500 150 13.300 to 0.0 207 39.25 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 207 39.25 16.04 1 2T 19.125 0.330 150 13.323 to 19.126 -0.143 204 39.58 32.09 1.101 19.456 0.1632 3.175 Vel = 10.81 0.0 204 32.09 16.355 K Factor = 7.93 208 39.25 4.40 16.05 1 0.500 150 13.300 to 0.0 207 39.25 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 0.0 207 16.05 13.323 K Factor = 4.40 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 7 500625593 SP MAHI MAHI CRISTELLE CAY Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ****' ** Notes Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf Computer Programs by Hydratec Inc. Revision: 50.5520.727 C.oml 1 lerc,ial ""'�Y P� Di itall 9 si ned i� by Jeffrey Collins STATE OF ,'p,I _Date:.2021.10.12 13:59:54-04'00' ADT COMMERCIAL 3150 SW 42ND AVE. PALM CITY, FL. 34990 772.232.2001 Job Name 500625593 SP MAHI MAHI CRISTELLE CAY Drawing MAHI MAHI Location UNIT 3G Remote Area 4 Contract 500625593 Data File 3RD FLR MAHI MAHI CRISTELLE CAY Area 3.WXF Computer Programs by Hydratec Inc. Revision: 50.5520.727 ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 1 Date HYDRAULIC DESIGN INFORMATION SHEET Name - CRISTELLE CAY Date - 09.14.2021 Location - UNIT 3G Building - MAHI MAHI System No. - 4 Contractor - ADTC Contract No. - 500625593 Calculated By - JPC Drawing No. - FP4 Construction: ( ) Combustible (X) Non -Combustible Ceiling Height OCCUPANCY - 13R S Type of Calculation: ( )NFPA 13 Residential (X)NFPA 13R ( )NFPA 13D Y Number of Sprinklers Flowing: ( )1 ( )2 (X)4 ( ) S ( ) Other T ( )Specific Ruling Made by Date E M Listed Flow at Start Point - 16 Gpm System Type Listed Pres. at Start Point - 13.3 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction E Domestic Flow Added - Gpm Sprinkler or Nozzle S Additional Flow Added - Gpm Make RELIABLE Model R3531 I Elevation at Highest Outlet - 18'11"Feet Size 1/2 K-Factor 4.4 G Note: Temperature Rating 155 N Calculation Gpm Required 163.386 Psi Required 56.279 At Test Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - Rated Cap. Cap. T Time of Test - @ Psi Elev. E Static (Psi) - 62 Elev. R Residual (Psi) - 40 Other Well Flow (Gpm) - 1000 Proof Flow Gpm S Elevation - 0 P Location: P L Source of Information: Y Computer Programs by Hydratec Inc. Revision: 50.5520.727 Water Supply Curve ADT COMMERCIAL Page 2 500625593 SP MAHI MAHI CRISTELLE CAY Date City Water Supply: Demand: C1 - Static Pressure : 62 D1 - Elevation 12.378 C2 - Residual Pressure: 40 D2 - System Flow : 63.386 C2 - Residual Flow 1000 D2 - System Pressure 56.279 Hose ( Demand) : 100 D3 - System Demand : 163.386 Safety Margin 4.951 150 140 130 P 120 R 110 E 100 S 90 S 80 U 70 C1 R 60 E 50 3 40 30 20 10 100 200 300 400 500 600 700 800 900 FLOW N"1.85) C2 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Diagram ADT COMMERCIAL Page 3 500625593 SP MAHI MAHI CRISTELLE CAY Date 15.6 63.4 63.4 63.4 63.4 301 F 302 E-- 203 F 304 *-- 3M1 F 3M2F 3M3<-. RSR4L 3SPT-- SPB<--. TEST 31.3 63.4 63.4 63.4 63.4 15.7 305 <- 302 16 306+- 307<- 303 32.1 16 308 <- 307 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Fittings Used Summary ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 4 Date Fitting Legend Abbrev. Name % % 1 1% 1% 2 21/ 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Summary - NFPA ADT COMMERCIAL Page 5 500625593 SP MAHI MAHI CRISTELLE CAY Date SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 62.0 40 1000.0 61.229 163.39 56.279 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 301 28.58 4.4 12.5 15.56 0.05 144 302 28.92 13.26 303 28.92 16.35 304 28.92 21.74 3M1 28.92 27.28 31VI2 28.92 31.58 3M3 28.92 35.68 RSR3 28.92 38.02 3SPT 28.92 38.59 SPB -5.0 53.32 TEST 0.0 56.28 100.0 305 28.58 4.4 12.79 15.74 0.05 144 306 28.58 4.4 13.3 16.05 0.05 256 307 28.58 13.32 308 28.58 4.4 13.3 16.05 0.05 196 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 6 500625593 SP MAHI MAHI CRISTELLE CAY Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ****'** Notes Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 301 28.58 4.40 15.56 1 3E 11.475 9.670 150 12.501 to 11.475 -0.147 302 28.92 15.56 1.101 21.145 0.0427 0.903 Vel = 5.24 302 28.92 15.73 1 2E 7.65 12.210 150 13.257 to 7.650 0.0 303 28.92 31.29 1.101 19.860 0.1558 3.094 Vel = 10.54 303 28.92 32.10 1.25 E 4.762 15.290 150 16.351 to T 9.523 14.284 0.0 304 28.92 63.39 1.394 29.574 0.1822 5.387 Vel = 13.33 304 28.92 0.0 1.5 4E 23.312 35.870 150 21.738 to 23.312 0.0 3M1 28.92 63.39 1.598 59.182 0.0937 5.544 Vel = 10.14 3M1 28.92 0.0 1.5 E 5.828 40.000 150 27.282 to 5.828 0.0 3M2 28.92 63.39 1.598 45.828 0.0937 4.294 Vel = 10.14 3M2 28.92 0.0 1.5 E 5.828 37.970 150 31.576 to 5.828 0.0 3M3 28.92 63.39 1.598 43.798 0.0937 4.102 Vel = 10.14 3M3 28.92 0.0 2 T 12.965 29.870 150 35.678 to 5E 32.412 45.377 0.0 RSR3 28.92 63.39 2.003 75.247 0.0312 2.347 Vel = 6.45 RSR3 28.92 0.0 2 2E 12.307 4.830 120 38.025 to 12.307 0.0 3SPT 28.92 63.39 2.157 17.137 0.0329 0.563 Vel = 5.57 3SPT 28.92 0.0 4 33.920 120 38.588 to 14.691 SPB -5 63.39 4.26 33.920 0.0012 0.040 Vel = 1.43 SPB -5 0.0 4 4E 63.728 100.000 150 53.319 to G 3.186 98.779 2.764 * * Fixed Loss = 4.929 TEST 0 63.39 4.07 T 31.864 198.779 0.0010 0.196 Vel = 1.56 Zaf 0.0 100.00 Qa = 100.00 TEST 163.39 56.279 K Factor = 21.78 305 28.58 4.40 15.74 1 E 3.825 0.660 150 12.791 to T 9.563 13.387 -0.147 302 28.92 15.74 1.101 14.047 0.0436 0.613 Vel = 5.30 0.0 302 15.74 13.257 K Factor = 4.32 306 28.58 4.40 16.05 1 0.500 150 13.300 to 0.0 307 28.58 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 307 28.58 16.04 1 2T 19.125 0.330 150 13.323 to 19.126 -0.147 303 28.92 32.09 1.101 19.456 0.1632 3.175 Vel = 10.81 0.0 303 32.09 16.351 K Factor = 7.94 308 28.58 4.40 16.05 1 0.500 150 13.300 to 0.0 307 28.58 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 7 Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ``**' ** Notes Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 0.0 307 16.05 13.323 K Factor = 4.40 Computer Programs by Hydratec Inc. Revision: 50.5520.727 C..om erc,ia t' Digitally signed by Jeffrey Collins sTaT= OF..--", rDate�,2021.10.12 Sfomn�E`� 13:59:29 -04 00 ADT COMMERCIAL 3150 SW 42ND AVE. PALM CITY, FL. 34990 772.232.2001 Job Name 500625593 SP MAHI MAHI CRISTELLE CAY Drawing FP2 Location MAHI MAHI Remote Area 5 Contract 500625593 Data File 1ST FLR MAHI MAHI CRISTELLE CAY Area 5.WXF Computer Programs by Hydratec Inc. Revision: 50.5520.727 Page 1 Date 09.14.2021 ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY HYDRAULIC CALCULATIONS for JOB NAME SP MAHI MAHI CRISTELLE CAY Location MAHI MAHI Drawing # FP2 Contract # 500625593 Date 09.14.2021 DESIGN Remote area # 5 Remote area location SOUTH SIDE Occupancy classification ORD HAZ GR I Density 0.15 - Gpm/SgFt Area of application 1000 - SgFt Coverage/sprinkler 128 - SgFt Type of sprinkler calculated 5.61< 200 DEG UPRIGHT # Sprinklers calculated 9 In -rack demand NA - GPM Hose streams 250 - GPM Total water required (including hose streams) 421.097 - GPM @ 49.2094 - Psi Type of system AUTOMATIC WET Volume of system (dry or pre -action) NA - Gal WATER SUPPLY INFORMATION Test date Location Source of info UTILITIES CONTRACTOR INFO ADT COMMERCIAL Address 3150 SW 42ND AVE. PALM CITY, FL. 34990 Phone # 772.232.2001 Name of designer JPC Authority having jurisdiction SLC FD NOTES: STATIC: 62PSI RESIDUAL: 40PSI FLOW: 1000GPM Computer Programs by Hydratec Inc. Revision: 50.5520.727 Water Supply Curve ADT COMMERCIAL Page 2 500625593 SP MAHI MAHI CRISTELLE CAY Date 09.14.2021 City Water Supply: Demand: C1 - Static Pressure : 62 D1 - Elevation 3.681 C2 - Residual Pressure: 40 D2 - System Flow : 171.097 C2 - Residual Flow 1000 D2 - System Pressure 49.209 Hose ( Demand) : 250 D3 - System Demand : 421.097 Safety Margin 8.349 150 140 130 p 120 R 110 E 100 S 90 S 80 U 70 C1 R 60 D2 E 50 40 30 20 10 T . ...... I 100 200 300 400 500 600 700 800 900 FLOW (NA1.85) C2 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Diagram ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 3 Date 09.14.2021 19.2 114.5 171.1 171.1 171.1 501 *- 502 *- 503 F 504 *- 1M1 F 1M2F TOR*- BOP(-- 505 <- TEST T 38.6 1 1711.1 171.1 171.1 1 38.6 1 56.¢ 171.1 191 1 1 506 F 503 1 1 1 1 1 1 18.1 37 J J 507 *- 508 <-. 509 F. 510 F 504 18.1 56.6 18.8 511 +-. 512 E- 503 1 56.$ 1 38.1 56.9 19y J 513 F 514 F 512 38.1 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Fittings Used Summary ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 4 Date 09.14.2021 Fitting Legend Abbrev. Name '/ '/< 1 1 % 1'/ 2 2'/ 3 3'/ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Summary - NFPA ADT COMMERCIAL Page 5 500625593 SP MAHI MAHI CRISTELLE CAY Date 09.14.2021 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 62.0 40 1000.0 57.559 421.1 49.209 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 501 8.5 5.6 11.76 19.2 0.15 128 502 8.5 5.6 11.99 19.39 0.15 112 503 8.5 12.94 504 8.5 14.11 1M1 8.5 16.18 1 M2 8.5 36.77 TOR 8.5 39.38 BOR 1.33 45.35 505 -5.0 48.14 TEST 0.0 49.21 250.0 506 8.5 5.6 11.55 19.03 0.15 112 507 8.5 5.6 10.45 18.1 0.15 118 508 8.5 11.18 509 8.5 5.6 11.4 18.91 0.15 112 510 8.5 5.6 12.2 19.56 0.15 112 511 8.5 5.6 11.26 18.79 0.15 117 512 8.5 12.61 513 8.5 5.6 11.46 18.96 0.15 117 514 8.5 5.6 11.69 19.15 0.15 117 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 6 500625593 SP MAHI MAHI CRISTELLE CAY Date 09.14.2021 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 501 8.5 5.60 19.20 1.25 9.330 120 11.755 to 0.0 502 8.5 19.2 1.442 9.330 0.0256 0.239 Vel = 3.77 502 8.5 5.60 19.39 1.25 T 7.432 2.670 120 11.994 to 7.432 0.0 503 8.5 38.59 1.442 10.102 0.0932 0.942 Vel = 7.58 503 8.5 75.93 2 12.000 120 12.936 to 0.0 504 8.5 114.52 2.157 12.000 0.0981 1.177 Vel = 10.05 504 8.5 56.58 2 10.040 120 14.113 to 0.0 1M1 8.5 171.1 2.157 10.040 0.2063 2.071 Vel = 15.02 1M1 8.5 0.0 2 T 12.307 87.540 120 16.184 to 12.307 0.0 1 M2 8.5 171.1 2.157 99.847 0.2062 20.589 Vel = 15.02 1 M2 8.5 0.0 2.5 E 8.237 25.340 120 36.773 to 8.237 0.0 TOR 8.5 171.1 2.635 33.577 0.0778 2.612 Vel = 10.07 TOR 8.5 0.0 2.5 2E 16.474 20.340 120 39.385 to 16.474 3.105 BOR 1.33 171.1 2.635 36.814 0.0778 2.864 Vel = 10.07 BOR 1.33 0.0 4 6.330 120 45.354 to 2.742 505 -5 171.1 4.26 6.330 0.0074 0.047 Vel = 3.85 505 -5 0.0 4 4E 63.728 100.000 150 48.143 to G 3.186 98.779 -0.166 * * Fixed Loss = 2 TEST 0 171.1 4.07 T 31.864 198.779 0.0062 1.232 Vel = 4.22 Zaf 0.0 250.00 Qa = 250.00 TEST 421.10 49.209 K Factor = 60.03 506 8.5 5.60 19.03 1 T 5.0 6.670 120 11.550 to 5.000 0.0 503 8.5 19.03 1.049 11.670 0.1188 1.386 Vel = 7.06 0.0 503 19.03 12.936 K Factor = 5.29 507 8.5 5.60 18.10 1 T 5.0 1.750 120 10.452 to 5.000 0.0 508 8.5 18.1 1.049 6.750 0.1083 0.731 Vel = 6.72 508 8.5 0.0 1.25 9.330 120 11.183 to 0.0 509 8.5 18.1 1.442 9.330 0.0230 0.215 Vel = 3.56 509 8.5 5.60 18.91 1.25 9.330 120 11.398 to 0.0 510 8.5 37.01 1.442 9.330 0.0863 0.805 Vel = 7.27 510 8.5 5.60 19.56 1.25 T 7.432 2.670 120 12.203 to 7.432 0.0 504 8.5 56.57 1.442 10.102 0.1891 1.910 Vel = 11.11 0.0 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 7 500625593 SP MAHI MAHI CRISTELLE CAY Date 09.14.2021 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ' `**'** Notes Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 504 56.57 14.113 K Factor = 15.06 511 8.5 5.60 18.79 1 T 5.0 6.670 120 11.260 to 5.000 0.0 512 8.5 18.79 1.049 11.670 0.1159 1.353 Vel = 6.98 512 8.5 38.11 2 12.000 120 12.613 to 0.0 503 8.5 56.9 2.157 12.000 0.0269 0.323 Vel = 5.00 0.0 503 56.90 12.936 K Factor = 15.82 513 8.5 5.60 18.96 1.25 9.330 120 11.460 to 0.0 514 8.5 18.96 1.442 9.330 0.0250 0.233 Vel = 3.72 514 8.5 5.60 19.15 1.25 T 7.432 2.670 120 11.693 to 7.432 0.0 512 8.5 38.11 1.442 10.102 0.0911 0.920 Vel = 7.49 0.0 512 38.11 12.613 K Factor = 10.73 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Commercial ADT COMMERCIAL 3150 SW 42ND AVE. PALM CITY, FL. 34990 772.232.2001 Job Name 500625593 SP MAHI MAHI CRISTELLE CAY Drawing MAHI MAHI Location UNIT 20 Remote Area 4 Contract 500625593 Data File 2ND FLR MAHI MAHI CRISTELLE CAY Area 4.WXF Computer Programs by Hydratec Inc. Revision: 50.5520.727 ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 1 Date 09.14.2021 HYDRAULIC DESIGN INFORMATION SHEET Name - CRISTELLE CAY Date - 09.14.2021 Location - UNIT 2G Building - MAHI MAHI System No. - 4 Contractor - ADTC Contract No. - 500625593 Calculated By - JPC Drawing No. - FP3 Construction: ( ) Combustible (X) Non -Combustible Ceiling Height OCCUPANCY - 13R S Y S T E M D E S I G N Type of Calculation: ( )NFPA 13 Residential (X)NFPA 13R ( )NFPA 13D Number of Sprinklers Flowing: ( )l ( )2 (X)4 ( ) ( )Other ( )Specific Ruling Made by Date Listed Flow at Start Point - 16 Gpm System Type Listed Pres. at Start Point - 13.3 Psi (X) Wet ( ) Dry MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction Domestic Flow Added - Gpm Sprinkler or Nozzle Additional Flow Added - Gpm Make RELIABLE Model R3531 Elevation at Highest Outlet - 18111"Feet Size 1/2 K-Factor 4.4 Note: Temperature Rating 155 Calculation Gpm Required 163.386 Psi Required 57.221 At Test Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: A Date of Test - T Time of Test - E Static (Psi) - 62 R Residual (Psi) - 40 Flow (Gpm) - 1000 S Elevation - 0 P Location: P L Source of Information: Y Pump Data: Tank or Reservoir: Rated Cap. Cap. @ Psi Elev. Elev. Other Well Proof Flow Gpm Computer Programs by Hydratec Inc. Revision: 50.5520.727 Water Supply Curve ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 2 Date 09.14.2021 City Water Supply: Demand: C1 - Static Pressure : 62 D1 - Elevation 8.047 C2 - Residual Pressure: 40 D2 - System Flow : 63.386 C2 - Residual Flow 1000 D2 - System Pressure 57.221 Hose ( Demand ) :100 D3 - System Demand : 163.386 Safety Margin 4.008 150 140 130 P 120 R 110 E 100 S 90 S 80 u 70 C1 R 60 E 50 3 40 30 20 10 D1 100 200 300 400 500 600 700 800 900 FLOW N^1.85) C2 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Diagram ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 3 Date 09.14.2021 15.6 63.4 63.4 63.4 63.4 63.4 401 F 402 F 403 F 404 F 2M1.(- 2M2+- 405 F 2M3<- RSR42- SP2<-. SPBf-. TEST 31.3 63.4 63.4 63.4 63.4 15.7 406 +- 402 16 407 F 408 *-. 403 32.1 16 409 <--. 408 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Fittings Used Summary ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 4 Date 09.14.2021 Fitting Legend Abbrev. Name '/2 '/ 1 1 % 1'/ 2 21/ 3 31/ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zaf Ames 3000SS Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.5520.727 Flow Summary - NFPA ADT COMMERCIAL 500625593 SP MAHI MAHI CRISTELLE CAY Page 5 Date 09.14.2021 SUPPLYANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 62.0 40 1000.0 61.229 163.39 57.221 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 401 18.58 4.4 12.5 15.56 0.05 144 402 18.92 13.26 403 18.92 16.35 404 18.92 21.74 2M1 18.92 27.28 2M2 18.92 31.03 405 18.92 35.09 2M3 18.92 35.68 RS R2 18.92 42.58 SP2 18.92 43.87 SPB -5.0 54.26 TEST 0.0 57.22 100.0 406 18.58 4.4 12.79 15.74 0.05 144 407 18.58 4.4 13.3 16.05 0.05 256 408 18.58 13.32 409 18.58 4.4 13.3 16.05 0.05 196 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 6 500625593 SP MAHI MAHI CRISTELLE CAY Date 09.14.2021 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 401 18.58 4.40 15.56 1 3E 11.475 9.670 150 12.501 to 11.475 -0.147 402 18.92 15.56 1.101 21.145 0.0427 0.903 Vel = 5.24 402 18.92 15.73 1 2E 7.65 12.210 150 13.257 to 7.650 0.0 403 18.92 31.29 1.101 19.860 0.1558 3.094 Vel = 10.54 403 18.92 32.10 1.25 E 4.762 15.290 150 16.351 to T 9.523 14.284 0.0 404 18.92 63.39 1.394 29.574 0.1822 5.387 Vel = 13.33 404 18.92 0.0 1.5 4E 23.312 35.870 150 21.738 to 23.312 0.0 2M1 18.92 63.39 1.598 59.182 0.0937 5.544 Vel = 10.14 2M1 18.92 0.0 1.5 40.000 150 27.282 to 0.0 2M2 18.92 63.39 1.598 40.000 0.0937 3.748 Vel = 10.14 2M2 18.92 0.0 1.5 2E 11.656 31.720 150 31.030 to 11.656 0.0 405 18.92 63.39 1.598 43.376 0.0937 4.063 Vel = 10.14 405 18.92 0.0 1.5 6.250 150 35.093 to 0.0 2M3 18.92 63.39 1.598 6.250 0.0936 0.585 Vel = 10.14 2M3 18.92 0.0 1.5 T 11.656 32.870 150 35.678 to 5E 29.14 40.796 0.0 RSR2 18.92 63.39 1.598 73.666 0.0937 6.901 Vel = 10.14 RSR2 18.92 0.0 1.5 2E 9.9 1.830 120 42.579 to 9.900 0.0 SP2 18.92 63.39 1.682 11.730 0.1103 1.294 Vel = 9.15 SP2 18.92 0.0 4 23.920 120 43.873 to 10.360 SPB -5 63.39 4.26 23.920 0.0012 0.029 Vel = 1.43 SPB -5 0.0 4 4E 63.728 100.000 150 54.262 to G 3.186 98.779 2.764 * * Fixed Loss = 4.929 TEST 0 63.39 4.07 T 31.864 198.779 0.0010 0.195 Vel = 1.56 Zaf 0.0 100.00 Qa = 100.00 TEST 163.39 57.221 K Factor = 21.60 406 18.58 4.40 15.74 1 E 3.825 0.660 150 12.791 to T 9.563 13.387 -0.147 402 18.92 15.74 1.101 14.047 0.0436 0.613 Vel = 5.30 0.0 402 15.74 13.257 K Factor = 4.32 407 18.58 4.40 16.05 1 0.500 150 13.300 to 0.0 408 18.58 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 408 18.58 16.04 1 2T 19.125 0.330 150 13.323 to 19.126 -0.147 403 18.92 32.09 1.101 19.456 0.1632 3.175 Vel = 10.81 0.0 Computer Programs by Hydratec Inc. Revision: 50.5520.727 Final Calculations: Hazen -Williams ADT COMMERCIAL Page 7 500625593 SP MAHI MAHI CRISTELLE CAY Date 09.14.2021 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe *`**'** Notes Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 403 32.09 16.351 K Factor = 7.94 409 18.58 4.40 16.05 1 0.500 150 13.300 to 0.0 408 18.58 16.05 1.101 0.500 0.0460 0.023 Vel = 5.41 0.0 408 16.05 13.323 K Factor = 4.40 Computer Programs by Hydratec Inc. Revision: 50.5520.727