HomeMy WebLinkAboutCreekside Lot 7 blower door and duct blast.pdfDuct Leakage Test Report
Prescriptive or Performance Method
Permit #
Job information
Builder; DR HORTON
Community: CREEKSIDE Lot: 7
Address: 3323 HOMESTEAD DRIVE Unit:
City: FORT PIERCE
State: FL zip: 34945
Duct Leakage Test Results
. Presciptive Method 0 Performance Method
System 1 cfm25 (94rescriptive Method cfm25 (total)
To qualify as "substantially leak free" Qn must be less than or equal to 0.04
System 2 cfm25 if air handler unit is installed. If air handler unit is not installed, Qn Total
must be less than or equal to 0.03. This testing method meets the
System 3 cfm25 requirements in accordance with Section R403.2.2
Sum of any additional
systems cfm25
Total of all systems 0Performance Method cfm25 (Out or Total)
cfm25 To qualify as "substantially leak free" Qn must not be greater than the
proposed duct leakage Qn specified on Form R405-2014
62 _ 2605 = 0.02 Qn
Total of all systems
PASS
Testing Company
Total Conditioned
Square Footage
L�! FAIL
Leakage Type selected
on Form R405-2014
(Energy Calc)
Qn specified on Form
R405-2014 (Energy Catc)
Company Name: SUN SEAL LLC Phone: 321-412-0035
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 03/22/2022
Signature of Tester:' 4 A in �r2,fa%fi
Printed Name of Tester: DANIEL MURPHY
License/Certification # 5066440 issuing Authority
N Envelope Leakage Test Report
(Blower Door Test)
R405.4.2.1 Compliance
Fermit #
Job information
Builder: DR HORTON Community:
CREEKSIDE Lot: 7
Address: 3323 HOMESTEAD DRIVE
Unit:
City: FORT PIERCE
State: FL Zip_ 34945
Air Leakage Test Results Passing results must be 7ACH(50) or less
1517 x 60 _ 22403.2 = 4.0
Method for calculating building volume:
CFM(50) Building Volume ACH(50)
O Retrieved from architectural plans
Code software calculated
PASS FAIL
Q Field measured and calculated
g When ACH(50) is less than 3, Mechanical
Ventilation installation must be verified by building department.
I ...�
Certification of Test Results
R402.4.1.2 Testing. The building or dwelling unit shau be tested and vermea as having an air IeaKage race VI IIVt eXCeeUlll6 i all a eal Igw
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of
all penetrations of the building thermal envelope.
Testing Company
Company Name: SUN SEAL LLC Phone: 321-412-0035
1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test: 03/22/2022
Signature of Tester: l
t
Printed Name of Tester: DANIEL MURPH`f
License/Certification # 5066440 Issuing Authority BPI