HomeMy WebLinkAboutEnvelope Leakage Test ReportEnvelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction:
Permit #:
Job Information
Builder: Express Homes Community: Lot: NA
Address:
City: FORT PIERCE State: FL Zip:
Air Leakage Test R@SUItS Passing results must meet either the Performance, Prescriptive, orERl Method .
PRESCRIPTIVE METHOD=The building or dwelling unit shall ,be.tested,and verified as having an air leakage rate of not exceeding 7 air
changes-per'hour at a pressure of 0:2,inchm.g. (50 Pascals) in;Climate Zones 1 and'2.
O PERFORMANCE or ERI METHOD The building or dwelling unit shall -be tested and•verified as having an air leakage rate of riot exceeding
the selected ACH(50) value, as shown on Foim R405-2020 (Performance) or R406-2020 (ERI), section labeled as_infiltrati.on,, sub -section ACH50.
ACH(50) specified'on Form R405-2020-Energy Calc (Performance) or'R406-2020 (ERI): 7.000
x 60 _ 14379 = Method for calculating building volume:
CFM(50) Building Volume ACH(50) O Retrieved from architectural plans
1-1PASS Code
0 software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(0, (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
3/25/2021 3:19:14 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Dui t Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
I Jurisdiction:
Job Inforrhation
Builder: Express Homes
Address:
City: FORT PIERCE
Duct Leakage Test A(
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of others
cfm25
Total of all
cfm25
1672 = Qn
Total of all Total Conditioned
systems Square Footage
1:1
PASS 1:1 FAIL
Community:
Permit #.
State: FL
Lot: NA
Zip:
Q Prescriptive Method cfm25 (Total)
'to qualify as "substantially leak'free'Qn Total must be less than or
equal,to:0.0.4 if air handler unit is. installed. If air handler unit is not,
installed,, Qn Total•:rnust be less than or equal to 0.03. This testing
method meet§ the requirements in accordance°with Section -R403.3.3.
Is the air handler'unitinstalled dunng,i6&hg?-`` 2YES (s0. D - ( N0: sc)i
0. Perforinance/ERI Method cfm25 (Out or Total)
To qualify using this -method, Qn must not,be greater than the
Leakage Type.selected.on Form
Proposed Qn 0.07
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes.
Testing •Company -
Company Name: Phone:
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method -or Performance Method.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
8/25/2021 3:19:17 PM Page 1 of 1