HomeMy WebLinkAboutAPPROVED, Underlayment FL19321 CREEK
Technical Services, LLC
SWI15001.2 FL19321-R2 Page 1 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
(813) 480-3421
EVALUATION REPORT FLORIDA BUILDING CODE 7TH EDITION (2020)
Manufacturer: STARWRAP INC Issued September 10, 2020
7324 Southwest Freeway, Suite 1440
Houston, TX 77074
(832) 742-8821
www.starwrapinc.com
Manufacturing Locations: Hebei, China
Quality Assurance: Intertek Testing Services NA Inc. (QUA1673)
SCOPE
Category: Roofing
Subcategory: Underlayments
Code Sections: 1507.1.1
Properties: Physical properties
REFERENCES
Entity Report No. Standard Year
Intertek Testing Services NA Ltd. (TST1509) 141128020SHJ-BP-1 ICC-ES AC 188 2012
Intertek Testing Services NA, Inc. (VAL1616) CCRR-1038 ICC-ES AC 188
ASTM D 226
2012
2009
PRI Construction Materials Technologies (TST5878) STRW-001-02-02 ASTM D 4533 2015
PRI Construction Materials Technologies (TST5878) 2109T0001 ASTM D 5035 2011(2019)
PRODUCT DESCRIPTION
20 LBS/roll Synthetic
Roofing Underlayment
A mechanically attached, synthetic underlayment consisting of three (3) layers: woven
scrim, bottom lamination and surface lamination; used an alternative to ASTM D 226,
Type II roofing underlayments with a minimum tear strength per ASTM D 4533 of 15
pounds, a minimum tensile strength per ASTM D 5035 of 20 pounds/inch, and meets
liquid water transmission test of Section 8.6 of ASTM D 4869. The roll is available in 48-
inch wide x 250-ft long format and has an overall weight of 20 lb/roll.
23 LBS/roll Synthetic
Roofing Underlayment
A mechanically attached, synthetic underlayment consisting of four (4) layers: grey non-
woven scrim, woven scrim, bottom lamination and surface lamination; used an
alternative to ASTM D 226, Type II roofing underlayments with a minimum tear strength
per ASTM D 4533 of 15 pounds, a minimum tensile strength per ASTM D 5035 of 20
pounds/inch, and meets liquid water transmission test of Section 8.6 of ASTM D 4869.
The roll is available in 48-inch wide x 250-ft long format and has an overall weight of 23
lb/roll.
30 LBS/roll Synthetic
Roofing Underlayment
A mechanically attached, synthetic underlayment consisting of four (4) layers: grey non-
woven scrim, woven scrim, bottom lamination and surface lamination; used an
alternative to ASTM D 226, Type II roofing underlayments with a minimum tear strength
per ASTM D 4533 of 15 pounds, a minimum tensile strength per ASTM D 5035 of 20
pounds/inch, and meets liquid water transmission test of Section 8.6 of ASTM D 4869.
The roll is available in 48-inch wide x 250-ft long format and has an overall weight of 30
lb/roll.
A CREEK
Technical Services, LLC
SWI15001.2 FL19321-R2 Page 2 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
STARWRAP INC.
Synthetic Underlayments
APPLICATION INSTRUCTIONS
Deck Type: The roof deck shall be constructed of closely fitted, solid sheathing for new or existing
construction. Sheathing shall be installed in accordance with FBC requirements. Roof
decks shall have no more than 1/8” gap at abutting joints.
Min. slope: In accordance with FBC requirements.
Attachment method: Underlayment shall be attached in accordance with the FBC and manufacturer’s
installation instructions. The underlayment is installed starting at the eave, with the
length of the roll parallel to the eave with the printed side facing up. All side laps shall be
installed to shed water from the deck. End laps shall be staggered between courses in
accordance with the manufacturer’s application instructions. Minimum application
temperature shall be 50°F.
Allowable roof coverings: In accordance with FBC requirements.
LIMITATIONS
1) This evaluation report is not for use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance is not within the scope of this evaluation.
4) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer’s published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) Contact the manufacturer when installing at temperatures below the minimum application temperature.
7) The underlayment may be used as described in other current FBC product approval documents.
8) Roof coverings shall not be adhered directly to the underlayment. Roof coverings shall be mechanically
fastened through the underlayment to the roof deck.
9) The underlayment shall be exposed on the roof deck for a maximum 30 days unless otherwise stated.
10) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
A CREEK
Technical Services, LLC
SWI15001.2 FL19321-R2 Page 3 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
STARWRAP INC.
Synthetic Underlayments
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code 7th Edition (2020) as evidenced in the referenced documents submitted by the named manufacturer.
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this
evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product.
END OF REPORT
2020.09.10
15:30:56
-04'00'