ENERGY CALCS & MANUAL J - 10 VISTA DE LAGUNA
FORM R405-2020 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method ProjectName: GEMINI IMPACT BuilderName: WYNNE BUILDING CORP. Street: Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, PermitNumber: Owner: Jurisdiction: Design Location: FL, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing New (From Plans) 10. Wall Types(1763.8 sgft.) Insulation Area 2. Single family or multiple family Detached a. Concrete Block - Int Insul, Exterior R=4.1 1507.80 ft2 3. Number of units, if multiple family 1 b. Frame- Wood, Adjacent c. N/A R=11.0 256.00 ft2 R= ft2 4. Number of Bedrooms 2 d. N/A R= ft2 5. Is this a worst case? Yes 11. Ceiling Types (1839.0 sqft.) Insulation Area a. UnderAttic (Vented) R=30.0 1839.00 ft2 6. Conditioned floor area above grade (ft2) 1839 b. N/A R= ft2 Conditioned floorarea belowgrade (ft2) 0 c. N/A R= ft2 7. Windows(155.3 sqft.) Description Area 12. Ducts R ft2 a. U-Factor: Sgl, U=1.02 115.28 ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 125 SHGC: SHGC=0.27 b. U-Factor: Sgl, U=1.11 40.00 ft2 13. Cooling systems kBtu/hr Efficiency SHGC: SHGC=0.27 a. Central Unit 34.8 SEER:15.00 c. U-Factor: N/A ft2 SHGC: Area Weighted Average Overhang Depth: 3.318 ft. 14. Heating systems kBtu/hr Efficiency Area Weighted Average SHGC: 0.270 a. Electric Heat Pump 34.8 HSPF:8.50 8. Skylights Area c. U-Factor:(AVG) N/A ft2 15. Hot water systems SHGC(AVG): N/A a. Electric Cap:40 gallons 9. Floor Types (1839.0 sqft.) Insulation Area EF:0.950 a. Slab -On -Grade Edge Insulation R=0.0 1839.00 ft2 b. Conservation features b. N/A R= ft. None c. N/A R= ft2 16. Credits None Glass/Floor Area: 0.084 Total Proposed Modified Loads: 51.52 PASS Total Baseline Loads: 52.96 I hereby certify that the plans and specifications covered by Review of the plans and this calculation are in compliance with the Florida Energy specifications covered by this Code. calculation indicates compliance with the Florida Energy Code. ni y: , ;�O PREPARED BY: Before construction is completed 8 DATE: 1-1 -2 21 this building will be inspected for - - compliance with Section 553.908 I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Cod -- ^0 WE, OWNER/APANT: BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). 1 /13/2021 7:44 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT PROJECT Title: GEMINI IMPACT Bedrooms: 2 Address Type: StreetAddress Building Type: User ConditionedArea: 1839 Lot# OwnerName: Total Stories: 1 Block/Subdivision: # of Units: 1 Worst Case: Yes PlatBook: BuilderName: WYNNE BUILDING CORP. RotateAngle: 270 Street: Permit Office: ST. LUCIE COUNTY CrossVentilation: No County: St. Lucie Jurisdiction: Whole House Fan: No City, State, Zip: FT. PIERCE, FamilyType: Detached FL, New/Existing: New (From Plans) Comment: CLIMATE / V DesignLocation DesignTemp TMY Site 97.5 % 2.5 % Int Design Temp Heating Design Winter Summer Degree Days Moisture DailyTemp Range FL, Fort Pierce FL_VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 1839 14712 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 BEDROOM 343 2744 No 0 1 1 Yes Yes Yes 2 WIC 63 504 No 0 1 No Yes Yes 3 M.BATH 56 448 No 0 1 Yes Yes Yes 4 KITCHEN 172 1376 Yes 0 1 No Yes Yes 5 MASTER BEDROO 256 2048 No 0 1 1 Yes Yes Yes 6 ENTRY 83 664 No 0 1 Yes Yes Yes 7 LAUNDRY 42 336 No 0 1 Yes Yes Yes 8 GREAT/DINING 568 4544 No 0 1 Yes Yes Yes 9 CLOSET 2 56 448 No 0 1 No Yes Yes 10 BATH 2 48 384 No 0 1 Yes Yes Yes 11 POWDER 42 336 No 0 1 No Yes Yes 12 SITTING ROOM 110 880 No 0 1 Yes Yes Yes FLOORS # FloorType Space Perimeter PerimeterR-Value Area JoistR-Value Tile Wood Carpet 1 Slab -On -Grade Edge Insulation BEDROOM 43 ft 0 343 ftz ---- 0 1 0 2Slab-On-Grade Edge Insulation WIC 1 ft 0 63ft2 ---- 0 1 0 3 Slab -On -Grade Edge Insulation M. BATH 8 ft 0 56 ftz ---- 0 1 0 4Slab-On-Grade Edge Insulation KITCHEN 1 ft 0 172ft2 ---- 0 1 0 5Slab-On-Grade Edge Insulation MASTER BEDRO 51 ft 0 256 ftz ---- 0 1 0 1/13/2021 7:44 AM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 6 FORM R405-2020 INPUT SUMMARY C14FCKI I-RT RFPnRT FLOORS # FloorType Space Perimeter PerimeterR-Value Area JoistR-Value Tile Wood Carpet 6 Slab -On -Grade Edge Insulation ENTRY 7 ft 0 83 ft2 ---- 0 1 0 7Slab-On-Grade Edge Insulation LAUNDRY 6ft 0 42ft2 ---- 0 1 0 8Slab-On-Grade Edge Insulation GREAT/DINING 39ft 0 568ft2 ---- 0 1 0 9 Slab -On -Grade Edge Insulation CLOSET 2 1 ft 0 56 ft2 ---- 0 1 0 10SIab-On-Grade Edge Insulation BATH 2 8 ft 0 48 ft2 ---- 0 1 0 11Slab-On-Grade Edge Insulation POWDER 1 ft 0 42ft2 ---- 0 1 0 12SIab-On-Grade Edge Insulation SITTING ROOM 22ft 0 110ft2 ---- 0 1 0 ROOF / Roof Gable Roof Rad Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Barr Absor. Tested Tested Insul. (deg) 1 Hip Metal 1938 ft2 0 ft2 Light N 0.6 No 0.7 No 0 18.43 ATTIC / V Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 150 1839 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 UnderAttic(Vented) BEDROOM 30 Blown 343ft2 0.1 Wood 2 UnderAttic(Vented) WIC 30 Blown 63ft2 0.1 Wood 3 Under Attic (Vented) M. BATH 30 Blown 56 ft2 0.1 Wood 4 UnderAttic(Vented) KITCHEN 30 Blown 172ft2 0.1 Wood 5 UnderAttic(Vented) MASTER BEDRO 30 Blown 256ft2 0.1 Wood 6 Under Attic (Vented) ENTRY 30 Blown 83ft2 0.1 Wood 7 UnderAttic(Vented) LAUNDRY 30 Blown 42ft2 0.1 Wood 8 UnderAttic(Vented) GREAT/DINING 30 Blown 568ft2 0.1 Wood 9 UnderAttic (Vented) CLOSET 2 30 Blown 56 ft2 0.1 Wood 10 UnderAttic (Vented) BATH 2 30 Blown 48 ft2 0.1 Wood 11 Under Attic (Vented) POWDER 30 Blown 42ft2 0.1 Wood 12 UnderAttic(Vented) SITTING ROOM 30 Blown 110ft2 0.1 Wood WALLS Adjacent Space Cavity Width RA/ableD Height Sheathing Framing Solar Below _ 1 S=>E Exterior Concrete Block- Int Insul BEDROOM 4.1 29 0 8 0 232.0 ft2 0 0 0.4 0 _ 2 W=>S Exterior Concrete Block - Int Insul BEDROOM 4.1 14 0 8 0 112.0 ft2 0 0 0.4 0 _ 3 S=>E Exterior Concrete Block- Int Insul M. BATH 4.1 8 0 8 0 64.0 ft2 0 0 0.4 0 4 N=>W Exterior Concrete Block - Int InsuMASTER BE 4.1 24 0 8 0 192.0 ft2 0 0 0.4 0 1/13/2021 7:44 AM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 6 FORM R405-2020 INPl1T Al IMMARV r141=r1C1 VZT 1011=onOT WALLS Adjacent Space Cavity Width - Height Sheathing Framing Solar Below o 5 E=>N Exterior Concrete Block - Int InsuMASTER BE 4.1 13 0 8 0 104.0 ft2 0 0 0.4 0 _ 6 S=>E Exterior Concrete Block - Int InsuMASTER BE 4.1 14 0 8 0 112.0 ft2 0 0 0.4 0 _ 7 E=>N Exterior Concrete Block- Int Insul ENTRY 4.1 6 0 8 0 48.0 ft2 0 0 0.4 0 8 S=>E Exterior Concrete Block- Int Insul ENTRY 4.1 1 0 8 0 8.0 ft2 0 0 0.4 0 9 S=>E Exterior Concrete Block- Int Insul LAUNDRY 4.1 6 0 8 0 48.0 ft2 0 0 0.4 0 10 N=>W Exterior Concrete Block- Int InsuIGREAT/DINT 4.1 30 0 8 11 267.5 ft2 0 0 0.4 0 11 W=>S Exterior Concrete Block - Int InsulGREAT/DINT 4.1 9 0 8 11 80.3 ft2 0 0 0.4 0 _ 12 N=>W Exterior Concrete Block- Int Insul BATH 2 4.1 8 0 8 0 64.0 ft2 0 0 0.4 0 13 N=>W Exterior Concrete Block - Int InsuBITTING RO 4.1 10 0 8 0 80.0 ft2 0 0 0.4 0 14 S=>E Exterior Concrete Block- Int InsuSITTING RO 4.1 1 0 8 0 8.0 ft2 0 0 0.4 0 15 W=>S Exterior Concrete Block- Int InsuSITTING RO 4.1 11 0 8 0 88.0 ft2 0 0 0.4 0 _16 N=>W Garage Frame -Wood KITCHEN 11 32 8 256.0ft2 0.23 0.4 0 DOORS # Ornt DoorType Space Storms U-Value Width Height Area Ft In Ft In 1 E=>N Insulated ENTRY None .32 3 6 8 20 ft2 WINDOWS Orientation shown is the entered orientation => changed to Worst Case. V Wall Overhang # Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation IntShade Screening 1 W=>S 2 Metal Low-ESingle Yes 1.02 0.27 Y 32.4 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds Exterior5 2 S=>E 3 Metal Low-ESingle Yes 1.02 0.27 Y 6.9 ft2 1 ft 0 in 1 ft 4 in None None 3 E=>N 5 Metal Low-ESingle Yes 1.02 0.27 Y 32.4 ft2 1 ft 0 in 1 ft 4 in None None 4 N=>W 10 Metal Low-ESingle Yes 1.02 0.27 Y 18.4 ft2 1 ft 0 in 1 ft 4 in None None 5 W=>S 11 Metal Low-ESingle Yes 1.11 0.27 Y 40.0 ft2 10 ft 0 in 1 ft 4 in None None 6 N=>W 12 Metal Low-ESingle Yes 1.02 0.27 Y 6.9 ft2 1 ft 0 in 1 ft 4 in None None 7 W=>S 15 Metal Low-ESingle Yes 1.02 0.27 Y 18.4 ft2 1 ft 0 in 1 ft 4 in None None GARAGE # FloorArea CeilingArea Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation 1 320 ft2 320 ft2 32 ft 8 ft 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse ProposedACH(50) .000254 1226 67.26 126.28 .0902 5 1/13/2021 7:44 AM 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPnRT HEATING SYSTEM # System Type Subtype Speed Efficiency Capacity Block Ducts 1 Electric Heat Pump/ Split Single HSPF:8.5 34.8 kBtu/hr 1 sys#1 COOLING SYSTEM # System Type Subtype Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 CentralUnit/ Split Single SEER:15 34.8 kBtu/hr cfm 0.85 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Garage 0.95 40 gal 60.9 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # CompanyName System Model# CollectorModel# Area Volume FEF None None ft2 DUCTS --- Supply---- V ---- Return ---- Air CFM 25 CFM25 HVAC # # Location R-Value Area Location Area LeakageType Handler TOT OUT QN RLF Heat Cool 1 Attic 6 125 ft2 Attic 40 ft2 DefaultLeakage Attic (Default) c(Default) c 1 1 TEMPERATURES ProgramableThermostat: N Ceiling Fans: CoolingJan Feb HeatinJan Feb Mar HX Mar Apr Apr Ma Jun Jul MaY [�Jun Jul Auge Au[ Sep Oct Nov Oct ] Nov Dec Dec Ventin Jan Feb Mar [X] Apr May [ Jun Jul Aug [ ] Se [X] Oct [X] Nov Dec ThermostatSchedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8lbs/sq.ft. 0 ft2 0 ft 0.3 BEDROOM Default(81bs/sq.ft. ft2 ft 0.3 WIC Default(8lbs/sq.ft. ft2 ft 0.3 M. BATH Default(81bs/sq.ft. ft2 ft 0.3 KITCHEN Default(8lbs/sq.ft. ft2 ft 0.3 MASTER BEDROO Default(8 Ibs/sq.ft. ft2 ft 0.3 ENTRY Default(8lbs/sq.ft. ft2 ft 0.3 LAUNDRY Default(8lbs/sq.ft. ft2 ft 0.3 GREAT/DINING 1/13/2021 7:44 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT MASS Mass Type Area Thickness Furniture Fraction Space Default(8lbs/sq.ft. ft2 ft 0.3 CLOSET 2 Default(8lbs/sq.ft. ft2 It 0.3 BATH 2 Default(8 Ibs/sq.ft. ft2 ft 0.3 POWDER Default 8lbs/s .ft. ft2 ft 0.3 SITTING ROOM 1/13/2021 7:44 AM 7.0.00- FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 6 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: GEMINI IMPACT Builder Name: WYNNE BUILDING CORP. Street: Permit Office: ST. LUCIE COUNTY City, State, Zip: FT. PIERCE, FL, Permit Number: Y Owner: Jurisdiction: w Design Location: FL, Fort Pierce U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealingmaterial. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned s ace shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be airtight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind pepano and wir 9 no. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids o V vier ylates and walls or ceilincis. a. ni auwtio i, inspection u, lug walls sndu ue in duuumance wan the provisions oT JUU-41JU. 1/13/2021 7:45 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 97 The lower the EnergyPerformance Index, the more efficient the home. 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area (ft2) 7. Windows- Description a. U-Factor: Sgl, U=1.02 SHGC: SHGC=0.27 b. U-Factor: Sgt, U=1.11 SHGC: SHGC=0.27 c. U-Factor: N/A SHGC: d. U-Factor: N/A SHGC: Area Weighted Average Overhang Depth: Area Weighted Average SHGC: 8. Skylights Description a. U-Factor(AVG): N/A SHGC(AVG): N/A , FT. PIERCE, FL, New (From Plans) 10. Wall Type and Insulation Insulation Area Detached a. Concrete Block - Int Insul, Exterior R=4.1 1507.80 ft2 b. Frame - Wood, Adjacent R=11.0 256.00 ft2 1 c. N/A R= ft2 2 d. N/A R= ft2 Yes 11. Ceiling Type and insulation level Insulation Area a. Under Attic (Vented) R=30.0 1839.00 ft2 1839 b. N/A R= ft2 Area c. N/A R= ft2 115.28 ft2 12. Ducts, location & insulation level R ft2 a. Sup: Attic, Ret: Attic, AH: Attic 6 125 40.00 ft2 13. Cooling systems kBtu/hr Efficiency ft2 a. Central Unit 34.8 SEER:15.00 ft2 3.318 ft. 0.270 Area ft2 9. Floor Types Insulation Area a. Slab -On -Grade Edge Insulation R=0.0 1839.00 ft2 b. N/A R= ft2 c. N/A R= ft2 14. Heating systems a. Electric Heat Pump 15. Hot water systems a. Electric b. Conservation features None Credits (Performance method) I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature: Date: Address of New Home: City/FL Zip: ` �S kBtu/hr Efficiency 34.8 HSPF:8.50 Cap: 40 gallons EF: 0.95 None *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 1/13/2021 7:45 AM 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Project Summary Job: wrightsoft® Date; `Ent re House y QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email: QUICKCALCS AOL.COM Project• • For: THE GEMINI WYNNE DEV., FT. PIERCE, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 21011 Btuh Structure 19448 Btuh Ducts 6289 Central vent (0 cfm) 0 Btuh Btuh Ducts Central vent (0 cfm) 9502 0 Btuh Btuh none Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 27300 Btuh Use manufacturer's data n Infiltration Rate/swingg multipplier Equipmentsensible 0.95 load 27502 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2170 Btuh Ducts 2590 Btuh Central vent (0 cfm) Btuh Heating Area Cooling (none) (ftz) 1839 1839 Equipment latent load 4768 Btuh Volume (ft3) 15562 15562 Airchanges/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 32271 Btuh Equiv. AVF (cfrr) 99 52 Req. total capacity at 0.70 SHR 3.3 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIERAIR CONDITIONING Model 25HBC536A O30 AHRI ref 7914585 Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat Capacity balance point = 36 OF 8.5 HSPF 34600 Btuh @ 47°F 27 0 1160 cfm 0.042 cfm/Btuh 0.50 in H2O Innpuutt =p7 kW, Output = 23009 Btuh,100 AFUE Make Carrier Trade CARRIERAIR CONDITIONING Cond 25HBC536A O30 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 12.0 EER,15 SEER Sensible cooling 24360 Btuh Latent000ling 10440 Btuh Total cooling 34800 Btuh Actual airflow 1160 c(m Airflow factor 0.040 cf-n/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0.86 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. =t wrightsoft® 2021-Jan-1307:44:09 �� Right-Stite®Uriversa1201919.021 RSU08101 Page 1 UICK\Docunerks\WdghtwftHVAC\WYNNE-GEMINI.rLp Calc=MJ8 FrontDoortoes: N -9- wrightsoftRight-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS(aAOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 212.0 It 8.5 ft d 1839.0 fF MASTER BEDROOM 43.0 ft 8.0 ft heat/cool 1.0 x 343.0 It 343.0 ft2 Ty Construction number U-value (Btuh/ft -°F) Or HTM (Btuh/F) Area (ft) or perimeter (ft) Load (Btuh) orsperimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 VI/ 13A-4ocs 1A-c1om 4A5-tom ocs 1Ac1om13Afl 11D0 13AAocs IA-c1om 13AAocs 1A-c1om 4A5-2om 4A5-2ovd 12C-Osw 16A-30md 22A tpl 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 0.143 1270 0.770 OA70 0.091 0.032 0.989 n n n e e e s s w w w w 4.00 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4.00 35.56 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 2.55 34.77 2.55 5525 44.72 35.61 128 2.32 0.00 628 7 19 152 33 21 473 7 295 33 19 41 224 1839 1839 602 0 0 98 2 21 466 7 203 2 2 2 224 1839 212 2412 247 407 394 1162 229 1868 247 813 1162 407 537 571 1648 5871 1533 241 365 250 2853 238 1187 241 517 1806 845 1453 287 4266 0 0 0 0 0 0 0 232 0 112 33 0 0 0 343 343 0 0 0 0 0 0 232 0 79 2 0 0 0 343 43 0 0 0 0 0 0 929 0 318 1162 0 0 0 307 1191 0 0 0 0 0 0 591 0 202 1806 0 0 0 796 0 I;_G, G �G D r� � --G P C F 6 c) AED excursion 508 618 Envelopeloss/gain 17975 16592 3907 4012 12 a) Infiltration b) Roomventilation 3037 0 856 0 674 0 190 0 13 Internal gains: Occupants@ 230 Appliances/other 0 0 2000 0 0 0 Subtotal (lines6 to 13) 21011 19448 4581 4202 14 15 Less external load Less transfer Redishibution Subtotal Dud loads 1 30% 49% 0 0 0 21011 6289 0 0 0 19448 9502 30% 49% 0 0 0 4581 1371 0 0 0 4202 2053 Total roam load Air required (clm) 27300 1160 28950 1160 5952 253 6255 251 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -rid- w Igkvmtsoft- 2021-Jan-1307:44:09 Rigtd-SuteC� Universal 201919.021 RSU08101 Page 1 UICK1Doaeris\WhgltsoftWAC\WYNNE-GEMINI.np Calc=W8 FrontDoorfaoes: N w -r- rightsoft° Right-JO Worksheet Date: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., I-T. PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS a( AOL.COM 1 Room name WIC M BATH 2 3 4 5 Exposed wall Room height Room dimensions Room area 0 ft 8.0 ft heat/000l 7.0 x 9.0 it 63.0 ft= 8.0 ft 8.0 ft heat/000l 7.0 x 8.0 ft 56.0 ft2 Ty Constivction number U-value (Btuh/F--°F) Or HTM (Btuh/ff) Area (it=) or perimeter (ft) Load (Btuh) Area or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 yJ 13AAocs ,A-c1om 4A5-2om 13A-4ocs 1A-c1om 11DO 13A-4as 1A-c1om 13A4ocs 1A-c1om 4A5-20m 4A5-2ovd 12C-0sw 16A-30md 22A-tpl 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 0.143 1270 0.770 0.470 0.091 0.032 0.989 - In4.00 In n e e e s s w w w w 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4.00 35.56 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 2.55 34.77 2.55 5525 44.72 35.61 128 2.32 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 63 63 0 0 0 0 0 0 0 0 0 0 0 0 0 63 0 0 0 0 0 0 0 0 0 0 0 0 0 0 56 0 0 0 0 0 0 0 0 0 0 0 0 0 0 146 0 0 0 0 0 0 0 64 7 0 0 0 0 0 56 56 0 0 0 0 0 0 57 7 0 0 0 0 0 56 8 0 0 0 0 0 0 228 247 0 0 0 0 0 50 222 0 0 0 0 0 0 145 241 0 0 0 0 0 130 0 I; -GC G D V)/ I G hG P C F 6 c) AED excursion -12 -47 Envelopeloss/gain 56 134 747 469 12 a) Infiltration b) Roomventlation 0 0 0 0 125 0 35 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 56 134 872 505 Less exlemal load 0 0 0 0 14 15 Less transfer Redistribution Subtotal Duct loads 30% 49%1 0 0 56 171 0 0 134 651 30% 49% 0 0 872 261 0 0 505 247 Total room load Air required (dm) 73 3 199 8 1 1133 48 751 30 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -P- wrlgtstsott" Mght-Sute®Universal 201919.021 RSU08101 2021-Jan 13oPage e2 UICK1Doam ris\WdgttmftHVAC\WYNNE-GEMINI.naip Calc=MJ8 FrontDoorfaces: N g - wrightsoft` Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST.. LUCIE LN., Fr. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772.466-6796 Email: QUICKCALCS AOL.COM 1 4 Room name I3 Room 9t Room dimensions Room area KrrCHEN 8.0 It 8.0 ItheaNcool 1.0 x 172.0 It 172.0 ft2 NASTIER BEDROOM2 &0 it51.0 It heat/000l 1.0 x 256.0 It5 256.0 ft2 Ty Construction number U-value (Muh/ft2-°F) Or HTM (Btuh/ft2) Area (ft-) or perimeter (ft) Load (Btuh) Area or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A-4as 1A-c1om 4A5-2om 13A-4ocs 1Ac1om 11D0 13A4ors 1Ac1om 1A-c1om 4A5-2om 4A5-2ovd 12C4)sw 16A-30md 22A tpI 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 0.143 1270 0.770 0.470 0.091 0.032 0.989 n n n a a a s s w w w w 4.00 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4.00 35.56 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 2.55 34.77 2.55 5525 44.72 35.61 128 2.32 0.00 0 0 0 0 0 0 0 0 0 0 0 0 64 172 172 0 0 0 0 0 0 0 0 0 0 0 0 64 172 8 0 0 0 0 0 0 0 0 0 0 0 0 163 154 222 0 0 0 0 0 0 _ 0 0 0 0 0 0 82 399 0 192 0 0 104 33 0 112 0 0 0 0 0 0 256 256 192 0 0 71 2 0 112 0 0 0 0 0 0 256 51 769 0 0: 286 1162 0 448 0 0 0 0 0 0 229 1412 489 0 0 182 2853 0 285 0 0 0 0 0 0 594 0 Val �G D V)/ G G ��13A4ocs P C F 6 c) AED excursion -211 -176 Envelope loss/gain 539 270 4307 4227 12 a) Infiltration b) Room ventilation 0 0 0 0 800 0 226 0 13 Internal gains. Occupants@ 230 Appliancestother 0 0 2000 0 0 0 Subtotal (lines 6 to 13) 539 2270 5106 4452 14 15 Less extemalload Less transfer Redistribution Subtotal Dud loads 130% 49%1 0 0 0 539 161 0 0 0 2270 1109 30% 49% 0 0 0 5106 1528 0 0 0 4452 2175 Total room load Air required (dm) 700 30 3380 135 6635 282 6627 266 Calculations approved byACCAto meet all requirements of Manual J 8th Ed wr10m�S Ork- 2021-Jan-13 07:44:09 "�A Riglt-Sute®Uriversa1201919.021 RSU08101 Page3 UlMDoarnerts\WdghfsoftHVAC\WYNNE-GEMINI.np Calc=MJ8 FrontDoorfeces: N - wrightsoft° Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Exposed `mall Room height Room dimensions Room area ENTRY 20.0 It 8D It heat/cool 1.0 x 83.0 It 83D IF LAUNDRY 13D ft 8.0 ft heat/ocol 7D x 6.0 ft 42.0 fF Ty Construction number U-value (Btuh(IF-°F) Or HTM (Btuh/F) Area or perimeter r (ft) Load (Btuh) or or�perim ter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A4ocs 1A-clom 4A5-2om 13A-4ocs 1A-clom 11DO 13A-0as 1Aclom 13A-4ocs 1A-clom 4A5-2om 4A5-2ovd 12C-Osw 16A-30md 22A-tpl 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 0.143 1270 0.770 0.470 0.091 0.032 0.989 n n n a a a s s w w w w 4.00 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4.00 35.56 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 2.55 34.77 2.55 5525 44.72 35.61 128 2.32 0.00 0 0 0 48 0 21 8 0 0 0 0 0 104 83 83 0 0 0 27 0 21 8 0 0 0 0 0 104 83 20 0 0 0 108 0 229 32 0 0 0 0 0 265 74 554 0 0 0 69 0 238 20 0 0 0 0 0 133 193 0 0 0 0 0 0 0 48 0 0 0 0 0 56 42 42 0 0 0 0 0 0 48 0 0 0 0 0 56 42 13 0 0 0 0 0 0 19 0 0 0 0 0 143 38 360 0 0 0 0 0 0 - 122 0 0 0 0 0 72 97 0 1-G D W i-G TE� P C F 6 c) AED excursion -58 -27 Envelope loss/gain 1263 695 733 264 12 a) Infiltration b) Room ventilation 110 0 31 0 94 0 27 0 13 Internal gains: Occupants@ 230 Applianoeslother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1372 625 827 291 14 15 Less exBmal load Less transfer Redishibution Subtotal Dud loads 30% 49% 0 0 0 1372 411 0 0 0 625 306 30% 49% 0 0 0 827 247 0 0 0 291 142 Total room load Air required (cfm) 1783 76 931 37 1074 461 433 17 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigF t:Madt- 2021-Jan•1307:44:09 .4CG�l� Right-Sute®Uriversal201919.021 RSU08101 Page4 UICK'Doaxmrts\WdghtsoftWAQWYNNE-GEMINI.np Calc=MJ8 Front Door faces: N -F- wrightsoft° Right-J® Worksheet Date: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 3 4 5 Room name RooExposed hI height t Room dimensions Room area GREAT/DINING 39.0 8.9 ft ft heat/cool 1.0 x 568.0 it 568.0 112 CLOSET2 O 9.4 It ft heat/000l 7.0 x 8.0 ft 56.0 fF Ty Construction number U-value (Btuhtff--°F) Or HTM (Btuh/ft�) Area or perimeter r (ft) Load (Btuh) s or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 \ 13A-flocs 1A-clom 4A5-2om 13A-4ocs IA-clom 11D0 1A-clom 13A4ocs 1A-clom 4A5-2om 4A5-2ovci 12C-0sw 16A-30md 22A-tpl 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 0.143 1270 0.770 0.470 0.091 0.032 0.989 n n n e e a s s w w w w 4.00 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4.00 35.56 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 2.55 34.77 2.55 55.25 44.72 35.61 128 2.32 0.00 267 0 19 0 0 0 0 0 80 0 0 41 0 568 568 248 0 0 0 0 0 0 0 39 0 0 2 0 568 39 993 0 407 0 0 0 0 0 157 0 0 537 0 509 1080 632 0 365 0 0 0 0 0 100 0 0 1453 0 1318 0 0 0 0 0 0 0 0 0 0 0 0 0 0 56 56 0 0 0 0 0 0 0 0 0 0 0 0 0 56 0 0 0 0 0 0 0 0 0 0 0 0 0 0 50 0 0 0 0 0 0 0 0 0 0 0 0 0 0 130 0 I!_G� G G D �13A-4ocs G G P C F 6 c) AED excursion 1256 -11 Envelope loss(gain 3684 4123 50 119 12 a) Infiltration b) Room ventilation 680 0 192 0 0 0 0 0 13 Internal gains: Occupants@ 230 Appliancescother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 4364 Q15 50 119 14 Less external load Less transfer Redistribution Subtc)tal Ductloads 30% 49% 0 0 0 4364 1306 0 0 0 4315 2108 30% 49%1 0 0 0 50 15 0 0 0 119 58 r Total room load Airrequired (dm) 5671 241 6423 257 65 3 1 177 7 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. �" L-rid- wrigFttsof`t- 2021-Jan•1307:44:09 A Right-Sute®Uriversal 20l919.021 RSU08101 Page s UICKtDoaxmrts\WrighfsoftHVAC\WYNNE-GEMINI.rLp Calc=NUB Front Door faces: N -�- wrightsoft° RighW@ Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone:772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BATH 2 8.0 ft 9.4 It heat/000l 6.0 x 8.0 It 48.0 fP POWDER 0 ft 9.4 It heat/cool 7.0 x 6.0 ft 42.0 it' Ty Construction number U-value (Btuh/fF--°F) Or HTM (Biuh/ft�) Area 011) or perimeter M Load (Btuh) Area or perimeter (ft) Load (B h) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 yJ 13A4o s 1Aclom 4A5-2om 13A11ocs 1A-c1om 11DO IA-c1om IA-c1om 4A5-2om 4A5-2ovd 12C-Osw 16A30md 22A tpI 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 .13 1270 0.770 0.470 0.091 0.032 0.989 n n n a a a . s s w w w w 4.00 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4. 35.5656 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 _ 2.55 34.77 525 5525 44.72 35.61 128 2.32 0.00 75 7 0 0 0 0 0 0 0 0 0 0 0 48 48 68 0 0 0 0 0 0 0 0 0 0 0 0 48 8 273 247 0 0 0 0 0 0 0 0 0 0 0 43 222 174 241 0 0 0 0 0 0 0 0 0 0 0 111 0 0 0 0 0 0 0 0 0 0 0 0 0 0 42 42 0 0 0 0 0 0 0 0 0 0 0 0 0 42 0 0 p 0: 0 0 0 0 0 0 0 0 0 0 38 0 0 p 0. 0 0 0 0 0 0 0 0 0 0 97 0 V�/ �G �p t13A•4ocs C TE�13A4ocs P C F - 6 c) AED excursion 48 $ Envelope losstgain 784 478 38 89 12 a) Infiltration b) Room ventilation 147 0 42 0 0 0 0 0 13 Internal gains., Occupants@ 230 Appliances/other 0 0 0 0 1 0 0 Subtotal (lines 6 to 13) 932 520 38 89 14 Less external load Lessiransrer Redistribution Subtotal Dud loads 130% 49%1 0 0 0 932 279 0 0 0 520 254 30% 49%1 0 0 0 38 11 0 0 0 89 44 r Total room load Airrequired (cfm) 1211 51 773 31 1 1 49 2 133 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed -rid- wrightsoTt^ 2021 -Jan-1 3 07:44:09 A&k Right-Sute®Uriversal201919.021 RSU08101 Page UICK\Docunerts\WrigtisoftHVAC\WYNNE-GEMINI.np Calc=MJ8 Front Door faces: N -PF wrightsoft° Right-M) Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., Fr.. PIERCE, FL 34946 Phone:772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS AOL.COM 1 3 4 5 Room name RoomheightAell eght Room dimensions Room area DEN 22 9.4 ItA It heaU000l 11.0 x 10.0 It 110.0 fz Ty Construction number U-value (Btuh/ttz-°F) Or HTM (Btuh/fl�) Area (ft2) I or perimeter (ft) Load (Btuh) Area or perimeter Load Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11G 13A-4ocs 1A-clom 4A5.2om 13A-4ocs 1A-clom 11DO 1A-clom 13A-4ocs 1Aclom 4A5-2om 4A5-2oNd 12C-0sw 16A-30md 22A-tpl 0.143 1270 0.770 0.143 1270 0.390 0.143 1270 0.143 1270 0.770 0.470 0.091 0.032 0.989 n n n e e a s s w w w w 4.00 35.56 21.56 4.00 35.56 10.92 4.00 35.56 4.00 35.56 21.56 13.16 2.55 0.90 27.69 2.55 34.77 19.31 2.55 8729 11.31 2.55 34.77 2.55 5525 44.72 35.61 128 2.32 0.00 94 0 0 0 0 0 9 0 103 0 19 0 0 110 110 94 0 0 0 0 0 9 0 84 0 2 0 0 110 22 376 0 0 0 0 0 38 0 338 0 407 0 0 99 609 239 0 0 0 0 0 24 0 215 0 845 0 0 255 0 D �13A-4ocs G ' G l_CG P C F 6 c) AED excursion 233 Envelope loss/gain 1868 1811 12 a) Infiltration b) Room ventilation 405 0 114 0 13 Internal gains: Occupants@ 230 0 0 Applianoes(other 0 Subtotal (lines 6 to 13) 2273 1926 14 1151 Less external load Less transfer Redistribution Subtotal Ductloads 130% 49% 0 0 0 2273 680 0 0 0 1926 941 Total room load Air required 0m) 2953 125 2867 115 Calculations approved byACCAto meet all requirements of Manual J 8th Ed -�- wrlghtsoft 2021-Jan-1307:44:09 Right Universal 201919.021 RSU08101 Page 7 UICK1Docunerps\WrigttsoftHVAC1WYNNE-GEMINI.nip Calc=MJ8 Front Door faces! N -- wrightsoft® Duct System Summary p: Entire House By. QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772.466-6796 Email: QUICKCALCS@AOL.COM Project• • For: THE GEMINI WYNNE DEV., FT. PIERCE, FL Heating Cooling External static pressure 0.50 in H2O 0.50 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 0.50 in H2O 0.50 in H2O Supply/ return available pressure 0.250 /0.250 in H2O 0.250 /0.250 in H2O Lowest friction rate 0.286 in/100ft 0.286 in/100ft Actual airflow 1160 cfm 1160 cfm Total etfec ive length (TEL) 175 ft Supply Branch Detail Table Name Design (Btuh) Htg (ctm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 1211 51 31 0.368 4.0 Ox 0 VIFx 21.0 115.0 st1 CLOSET2 c 177 3 7 0.363 4.0 Ox0 VIFx 22.6 115.0 st1 DEN h 2953 125 115 0.289 7.0 Ox0 VIFx 38.1 135.0 st2 ENTRY h 1783 76 37 0.485 4.0 Ox0 VIFx 8.1 95.0 GREAT/DINING-A c 3211 120 129 0.300 6.0 Ox 0 VIFx 31.7 135.0 st2 GREAVDINING-B c 3211 120 129 0.308 6.0 Ox 0 VIFx 27.3 135.0 st2 KITCHEN c 3380 30 135 0.376 7.0 Ox0 VIFx 18.1 115.0 st1 LAUNDRY h 1074 46 17 0.369 6.0 Ox0 MFx 20.4 115.0 st1 M. BATH h 1133 48 30 0.366 4.0 Ox 0 VIFx 21.6 115.0 st1 MASTERBEDROOM h 2976 126 125 0.286 6.0 Ox0 VIFx 40.1 135.0 st2 MASTERBEDROOM2 h 6635 282 266 0.352 7.0 Ox0 MFx 27.2 115.0 st1 MASTER BEDROOM -A h 2976 126 125 0.297 6.0 Ox0 MFx 33.1 135.0 st2 POWDER c 133 2 5 0.379 4.0 Ox0 VIFx 17.1 115.0 st1 wlc c 199 3 8 0.309 4.0 Ox 0 VIFx 26.6 135.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 622 631 0.286 803 12.0 0 x 0 VinlFlx st1 st1 PeakAVF 1084 1123 0.286 804 16.0 0 x 0 VinlFlx wrightsoft® 2021-Jan•1307:44:09 �� w �h*� �q�mo•� Rigf-Stite@Uriversal20l9l9.021 RSU08101 Page 1 ...UICK\Docunerts\Wdghtso$HVAC\WYNNE-GEMINI.nip Calc=MJ8 FrortDoorfaces: N Return Branch Detail Table Name Grille Size (in) Htg 0m) Clg (Cfm) TEL 00 Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rb1 Ox 0 1160 1160 0 0 0 0 Ox 0 VIFx 1 ' wrightsoft® 2021-Jan-1307:44:09 Rigid-Sute®Uriversal201919.021 RSU08101 Page UICK\Doamerds\WrightsoftHVAC\WYNNE-GEMINI.np Calc=MJ8 Frorft Door faces: N