RE: Revels Residence, 5217 Palm Drive Ft Pierce
Permit # 2201-0058
To Whom It My Concern
Please accept the following responses to the comments from your agency. Response shown on plans
corresponding (if required) to these comments are noted.
COMMENT: DRAWING A1.00 ROOFING MATERIAL FL PRODUCT APPROVAL FOR SHINGLES NOT
CORRECT.
Response: Product FL# 30320.1 shows as a correct and valid product on the floridabuilding.org
website.
COMMENT: PRODUCTAPPROVAL LISTING ON SHEETA1.00 SIGNED BYTHE HEALTH DEPARTMENT
DOES NOT MATCH THE REVISED VERSION ALSO ATTACHED IN THE SUBMITTAL PACKAGE. THE
PRODUCTS ON THE HEALTH DEPT PAGE ARE NOT CURRENT HOWEVER THE NEWER REVISION HAS
ACCPETABLE PRODUCT APPROVALS. PROCUT APPROVALS MUST BE ONSITE DURING CONSTRUCTION
FOR USE BY THE CONTRACTOR AND INSPECTOR.
Response: Contractor to update as necessary, product approval listings on A1.00 are all valid.
COMMENT: NO PRODUCT APPROVAL SHOWN ON DRAWING A1.00 REVISED HORIZONTAL SLIDE AS
DEPICTED ON DRAWING A3.00.
Response: Window above kitchen sink has been revised to be a SH23, to match product approval
listings.
COMMENT: 220 VOLT DISCONNECT SYMBOL NOT SHOWN ON LEGEND. IN ADDITION, CANNOT BE
BEHIND UNIT.
Response: Symbol added to legend. Disconnects adjusted on plans to be shown more explicitly on
the side of units.
COMMENT: OUTLETS IN GARAGE TO BE 20 AMP, GFCI PROTECT PER NEC 210.
Response: All outlets in garage have GFI notation and symbol as shown in the legend.
COMMENT: NO ATTIC LIGHT SHOWN ON ELECTRICAL PLAN.
gni 806 Delaware Ave, Fort Pierce FL 34950 1 772-460-7751
��,�f 1790 A1A Ste 209, Satellite Beach FL 32937 1 321-732-4077
®www.architectonicinc.com
AR26003348
Page 1 of 2
}
Architectonic Inc
Response: In addition to the note already in plans calling out the light in the attic, a light symbol has
been added to be explicitly clear on intent.
COMMENT: IF LIGHT NOT INSTALLED IN BEDROOM CEILIGNS, ONE OUTLET MUST BE SWITCHED.
Response; There are Z switches and 2 wires shown going to what is.11sted in the legend as a
"Yon/light combo" in all bedrooms. 1 switch/wire for fan, l switch/wire for light.
COMMENT: MASTER BATH, IS THE FAN SHOWN NEAR BATHUB A COMBO FAN/LIGHT UNIT?
Response: It is a fan/light combo. Note added to plan for clarity.
COMMENT: PRODUCT APPROVAL ON PG A1.00 CALLS OR SELF ADHERED, HOWEVER, SHEET A5.00
Response: Detail on A5.00 has been updated to match Self Adhered.