Loading...
HomeMy WebLinkAboutEngineering DesignFILE COPY a domstructures Zzo3 9° construction • engineering • design REVIEWED FOR CODE COMPLIANCE ST• LUCIE CO NTV BOCC �f' L� Proi ,ct Name. ALUMINUM TUBE FRAMING SUPPORTS Project Address: 13239 NW HARBOUR RIDGE BLVD. PALM CITY, FL Scope of Calculations: CALCULATIONS FOR NEW TUBE SUPPORTS Calculations Provided: Wind load calculations • Load combinations per ASCE 7-16 Forces, reactions, and design checks for framing Related Documents: Anchor Data, Product Approvals as Referenced Codes and Standards: 2020 Florida Building Code, 7th Ed. ASCE 7-16 Project Drawing Notes: AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191ST ST #29889, MIAMI, FL, 33179 Date: 3/21/2022 Project #: J22175 Please refer to attached details and general notes by this engineer for any additional i fP �. not mentioned herein. %N OY // essional Engineers Seal: Fht' pY B 0IS&� q.. Nod .. S• ,o ., =No 76131 � DA ' Otiq`••ENC ! ��lllllllt�r— ()'Z Z? -Z-Z Page 1 of 8 axiomstructures construction • engineering • design General Notes: 1. THE INSTALLATION OF ANY ACCESSORIES THAT DO NOT AFFECT THE STRUCTURAL INTEGRITY OF THE STRUCTURE ARE OUTSIDE THE SCOPE OF THIS CERTIFICATION AND ARE NOT REQUIRED TO BE CERTIFIED UNDER THIS STRUCTURAL DRAWING. EQUIPMENT WEIGHT IS ACCOUNTED FOR ONLY IF SPECIFICALLY SHOWN HEREIN. ENGINEER OR ARCHITECT OF RECORD SHALL APPROVE THE USE OF ALL PROPOSED UNIT WEIGHTS AS APPLICABLE TO THIS PROJECT. USE MANUFACTURER'S CERTIFIED DRAWINGS AND SPECIFICATIONS FOR ACCESSORY ANCHORAGE AND DETAILS. 2. THESE PLANS CERTIFY THE STRUCTURAL ADEQUACY OF THE PROPOSED SYSTEM IN ACCORDANCE WITH THE STRUCTURAL REQUIREMENTS OF THE BUILDING CODE ONLY. NO CERTIFICATION OR REVIEW IS OFFERED THAT THE PROPOSED UNITS MEET ANY EGRESS REQUIREMENTS. ALL EGRESS ISSUES ARE TO BE ADDRESSED BY THE ENGINEER/ARCHITECT OF RECORD AND THE LOCAL BUILDING OFFICIAL. THESE PLANS SHALL BE REVIEWED AND APPROVED BY THE ENGINEER/ARCHITECT OF RECORD PRIOR TO CONSTRUCTION. 3. THIS ENGINEER HAS NOT VISITED THIS JOBSITE. INFORMATION CONTAINED HEREIN IS BASED ON CONTRACTOR SUPPLIED DATA AND MEASUREMENTS. USE OF THIS DOCUMENT BY THE END USER CONSTITUTES ACCEPTANCE THAT THE SIGNING ENGINEER, AND THIS OFFICE, SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS OR INACCURATE DATA OR MEASUREMENTS. WORK SHALL BE FIELD VERIFIED PRIOR TO CONSTRUCTION. THIS OFFICE SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO REEVALUATE OUR WORK UPON DISCOVERY OF.ANY INACCURATE INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS AND FABRICATION AND INSTALLATION OF MATERIALS. 4. THE EXISTING HOST STRUCTURE MUST BE CAPABLE OF SUPPORTING THE LOADED SYSTEM AS VERIFIED BY THE ENGINEER & OR ARCHITECT OF. RECORD, et.al. THE ROLE OF THIS'ENGINEER FOR THIS PROJECT IS SPECIFICALLY LIMITED TO THAT OF SPECIALTY ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED BY THE PERMITTING CONTRACTOR. THE HOST STRUCTURE WHICH IS DESIGNED, CERTIFIED, AND INSPECTED BY OTHERS MUST PROVIDE SUFFICIENT; SOUND ANCHORAGE FOR THIS SPECIFIED SYSTEM. 5. ALL MECHANICAL, ELECTRICAL, OR LIGHTING (IF APPLICABLE) SPECIFICATIONS SHALL BE AS PER MANUFACTURER RECOMMENDATIONS OR BUILDING OFFICIAL REQUEST AND ARE THE EXPRESS RESPONSIBILITY OF THE CONTRACTOR. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY OTHERS. 6. THESE CALCULATIONS ARE INTENDED TO PROVIDE SITE -SPECIFIC STRUCTURAL SPECIFICATIONS FOR THE REFERENCED STRUCTURE FOR THE PURPOSE OF THE INSTALLATION OF PRODUCTS AS PROPOSED AND PROVIDED BY OTHERS. NO CERTIFICATION, EITHER EXPRESSED OR IMPLIED, IS OFFERED AS TO THE VALIDITY OR APPLICABILITY OF ANY PROPOSED SYSTEM OR COMPONENT USED ALONG WITH THESE CALCULATIONS UNLESS PRODUCT AND EVALUATION/LIMITATION INFORMATION IS SPECIFICALLY REFERENCED AND ADDRESSED HEREIN, AND WITHIN THE ATTACHED DRAWINGS SEALED BY THIS ENGINEER. AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191ST ST #29889, MIAMI, FL, 33179 Page 2 of 8 BUILDING INFORMATION Ultimate Wind Speed Nominal Wind Velocity (mph) 170 Exposure C Internal Pressure Enclosed Height above ground (z) -(ft.) 20.0 Standard Wall Height-(ft.) 8.0 Mean Roof Height (h) - (k.) 20.0 Roof Slope (x:12) 4.0 Roof Angle (degrees) 18.43 Roof Type Hip Least Horizontal Dimension - LHD (R.) 40.0 Largest Horizontal Dimension (k.) 90.0 (a) Edge Strip (k.) 4.00 End Zone (k.) 12.00 Im aAomstrudures construction - engheering - design Wall Openings (windows, doors, shutters, etc.) ASCE 7-16 WIND LOAD DESIGN INFORMATION -VERTICAL SURFACES JOB INFORMATION Job Name ALTENKIRCH, BETX Address 13139 NW HARBDDR RIDGE 13D. PALM OTY, FL ' Company WRIGHT%WINDOW TOPOGRAPHIC FACTOR Hill Shape Flat- No Hill H, (k.) 0.0 Lh, (k.) 0.0 x, (k.) 0.0 0.0 vr.. voh�c�vn wrviiv.s. � ricw MEASUREMENTS. ANY INACCURACIES HEREIN SHALL BE BROUGHT TO THE ATTENTION OFTHE ENGINEER PRIORTO INSTALLATION. Nominal -ASD- Wind Load Pressures PRESSURE PRESSURE EFFECTIVE d z APPLYING WIND LOAD FOR: ZONE WIDTH HEIGHT WIND AREA MAXIMUM POSITIVE MAXIMUM NEGATIVE Product Approval Max Pressure Per Manufacturer Model (sQ'ft') PRESSURE (psf) PRESSURE (psf) Number Approval (in.) (in.) 2 4 35.3 59.3 14.5 39.2 -42.6 FL# 23358.2 +55/-65 CGI SH-4000A Q Z 3 4 1 35.3 1 59.3 1 14.5 1 39.2 -42.6 FL# 23358.2 +55/-65 CGI I SH-4000A � a O THIS CALCULATION IS INTENDED TO PROVIDE SPECIFIC DESIGN PRESSURES FORTHE PURPOSE OF THE INSTALLATION OF BUILDING PRODUCTS AS PROPOSED AND PROVIDED BY OTHERS. NO CERTIFICATION, EITHER EXPRESSED OR IMPLIED, IS OFFERED ASTO THE VALIDITY OR APPLICABILITY OF ANY PROPOSED SYSTEM OR COMPONENT USED ALONG WITH THESE PRESSURES UNLESS PRODUCT AND APPROVAL CRITERIA IS SPECIFICALLY REFERENCED AND ADDRESSED HEREIN. AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 Page 3 Of 8 382 NE 191ST ST 1129889, MIAMI, FL, 33179 cDdomstructures construction • engineering • design Member: 3x6 Vertical Aluminum Mullion for Opening 2-3 Alloy: 6063 Temper: T6 Critically Welded: N Flange Width (b): 3.000" Flange Thickness (tb): 0.250" Web Height (h):. 6.000" Web Thickness (tb): 0.250" Moment of inertia about axis parallel to flange (Ix): 19.34 ie4 Moment of inertia about axis parallel to web (Iy): 6.34 ie4 Section modulus about the x-axis (Sx): 6.45 in^3 Unsupported member length (L): 5.0 ft Unbraced length for bending (Lb): 1.0 ft Effective length factor (k): 1.0 Tensile ultimate strength (Ftu): 30 ksi Tensile yield strength (Fty): 25 ksi Compressive yield strength (Fcy): 25 ksi Shear ultimate strength (Fsu): 18 ksi Shear yield strength (Fsy): 15 ksi Compressive modulus of elasticity (E): 10100 ksi Yielding 25.00 ksi / 1.65 =15.15 ksi Rupture 30.00 ksi / 1.95 =15.38 ksi AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191 ST ST #29889, MIAMI, FL, 33179 Page 4 of 8 axiomstructures construction • engineering • design Member: 3x6 Vertical Aluminum Mullion for Opening 2-3 Axial Compression E.2 Compression Member Buckling 22.99 ksi / 1.65 =13.93 ksi EA Buckling Interaction Flange Member Buckling 22.99 ksi / 1.65 =13.93 ksi Web Member Buckling 22.99 ksi / 1.65 =13.93 ksi Flexural Members F.2 Yielding and Rupture Yielding 25.00 ksi / 1.65 =15.15 ksi Rupture 30.00 ksi / 1.95 -15.38 ksi Lateral Torsional Buckling 29.87 ksi / 1.65 -18.10 ksi Uniform Compression Elements B.5.4.2 Flat Elements Supported on Both Edges - Web & Flange. Flange 25.00 ksi / 1.65 =15.15 ksi Web 25.00 ksi / 1.65 =15.15 ksi AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191 ST ST #29889, MIAMI, FL, 33179 Page 5 of 8 a domstructures construction • engineering • design .Member:. 3x6 Vertical Aluminum Mullion for Opening 2-3 Flexural Compression Elements B.5.5.1 Flat Elements Supported on Both Edges - Web 37.50 ksi / 1.65 =22.73 ksi Shear G.2 Shear Supported on Both Edges - Web 15.00 ksi / 1.65 =9.09 ksi Elastic buckling stress (Fe): 64.61 ksi Weighted average allowable compressive stress (Fao): 15.15 ksi Allowable bending stress (Fb): 15.15 ksi Allowable axial stress, compression (Fac): 13.93 ksi Allowable shear stress; webs (Fv): 9.09 ksi AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191ST ST #29889, MIAMI, FL, 33179 Page 6 of 8 axiomstructures construction • engineering • design Member: M Vertical Aluminum Mullion for Opening 2-3 Member Loading Support Type Simple. Beam Length (L): 5.0 ft Tributary Width (W): : 2.94 ft Load on Tributary (RL): 42.60 psf Additional Beam Load (DL):' 0.00 lb/ft Total Loading on Beam (w): 125.14 lb/ft Shear Loading at End of Beam (Vy): 3131bs Calculated Moment (Mmax): 0.4 kip-ft Bending Moments Bending moment developed in member (Mz): 0.4 kip-ft Bending stress developed in member (fb): 0.73 ksi Allowable bending stress of member (Fb): 15.15 ksi Axial Axial load developed in member (Fx): 0 lbs Axial stress developed in member (Fa): 0.00 ksi Allowable compressive axial stress of member (Fac): 13.93 ksi Shear Shear load developed in member (Vz): 313 lbs <—Clip Reaction at Each End Shear stress developed in member ft): 0.11 ksi Allowable shear stress of member webs (Fv): 9.09 ksi Interaction Equations ,1 [(fb/Fb)^2 + (fv/Fv)^21 = 0.05 < 1.0 fa/Fa + fb/Fb = 0.00 < 1.0 fa/Fa + (fb/Fb)^2 + (fv/Fv)^2 = 0.00 < 1.0 Support Type: Simple Deflection Limit: w = 125.14 lb/ft Allow - 0.33 in OMax - 0.01 in OK, Allowable Deflection Sufficient AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191ST ST #29889, MIAMI, FL, 33179 Page 7 of 8 axiomstructures construction • engineering • design Work Prepared For: Wrights Windows Project: ALUMINUM TUBE FRAMING SUPPORTS Detail/Member: 3x6 Vertical Aluminum Mullion for Opening 2-3 N = 6 Quantity of anchors V = 52 Ibs Required shear per anchor T = Required tension per anchor Check Anchor Capacity to Concrete Anchor: ITW 1/4" Tapcon to 3000 psi normal concrete Diameter: 0.25" 1.75' Embedment for Full Capacity 2200 lb Ultimate Tensile Capacity of Anchor 1670 lb Ultimate Shear Capacity of Anchor 4 Safety Factor 4.0" Edge Distance for Full Capacity (Tension) 1.25" Minimum Edge Distance Allowed (Tension) 82.0% Reduction Factor at Minimum Allowable Edge Distance (Tension) 4.0" Edge Distance for Full Capacity (Shear) 1.5' Minimum Edge Distance Allowed (Shear) 59.0% Reduction Factor at Minimum Allowable Edge Distance (Shear) 4.0" Spacing for Full Capacity (Tension) 2.0" Minimum Spacing Allowed (Tension) 66.0% Reduction Factor at Minimum Allowable Spacing (Tension) 4.0" Spacing for Full Capacity (Shear) 2.0" Minimum Spacing Allowed (Shear) 82.0% Reduction Factor at Minimum Allowable Spacing (Shear) 2.5" Desired Edge Distance ------ W- 2.5" Desired Min Spacing 90.18% Edge Distance Reduction Factor for Tension 75.4% Edge Distance Reduction Factor for Shear 74.5% Spacing Reduction Factor for Tension 86.5% Spacing Reduction Factor for Shear Allowable Tension (Tn): 365.52 [Ibf per Anchor] Allowable Shear MY 272.30 [Ibf per Anchor] CTnln+(Vnln _0.19 where n = 1.00 /I AXIOM STRUCTURES INC. (954) 947-0880 1 C OF A 31329 382 NE 191 ST ST #29889, MIAMI, FL, 33179 OK, less than 1, anchors are sufficient to support structure Page 8 of 8