HomeMy WebLinkAboutCHVAC LoadsAccelerated Academies HVAC Load Analysis for Accelerated Academies 7526-7532 US Highway 1 Port St. Lucie, Florida 0,Qi,I/II v 4 IN O w dP ; • + AN w w r Eric J. Svoboda, PE Fort Pierce Engineering, Inc. 315 South 7th Street Fort Pierce, FL 34950 772-672-4636 Friday, December 17, 2021 1 0 Chvac Fyll Commercial HVi4C Loads Calculation Program ,��� Elite Software Development, Inc:: Fork Pierce EngineeringK Accelerated Academies -f.. t- Fort Pierce. FL 34950 - _ P"age 2, General Pro "ect Data Input h General 6i'6 ',6forma i' Project file name: Accelerated Academies Heat Load.CH8 Project title: Accelerated Academies Designed by: Eric J. Svoboda, PE Project date: Monday, July 07, 2008 Weather reference city: FORT PIERCE, FLORIDA, USA Client name: Accelerated Academies Client address: 7526-7532 US Highway 1 Client city: Port St. Lucie, Florida Company name: Fort Pierce Engineering, Inc. Company representative: Eric J. Svoboda, PE Company address: 315 South 7th Street Company city: Fort Pierce, FL 34950 Company phone: 772-672-4636 Company fax: 772-672-4637 Barometric pressure: 29.894 in.Hg. Altitude: 25 feet Latitude: 27 Degrees Mean daily temperature range: 15 Degrees Starting & ending time for HVAC load calculations: 7am - 10pm Number of unique rooms in this project: 16 Bia ldln efault'Values Calculations performed: Both heating and cooling loads Lighting requirements: 2.00 Watts per square foot Equipment requirements: 1.00 Watts per square foot People sensible load multiplier: 250 Btuh per person People latent load multiplier: 200 Btuh per person Room sensible safety factor: 0 % Room latent safety factor: 0 % Room heating safety factor: 0 % People diversity factor: 100 % Lighting profile number: 0 Equipment profile number: 0 People profile number: 0 Building default ceiling. height: 10.00 feet Building default walf;,height: 12.00 feet Iriternal .O`'4eratin" Load I?ro llesn C 100r hr I hr hr -• - hr I hr W fir hr hr I hr I hr hr hr hr hr hr hr I hr hr I hr I hr hr hr hr 1 : :'2 3 4 ' S ' 6 7 8 9 1 10 1 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 C C; C C C C "C C C C C C C C C C C C C C C C C c 2 C y P. C C,'. C C c C c c C C C C C C C C C C C C C c 3 C a—c' C C C c `•,C:; C c C C C C C C C C C C C C C C C 4 C °; C C ':. C, �c C, C: C C C C C C C C C C C C C C C C C 5 C 'r.'C:. C C C c' C• C C C c c c C C C C C C C C C C C 6 C 'c"Jc `-? ,C C c 'C C C C C C C C C C C C C C C C C C 7 C C� ,; C = C C C C C C C C C C C C C C C C C C C C 8 C C C C Ca C C C C C C C C C C C C C C C C C C 9 C c "` C -c -: C C C C C C C C C C C C c c c C C C C 10 C C."0 "' C C C C C C C C C C C C C C C C C C C C Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chvac,- Full'Commercial HVAC Loads Calculation` ir6 ram, `` `' Elite Software Development. Inc. Fort,Pierce,Enpineerind v " . �, . Accelerated Academies . Pa e 3 General Pro "ect Data Input(cont'd Buildin-LevelDesicin,Conditions� Design Outdoor Outdoor Indoor Month Dry Bulb Wet Bulb Rel.Hum Indoor Dry Bulb Grains Diff In/Outdoor Correction August 95 80 Winter 42 50% 75 75 66.33 6 Roof ASHRAE No. Roof# Roof U-Fac Dark Color Susp. Ceil 1 1 Roof #1 Description: Metal Roof, R-20 0.050 No No Master'V1lalfs"` �' Wall ASHRAE No. Group Wall U-Fac Wall Color 1 C 0.095 L Wall #1 Description: Block wall, 8" sand & gravel, hollow core, siding exterior, interior finish, 1" extruded poly, R-5.0 Master'Gass' Glass Summer Winter No. U-Factor U-Factor Glass Shd.Coef. Interior Shading Interior Shd.Coef 1 0.810 0.830 Glass #1 Description: Default Glass 1.000 1 0.550 Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chvac Full Cornmercial HUAC Loads Calculation Program - Elite Software Development, Inc.,, Eort;Fierce Eneerinq gmFL q„ Accelerated Academies i r 4950 a 4 Building Summaly Loads Building peaks in August at 4pm. ad BldgLoat Area Sen %Tot L` ;Sen Net %Net` Descri tions , an Loss 1 -Loss •�Galm. E ,_' Galn Galn '{" _ Gain; Roof 5,639 9,304 11.23 0 11,366 11,366 3.86 Wall 1,710 5,361 6.47 0 2,690 2,690 0.91 Glass 774 21,200 25.59 0 79,999 79,999 27.18 Floor Slab 207 4,235 5.11 0 0 0 0.00 Skin Loads 40,100 48.41 0 94,055 94,055 31.95 Lighting 11,206 0 0.00 0 38,236 38,236 12.99 Equipment 6,085 0 0.00 0 20,763 20,763 7.05 Pool Latent 0 0 0.00 0 0 0 0.00 People 131 0 0.00 26,200 32,750 58,950 20.03 Partition 0 0 0.00 0 0 0 0.00 Cool. Pret. 0 0 0.00 0 0 0 0.00 Heat. Pret. 0 0 0.00 0 0 0 0.00 Cool. Vent. 1,200 0 0.00 54,081 26,376 80,457 27.33 Heat. Vent. 1,200 42,729 51.59 0 0 0 0.00 Cool.lnfil. 0 0 0.00 0 0 0 0.00 Heat.lnfil. 0 0 0.00 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 1,892 1,892 0.64 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap. 0 0 0.00 0 0 0 0.00 Reheat Cap. 0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 82,830 100.00 80,281 214,072 294,354 100.00 Building Sen %Tot Lat Sen' Net %Net= Summa4 _ .. r.< ... �_:-� Loss' Loss,, Galn Gainn3 Gain Gala: Ventilation 42,729 51.59 54,081 26,376 80,457 27.33 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 0 0.00 0 0 0 0.00 Room Loads 40,100 48.41 26,200 185,804 212,004 72.02 Plenum Loads 0 0.00 0 0 0 0.00 Fan/Duct/Misc Loads 0 0.00 0 1,892 1,892 0.64 Building Totals 82,830 100.00 80,281 214,073 294,354 100.00 LC'heck Fi' ures- ,t µ. Total Building Supply Air (based on a 220 TD): 7,905 CFM Total Building Vent. Air (15.18% of Supply): 1,200 CFM Total Conditioned Air Space: 5,603 Sq.ft Supply Air Per Unit Area: 1.4109 CFM/Sq.ft Area Per Cooling Capacity: 228.4 Sq.ft/Ton Cooling Capacity Per Area: 0.0044 Tons/Sq.ft Heating Capacity Per Area: 14.78 Btuh/Sq.ft Total Heating Required With Outside Air: 82,830 Btuh Total Cooling Required With Outside Air: 24.53 Tons Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chvac -Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineering Accelerated Academies o' ier d ., .. �. �,< .. .. �,, Page 5 Air Handler #1- RTU 1- Summaty Loads Rm' Description Area Htg.Lo 's ` Sen.Galn Lat.Gain i Htg:O A: CIg.O A. . People Htg.GM ,GNoRoom.?eakTlmelg CFM ,CFM/ SvExh Req:CEM ReqCFM 'Volume_'`GFM/S et- NEXt Act:CFM< Act,"CFM 1 Reception 240 2,389 10,735 400 Direct Direct 4pm August 2 111 446 0 48 48 2,400 0.46 1.86 0 50 63 2 Multipurpose 3 224 4,950 18,003 1,200 Direct Direct 4pm August 6 229 748 0 45 45 2,240 1.02 3.34 0 103 105 3 Multipurpose 2 224 1,183 4,455 1,200 Direct Direct 2pm August 6 55 185 0 45 45 2,240 0.24 0.83 0 25 26 Open Colaboration / 990 7,215 23,580 5,600 Direct Direct 4 Cafe 2pm August 28 334 980 0 199 199 9,900 0.34 0.99 0 150 138 5 I.T. Closet 18 612 2,102 0 Direct Direct 3pm August 0 28 87 0 4 4 180 1.58 4.85 0 13 12 6 RR 1 49 487 1,050 200 Direct Direct 3pm August 1 23 44 0 10 10 490 0.46 0.89 0 10 6 Room Peak Totals: 1,745 16,836 59,925 8,600 Total Rooms: 6 43 780 2,490 0 350 350 Unique Rooms: 6 17,450 0.45 1.43 0 350 350 Z:\...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chvac Fu11 Commercial HVAC Loads CionalculatPirogram _ Elite Software Development, Inc FortrPierce Engineennq Accelerated Academies' -:'FLL 950 Air Handler ##1- RTU 1- Total Load Summar Air Handler Description: RTU 1 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.23 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.87 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 4pm in August. Outdoor Conditions: Clg: 950 DB, 80' WB, 131.77 grains, Htg: 42' DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75' DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 16,836 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 12,463 Btuh 350 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 29,298 Btuh Heating Supply Air: 16,836 / (.999 X 1.08 X 20) = 780 CFM Winter Vent Outside Air (44.9% of supply) = 350 CFM Room space sensible gain: 59,597 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 596 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 60,193 Btuh Cooling Supply Air: 60,193 / (.999 X 1.1 X 22) = 2,490 CFM Summer Vent Outside Air (14.1 % of supply) = 350 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 7,693 Btuh 350 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 7,693 Btuh Total sensible gain on air handling system: 67,886 Btuh Room space latent gain: 8,600 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 15,774 Btuh Total latent gain on air handling, system: 24,374 Btuh Total system sensible and latent gain: _ 92,260 Btuh dh6dK Fi ulres _ r Q L ry Total Air Handler Supply Air (based on a 22° TD): 2,490 CFM Total Air Handler Vent. Air (14.06% of Supply): 350 CFM Total Conditioned Air,Space: 1,745 Sq.ft Supply Air Per Unit Area: 1.4267 CFM/Sq.ft Area Per Cooling Capacity: 227.0 Sq.ft/Ton Cooling Capacity Per Area: 0.0044 Tons/Sq.ft Heating Capacity Per Area: 16.79 Btuh/Sq.ft Total Heating Required With Outside Air: 29,298 Btuh Total Cooling Required With Outside Air: 7.69 Tons Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chvac - Full'Commercial HVAC Loads Calcalation'Program"* Elite Software Development, Inc. Fort Pierce Engineering Accelerated Academies . Pierce.Fort FL� 3 950 Page Air Handler #2 - RTU 2 - Summaly Loads Rm.`° Descripti'on ' Area HtgIoss' `Sen.Gain Lat.Gain 1-"Htg.O.A. 1 Clg`;0..4:` No Room Peak Time 'People Htg.CFM '-CIg.CFM S.Exh Req.CFMIJ, Req.CFM . ; �° �� '� ..,.. .. ...UoluM _ �' ,FWS ftv �- CFM/S ft - ; �� ° W..Exh -' d;Act.CFMi - ' Act..CFM Reception / Collab / 7 Cafe 4pm August 8 RR 2 3pm August 9 RR 3 2pm August Room Peak Totals: Total Rooms: 3 Unique Rooms: 3 1,720 9,687 52,857 7,600 Direct Direct 38 449 2,207 0 331 331 17,200 0.26 1.28 0 331 338 49 487 1,050 200 Direct Direct 1 23 44 0 9 9 490 0.46 0.89 0 17 7 49 81 861 200 Direct Direct 1 4 36 0 9 9 490 0.08 0.73 0 3 6 -..-..-------- -- 1,818 10,256 54,768 8,000 40 475 2,287 0 350 350 18,180 0.26 1.26 0 350 350 Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Full Commercial HVAC Loads Calculation Proqram Elite Software Development, Inc.. �.','2ttaPi'ercc e Engmeerinq Accelerated Academies, s _ Air Handler ##2 - RTU 2 - Total Load Summar Air Handler Description: RTU 2 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.22 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.87 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 4pm in August. Outdoor Conditions: Clg: 95° DB, 80° WB, 131.77 grains, Htg: 42° DB Indoor Conditions: Clg: 750 DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 10,256 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 12,463 Btuh 350 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 22,718 Btuh Heating Supply Air: 10,256 / (.999 X 1.08 X 20) = 475 CFM Winter Vent Outside Air (73.6% of supply) = 350 CFM Room space sensible gain: 54,749 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 547 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 55,296 Btuh Cooling Supply Air: 55,296 / (.999 X 1.1 X 22) = 2,287 CFM Summer Vent Outside Air (15.3% of supply) = 350 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 7,693 Btuh 350 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 7,693 Btuh Total sensible gain on air handling system: 62,989 Btuh Room space latent gain: 8,000 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 15,774 Btuh Total latent gain on air handling system: 23,774 Btuh Total system sensible and latent gain: 86,763 Btuh .Check•Fi`�ures � Total Air Handler Supply Air (based on a 22' TD): 2,287 CFM Total Air Handler Vent. Air (15.30% of Supply): 350 CFM Total Conditioned Air Space: 1,818 Sq.ft Supply Air Per Unit Area: 1.2580 CFM/Sq.ft Area Per Cooling Capacity: — 251.4 Sq.ft/Ton Cooling Capacity Per Area: 0.0040 Tons/Sq.ft Heating Capacity Per Area: 12.50 Btuh/Sq.ft Total Heating Required With Outside Air: 22,718 Btuh Total Cooling Required With Outside Air: 7.23 Tons Zft ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM FuII Commercial HVAC Loads Calculation`Program 'Foh'e Elite Software Development, Inc. �Chvac; Fort'Pierce Engineering H Accelerated Academies ce FL 34050 . - a Air Handler #3 - RTU 3 - Summaty Loads Rm Description ' Area Htg.L:oss Sen.Galn Lat.Gain Htg.O A.1 . 'CIg'.O.A. 'No Room, Peak Tlme' . Peop`fe Htg.CFM_ M' C�FM � `�� S.Exh t Req.,CFM. "� Req.CFM e Volume. _... CFM%Sft -CF.MIS: ft1N,Exh a ActCFM'� Act.CFM 10 Open Collaboration 930 6,625 36,142 4,800 Direct Direct 4pm August 24 307 1,582 0 239 239 9,300 0.33 1.70 0 247 245 11 RR 4 42 69 774 200 Direct Direct 2pm August 1 3 34 0 11 11 420 0.08 0.81 0 3 5 Room Peak Totals: 972 6,695 36,916 5,000 Total Rooms: 2 25 310 1,616 0 250 250 Unique Rooms: 2 9,720 0.32 1.66 0 250 250 Z:1... \Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chvac Full Commer`c�al HVAC Loads Calculation Program ^ a Fort FierceEngmeerm,A Ehte Software Development, Inc , Accelerated Academies.' _- o .v..i . x •9.. .e. a.. r n-. .: .ek1 e re Y .. 'i X. Air Handler #3 - RTU 3 - Total Load SumMar Air Handler Description: RTU 3 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.15 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.88 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 4pm in August. Outdoor Conditions: Clg: 95' DB, 80' WB, 131.77 grains, Htg: 42' DB Indoor Conditions: Clg: 75° DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 6,695 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 8,902 Btuh 250 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 15,597 Btuh Heating Supply Air: 6,695 / (.999 X 1.08 X 20) = 310 CFM Winter Vent Outside Air (80.6% of supply) = 250 CFM Room space sensible gain: 36,906 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 387 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 37,293 Btuh Cooling Supply Air: 37,293 / (.999 X 1.1 X 21) = 1,616 CFM Summer Vent Outside Air (15.5% of supply) = 250 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 5,495 Btuh 250 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 5,495 Btuh Total sensible gain on air handling system: 42,788 Btuh Room space latent gain: 5,000 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 11,267 Btuh Total latent gain on air handling system: 16,267 Btuh Total system sensible and latent gain: 59,055 Btuh Cleck.F' ures Total Air Handler Supply Air (based on a 21' TD): 1,616 CFM Total Air Handier Vent. Air (15.47% of Supply): 250 CFM Total Conditioned Air Space: 972 Sq.ft Supply Air Per Unit Area: 1.6624 CFM/Sq.ft Area Per Cooling Capacity: 197.5 Sq.ft/Ton Cooling Capacity Per Area: 0.0051 Tons/Sq.ft Heating Capacity Per Area: 16.05 Btuh/Sq.ft Total Heating Required With Outside Air: 15,597 Btuh Total Cooling Required With Outside Air: 4.92 Tons Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM ChC Loads Calculation Rrogram Elite Sott re'Development, Inc: ForfaPierce E"ngmeen q Accelerated Academies Fort: ce � Air Handier #4 - RTU 4 - Summaty Loads 12 13 14 15 16 Open Collaboration 172 516 2pm August 2 24 1,720 0.14 Multi Purpose 1 288 4,795 4pm August 8 222 2,880 0.77 Testing 396 653 2pm August 10 30 3,960 0.08 File 170 281 2pm August 2 13 1,700 0.08 Utility ............ ....... 42 ..... 69 2pm August 1 3 420 0.08 Room Peak Totals: 1,068 6,314 Total Rooms: 5 23 293 Unique Rooms: 5 10,680 0.27 2,708 400 Direct Direct 118 0 40 40 0.69 0 20 19 21,175 1,600 Direct Direct 923 0 67 67 3.20 0 190 152 7,441 2,000 Direct Direct 324 0 93 93 0.82 0 26 54 2,621 400 Direct Direct 114 0 40 40 0.67 0 11 19 _ - 774 .._ .... 200 ..... ... . Direct - - Direct 34 0 10 10 0.80 0 3 6 34,719 4,600 1,513 0 250 250 1.42 0 250 250 Z:1... \Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM Chuacy rFull Commercial HVAC'Loatls calculation Paogratn ff F ` jEhte Software Deuelopment,'In`c FortP�erceEhgmeennq=r � �r AcceleratedAcatlmies k u;� 'g }x ,r ra.. .'^r 'pr rt ,ag a. P`er•^a ea"'' r x.''r oPi rfL.34 _ ...<,.�._, ar. h �.a�I... ,.r,. a_�� 2,. Air.Handler 4 RTU 4 o Total Load Summar Air Handler Description: RTU 4 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.14 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.88 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 4pm in August. Outdoor Conditions: Clg: 95' DB, 80' WB, 131.77 grains, Htg: 420 DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 6,314 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 8,902 Btuh 250 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 15,216 Btuh Heating Supply Air: 6,314 / (.999 X 1.08 X 20) = 293 CFM Winter Vent Outside Air (85.4% of supply) = 250 CFM Room space sensible gain: 34,552 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 362 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 34,914 Btuh Cooling Supply Air: 34,914 / (.999 X 1.1 X 21) = 1,513 CFM Summer Vent Outside Air (16.5% of supply) = 250 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 5,495 Btuh 250 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 5,495 Btuh Total sensible gain on air handling system: 40,409 Btuh Room space latent gain: 4,600 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 11,267 Btuh Total latent gain on air handling system: 15,867 Btuh Total system sensible and latent gain: 56,276 Btuh Sx,? di e��,. � � ? .M�a"�."�+s a• ,.rc�s"� &a,„ rr�,V^ �s`�i Total Air Handler Supply Air (based on a 21' TD): 1,513 CFM Total Air Handler Vent. Air (16.53% of Supply): 250 CFM Total Conditioned Air Space: 1,068 Sq.ft Supply Air Per Unit Area: 1.4165 CFM/Sq.ft Area Per Cooling Capacity: 227.7 Sq.ft/Ton Cooling Capacity Per Area: 0.0044 Tons/Sq.ft Heating Capacity Per Area: 14.25 Btuh/Sq.ft Total Heating Required With Outside Air: 15,216 Btuh Total Cooling Required With Outside Air: 4.69 Tons Z:\ ...\Accelerated Academies Heat Load.CH8 Friday, December 17, 2021, 03:24 PM