HomeMy WebLinkAboutTRUSSLumber design values are in accordance with ANSI/TPI 1 section 6.3
These truss designs rely on lumber values established by others.
MiTek'
RE: 77930 - BILLIS RESIDENCE
Site Information:
Customer Info: Deborah & Stephen Billis
Lot/Block: .
Address: Unknown, .
City: St Lucie County
Project Name: Billis Residence Model: .
Subdivision: .
State: FL
MiTek USA, Inc.
6904 Parke East Blvd.
Tampa, FL 33610-4115
Name Address and License # of Structural Engineer of Record, If there is one, for the building.
Name: License #:
Address:
City: State:
General Truss Engineering Criteria & Design Loads (Individual Truss Design Drawings Show Special
Loading Conditions):
Design Code: FBC2020/TP12014 Design Program: MiTek 20/20 8.4
Wind Code: ASCE 7-16 Wind Speed: 165 mph
Roof Load: 45.0 psf Floor Load: N/A psf
This package includes 48 individual, Truss Design Drawings and 0 Additional Drawings.
With my seal affixed to this sheet, I hereby certify that I am the Truss Design Engineer and this index sheet
conforms to 61G15-31.003, section 5 of the Florida Board of Professional Engineers Rules.
No.
Seal#
Truss Name
Date
No.
Seal# .
Truss Name
Date
1
T25912298
A
11/9/21
15
T25912312
G1
11/9/21
2
T25912299
Al
11/9/21
16
T25912313
G2
11/9/21
3
T25912300
A2
11/9/21
17
T25912314
G3
11/9/21
4
T25912301
A3
11/9/21
18
T25912315
G4
11/9/21
5
T25912302
D
11/9/21
19
T25912316
G5
11/9/21
6
T25912303
D1
11/9121
20
T25912317
G6
11/9/21
7
T25912304
D2
11/9/21
21
T25912318
GR5
11/9/21
8
T25912305
D3
11/9/21
22
T25912319
GRA
11/9/21
9
T25912306
D4
11/9/21
23
T25912320
GIRD
11/9/21
10
T25912307
D5
11/9/21
24
T25912321
GRG
11/9/21
11
T25912308
D6
11/9/21
25
T25912322
GRK
11/9/21
12
T25912309
D7
11/9/21
26
T25912323
A
11/9/21
13
T25912310
D8
11/9/21
27
T25912324
J3
11/9/21
14
T25912311
G
11/9/21
28
T25912325
J3A
11/9/21
This item has been electronically signed and sealed by Velez, Joaquin, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies
The truss drawing(s) referenced above have been prepared by
MiTek USA, Inc. under my direct supervision based on the parameters
provided by Chambers Truss.
Truss Design Engineer's Name: Velez, Joaquin
My license renewal date for the state of Florida is February 28, 2023.
IMPORTANT NOTE: The seal on these truss component designs is a certification
that the engineer named is licensed in the jurisdiction(s) identified and that the
designs comply with ANSI/TPI 1. These designs are based upon parameters
shown (e.g., loads, supports, dimensions, shapes and design codes), which were
given to MiTek or TRENCO. Any project specific information included is for MiTek's or
TRENCO's customers file reference purpose only, and was not taken into account in the
preparation of these designs. MiTek or TRENCO has not independently verified the
applicability of the design parameters or the designs for any particular building. Before use,
the building designer should verify applicability of design parameters and properly
incorporate these designs into the overall building design per ANSI/TPI 1, Chapter 2.
PQUiN VFW i�i
No 68182
�:• STATE OF :�44/Z
AI
Joaquin Velez PE No.68182
MR USA, Mo. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
Velez, Joaquin 1 of 2
NEI 0
M!Tek 0
RE: 77930 - BILLIS RESIDENCE
Site Information:
MiTek USA, Inc.
6904 Parke East Blvd.
Tampa, FL 33610-4115
Customer Info: Deborah & Stephen Billis Project Name: Billis Residence Model: .
Lot/Block: . Subdivision: .
Address: Unknown, .
City: St Lucie County State: FL
No. Seal# Truss Name Date
29
T25912326
J5
11/9/21
30
T25912327
J5P
11/9/21
31
T25912328
J7
11/9/21
32
T25912329
RA
11/9/21
33
T25912330
JA
11/9/21
34
T25912331
JA3
11/9/21
35
T25912332
JA5
11/9/21
36
T25912333
JC5
11/9/21
37
T25912334
K
11/9/21
38
T25912335
KJ5
11/9/21
39
T25912336
KJ7
11/9/21
40
T25912337
KJA
11/9/21
41
T25912338
MV2
11/9/21
42
T25912339
MV4
11/9/21
43
T25912340
PBA
11/9/21
44
T25912341
PBB
11/9/21
45
T25912342
V4
11/9/21
46
T25912343
V8
11/9/21
47
T25912344
V12
11/9/21
48
T25912345
V16
11/9/21
2 of 2
Job
Truss
Truss Type
City
Ply
BILLIS RESIDENCE
T25912298
77930
A
Hip
2
1
Job Reference (optional)
EFS , rurvr r rie rya, rL - oyaoc, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:47 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-72_9tms8p8fAM_T8575Szkfw5zzBvUal P7ryWsyLHIo
2-0-0 6-3.8 9-0-0 13.8-0 18-0-0 21-0-7 27-4-0 29-4-0
2-0-0 6-3-8 2 8 7 4 8 0 4-8-0 2 8 7 639 2-0-0
Scale = 1:51.5
4x4 =
3x4 =
215 22
04 =
3x5 = 3x8 = ""'" — 3x8 = 3x5 =
9-M
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/rP12014
CSI.
TC 0.30
BC 0.51
WB 0.28
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) I/defl Ud
-0.12 10-18 >999 360
-0.28 10-18 >999 240
0.06 8 n/a n/a
0.09 10-12 >999 240
PLATES GRIP
MT20 244/190
Weight: 134 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-7-4 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 7-7-6 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 8=0-8-0
Max Horz 2=-224(LC 10)
Max Uplift 2=-758(LC 12), 8=758(LC 12)
Max Grav 2=1375(LC 1),8=1375(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-2163/1204, 3-4=1887/1114, 4-5=1646/1035, 5-6=1846/1035, 6-7=1887/1114,
7-8=-2163/1204
BOT CHORD 2-12=-861/1884, 10-12=-823/1834, 8-10=-916/1863
WEBS 3-12=397/350, 4-12=-348/633, 5-12=347/236, 5-10=-347/237, 6-10=-348/633,
7-10=-398/350
NOTES -
I) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=27ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 9-0-0, Extedor(2R)
9-0-0 to 13-2-15, Interior(1) 13-2-15 to 18-4-0, Exterior(2R) 18-4-0 to 22-6-15, Interior(1) 22-6-15 to 29-4-13 zone;C-C for members
and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
This item has been
4) Provide adequate drainage to prevent water ponding.
electronically Signed and
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
'
Sealed by Velez, Joaquin, PE
6) This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
using a Digital Signature.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 758 lb uplift at joint 2 and 758 lb uplift at
Printed copies of this
joint 8.
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc: FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
--
Design valid for use only with MTeke1 connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall Inv ff
building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSOP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldod, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
13ILLIS RESIDENCE
T25912299
77930
Al
Hip
2
1
Job Reference (optional)
Chambers Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:48 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-bFYX56tmaSnl_81 KfgchWxC5FMLHevlAenaW2lyLHln
-2 O O 5-9 4 11-0-0 16-4-0 21-0-12 27-4-0 29-4-0
2-0-0 5-9-4 5-2-12 5-4-0 5-2-12 5-9-4 2-0-0
4x8 =
4x5 =
4 22 2324 25 5
Scale = 1:51.5
It
3x4 = 2x3 II 3x4 = — — 3x8 = 2x3 II 3x4 =
12
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TP12014
CSI.
TC 0.28
BC 0.33
WB 0.44
Matrix -MS
DEFL. in (loc) Vdefl L/d
Vert(LL) -0.06 12 >999 360
Vert(CT) -0.15 12-13 >999 240
Horz(CT) 0.06 7 n/a n/a
Wind(LL) 0.09 12 >999 240
PLATES GRIP
MT20 244/190
Weight: 144 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-9-2 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 7-6-10 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 7=0-8-0
Max Horz 2=-264(LC 10)
Max Uplift 2=-758(LC 12), 7=758(LC 12)
Max Grav 2=1375(LC 1),7=1375(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-2238/1226, 3-4=-1706/1022, 4-5=1456/996, 5-6=1707/1022, 6-7=-2238/1226
BOT CHORD 2-13=-894/1993, 12-13=-894/1993, 10-12=-566/1455, 9-10=-949/1934,
7-9=-949/1934
WEBS 3-12=-626/415, 4-12=-1671418, 5-1 0=1 57/419, 6-10=625/415
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=27ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 11-0-0, Extedor(2R)
11-0-0 to 15-2-15, Interior(1) 15-2-15 to 16-4-0, Extedor(2R) 16-4-0 to 20-6-15, Interior(1) 20-6-15 to 29-4-13 zone;C-C for members
and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 pelf bottom chord live load nonconcurrent with any other live loads.
This item has been
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
electronically signed and
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 758 lb uplift at joint 2 and 758 lb uplift at
Sealed by Velez, Joaquin, PE
joint 7.
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING - Vedfy design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
•
a truss system. Before use, the building designer must vedly the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek`
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI?P/f Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912300
77930
A2
Hip
2
1
('k-- T�, n
Job Reference (optional)
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:50 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-XdgHVovl631 IDRBjm Ff9bMHQhA196jKT553c7ByLHII
2-M 6-94 13-0-0 14 4-0 20b-12 27.4-0 29-4-0
2 0 0 6-9-4 6-2-12 1 4-0 6-2-12 6-9 4 2-0-0
Scale = 1:54.7
4x5 r
4x5 =
6.00 12 5 24 625
3x4 = 2x3 II 3x6 = 24 11 3x4 =
3x4 = 3x4 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TIC 0.34
BC 0.37
WB 0.79
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in floc) I/deft L/d
-0.07 11-12 >999 360
-0.1711-12 >999 240
0.06 9 n/a n/a
0.09 12 >999 240
PLATES GRIP
MT20 2441190
Weight: 141 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-8-7 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 7-9-8 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 9=0-8-0
Max Horz 2=-305(LC 10)
Max Uplift 2=-758(LC 12), 9=758(1_C 12)
Max Grav 2=1375(LC 1), 9=1375(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-4=-2196/1159, 4-5=-1532/914, 5-6=1279/897, 6-7=-1532/914, 7-9=2196/1159
BOT CHORD 2-15=-820/1964, 14-15=-820/1964, 12-14=-429/1279, 11-12=-876/1887, 9-11=-876/1887
WEBS 4-15=0/282, 4-14=801/511, 5-14=225/420, 6-12=-225/420, 7-12=802/511, 7-11=0/282
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=27ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 13-0-0, Exterior(2E)
13-0-0 to 14-4-0, Exterior(2R) 14-4-0 to 18-6-15, Interior(1) 18-6-15 to 29-4-13 zone;C-C for members and forces & MWFRS for
reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
This Item has been
6) . This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
electronically signed and
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 758 lb uplift at joint 2 and 758 lb uplift at
sealed by Velez, Joaquin, PE
joint 9.
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEk REFERENCE PAGE MII-7473 rev. 5I79/2020 BEFORE USE. _ _=�•
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek*
1Tel.'
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the fIY� iC
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSYTP11 quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912301
77930
A3
Common
3
1
Job Reference (optional)
unamoers 1 russ, Tort Pierce, FL - 34962, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:51 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-UOo2wUwHehHTSIL5tghdgnNIV fcahamZPYjB5yLHlj
-211 7-1-4 13-8-0 20-2-12 27-4-0 29-4-0
2-0-0 7-1-4 6-6-12 6-6-12 7-1-4 2-M
4x5 =
6.00 12
3x5
Scale = 1:50.7
3x5 =
IY
0
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.39
BC 0.59
WB 0.55
Matrix -MS
DEFL. in (loc) I/defl Ud
Vert(LL) -0.17 10-12 >999 360
Vert(CT) -0.32 12-15 >999 240
Horz(CT) 0.06 8 n/a n/a
Wind(LL) 0.09 12-15 >999 240
PLATES GRIP
MT20 244/190
Weight: 128 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 4-5-6 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 7-7-5 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 8=0-8-0
Max Horz 2=-318(LC 10)
Max Uplift 2=758(LC 12), 8=758(LC 12)
Max Grav 2=1545(LC 17). 8=1545(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-4=-2371/1212, 4-5=-2150/1187, 5-6=2150/1187, 6-8=2372/1212
BOT CHORD 2-12=867/2277, 10-12=-426/1450, 8-10=-912/2040
WEBS 5-10=-426/987, 6-10=-553/477, 5-12=-426/987, 4-12=-552/477
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=27ft; eave=4ft; Cat.
Il; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 13-8-0, Extedor(2R)
13-8-0 to 16-8-0, Interior(1) 16-8-0 to 29-4-13 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60
plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.0psf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
This item has been
will fit between the bottom chord and any other members, with BCDL = 10.0psf.
electronically signed and
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 758 lb uplift at joint 2 and 758 lb uplift at
sealed b Velez, Joaquin, PE
y q
joint 8.
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68162
MiTek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7470 rev. 5/192020 BEFORE USE.
--
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP11 Quality Criteria, DSB-89 and BCSI Building Component
6904 Padre East Blvd.
Safety information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912302
77930
D
Hip
1
1
Job Reference (optional)
----- -- . _....- - - - •---, uy � en niuusulna, nlu. IVIun Ivuv o ua:cl.00 �uZ I rage -I
IDAtBbed8VbYEjpOwaV5X9TayML6T-yCMQ8pxv0_PK4vwHRNCsD_vwhNwgJ8bwo31GkWYLHli
2-0-0 6-3-8 9-0A 15-2-14 21-4-0 27-5-2 33 8-0 36�-7 42-8-0
2-0-0 6 3-8 2.8-7 6-2-14 6-1-2 6-1-2 6-2-14 2 8 8 639
Scale = 1:75.0
5x6 =
3x4 = 46 =3x8 = 3x4 =
5x6
6.00 12 4 25 26 5 6 7 278 28 9
3x4 \
3x4
3
10
29
24
30
23
2
18 17 16 15 14 13 12
4x6 — 4x8 = 5x8 = 3x4 II 4x4 = 4x8 =
44 = 5x8 =
06 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.42
BC 0.88
WB 0.56
Matrix -MS
DEFL. in
Vert(LL) -0.28
Vert(CT) -0.64
Horz(CT) 0.18
Wind(LL) 0.40
(loc) Vdeft L/d
15 >999 360
15 >802 240
11 n/a n/a
15 >999 240
PLATES GRIP
MT20 244/190
Weight: 254 Ib FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
Structural wood sheathing directly applied or 3-4-0 oc purlins.
BOT CHORD 2x6 SP No.2 BOT CHORD
Rigid ceiling directly applied or 4-10-2 oc bracing.
WEBS 2x4 SP No.3 WEBS
1 Row at midpt 5-18, 8-12
REACTIONS. (size) 11=0-8-0, 2=0-8-0
Max Horz 2=232(LC 11)
Max Uplift 11=-921(LC 12), 2=1096(LC 12)
Max Grav 11=1917(LC 1), 2=2068(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3747/2083, 3-4=-3488/1990, 4-5=3109/1834, 5-7=-4232/2438, 7-8=-4240/2482,
8-9=-3134/1872,9-10=-3519/2041,10-11=-3766/2123
BOT CHORD 2-18=-1755/3283, 16-18=-2141/4232, 15-16=-2345/4612, 14-15=2345/4612,
12-14=-2185/4240, 11-12=1769/3319
WEBS 3-18=-375/345, 4-18=-686/1273, 5-18=1461/800, 5-16=-97/415, 7-16=-530/253,
7-15=0/270, 7-14=522/233,8-14=-81/409,8-12=-1449/756,9-12=-693/1292,
10-12=-391/357
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 9-0-0, Exterior(2R) 9-0-0
to 16-2-14, Interior(1) 15-2-14 to 33-8-0, Exterior(2R) 33-8-0 to 39-8-7, Interior(1) 39-8-7 to 42-8-0 zone;C-C for members and forces
& MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
This item has been
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
electronically signed and
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
Sealed b Velez, Joaquin, PE
y q
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
using a Digital Signature.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Printed copies of this
will fit between the bottom chord and any other members.
document are not Considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 921 lb uplift at joint 11 and 1096 lb uplift
signed and sealed and the
at joint2.
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cott 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE. _-:�•
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not L---LL.•••�_JJJYYYtttq
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing Mi l4
ek•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP/f quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912303
77930
D1
Hip
1
1
Job Reference (optional)
Chambers Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:54 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-QPvoL9yX91XBi3VU75j51CS4pnL62cQ30j 1 gGyyLHlh
-2-0-0 5-9- 11-0-0 17-11-0 24.8-12 31-8-0 36-10-12 42-8-0
2.0-0 5-9� 5-2-12 6-11.4 6-9-8 6-11-4 5-2-12 5-9_4
m
d
5x6 =
27
3x6
3x4 11 3x8 = 5x6 WB =
=
3x4 = 4x6 =
28 5 6
3x8 =
7 29 30
5x6 =
31 8
5x6 WB = 3x8 = 3x4 11
5-94 , 11-0-0 17-11-4 24-8-12 31-8-0
Scale = 1:75.3
34 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.46
BC 0.56
WB 0.46
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) I/deft Ud
-0.24 14-15 >999 360
-0.55 14-15 >924 240
0.19 10 n/a hire
0.34 14-15 >999 240
PLATES GRIP
MT20 244/190
Weight: 231 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 3-6-1 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 5-4-12 oc bracing.
WEBS 2x4 SP No.3
WEBS
1 Row at midpt 5-17, 7-15, 7-12
OTHERS 2x4 SP No.3
REACTIONS. (size) 10=0-8-0, 2=0-8-0
Max Horz 2=276(LC 11)
Max Uplift 10=-921(LC 12), 2=1096(LC 12)
Max Grew 10=1917(LC 1), 2=2068(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3750/2071, 3-4=-3251/1863, 4-5=-2856/1759, 5-7=3641/2170, 7-8=2868/1766,
8-9=-3265/1889, 9-10=-3800/2111
BOT CHORD 2-18=-1765/3289, 17-18=-1765/3289, 15-17=181313641, 14-15=1838/3646,
12-14=-1838/3646, 11-12=1777/3333, 10-11 =1 777/3333
WEBS 3-17=-612/428, 4-17=-510/1023, 5-17=1107/567, 5-15=0/275, 7-14=0/274,
7-12=-1100/554, 8-12=-518/1033, 9-12=-659/461
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 11-0-0, Exterior(2R)
11-0-0 to 17-0-7, Interior(1) 17-0-7 to 31-8-0, Extedor(2R) 31-8-0 to 37-8-7, Interior(1) 37-8-7 to 42-8-0 zone;C-C for members and
forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
This item has been
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
electronically signed and
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
sealed by Velez, Joaquin, PE
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
using a Digital Signature.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Printed copies of this
will fit between the bottom chord and any other members.
document are not Considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 921 lb uplift at joint 10 and 1096 lb uplift
signed and sealed and the
at joint 2.
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MITek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
®WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE. *
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSb111711 Duality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Saletylnforma0on available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Oty
Ply
BILLIS RESIDENCE
I
T25912304
77930
D2
Hip
1
1
Job Reference (optional)
�r rau,ual a r 1 u rvl r rrerca, r� - �ryoc, 6.43D S Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:56 2021 Page 1
ID:4tBbed8VbYEjpOwav5X9TayML6T-MnlYmrzohvnvxMfs6WmZrdXMjbxdWPxMU1 WxKryLHlf
2-0-0 2 8 0 6-0-0 13-0-0 141 0 22-2-0 29-8-0 35-10-12 42-8.0
2-0-0 2-8-0 3-4-0 7-0-0 1-B-0 7-6-0 7-6-0 6-2-12 6-9-4
r�
d
Scale = 1:77.9
5x8 =
6.00 12 06 = 5x8 =
5 30 6 31 7 8 32 33 9
10x18 MT20HS = 1O -10 1s 12
7x8 = 6x8 = 4x6 = 3x6 =
4x12
4.00 F12
13-0-0
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.76
BC 0.94
WB 0.91
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(ILL)
in (loc) I/deft Ud
-0.32 15-16 >999 360
-0.68 15-16 >752 240
0.32 11 n/a n/a
0.37 6 >999 240
PLATES
MT20
MT20HS
Weight: 260 lb
GRIP
244/190
187/143
FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 2-2-0 oc purlins.
BOT CHORD 2x4 SP M 30 'Except'
BOT CHORD
Rigid ceiling directly applied or 2-2-0 oc bracing.
2-21: 2x6 SP No.2, 2-20: 2x6 SP 240OF 2.0E
WEBS
1 Row at midpt 4-18, 8-17
WEBS 2x4 SP No.3 *Except*
15-17: 2x4 SP M 30
REACTIONS. (size) 11=0-8-0, 2=0-8-0
Max Horz 2=320(LC 11)
Max Uplift 11=-921(LC 12). 2=-1096(LC 12)
Max Grav 11=2216(LC 18), 2=2351(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-7831/3618, 3-4=4491/3467, 4-5=3812/1947, 5-6=3498/1939, 6-8=3488/1938,
8-9=-3472/1978,9-10=-3456/1811,10-11=-4250/2082
BOT CHORD 19-20=-2334/5148, 18-19=2334/5159, 17-18=1437/3462, 6-17=372/290,
15-16=-202/620, 13-15=-1280/2930, 12-13=-1746/3725, 11-12=-1746/3725,
2-20=-3206/7271
WEBS 4-19=0/308, 4-'18=1807/950, 5-18=312/921, 5-17=-390/692, 15-17=-1371/2946,
8-15=596/425, 9-15=-375/823, 9-13=-220/711, 10-13=-923/549, 10-12=0/270,
3-20=-269/501, 4-20=-881/2209
NOTES-
1) Unbalanced roof live loads have been considered for this design
M
d
0
fata
2) Wind: ASCE 7-16; Vuit=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
This item has been
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 13-0-0, Exterior(2R)
electronically signed and
13-0-0 to 19-0-7, Interior(1) 19-0-7 to 29-8-0, Exterior(2R) 29-8-0 to 35-10-12, Interior(1) 35-10-12 to 42-8-0 zone;C-C for members
sealed b Velez, Joaquin, PE
y q
and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
using a Digital Signature.
to the use of this truss component.
Printed Copies Of this
4) Provide adequate drainage to prevent water ponding.
document are not Considered
5) All plates are MT20 plates unless otherwise indicated.
signed
red and sealed and the
6) All plates are 3x4 MT20 unless otherwise indicated.
7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
signature must be Verified
8) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
on any electronic copies.
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
Joaquin Velez PE No.68182
9) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
MiTek USA, Inc. FL Cart 6834
Capacity of bearing surface.
6904 Parke East Blvd. Tampa FL 33610
10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 921 Ito uplift at joint 11 and 1096 lb
Data:
uplift at joint 2.
November 9,2021
WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MTelc® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall my
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MO 20601 Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
BILLISRESIDENCE
T25912305
77930
D3
Hip
1
1
Job Reference o tionai
Unarnuers Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:21:58 2021 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-IA9JBX?2DX1cAgoFEwolw2debOd3_KcfxL?1 PjyLHld
-2-0-0 , 2 8-0 7-0-0 14-8-0 15r0-0 21-4-0 27 8-0 3410-0 42-M
2-0-0 ' 29 ' 4-0-0 7.8-0 0.4-0 6.4-0 6-4-0 7-21 7-10-0
5x6 =
6.00 12
3x8 = 5x6 =
29
Scale = 1:77.9
3x4 II 3x4 II 16 1D 14 n6 17
6x10 = 5x6 = 5x6 WB = 3x4 I I 3x6 =
4x12q$p11f8 MT20HS = 3x4 I I 3x8 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.93
BC 0.94
WB 0.83
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) Udefl Ud
-0.37 17-18 >999 360
-0.79 17-18 >645 240
0.34 10 n/a n/a
0.36 17 >999 240
PLATES
MT20
MT20HS
Weight: 255 lb
GRIP
244/190
187/143
FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
Structural wood sheathing directly applied.
BOT CHORD 2x4 SP M 30 *Except* BOT CHORD
Rigid ceiling directly applied or 2-2-0 oc bracing.
2-20: 2x6 SP No.2, 2-19: 2x6 SP 240OF 2.0E WEBS
1 Row at midpt 4-17,
7-13, 9-13, 7-17
WEBS 2x4 SP No.3 *Except*
14-17: 2x4 SP M 30
OTHERS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 10=0-8-0
Max Horz 2=364(LC 11)
Max Uplift 2=-1095(LC 12), 10=-921(LC 12)
Max Grav 2=2371(LC 17), 10=2221(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-7924/3613, 3-4=-7643/3512, 4-6=3549/1851, 6-7=3088/1767, 7-8=2836/1642,
8-9=-3232/1734,9-10=-4199/2048
BOT CHORD 18-19=-2174/4931, 17-18=2174/4928, 13-14=1313/3131, 11-13=1697/3643,
10-11=-1696/3649,2-19=-3202/7390
WEBS 4-18=0/386, 4-17=1825/936, 7-13=578/238, 8-13=-428/1018, 9-13=-1099/629,
9-11=0/331,3-19=192/404,4-19=1063/2574,6-17=-439/1115,14-17=-1279/3025,
7-17=-257/208
NOTES-
1) Unbalanced roof live loads have been considered for this design
2) Wind: ASCE 7-16; Vuit=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
This item has been
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E)-2-0-13 to 2-2-7, Interior(l) 2-2-7 to 15-0-0, Exterior(21R)
electronically signed and
15-0-0 to 21-4-0, Interior(l) 21-4-0 to 27-8-0, Exterior(2R) 27-8-0 to 33-8-7, Interior(1) 33-8-7 to 42-8-0 zone;C-C for members and
sealed by Velez, Joaquin, PE
forces 8r MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
using a Digital Signature.
to the use of this truss component.
Printed copies Of this
4) Provide adequate drainage to prevent water ponding.
document are not considered
5) All plates are MT20 plates unless otherwise indicated.
Signed and Sealed and the
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
signature must be verified
will fit between the bottom chord and any other members, with BCDL = IO.Opsf.
On any electronic Copies.
8) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
Joaquin Velez PE No.68182
capacity of bearing surface.
MiTek USA, Inc. FL Cert 6634
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1095 lb uplift at joint 2 and 921 lb uplift
8904 Parke East Blvd. Tampa FL 33810
at joint 10.
Date:
November 9,2021
WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Ivlll-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing ivi iTek`
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
ss
Truss Type
City
Ply
BILLIS RESIDENCE
FD4
T25912306
77930
Hip
1
1
rr..,...r.., T
Job Reference (optional)
rs russ, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:01 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6Tj[rRpY1 wWSQB 17Xgv3LkXgEBicfKBfc5dJEiO2yLHia
2 0-0 2-8-0 8 8-0 14 8-0 17-0-0 21-0-0 25 8-0 31-1-13 36 7-11 42-5-7
2 0 0 2 8-0 6-0-0 6-0 0 2 4-0 4 4-0 4-4-0 5 5 13 5-5-13 5-9-12
6.00 12
5x6 =
5x6 =
r 31 8 32 9
Scale = 1:76.6
1 0x1 8 MT20HS = 4x6 = 4x5 =
7x10 = WO= 3x8 =
5x14 5
4.00 FIT
25-8-0
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.81
BC 0.84
WB 0.94
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) Vdefl Lid
-0.37 16-17 >999 360
-0.73 16-17 >701 240
0.35 13 n/a n/a
0.39 20-21 >999 240
PLATES GRIP
MT20 2441190
MT20HS 187/143
Weight: 273 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30 *Except'
TOP CHORD
Structural wood sheathing directly applied or 2-2-0 oc purlins.
1-5: 2x4 SP M 31
BOT CHORD
Rigid ceiling directly applied or 5-1-5 oc bracing.
BOT CHORD 2x4 SP M 30 *Except'
WEBS
1 Row at midpt 4-19,
7-19, 7-17, 8-17, 8-16, 10-16
2-22: 2x6 SP No.2, 6-18: 2x4 SP No.3, 2-21: 2x6 SP 240OF 2.0E
WEBS 2x4 SP No.3 *Except*
4-21: 2x4 SP M 30
REACTIONS. (size) 2=0-8-0, 13=0-5-7
Max Horz 2=406(LC 11)
Max Uplift 2=-1091(LC 12), 13=-917(LC 12)
Max Grav 2=2377(LC 17), 13=2242(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-8229/3705, 3-4=-8123/3797, 4-6=3583/1880, 6-7=3540/2033, 7-8=2628/1569,
8-9=-2639/1557, 9-10=2993/1655, 10-12=-3932/1962, 12-13=-4193/2042
BOT CHORD 20-21 =-1 918/4496, 19-20=1918/4495, 6-19=-314/349, 16-17=-110112762,
14-16=-1397/3098. 13-14=1706/3655, 2-21=-3325/7740
WEBS 4-20=01329, 4-19=1411/698, 17-19=925/2694, 7-19=987/1879, 7-17=-426/178,
8-17=-333/185, 8-16=-340/180, 9-16=-482/1025, 10-16=901/558, 10-14=218/657,
12-14=-399/346, 4-21 =-1 574/3514
NOTES-
1) Unbalanced roof live loads have been considered for this design
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=42ft; eave=5ft; Cat.
This item has been
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-3, Interior(1) 2-2-3 to 17-0-0, Exterior(2R)
electronically signed and
17-0-0 to 23-0-1. Interior(1) 23-0-1 to 25-8-0, Exterior(2R) 25-8-0 to 31-8-1, Interior(1) 31-8-1 to 42-5-7 zone;C-C for members and
sealed b Velez, Joaquin, PE
y q
forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
using a Digital Signature.
to the use of this truss component.
Printed copies of this
4) Provide adequate drainage to prevent water ponding.
document are not Considered
5) All plates are MT20 plates unless otherwise indicated.
SI g
signed and sealed and the
6) All plates are 3x4 MT20 unless otherwise indicated.
7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Signature must be Verified
8) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
on any electronic copies.
will fit between the bottom chord and any other members, with SCOL = I O.Opsf.
Joaquin Velez PE No.68182
9) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
MiTek USA, Inc. FL Cert 6634
capacity of bearing surface.
6904 Parke East Blvd. Tampa FL 33610
10) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1091 lb uplift at joint 2 and 917 lb uplift
Date:
at joint 13.
November 9,2021
A WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/1912020 BEFORE USE.
WWI) valid for use only with connectors. This design is based only upon parameters shown, and is for an individual building Component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSM11 Quality Criteda, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Iu:4tt3bedbVbYEjpOwaV5X9TayML6T-f7yCEE3B23gvHRhC1 UOCd5KXBPLnfbQO5djo4xyLHIY
2 0 0 2 8 0 8-8 0 14 8-0 19-0-0 23-M 29-9-13 35-11-11 42-8-0 44-8-0
2 0 0 29 6-0-0 6-0.0 4 4.0 4-8-0 6-1-13 6.1-13 6 8-5 2-0-0
Scale = 1:85.1
5x8 =
6.00 12
5x6 =
M
d
IV6
3x4 11 3x4 11 7x10 = 6x8 — 3x8 —_ 5x6 WE = 3x4 = 3x6 =
5x14 � II
10x18 MT20HS = 3x4
4.00 12
19-0-0
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.81
BC 0.84
WB 0.80
Matrix -MS
DEFL. in (loc) Vdefl L/d
Vert(LL) -0.39 14-16 >999 360
Vert(CT) -0.74 14-16 >687 240
Horz(CT) 0.35 12 n/a n/a
Wind(LL) 0.37 20-21 >999 240
PLATES GRIP
MT20 244/190
MT20HS 187/143
Weight: 278 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 *Except* TOP CHORD
Structural wood sheathing directly applied or 2-2-0 oc purlins.
1-5,10-13: 2x4 SP M 31 BOT CHORD
Rigid ceiling directly applied or 5-4-11 oc bracing.
BOT CHORD 2x4 SP M 30 'Except- WEBS
1 Row at midpt 4-19, 7-19, 7-17, 7-16, 9-16
2-22: 2x6 SP No.2, 6-18: 2x4 SP No.3, 2-21: 2x6 SP 240OF 2.0E
WEBS 2x4 SP No.3 *Except*
4-21: 2x4 SP M 30
OTHERS 2x4 SP No.3
/
REACTIONS. (size) 2=0-8-0, 12=0-8-0
Max Harz 2=-466(LC 10)
Max Uplift 2=-1091(LC 12). 12=1091(LC 12)
Max Grav 2=2378(LC 17),12=2396(LC 18)
FORCES. (lb) -Max. Camp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=8298/3526, 3-4=-8194/3635, 4-6=3593/1838, 6-7=3590/2024, 7-8=2417/1491,
8-9=2755/1561, 9-11=3916/1918, 11-12=-4214/2006
BOT CHORD 20-21=-1732/4566, 19-20=173214565, 6-19=-401/401, 17-18=-114/277, 16-17=-812/2562,
14-16=1264/2964, 12-14=1630/3686, 2-21=-3040/7865
WEBS 4-20=0/331, 4-19=1409/656, 17-19=708/2315, 7-19=892/1813, 7-16=241/292,
8-16=-399/907, 9-16=-1062/627, 9-14=242/852, 11-14=514/378, 4-21=-1477/3575
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
This item has been
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 19-0-0, Exterior(2E)
electronically signed and
19-0-0 to 23-8-0, Exterior(2R) 23-8-0 to 29-9-13, Interior(1) 29-9-13 to 44-8-13 zone;C-C for members and forces & MWFRS for
sealed b VelezJoaquin, PE
Y 9
reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements speck
,
using a Digital Signature.
to the use of this truss component.
Printed Copies Of this
4) Provide adequate drainage to prevent water ponding.
document are not Considered
55) All plates are MT20 plates unless otherwise indicated.
This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Signed and Sealed and the
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
signature must be verified
will fit between the bottom chord and any other members, with BCDL = IO.Opsf.
On any electronic Copies.
8) Bearing at joint(s) 2 considers parallel to grain value using ANSlrrPI 1 angle to grain formula. Building designer should verify
Joaquin Velez PE No.68182
rapacity of bearing surface.
MiTek USA, Inc. FL Cart 6834
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1091 lb uplift at joint 2 and 1091 lb uplift
8904 Parke East Blvd. Tampa FL 33610
at joint 12.
Date:
November 9,2021
® WARNING - Venfy design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not �®
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall rL�•
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing iwiTek�
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery. erection and bracing of trusses and truss systems, see ANSI?PI1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
77930
D6
Piggyback Base
2
1
T25912308
Chambers Truss, Fort
Pierce. FL - 34982
Job Reference (optional)
6.430 s Aug no 2021 MI I ek industries, Inc. Mon Nov 8 09:22:05 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-bW4yfw4RagwdWrb8vQgiWPtgD1 F7VvhYxCv9pyLHIW
2-0 0 2-8-0 B-8-0 6 8-0 19-0-0 2 -U-U 29-9-13 35-11-11 42-8-0 44 8-0
2 0 0 2� 0 6-0-0 6-0-0 4.4-0 4 8-0 6-1-13 6-1-13 6 8-5 2-0-0
Scale = 1:85.1
Sx8 =
8.00 12
5x6 =
IV6
3x4 II 3x4 II 7x10 = 6x8 — 3x8 —_ 5x6 WB = 3x4 = 3x6 =
Sx14 � II
10x18 MT20HS = 3x4
4.00 F12
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Cade FBC2020rrP12014
CSI.
TIC 0.81
BC 0.84
WB 0.80
Matrix -MS
DEFL. in (too) I/defl Ud
Vert(LL) -0.39 14-16 >999 360
Vert(CT) -0.74 14-16 >687 240
Horz(CT) 0.35 12 n/a n/a
Wind(LL) 0.37 20-21 >999 240
PLATES GRIP
MT20 244/190
MT20HS 1871143
Weight: 278 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 *Except* TOP CHORD
Structural wood sheathing directly applied or 2-2-0 cc purlins.
1-5,10-13: 2x4 SP M 31 BOT CHORD
Rigid ceiling directly applied or 5-4-11 cc bracing.
BOT CHORD 2x4 SP M 30 *Except* WEBS
1 Row at micipt 4-19,
7-19, 7-17, 7-16, 9-16
2-22: 2x6 SP No.2, 6-18: 2x4 SP No.3, 2-21: 2x6 SP 240OF 2.0E
WEBS 2x4 SP No.3 *Except*
4-21: 2x4 SP M 30
OTHERS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 12=0-8-0
Max Horz 2=-466(LC 10)
Max Uplift 2=-1091(LC 12). 12=-1091(LC 12)
Max Grav 2=2378(LC 17), 12=2396(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=8298/3526, 3-4=-8194/3635, 4-6=3593/1838, 6-7=3590/2024, 7-8=2417/1491,
8-9=275511561, 9-11=3916/1918, 11-12=-4214/2006
BOT CHORD 20-21=1732/4566, 19-20=1732/4565, 6-19=-401/401, 17-18=114/277, 16-17=-812/2562,
14-16=1264/2964, 12-14=1630/3686, 2-21=-3040/7865
WEBS 4-20=0/331, 4-19=1409/656, 17-19=708/2315, 7-19=892/1813, 7-16=-241/292,
8-16=-399/907, 9-16=1062/627, 9-14=242/852, 11-14=514/378, 4-21=-1477/3575
NOTES-
1) Unbalanced roof live loads have been considered for this design
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; cat.
This item has been
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 19-0-0, Exterior(2E)
electronically signed and
19-0-0 to 23-8-0, Exterior(2R) 23-8-0 to 29-9-13, Interior(1) 29-9-13 to 44-8-13 zone;C-C for members and forces & MWFRS for
sealed b VelezJoaquin, PE
y q
reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
,
using a Digital Signature.
to the use of this truss component.
Printed Copies of this
4) Provide adequate drainage to prevent water ponding.
document are not considered
5) All plates are MT20 plates unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Signed and Sealed and the
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
signature must be verified
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
On any electronic Copies.
8) Bearing at joint(s) 2 considers parallel to grain value using ANSIrrPI 1 angle to grain formula. Building designer should verify
Joaquin Velez PE No.68182
capacity of bearing surface.
MiTek USA, Inc. FL Cart 6634
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1091 lb uplift at joint 2 and 1091 lb uplift
8904 Parke East Blvd. Tampa FL 33610
at joint 12.
Data:
November 9,2021
® WARNING - Vedfy design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mil-7473 rev. 5/19/2020 BEFORE USE. __=�'
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual budding component, not G---GG_•••�JJJfifiY CCCg777
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall p �
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing iViiTek�
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUfP/f Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
77930 ID7
Truss
Piggyback Base
T25912309
r�
a
ars Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MTek Industries, Inc. Mon Nov 8 09:22:06 2021 Page 1
ID:4tBbed8VbYEjp OwaV5X9TayML6T3ieKsG53L_2U8vQ ni cxvEkyBXdN eszFgnbxThGyLH IV
2-0-0 6 8 5 12-103 19-0-0 23.8-0 29-9-13 35-11-11 42-8-0 44-M
2-0 0 6 8 5 6-1-13 6-1-13 4-8-0 6-1-13 6-1-13 6_ 2 0 0
Scale = 1:77.7
5x6 =
6.00 12 5x8 =
3x6 = 3x4 = 5x6 WB = 3x8 = 3x4 = 5x8 WB = 3x4 = 3x6 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020ITP12014
CSI.
TC 0.42
BC 0.83
WB 0.73
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) Udefl L/d
-0.36 13-15 >999 360
-0.67 13-15 >764 240
0.17 11 n/a n/a
0.24 13-15 >999 240
PLATES GRIP
MT20 244/190
Weight: 245 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly applied or 3-2-15 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD Rigid ceiling directly applied or 5-8-11 oc bracing.
WEBS 2x4 SP No.3
WEBS
1 Row at midpt 5-16. 7-16. 8-15
OTHERS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 11=0-8-0
Max Horz 2=466(LC 11)
Max Uplift 2=-1091(LC 12), 11=1091(LC 12)
Max Grav 2=2414(LC 17). 11=2416(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-4254/2006, 3.5=-3958/1918, 5-6=2792/1561, 6-7=2451/1492, 7-8=2795/1561,
8-10=3962/11918, 10-11=-4259/2006
BOT CHORD 2-18=-1578/4070, 16-18=-1213/3350, 15-16=-833/2535, 13-15=-1265/3003,
11-13=-1629/3725
WEBS 3-18=-511/377, 5-18=241/855, 5-16=1066/627, 6-16=-412/932, 7-16=266/270,
7-15=-407/1035, 8-15=1068/628, 8-13=-241/857, 10-13=-511/377
c�
2IV.
6
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 19-0-0, Exterior(2E)
19-0-0 to 23-8-0, Exterior(2R) 23-8-0 to 29-9-13, Interior(1) 29-9-13 to 44-8-13 zone;C-C for members and forces & MWFRS for
reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
This item has been
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
electronically signed and
to the use of this truss component.
sealed by Velez, Joaquin, PE
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
using a Digital Signature.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chard in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Printed copies of this
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
document are not Considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1091 Ib uplift at joint 2 and 1091 lb uplift
signed and sealed and the
at joint 11.
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MIT& USA, Inc. FL Cert 8834
6904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/1912020 BEFORE USE.
--
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing iVliTek`
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing oftrusses and truss systems, see ANSM11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912310
77930
D8
PIGGYBACK BASE
7
1
Job Reference (optional)
:rb !rubs, Fort Pierce, FL - 34982, 8,430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:08 2021 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-05m5Hy6JsbICNCZAplzNK91VzQ5sKwH7EuQZm8yLHIT
2 0 0 65� 12-4-0 19-0.0 23-8-0 29-9-13 3111-11 42-8-0 44-8-0
2-0-0 6 5 4 5-10-12 6 8-0 4-8 0 6 1-13 6-1-13 6-8-5 2-0-0
5x8 =
6.00 12
5x6 =
Scale = 1:77.7
3x5 =
3x4 II 6x8 = 3x6 = 3x5 = 3x8 = 4x6 = 3x4 = 3x5 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.36
BC 0.66
WB 0.56
Matrix -MS
DEFL. in (loc) Vdefl L/d
Vert(LL) -0.23 13-15 >999 360
Vert(CT) -0.40 13-15 >905 240
Horz(CT) 0.04 11 n/a n/a
Wind(LL) 0.15 19-22 >999 240
PLATES GRIP
MT20 244/190
Weight: 249 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-1-8 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3
WEBS
1 Row at midpt 5-18, 5-16, 6-16, 6-15, 8-15
REACTIONS. (size) 2=0-8-0, 18=0-8-0, 11=0-8-0
Max Horz 2=466(LC 11)
Max Uplift 2=-560(LC 12), 18=1365(LC 12), 11=771(1_C 12)
Max Grav 2=533(LC 21), 18=2485(LC 2), 11=1738(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=353/709, 3-5=360/672, 5-6=-899/468, 6-7=-1094/698, 7-8=1286/681,
8-10=-2463/1044, 10-11=2763/1134
BOT CHORD 2-19=-503/242,18-19=-503/242,16-18=-576/681,15-16=0/723,13-15=-479/1656,
11-13=-851/2390
WEBS 3-19=-743/256, 3-18=655/1279, 5-18=197911178, 5-16=703/1470, 6-16=785/539,
6-15=-487/967, 8-15=1069/630, 8-13=249/868, 10-13=521/383
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.0psf; h=16ft; B=45ft; L=43ft;'eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 19-0-0, Exterior(2E)
19-0-0 to 23-8-0, Exterior(2R) 23-8-0 to 29-9-13, Interior(1) 29-9-13 to 44-8-13 zone; porch left exposed;C-C for members and forces
& MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60'
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
This item has been
to the use of this truss component.
electronically signed and
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Sealed by Velez, Joaquin, PE
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
using a Digital Signature.
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
Printed Copies Of this
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 560 lb uplift at joint 2, 1365 lb uplift at
document are not considered
joint 18 and 771 lb uplift at joint 11.
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.88182
MiTek USA, Inc. FL Cart 8634
6904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 1111-7473 rev. 5l19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall H AV t
iTek�
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the iVl
fabrication, storage, delivery, erection and bracing of trusses andtruss systems, see ANSUTP/f quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Za-a-U su-U-U 35.8-0 42-6-0 44-8-0
2-0-0 7-M 3-10-0 3-10-0 5-0-0 5-6-0 5-0-0 5-0 0 7-0-0 2-0-0
6x8 =
44 = 5x6 =
6.00 12 3 4 33 634 35
3x5 =
CX4 11
3x5 11
-iR
WON
24 23 44 22y^y — 3x8 = J^� — 18
3x4 II 4x8 = 3x4 11 3x4 II
45 17 16 1514
4x4 = 3x6 =
4x5 =
6x8 =
46
7-0 0 10.10-0 14 8-0 20.2-0 25 8-0 30-8-0 35 8-0 8- 42-B-0
7-0 0 3-10-0 3-10-0 5.6-0 5-0-0 5-M 5-0-0 -0- 6-0.0
Scale = 1:77.7
d
41 1i0 A
1213IZ 12i
47
3x5 =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc)
Udefl
Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.68
Vert(LL)
-0.18 20-21
>999
360
MT20 244/190
TCDL 15.0
Lumber DOL
1.25
BC 0.59
Vert(CT)
-0.40 20-21
>999
240
BCLL 0.0
Rep Stress Incr
NO
WB 0.69
Horz(CT)
-0.15 14
n/a
n/a
BCDL 10.0
Code FBC2020/TPI2014
Matrix -MS
Wind(ILL)
0.53 20-21
>825
240
Weight: 522 lb FT = 20%
LUMBER -
TOP CHORD
2x4 SP M 30 *Except*
3-7,7-10: 2x6 SP No.2
BOT CHORD
2x4 SP M 30 *Except*
5-22,8-18: 2x4 SP No.3
WEBS
2x4 SP No.3 *Except*
11-14: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 14=0-8-0
Max Horz 2=371(LC 11)
Max Uplift 2=1120(LC 9), 14=2114(LC 9)
Max Grav 2=1692(LC 21), 14=2827(LC 1)
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc puriins.
BOT CHORD Rigid ceiling directly applied or 4-11-12 oc bracing.
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
TOP CHORD 2-31=-2850/4876, 31-32=-2837/4880, 3-32=2748/4898, 3-4=-3266/5852,
4-33=5168/9040, 33-34=5168/9040, 34-35=-5168/9040, 5-35=-5168/9040,
5-6=5221/8944, 6-7=5221/8944, 7-8=5221/8944, 8-36=3949/6469, 36-37=3949/6469,
37-38=-3949/6469, 9-38=-3949/6469, 9-10=-1689/972, 10-39=-1973/1112,
11-39=1965/1090, 11-40=2515/1444, 40-41=2383/1241, 12-41=2329/1159
BOT CHORD 2-42=-4505/2458, 42-43=-4505/2458, 24-43=-4505/2458, 23-24=-4533/2465,
23-44=501/253, 22-44=501/253, 5-21=-275/175, 20-21=9073/5259, 19-20=6490/4031,
8-19=-895/1243, 16-17=-1979/1494, 15-16=-1979/1494, 14-15=-1066/2123,
14-46=-1148/2374. 46-47=114812374, 1247=1148/2374
WEBS 3-24=-758/263; 4-21=-3825/2282, 5-20=-155/284, 6-20=418/306, 8-20=-2538/1398,
9-19=-4701/2750,9-17=-288/51,10-15=-2105/1150,10-14=-1395/2480,11-14=-962/1569,
4-23=-1565/2452, 3-23=-1836/1109, 21-23=5590/3127, 17-19=-1814/1342,
9-15=-2587/4652
NOTES-
1) 2-ply truss to be connected together with 10d (0.131"x3") nails as follows:
Top chords connected as follows: 2x4 - 1 row at 0-9-0 oc, 2x6 - 2 rows staggered at 0-9-0 oc.
Bottom chords connected as follows: 2x4 - 1 row at 0-9-0 oc.
Webs connected as follows: 2x4 - 1 row at 0-9-0 oc, 2x6 - 2 rows staggered at 0-9-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to
ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6804 Parke East Blvd. Tampa FL 33610
Date:
NnVPnnht=r Q qn,)1
3) Unbalanced roof live loads have been considered for this design.
- -"'--' -'--- '
m0ontinueolonipage:
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE.
■■■
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not•
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
is
MiTek
always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
,
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and SCSI Building Component
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldod, MD 20601
6904 Parke East Blvd.
Tampa, FL 36610
Job
Truss
Truss Type
QrY
Ply
BILLIS RESIDENCE
77930
G
HIP
1
T25912311
2
Job Reference (optional)
-----•-- •-••• •� tr.aau suul l6zuzl MlleK Industries, Inc. Tue Nov 916:03:472021 Paget
NOTES-
ID:4tBbed8VbYEjpOwaV5X9TayM L6T-B E5RQLZifySalbtRM50roE l7 W tUTcyd3oiFl_YyL2CA
4) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat. II; Exp C; Encl., GCpi=0.18; MWFRS
(directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 7-0-0, Exterior(2R) 7-0-0 to 13-0-7, Interior(1) 13-0-7 to 35-8-0, Exterior(2R) 35-8-0 to 41-8-7,
Interior(1) 41-8-7 to 44-8-13 zone; cantilever right exposed ; porch right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
5) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific to the use of this truss component.
6) Provide adequate drainage to prevent water ponding.
7) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
8) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide will fit between the bottom chord and
any other members.
9) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1120 lb uplift at joint 2 and 2114 lb uplift at joint 14.
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=70, 3-10=70, 10-39=-70, 13-39=-11O(F=40), 22-25=20, 19-21=-20, 18-28=20
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE NIII-7473 rev. 511912020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not �I
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall �i�AA� I'
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing i Vl iTei(• is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Duality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLISRESIDENCE
T25912312
77930
G1
HIP
1
1
Job Reference (optional)
goers I russ, Tort Nlerce, I-L - 349td2, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:11 2021 Page 1
ID:4tB bed8VbYEjp OwaV5X9TayM L6T-QgRDvz9 C9 Wgm Egl IV9X4xnfzwegjXBrZwsf DMTyLHIQ
3fi-4-8
-2-0-0 638 9.0.0 14$0 20.2-0 25.8.0 30.8-0 36-4-0 42-8-0 44-8-0
2-0-06.3•a 2.8-7 0 5-6-0 ii 6 o a-0.0 2.8.0 0- 8 6-3.9 2.0.0
Scale = 1:77.7
5x8 =
6.00 FIT -� 4
d
3x8 =
3x4 II 3x6 = 3x4 II
30 531 32 6 7 a
8x10 =
33 34 35 a e
14 3839
3x5 i 6x8 = 3x4 II 3x4 II 3x6 = 3x6 =
33-8-0
6x8 = 3x6 11
M
d
4
2l$I
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020/TPI2014
CSI.
TC 0.57
BC 0.52
WB 0.96
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wtnd(LL)
in (loc) Vdefl Ud
-0.20 18-19 >999 360
-0.46 18-19 >941 240
0.13 13 n/a n/a
0.28 18-19 >999 240
PLATES GRIP
MT20 244/190
Weight: 244 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural woad sheathing directly applied or 3-9-15 oc pudins.
BOT CHORD 2x4 SP M 30 -Except-
BOT CHORD . Rigid ceiling directly applied or 4-9-8 oc bracing.
5-20,8-16: 2x4 SP No.3
WEBS
1 Row at midpt 9-17
WEBS 2x4 SP No.3 *Except*
9-17: 2x4 SP M 30, 10-13: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 13=0-8-0, 11=0-8-0
Max Harz 2=245(LC 11)
Max Uplift 2=871(LC 12). 13=1615(LC 12), 11=905(LC 21)
Max Grav 2=1584(LC 1). 13=3238(LC 1), 11=41(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=2620/1476, 3-4=-2353/1389, 4-5=3191/1836, 5-6=3220/1843, 6-8=2064/1265,
8-9=-2080/1293, 9-10=157/638, 10-11=1090/2501
BOT CHORD 2-21=-1102/2327, 5-19=-427/359, 18-19=1344/3028, 17-18=-1344/3028, 8-17=-533/430,
13-15=-2164/1176,11-13=2164/1176
WEBS 3-21=-403/361, 19-21 =-808/1 950, 4-19=-724/1386, 6-19=166/270. 6-18=0/262,
6-17=-1143/584, 15-17=-600/486, 9-17=152012876, 9-15=-1754/934, 10-15=1056/2518,
10-13=-3082/1531
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 9-0-0, Exterior(2R) 9-0-0
This item has been
to 15-0-7, Interior(1) 15-0-7 to 33-8-0, Exterior(2R) 33-8-0 to 39-8-7, Interior(1) 39-8-7 to 44-8-13 zone; porch right exposed;C-C for
electronically signed and
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
sealed by Velez, Joaquin, PE
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the this
using a Digital Signature.
use of truss component.
4) Provide adequate drainage to prevent water ponding.
Printed Copies Of this
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
document are not Considered
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
signed and sealed and the
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 871 lb uplift at joint 2, 1615 lb uplift at
signature must be verified
joint 13 and 905 lb uplift at joint 11.
On any electronic Copies.
Joaquin Velez PE No.68182
MIek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date;
November 9,2021
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE hill-7473 rev. 5119/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall i �•
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUlP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Type
Oty
Ply
BILLISRESIDENCET25912313
FPs
77930
G2
1
1
Job Reference (optional)
Chambers I russ, tort Pierce, FL - 349dZ. 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:13 2021 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-M3Z_KfASh7wUTzS7caZY1CkNIRtt?AusOA8KRMyLH10
2-0 0 , 5-9 4 11-0-0 12�-0 14' 212-0 25�-0 31-8-0 36�-0 42-M 44:8-0
2-0-0 1 0 2 4-0 5-0-0 5 6 0 6-0-0 4 8 0 6-4-0 2-0-0
3x8 =
Us =
4x6 = 3x6 = 5x8 =
4 533 634 35 7 8 9 36 37 10
3x5 = 6x10 =
14-8-0
4x8 = 3x6
3x6 =
Scale = 1:77.7
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) Udefl L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.29
Vert(LL) 0.16 14-30 >480 240
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.34
Vert(CT) -0.09 16-17 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.60
Horz(CT) 0.02 14 file n/a
BCDL 10.0
Code FBC2020rTP12014
Matrix -MS
Weight: 272 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly applied or 6-D-0 oc pudins.
BOT CHORD 2x4 SP M 30 -Except-
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
6-21,9-17: 2x4 SP No.3
WEBS 1 Row at midpt 7-20
WEBS 2x4 SP No.3 *Except*
5-22,11-14: 2x6 SP No.2
REACTIONS. All bearings 0-8-0.
(lb) - Max Horz 2=289(LC 11)
Max Uplift All uplift 100 lb or less at joints) except 2=544(LC 12), 22=1261(1_10 12), 14=-735(LC 12),
12=-419(LC 12)
Max Grav All reactions 250lb or less atjoint(s) except 2=382(LC 21). 22=2088(LC 1). 14=1406(LC 22), 12=283(LC
1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=72/883, 3-4=179/683, 4-5=340/729, 5-6=222/350, 6-7=-218/338, 7-9=952/595,
9-10=-950/602, 10-11=-618/435, 11-12=-16/382
BOT CHORD 2-24=-607/9, 23-24=-607/9, 22-23=557/502, 6-20=-317/267, 19-20=-5/672,
18-19=-5/672, 9-18=-4351360, 14-16=267/186, 12-14=267/186
WEBS 3-24=-693/254, 3-23=-610/1293, 4-23=1018/322, 4-22=809/1321, 5-22=875/364,
20-22=-767/860, 5-20=-329/898, 7-20=1223/721, 7-19=01256, 7-18=-324/389,
16-18=-11/419, 10-18=-230/621, 10-16=-462/193, 11-16=215/857, 11-14=1259/641
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=431t eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 11-0-0, Exterior(2R)
11-0-0 to 17-0-7, Interior(1) 17-0-7 to 31-8-0, Exterior(2R) 31-8-0 to 37-8-7, Interior(1) 37-8-7 to 44-8-13 zone; porch left and right
exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
5) All plates are 3x4 MT20 unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 544 lb uplift at joint 2, 1261 lb uplift at
joint 22, 735 lb uplift at joint 14 and 419 lb uplift at joint 12.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MITek USA, Inc. FL Cart 6834
8904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MTek& connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design into the overall A�,
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing IV IiTek•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/fPil Duality Criteria, DSO-89 and BCSI Building Component 6904 Parke East Blvd.
Safety lnformaeon available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
BILLIS RESIDENCE
T25912314
77930
G3
HIP
1
1
Job Reference (optional)
s Truss, Fort Pierce, FL - 34982,
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:15 2021 Page 1
ID:4tB bed8VbYEj pOwaV5X9TayML6T-J RhkILCi DIACj H cWk?bO6dghAFVhT1 ?9rUd RV EyLH IM
14-e-0
-2-0-0 I fi-9-4 I 124-0 13" 20.20 25-8-0 _ 29-8-0 36-0-0 42- 44-a-0
L-il-I/ IN � 5-6-12 0-e-01-8-0 ' S40
5x12 i 4x5 =
8.00 12
5 6 733
3x4 II
3x6 = 4x5 = 5x8 =
34 8 9 35 10 36 11
3x6 =
3x4 II 6x10 = 3x4 11 3x4 II 3x8 = 3x6 = 3x6
3x4 II
144W
Scale = 1:79.0
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) Udefl L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.36
Vert(LL) 0.18 25-28 >818 240
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.58
Vert(CT) -0.10 25-28 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.82
Horz(CT) 0.02 16 n/a n/a
BCDL 10.0
Code FBC2020/rP12014
Matrix -MS
Weight: 267 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30 *Except*
BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing, Except:
7-23,10-19: 2x4 SP No.3
10-0-0 oc bracing: 20-21,19-20.
WEBS 2x4 SP No.3 *Except*
12-16,5-24: 2x6 SP No.2
REACTIONS. All bearings 0-8-0.
(lb) - Max Horz 2=334(LC 11)
Max Uplift All uplift 100 lb or less at joint(s) except 2=547(LC 12), 24=1258(1_10 12), 16=-727(LC 12).
14=-426(LC 12)
Max Grav All reactions 250 lb or less at joint(s) except 2=431(LC 21), 24=2025(LC 1), 16=1391(LC 22), 14=316(LC
22)
FORCES. (lb) -Max. Camp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-4=-114/685, 4-5=379/693, 7-8=663/402, 8-10=663/402, 10-11=874/546,
11 -1 2=-794/469, 12-14=0/288
BOT CHORD 2-25=-418/40, 24-25=-418/40, 7-22=1048/741, 21-22=-263/683, 20-21=62/885
WEBS 4-25=-764/278, 4-24=-653/1369, 22-24=-626/820, 7-21=702/1093, 8-21=419/333,
10-21=-345/282, 18-20=0/599, 11-20=103/486, 11-18=425/151, 12-18=172/819,
12-16=-1251/698, 5-24=-1291/544, 5-22=251/899
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpl=0.18; MWFRS (directional) and C-C Extedor(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 13-0-0, Extedor(2R)
13-0-0 to 19-0-7, Interior(1) 19-0-7 to 29-8-0, Exterior(2R) 29-8-0 to 35-8-7, Interior(1) 35-8-7 to 44-8-13 zone; porch left and right
exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements speck
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 547 lb uplift at joint 2, 1258 lb uplift at
joint 24, 727 lb uplift at joint 16 and 426 lb uplift at joint 14.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE NIII-7473 rev. 5/19/2020 BEFORE USE.
M Design valid for use only with Tek® connectors. This design Is based any upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek'
is ahvays required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing o1 trusses and truss systems, see ANSLITP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Type
Qty
Ply
BILLIS RESIDENCET25912315
THI
77930
G4
1
1
Job Reference (optional)
ars Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:17 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-FgoUA1 DzIMRwyblvrQeUB2v?53DaxwDSJo6Ya7yLHIK
i5-0-o
-2-0-0 6 4 12-4-0 14-8-0 21-0-4 z69-0 27-8-0 35.6.0 42-8-0 aa-9-0
2-a0 5.10-12 2-4-0 0.4.0 6-0-4 4.7-12 2-a0 7-ta0 7-2-0 2-a0
Scale = 1:79.0
3x4 II
3x6 =
6.00 F12 3x8 =
a.,a _ 6 7 8 32
5x6 =
17 3x5 =
3x5 —_ 3x4 II 6x10 = 3x4 II 3x4 II 3x6 =
6xB =
14-M
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020rrP12014
CSI.
TIC 0.46
BC 0.49
WB 0.84
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) I/deft Ud
-0.14 14-16 >999 360
-0.31 14-16 >999 240
0.07 12 n/a n/a
0.14 23-26 >999 240
PLATES GRIP
MT20 244/190
Weight: 266 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-3-1 oc purlins.
BOT CHORD 2x4 SP M 30 -Except'
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
6-21: 2x4 SP No.3
WEBS
1 Row at midpt 11-18, 8-20, 14-18
WEBS 2x4 SP No.3 *Except*
5-22: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 22=0-8-0, 12=0-8-0
Max Harz 2=378(LC 11)
Max Uplift 2=510(LC 12), 22=1430(LC 12), 12=746(LC 12)
Max Grav 2=388(LC 21), 22=2739(LC 2), 12=1662(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=0/595, 3-5=485/1064, 5-6=-147/372, 7-8=76/292, 8-9=-1585/813, 9-11=-1831/780,
11-12=2688/1099
BOT CHORD 2-23=-664/45, 22-23=-664/45, 6-20=-416/311, 19-20=-13/1037, 18-19=-13/1037,
12-14=-824/2301
WEBS 3-23=-727/272, 3-22=-709/1329, 5-22=1980/779, 20-22=995/854, 5-20=-487/1484,
8-19=0/401, 8-18=380/739, 9-18=0/319, 11-18=-928/578, 8-20=18341884,
14-18=-815/2238
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 15-0-0, Exterior(2R)
This item has been
15-0-0 to 21-04, Interior(1) 21-0-4 to 27-8-0, Extedor(2R) 27-8-0 to 33-8-7, Interior(1) 33-8-7 to 44-8-13 zone; porch left
electronically signed and
exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
sealed by Velez, Joaquin, PE
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the truss
using a Digital Signature.
use of this component.
4) Provide adequate drainage to prevent water ponding.
Printed Copies Of this
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
document are not considered
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
signed and sealed and the
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 510 lb uplift at joint 2, 1430 lb uplift at
signature must be verified
joint 22 and 746 lb uplift at joint 12.
On any electronic Copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 1,111-7473 rev. 5l19/2020 BEFORE USE.
--
valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
ISO'
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek'
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIMP/f quality Criteria, DSB-89 and SCSI Building Component
6904 Parke East Blvd.
Safely Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
RESIDENCET25912316
77930
G5
HIP
TB11b[LIS
Reference (optional)
Chambers Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MTek Industries, Inc. Mon Nov 8 09:22:18 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6TIOMtNNEbWgZnaIK5P79jkGSCtSY4gM6bXSr56ZyLHIJ
5 4 12 4-0 17-0-0 21 4-0 25 B-0 31-1113 36-7-11 42-8-0 44 8-0
6 5 4 S 10-12 4 8 0 4-4-3 4 4-0 5-5 13 5 5 13 6 0 5 2-0 0
m
d
5x6 =
6.00 F12
3x4 = 5x6 —
29 7 30 8
Scale = 1:77.7
3x5 =
3x4 II 6x8 = 3x6 = 4x10 = U8 = 3x6 = 3x4 = 3x5 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020rrPI2014
CSI.
TIC 0.33
BC 0.53
WB 0.93
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) VdeO Ud
-0.16 16-17 >999 360
-0.28 16-17 >999 240
0.04 12 n/a n/a
0.14 20-23 >999 240
PLATES GRIP
MT20 244/190
Weight: 257 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-2-14 cc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP ND.3 *Except*
WEBS
1 Row at midpt 6-17, 7-17, 9-16
5-19: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 19=0-8-0, 12=0-8-0
Max Horz 2=422(LC 11)
Max Uplift 2=-512(LC 12), 19=1432(LC 12), 12=751(LC 12)
Max Grav 2=455(LC 21), 19=2590(LC 2), 12=1698(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=189/582, 3-5=507/879, 5-6=-532/301, 6-7=395/318, 7-8=1246/715,
8-9=-1447/709, 9-11=-2461/1032, 11-12=-2726/1110
BOT CHORD 2-20=-581/137, 19-20=-581/137, 17-19=780/818, 16-17=01850, 14-16=-513/1730,
12-14=-839/2363
WEBS 3-20=-734/281, 3-19=-703/1304, 5-19=2166/1237, 5-17=799/1651, 7-17=11261665,
7-16=-351/810, 8-16=-73/296, 9-16=-935/570, 9-14=-218/739, 11-14=-461/337
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 17-0-0, Exterior(21R)
17-0-0 to 23-0-7, Interior(1) 23-0-7 to 25-8-0, Exterior(2R) 25-8-0 to 31-8-7, Interior(1) 31-8-7 to 44-8-13 zone; porch left
exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
This item has been
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
electronically signed and
to the use of this truss component.
sealed by Velez, Joaquin, PE
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
using a Digital Signature.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Printed copies of this
will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
document are not considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 512 lb uplift at joint 2, 1432 Ib uplift at
signed and sealed and the
joint 19 and 751 lb uplift at joint 12.
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTtik USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date.
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mg-7473 rev. 5/192020 BEFORE USE.
--
Design valid for use only with MTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not �•
a truss system. Before use, the building designer must verify the applicability of design parameters and properly Incorporate this design into the overall ■
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSLITP11 Quality Criteria, DSB.89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Oty
PlyTB11bLLIS
RESIDENCEI
77930
]
G6
HIP
T25912317
P4......4...... T-......
Reference o tional
-•- • •-- • -• • • •-• •- - �,� OAOU s Hug 10 zuzl ml I eK inoustnes, Inc. Mon Nov t3 09:22:19 2021 Pagel
ID:4tBbed8VbYEjpOwaV5X9TayML6T-BCwFbiFDHzheCuvHzrgyGT_N srTPpLkm6bfe?yLHll
-2.0.0 6-5-4 12 4-0 19-0-0 23�-0 29 9-13 35-11-11 42-M 44.8-0
2-0-0 6-5-0 5-10-12 6-8-0 4-8-0 5-1-13 6-1-13 6-8-5 2-0-0
Scale = 1:77.7
5x8 =
6.o0 12 5x6 =
3x5 =
3x4 II 6x8 = 3x6 = 04 = US = U6 = 3x4 = 3x5 =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr YES
Code FBC2020rrP12014
CS1.
TC 0.37
BC 0.65
WB 0.86
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) Vdefl Ud
-0.23 13-15 >999 360
-0.40 13-15 >913 240
0.04 11 n/a n/a
0.15 19-22 >999 240
PLATES GRIP
MT20 2441190
Weight: 254 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 4-1-12 oc purlins.
BOT CHORD 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3 *Except*
WEBS
1 Row at midpt 5-16, 6-16, 6-15, 8-15
5-18: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 18=0-8-0, ll=0-8-0
Max Horz 2=-466(LC 10)
Max Uplift 2=-541(LC 12), 18=1392(LC 12), 11=763(LC 12)
Max Grav 2=504(LC 21), 18=2540(LC 2), 11=1723(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=287/657, 3-5=-41W761, 5-6=-859/447, 6-7=1065/679, 7-8=1253/659,
8-10=-2431/1023,10-11=-2731/1113
BOT CHORD 2-19=-5361189, 18-19=536/189, 16-18=-648/728, 15-16=0/684, 13-15=-460/1627,
11-13=832/2361
WEBS 3-19=-744/257, 3-18=-656/1279, 5-18=2036/1212, 5-16=735/1520, 6-16=816/560,
6-15=-497/983, 8-15=-10691630, 8-13=249/869, 10-13=521/383
NOTES -
I) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 2-2-7, Interior(1) 2-2-7 to 19-0-0, Exterior(2E)
19-0-0 to 23-8-0, Exterior(2R) 23-8-0 to 29-9-13, Interior(1) 29-9-13 to 44-8-13 zone; porch left exposed;C-C for members and forces
& MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
This item has been
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
electronically signed and
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
Sealed b Velez, Joaquin, PE
y Q
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Using a Digital Signature.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-13 0 tall by 2-0-0 wide
Printed copies of this
will fit between the bottom chord and any other members, with BCDL = IO.Opsf.
document are not considered
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 541 lb uplift at joint 2, 1392 lb uplift at
signed and sealed and the
joint 18 and 763 lb uplift at joint 11.
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
6904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
WARNING - Vediy design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7470 rev. 5/1912020 BEFORE USE.
--
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall �•
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members ony. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing oftrusses and truss systems, see ANSNTP/1 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safetyinformation available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
ss
Truss Type
Oty
Ply
BILLIS RESIDENCE
77930
TGrRS
Monopitch Girder
1
1
T25912318
Chamhwrs Tnrec Fnn
Di--- FI _ 9A0w0
Job Reference (optional)
nuy ru cuc r wa I un Irluustries, Inc. Mon NOV O Uti2Z:ZU ZUZ1 Pagel
ID:4tBbed8VbYEjpOwaV5X9TayML6T-fPUdo2Gr1 HpVp2UUWYBBphXZDGEF8Siu7mKCBSyLHIH
2-4-12 5.0.0
2-4-12 2-7.4
Scale = 1:17.0
4x4 - HUS26 3x4 II
5-0-0
5-M
Plate Offsets (X,Y)— (1:0-2-0,Edgel
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/defl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.27
Vert(LL) -0.05 5 >999 360
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.49
Vert(CT) -0.10 5 >567 240
BCLL 0.0
Rep Stress Incr NO
WB 0.09
Horz(CT) 0.00 4 file n/a
BCDL 10.0
Code FBC20201TPI2014
Matrix -MP
Wind(LL) 0.07 5 >804 240
Weight: 25 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-0-0 cc pudins,
BOT CHORD 2x6 SP 240OF 2.0E except end verticals.
WEBS 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 cc bracing.
REACTIONS. (size) 1=0-8-0, 4=Mechanical
Max Horz 1=140(LC 21)
Max Uplift 1=318(LC 8). 4=601(LC 8)
Max Grav 1=724(LC 25), 4=1126(LC 25)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
WEBS 2-5=-219/293
NOTES-
1) Wind: ASCE 7-16: Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
il; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 318 lb uplift at joint 1 and 601 lb uplift at
joint 4.
7) Use USP HUS26 (With 14-16d nails into Girder'& 6-16d nails into Truss) or equivalent spaced at 2-0-0 cc max. starting at 2-4-12
This item has been
from the left end to 4-4-12 to connect truss(es) to back face of bottom chord.
electronically signed and
8) Fill all nail holes where hanger is in contact with lumber.
9) In the LOAD CASE(S) loads
sealed
d by Velez, Joaquin, PE
section, applied to the face of the truss are noted as front (F) or back (B).
using a Digital Signature.
LOAD CASE(S) Standard
Printed copies of this
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
document are not considered
Uniform Loads (plf)
Vert: 1-3=70, 1-4=20
signed and sealed and the
Concentrated Loads (lb)
signature must be verified
Vert: 5=-810(B) 8=559(B)
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
8904 Parke East Blvd. Tampa FL 33810
Data:
November 9,2021
® WARNING - verify design parameters and READ NOTES 014 THIS AND INCLUDED MITEK REFERENCE PAGE 10I-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members onty. Additional temporary and permanent bracing
Is ahvays required for to
MiTek
stability and prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSMI1 Quality Criteria, DSB-89 and SCSI Building Component
SafetyInformation available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
6904 Parke East Blvd.
Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
BILLIS RESIDENCE
T25912319
77930
GRA
Hip Girder
2
1
Job Reference o tional
�C"_ or, err: � -. Q4' 6.43U S Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:22 2021 Page l
ID:4tBbedBVbYEjpOwaV5X9TayML6T-bncNDkH5Zu3D3MesezEfu6c174xec9PBS4pJFKyLHIF
2 0 0 3-9 4 7-0-0 11-5-15 1510-1 20.4-0 23E-12 27-4-0 29 4 0
2-0-0 3-94 3-2-12 4-5.15 4-4-3 4-5-15 3-2-12 3-94 2-0.0
Scale = 1:51.5
4x6 =
3x4 = 3x8 = 5x6
3 18 194 20 21 22 235 24 25 6
bXb = 4x5 = 3x4 = . "" "- — 3x4 11 4x5 = 5x6 =
3-9-4
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in (loc) Udefl Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.96
Vert(LL)
0.31 10-12 >999 240
MT20 2441190
TCDL 15.0
Lumber DOL
1.25
BC 0.43
Vert(CT)
-0.41 10-12 >792 240
BCLL 0.0
Rep Stress Incr
NO
WB 0.91
Horz(CT)
0.11 7 n/a n/a
BCDL 10.0
Code FBC20201TP12014
Matrix -MS
Weight: 157 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied.
BOT CHORD 2x6 SP 240OF 2.0E
BOT CHORD
Rigid ceiling directly applied or 5-9-13 oc bracing.
WEBS 2x4 SP No.3
OTHERS 2x4 SP No.3
REACTIONS. (size) 2=0-8-0, 7=0-8-0
Max Horz 2=184(LC 24)
Max Uplift 2=1624(LC 8), 7=1673(LC 8)
Max Grav 2=2617(LC 29), 7=2664(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-4958/2932, 3-4=-4442/2728, 4-5=5568/3469, 5-6=-4522/2825, 6-7=5085/3040
BOT CHORD 2-13=-2399/4453, 12-13=3174/5612, 10-12=-3229/5638, 9-10=3229/5638,
7-9=-2495/4455
WEBS 3-13=-820/1597, 4-13=-1581/982, 4-12=-92/390, 5-10=60/392, 5-9=-1503/925,
6-9=-847/1608
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=27ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 1624 lb uplift at joint 2 and 1673 lb uplift
at joint 7.
8) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 324 lb down and 380 lb up at
7-0-0. 211 lb down and 197 lb up at 9-0-12, 216 lb down and 213 lb up at 11-0-12, 216 lb down and 213 lb up at 13-0-12, 216 lb
down and 213 lb up at 14-3-4. 216 lb down and 213 lb up at 16-3-4, and 216 lb down and 213 lb up at 18-3-4, and 398 lb down and
393 lb up at 20-4-0 on top chord, and 419 lb down and 239 lb up at 7-0-0, 91 lb down and 22 lb up at 9-0-12, 96 lb down and 38 lb
up at 11-0-12, 96 lb down and 38 lb up at 13-0-12, 96 lb down and 38 lb up at 14-3-4, 96 lb down and 38 lb up at 16-3-4, and 96 lb
down and 38 lb up at 18-3-4, and 454 lb down and 303 lb up at 20-3-4 on bottom chord. The design/selection of such connection
device(s) is the responsibility of others.
9) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
lituoritirluealuilpageli-
A WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/1912020 BEFORE USE.
M Design valid for use only with Tek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify me applicability of design parameters and property incorporate this design into the overall
building design. Bracing indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Cdfeda, DSB-69 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldod, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912319
77930
GRA
Hip Girder
2
1
Job Reference (optional)
Chambers Truss, Fort Pierce, FL - 34982.
8.430 s Aug 16 2021 MTek Industries, Inc. Mon Nov 8 09:22:22 2021 Page 2
ID:4tBbed8VbYEjpOwaV5X9TayML6T-bncNDkH5Zu3D3MesezEfu6cl?4xec9PBS4pJFKyLHIF
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=70, 3-6=70, 6-8=70, 2-7=20
Concentrated Loads (lb)
Vert: 3=205(17) 6=205(F) 11=78(F) 13=-337(F) 9=-454(F) 18=134(F) 19=144(F) 20=-144(F) 23=144(F) 24=144(F) 25=-144(F) 26=-67(F) 27=78(F) 28=78(F)
29=-78(F) 30=-78(F)
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/1912020 BEFORE USE.
Design valid for use only with MTek® connectors. This design Is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property Incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing iw iTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
77930
GRD
HIP GIRDER
1
T25912320
Job Reference o floral
-_-- --- - - -- nuy iv uJeltlJ, rrlU. w—I IVUV 0Uy:GL:L1 LOCI rage l
1 D:4tBbedBVbYEjpOwaV5X9TayM L6T-y1 PG G RLEO RhV97 Wq R Wpgb9JiH 5eS HV2wcMX4xYyLH IA
-2-0.0 3-9-4 7-0.0 11-10-8 16-7-4 21-4-0 26-0-12 30-9.8 35-8-0 38-10-12 42-8-0
2 0 0 3 9-0 3-2-12 4-10 8 4A 12 4 8 12 4 8 12 4 8-12 4-10 8 3-2-12 3-9 4
5x6 =
3x4 = 3x4 =
6.00 12 3 24 25 4 26 27 28 295 30
5x8 = 3x4 = 3x4 =
=
31 6 32 7 33 34 35 36 8 37 38 39 9 5x6
Scale = 1:75.2
' 40 41 ,0 42 17 43 44 45 10 46 19 47 1348 1149 50 51 11
06 — 4x5 = 10x18 MT20HS —_ 3x4 11 04 = 4x4 = 4x5 = 4x6 _
4x4 = 4x4 = 10x18 MT20HS =
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr NO
Code FBC2020(rP12014
CSI.
TIC 0.54
BC 0.39
WB 0.62
Matrix -MS
DEFL. in
Vert(LL) 0.64
Vert(CT) -0.88
Horz(CT) 0.17
(loc) Vdefl L/d
15 >797 240
15 >584 240
10 n/a n/a
PLATES GRIP
MT20 244/190
MT20HS 187/143
Weight: 500 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
Structural wood sheathing directly applied or 4-0-1 oc purlins.
BOT CHORD 2x6 SP 240OF 2.0E BOT CHORD
Rigid ceiling directly applied or 8-3-13 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 10=0-8-0, 2=0-8-0
Max Horz 2=188(LC 7)
Max Uplift 10=2248(LC 8). 2=2391(LC 8)
Max Grav 10=3943(LC 1), 2=4078(LC 29)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=8209/4659, 3-4=-7413/4303, 4-5=10500/6119, 5-6=12448/7224, 6-7=12502/7261,
7-8=10604/6187, 6-9=-7503/4428, 9-10=8349/4794
BOTCHORD 2-19=-4034/7340, 18-19=-5916/10551, 16-18=7021/12448, 15-16=-7471/13221,
14-15=-7471/13221, 12-14=7058/12502, 11-12=5984/10604, 10-11=-4157/7375
WEBS 3-19=-1573/3009, 4-19=-3993/2253, 4-18=-786/1663, 5-18=-2429/1371, 5-16=-309/838,
6-16=-983/559,6-15=-18/494,6-14=-945/513, 7-14=-286/817, 7-12=-2382/1332,
8-12=-746/1630, 8-11=-3924/2183, 9-11 =-1 625/3049
NOTES-
1) 2-ply truss to be connected together with 10d (0.131"x3") nails as follows:
Top chords connected as follows: 2x4 - 1 row at 0-7-0 oc.
Bottom chords connected as follows: 2x6 - 2 rows staggered at 0-9-0 oc.
Webs connected as follows: 2x4 - 1 row at 0-9-0 oc.
2) All loads are considered equally applied to all plies, except if noted as front (F) or back (B) face in the LOAD CASE(S) section. Ply to
This item has been
ply connections have been provided to distribute only loads noted as (F) or (B), unless otherwise indicated.
electronically Signed and
3) Unbalanced roof live loads have been considered for this design.
Sealed by Velez, Joaquin, PE
4) Wind: ASCE 7-16: Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
using a Digital Signature.
5) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
Printed copies of this
to the use of this truss component.
document are not considered
6) Provide adequate drainage to prevent water ponding.
Signed and Sealed and the
7) All plates are MT20 plates unless otherwise indicated.
8) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Signature must be Verified
9) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
on any electronic copies.
will fit between the bottom chord and any other members.
Joaquin Velez PE No.68182
10) Provide mechanical connection (by others) of truss to bearing plate Capable of withstanding 2248 lb uplift at joint 10 and 2391 lb
MiTek USA, Inc. FL Cott 6834
uplift at joint 2.
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
9
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/1912020 BEFORE USE
Design valid for use ony with MITek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall A
iTek�
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members ony. Additional temporary and permanent bracing
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the iVi
fabdeation. storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway. Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Oty
Ply
BILLIS RESIDENCE
77930
GIRD
HIP GIRDER
1
T25912320
Job Reference o tional
�^ • ����• 15.43u S Aug 1 ti 1UZ1 MI I eK Industries, Inc. Mon Nov 8 09:22:27 2021 Page 2
NOTES-
ID:4tBbed8VbYEjpOwaV5X9TayML6T-yIPGGRLEORhV97WgR Wpgb9JiH5eSHV2wcMX4xYyLHIA
11) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 324lb down and 385 lb up at 7-0-0, 211 lb down and 197 lb up at
9-0-12, 211 lb down and 197 lb up at 11-0-12, 211 lb down and 197 lb up at 13-0-12, 211 lb down and 197 lb up at 15-0-12, 211 lb down and 197 lb up at 17-0-12, 211
lb down and 197 lb up at 19-0-12, 211 lb down and 197 lb up at 21-0-12, 211 lb down and 197 lb up at 21-7-4, 211 lb down and 197 lb up at 23-74, 211 lb down and
197 lb up at 25-74, 211 lb down and 197 lb up at 27-7-4, 211 lb down and 197 lb up at 29-74, 211 lb down and 197 lb up at 31-74, and 211 lb down and 197 lb up at
33-74, and 392 lb down and 382 lb up at 35-8-0 on top chord, and 419 lb down and 239 lb up at 7-0-0, 91 lb down and 22 lb up at 9-0-12, 91 lb down and 22 lb up at
11-0-12, 91 lb down and 22 lb up at 13-0-12, 91 lb down and 22 lb up at 15-0-12, 91 lb down and 22 lb up at 17-0-12, 91 lb down and 22 lb up at 19-0-12, 91 lb down
and 22 lb up at 21-0-12, 91 lb down and 22 lb up at 21-7-4, 91 lb down and 22 lb up at 23-7-4, 91 lb down and 22 lb up at 25-7-4. 91 lb down and 22 lb up at 27-7-4, 91
lb down and 22 lb up at 29-74, 91 lb down and 22 lb up at 31-7-4, and 91 lb down and 22 lb up at 33-74, and 443 lb down and 287 lb up at 35-7-4 on bottom chord.
The design/selection of such connection device(s) is the responsibility of others.
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (pif)
Vert: 1-3=70, 3-9=70, 9-10=70, 2-10=-20
Concentrated Loads (lb)
Vert: 3=-205(B) 9=195(B) 19=-337(B) 6=-268(B) 15=134(B) 11=443(B) 24=-134(B) 26=134(B) 27=134(B) 29=-134(B) 30=134(B) 31=134(B) 32=-134(B)
33=-134(B) 35=134(B) 36=134(B) 38=134(B) 39=134(B) 40=-67(B) 41=-67(B) 42=67(B) 43=67(8) 44=67(B) 45=-67(B) 46=-67(B) 47=67(B) 48=67(1]1)
49=-67(B) 50=-67(B) 51=67(B)
WARNING -Verity design parameters and READ NOTES ON THIS AND INCLUDED MIITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members ony. Additional temporary and permanent bracing M iTek•
Is always requlred for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI?p/1 Quality Criteria, DSBA9 and BCS1 Building Component 6904 Parke East Blvd.
Saterylnrormatlon available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Type
City
Ply
BILLIS RESIDENCET25912321
T
77930
GRG
IRDER
1
1
Job Reference o tional
a.96u s Aug io YU21 MI I eK Inaustrles, Inc. Mon NOV 6 UU:2Z:3U 2U21 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-MK5PvTN6hM340bFP6fNXDoxD W bfUmDMIKIkXIyLHl7
2 0 0 5 0 0 8 6 14 12-0-0 14 8-0 16 7 4 21-2 8 25�-0 28-0-0 32-9-10 37 8-0 5 8-0 44 8-0
2-0-0 5-0-0 3-6-14 3-5-2 2�-0 1-11-4 4-7-4 4-5-8 2�-0 4-9-10 4-10-6 5-0-0 2-0-0
"Special" indicates special hanger(s) or other
connection device(s) required at location(s) Scale = 1:81.2
shown. The design/selection of such special
connection device(s) is the responsibility of
others. This applies to all applicable truss Special Special Special Special
designs in this job.
7x14 = Special Special Special Special 8x10 = Special Special
6x8 = Special
6.00 FIT 4x10 = 3x4 11 6x8 = 10x18 MT20HS = 3x4 11 Special 4x10 = Special 6x8 —
3 4 5 33 34 6 735 36 8 37 389 10 39 40 4142 ga 45 44 48 12
45 =
3x4 II 5x14 =
"' 47 GO O14 II Special rxo —
3x4 11 3x8 11 Special Special Special
10x18 MT20HS =
3x4 II
HUS26 Special
,a 54 10 55
45 =10x10 =
602 = Special
Special Special Special
B 57 " 58 16 59 10
3x4 11 4x8 = 05 =
Special Special Special Special
5-0-0 , B-6-14 , 12-0-0 , 14.8-0 ,16-7-4 , 21-2-8 25-8-0 , 28-0-0 , 32-9-10
4x5 =
d
4Ig
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr NO
Code FBC2020/TPI2014
CSI.
TC 0.48
BC 0.74
WB 0.98
Matrix -MS
DEFL.
Vert(LL)
Vert(CT)
Horz(CT)
Wind(LL)
in (loc) Udefl Lid
-0.37 25-26 >920 360
-0.82 25-26 >411 240
0.16 18 n/a n/a
0.53 25-26 >637 240
PLATES
MT20
MT20HS
Weight: 286 lb
GRIP
244/190
187/143
FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x6 SP 240OF 2.0E *Except*
TOP CHORD
Structural wood sheathing directly applied or 3-2-5 oc purlins.
1-3,12-14: 2x4 SP M 30
BOT CHORD
Rigid ceiling directly applied or 4-6-12 oc bracing.
BOT CHORD 2x6 SP No.2 'Except'
WEBS
1 Row at midpt 11-18. 8-20
20-24: 2x6 SP 240OF 2.OE, 9-19: 2x4 SP M 30
2 Rows at 1/3 pts 7-21
WEBS 2x4 SP M 30 *Except*
8-21,18-20,10-20,11-18,11-15,3-27,23-25,7-22,7-21: 2x4 SP No.3
10-18: 2x6 SP No.2
REACTIONS. (size) 2=0-8-0, 18=0-8-0, 13=0-8-0
Max Horz 2=-158(LC 6)
Max Uplift 2=970(LC 8), 18=2916(LC 8), 13=-729(LC 25)
Max Grav 2=1730(LC 17), 18=4610(LC 1), 13=168(LC 18)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-3127/1520, 3-4=-4261/2207, 4-5=8353/4225, 5-7=8591/4334, 7-8=2140/983,
8-9=-2206/4171, 9-10=-2255/4288, 10-11=2429/5002, 11-12=0/924, 12-13=0/990
BOT CHORD 2-28=-117112740, 27-28=-1170/2748, 26-27=-215/445, 23-24=-3188/6811,
22-23=-3188/6811,21-22=-3188/6811,20-21=749/2165,9-20=-554/286,18-19=-643/354,
17-18=2423/509, 15-17=2423/509, 13-15=-798/0
WEBS 24-26=-388/720, 8-21=635/1420, 18-20=-4668/2469, 10-20=139/860, 10-18=822/456,
11-18=3149/2406, 11-15=1006/1907, 12-15=791/105, 4-27=2042/1059,
24-27=-1823/3959,3-27=-978/1884,4-24=-2168/4394,23-25=-265/518,7-22=-92/378,
7-24=-958/1865, 8-20=-6535/3331, 7-21=4930/2547
This.item has been
NOTES-
electronically signed and
1) Unbalanced roof live loads have been considered for this design.
Sealed by Velez, Joaquin, PE
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=43ft; eave=5ft; Cat.
II; Exp Encl.,
Digital Signature.
using 9 a g 9
C; GCpi=0.18; MWFRS (directional); porch right exposed; Lumber DOL=1.60 plate grip DOL=1
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
Printed copies of this
to the use of this truss component.
document are not considered
4) Provide adequate drainage to prevent water ponding.
Signed and Sealed and the
5) All plates are MT20 plates unless otherwise indicated.
6) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
Signature must be Verified
7) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
on any electronic copies.
will fit between the bottom chord and any other members.
Joaquin Velez PE No.68182
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 970 lb uplift atjoint 2, 2916 lb uplift at
MiTek USA, Inc. FL Cert 8834
joint 18 and 729 lb uplift at joint 13.
6904 Parke East Blvd. Tampa FL 33610
9) Use USP HUS26 (With 14-16d nails into Girder & 6-16d nails into Truss) or equivalent at 13-0-12 from the left end to connect
Date:
truss(es) to front face of bottom chord, skewed 0.0 deg.to the right, sloping 0.0 deg. down.
November 9,2021
10) Fill all nail holes where hanger is in contact with lumber.
WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 511912020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall Inv 1•
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing M iTe k•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP/1 Duality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Sofetyinformatlon available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
RESIDENCET25912321
77930
GRG
HIP GIRDER
1
�7BIbLLIS
Reference o tional
L:namoers I russ, t-on Pierce, t-L - 3496Z,
6.430 s Aug 16 ZU21 MITek Industries, Inc. Mon Nov 8 09:22:30 2021 Page 2
ID:4lBbed8VbYEjpOwaV5X9TayML6T-MK5PvTN6hM34ObFP6fNXDoxD WlbfUmDMIKIkXtyLH17
NOTES-
11) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 190 Ib down and 134 Ib up at 15-0-12, 190 Ib down and 134 Ib up at
17-0-12, 190 Ib down and 134 Ib up at 19-0-12, 190 Ib down and 134 Ib up at 21-0-12, 190 Ib down and 134 Ib up at 23-0-12, 190 Ib down and 134 Ib up at 25-0-12, 162
Ib down and 129 Ib up at 27-0-12, 86 Ib down and 126 Ib up at 29-0-12, 86 Ib down and 126 Ib up at 29-7-4, 86 Ib down and 126 Ib up at 31-7-4, 86 Ib down and 126 Ib
up at 33-7-4, and 86 Ib down and 126 Ib up at 35-7-4, and 284 Ib down and 334 Ib up at 37-8-0 on top chord, and 22 Ib down at 15-0-12, 22 Ib down at 17-0-12, 22 Ib
down at 19-0-12, 22 Ib down at 21-0-12, 22 Ib down at 23-0-12, 22 Ib down at 25-0-12, 53 Ib down at 27-0-12, 36 Ib down and 46 Ib up at 29-0-12, 36 Ib down and 46
Ib up at 29-7-4. 36 Ib down and 46 Ib up at 31-7-4, 36 Ib down and 46 Ib up at 33-7-4, and 36 Ib down and 46 Ib up at 35-7-4, and 82 Ib down and 128 Ib up at 37-7-4
on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
12) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=70, 3-12=70, 12-14=-70, 2-25=20, 20-23=20, 13-19=20
Concentrated Loads (lb)
Vert: 6=98(F) 12=119(F) 8=98(F) 21=-8(F) 15=-47(F) 35=-98(F) 36=-98(F) 37=98(F) 38=98(F) 39=69(F) 41=-48(F) 42=-48(F) 44=48(F) 45=48(F) 46=48(F)
47=-1105(F) 49=8(F) 50=8(F) 51=8(F) 52=8(F) 53=-8(F) 54=-33(F) 55=-25(F) 56=-25(F) 57=-25(F) 58=25(F) 59=25(F)
® WARNING -Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/I92020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
sot
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
MiTek`
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and buss systems, see ANS11rPl1 Quality Criteria, DSB-89 and BCSI Building Component
6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912322
77930
GRK
Hip Girder
1
1
1" _�_ - r^ --
Job Reference (optional)
• •- ••--•- - a.adU s Aug 1 t ZUz1 mt i eK Inoustnes, Inc. Mon Nov 8 09:22:32 2021 Pagel
ID:4tBbed8VbYEjpOwaV5X9TayML6T-JjC9K9PNDzKoFuPnD3P71D1 dd6NuyuPfmdErclyLH15
-2-M 5-0.0 8-M 13-0-0
2-M 6-0-0 3-M 5-0-0
4x8 =
14 15
4x4 =
Scale = 1:24.6
LOADING (psf)
TCLL 20.0
TCDL 15.0
BCLL 0.0
BCDL 10.0
SPACING- 2-0-0
Plate Grip DOL 1.25
Lumber DOL 1.25
Rep Stress Incr NO
Code FBC20201rP12014
CSI.
TIC 0.25
BC 0.31
WB 0.10
Matrix -MS
DEFL. in (loc) Udefl Lid
Vert(LL) 0.05 6-10 >999 240
Vert(CT) -0.06 6-10 >999 240
Horz(CT) 0.02 5 n/a n/a
PLATES GRIP
MT20 244/190
Weight: 56 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-10-6 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 7-8-6 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 5=Mechanical, 2=0-8-0
Max Horz 2=131(LC 24)
Max Uplift 5=581(LC 8), 2=779(LC 8)
Max Grav 5=819(LC 1), 2=986(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-1393/1046, 3-4=-1218/1031, 4-5=1419/1083
BOT CHORD 2-7=-870/1201, 6-7=-876/1209, 5-6=-879/1209
WEBS 3-7=111/267, 4-6=120/276
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Provide adequate drainage to prevent water ponding.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
This item has been
7) Refer to girder(s) for truss to truss connections.
electronically signed and
8) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 581 lb uplift at joint 5 and 779 lb uplift at
sealed by Velez, Joaquin, PE
joint 2.
9) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 360 lb down and 331 lb up at
using a Digital Signature.
5-0-0, and 169 lb down and 129 lb up at 6-6-0, and 360 lb down and 331111, up at 8-0-0 on top chord, and 93 lb down and 141 lb up
Printed copies of this
at 5-0-0, and 52 lb down at 6-6-0, and 93 lb down and 141 lb up at 7-11-4 on bottom chord. The design/selection of such
document are not considered
connection device(s) is the responsibility of others.
signed and sea led and the
10) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B). J
Signature must e Verified
LOAD CASE(S) Standard
on any electronic copies.
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Joaquin Velez PE No.68182
Uniform Loads (plf)
MiTek USA, Inc, FL Cert 6834
Vert: 1-3=70, 3-4=70, 4-5=70, 8-11=-20
8904 Parke East Blvd. Tampa FL 33810
Concentrated Loads (lb)
Date:
Vert: 3=-140(F) 4=140(F) 7=55(F) 6=55(F) 15=69(F) 16=-33(F)
November 9,2021
® WARNING - Vedfy design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev, 5119t202O BEFORE USE.
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify, the applicability of design parameters and properly incorporate this design into the overall Not
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
uMiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSLITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MO 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912323
77930
AJACK-OPEN
14
1
Job Reference (optional)
cuss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:33 2021 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-nvmYXVQ7_HSft2_znnwEgQZmrVkghMHo—H OBCyLHl4
2-0-0 1-M
2-M 1-M
Scale = 1:9.5
1-0-0
1-OA
Plate Offsets (X,Y)— [2:0-5-0,0-0-41
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in
(loc) I/deft Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.34
Vert(LL) 0.00
7 >999 360
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.21
Vert(CT) 0.00
7 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) 0.00
4 n/a file
BCDL 10.0
Code FBC2020RPI2014
Matrix -MP
Wind(LL) -0.00
7 >999 240
Weight: 7 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP M 30
TOP CHORD
Structural wood sheathing directly applied or 1-0-0 oc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=120(LC 12)
Max Uplift 3=-45(LC 1). 2=395(LC 12), 4=-62(LC 1)
Max Grav 3=82(LC 12), 2=340(LC 1). 4=105(LC 12)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) zone; porch left and right exposed;C-C for members and
forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 45 lb uplift at joint 3, 395 lb uplift at joint
2 and 62 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL'Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE. _-:�•
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSBTPII Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
RESIDENCE
T25912324
77930
J3
JACK -OPEN
15
1
�BIILIS
1 _1eference
Job R o tional
are Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:34 2021 Page 1
I D:4lBbedBVbYEjpOwaV5X9TayML6T-F5KwkrRdkaaV W CYALU RTNe6xbv3S QpXyDxjxgeyLHl3
-2-0-0 3-"
2-M 3-0-0
Scale = 1:14.6
ig
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/deft Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.34
Vert(LL) 0.01 4-7 >999 240
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.30
Vert(CT) -0.00 4-7 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00 3 filial n/a
BCDL 10.0
Code FBC2020rrP12014
Matrix -MP
Weight: 13 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 3-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=176(LC 12)
Max Uplift 3=53(LC 9), 2=-341(LC 12), 4=-43(LC 9)
Max Grav 3=65(LC 17), 2=328(LC 1), 4=44(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E)-2-D-13 to 0-11-3, Interior(1) 0-11-3 to 2-11-4 zone; porch left
and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
Will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 53 lb uplift at joint 3, 341 lb uplift at joint
2 and 43 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.98182
MiTek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33810
Date:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 6/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall '� �•
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/TPIt Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldod, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912325
77930
J3A
Jack -Open
1
1
Job Reference (optional)
Chambers Truss, Fort Pierce, FL - 34982,
3x4 =
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:34 2021 Page 1
I D:4lBbed8VbYEj pOwaV5X9TayM L6T-F5KwkrRdkaaWV CYALU RTNe6y2v20 QpXyDxjxg eyLH I3
34)-0
34)-0
3-OA
3-M
Scale: 1"=1'
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL,
in
(loc)
I/defl
Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.31
Vert(LL)
-0.00
3-6
>999
360
MT20 244/190
TCDL 15.0
Lumber DOL
1.25
BC 0.33
Vert(CT)
-0.01
3-6
>999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT)
-0.00
2
n/a
rile
BCDL 10.0
Code FBC2020fTP12014
Matrix -MP
Wind(LL)
0.01
3-6
>999
240
Weight: 10 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD
BOT CHORD 2x4 SP No.3 BOT CHORD
REACTIONS. (size) 1=0-8-0, 2=Mechanical, 3=Mechanical
Max Horz 1=85(LC 12)
Max Uplift 1=-41(LC 12), 2=74(LC 12). 3=-12(LC 12)
Max Grav 1=133(LC 17), 2=97(LC 17), 3=57(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
Structural wood sheathing directly applied or 3-0-0 oc purlins.
Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3.6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 41 lb uplift at joint 1, 74 lb uplift at joint 2
and 12 lb uplift at joint 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MITek USA, Inc. FL Cert 6634
8904 Parke East Blvd. Tampa FL 33810
Date:
November 9,2021
® WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED hIITEK REFERENCE PAGE hill-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall Sal'
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSVTR11 Quality Crlteds, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss Type
City
Ply
BILLIS RESIDENCE
]d5'USS
T25912326
77930
Jack -Open
14
1
Job Reference (optional)
_„. of s r F rvi r ricrue, rL - r 9OZ, 6.43D s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:35 2021 Page 1
I D:4tB bed8VbYEj pOwaV5X9TayM L6TI H ulyBRFVui M6M7MvCyiiwrf6LJLT9G n5SbTV D4yLH 12
2 0 0 5-0.0
2 0 0 5.0-0
Scale = 1:19.5
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
Udefl
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.34
Vert(LL)
-0.02
4-7
>999
360
MT20 244/190
TCDL 15.0
Lumber DOL
1.25
BC 0.57
Vert(CT)
-0.05
4-7
>999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT)
-0.00
3
n/a
n/a
BCDL 10.0
Code FBC2020/TP12014
Matrix -MP
Wind(LL)
0.05
4-7
>999
240
Weight: 19 lb FT = 20%
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP No.3
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=234(LC 12)
Max Uplift 3=1109(LC 12), 2=279(LC 12)
Max Grav 3=157(LC 17), 2=397(LC 1), 4=87(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
BRACING -
TOP CHORD Structural wood sheathing directly applied or 5-0-0 cc purlins.
BOT CHORD Rigid ceiling directly applied or 10-0-0 cc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 4-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements speck
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 109 lb uplift at joint 3 and 279 lb uplift at
joint 2.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 8834
8904 Parke East Blvd. Tampa FL 33810
Date:
November 9,2021
®WARNING . Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not '
a truss system. Before use, the building designer must verily the applicability of design parameters and property Incorporate this design into the overall ■
building design. Bracing indicated is to prevent bucking of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSM11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Sulte 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
77930
J5P
JACK -OPEN
6
1
T25912327
rti.,.,he.� r..,« o....
o
Job Reference o tional
•-• - ^� b.vsU s Aug lb ZUz1 MI I eK Industries, Inc. Mon Nov 8 09:22:36 2021 Page 1
ID:4tBbed8V5b-YYEEjpOwaV5X9TayML6T-B USg9WStGCgDkWiiYSvUxS3BGLja2ujOFgFC21 WyLHIt
-2- 0
2-0-0 5-0-0
Scale = 1:19.5
I 5-0-0
5-M
Plate Offsets (X,Y)— [2:0-1-8,0-2-51,[2:0-1-10 0-3-21
LOADING (psf)
SPACING- 2-0-0
CS1.
DEFL. in (too) Vdefl Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.39
Vert(LL) 0.12 5-10 >495 240
MT20 2441190
TCDL 15.0
Lumber DOL 1.25
BC 1.00
Vert(CT) -0.03 5-10 >999 240
BCLL 0.0
Rep Stress [nor YES
WB 0.00
Horz(CT) -0.01 4 n/a n/a
BCDL 10.0
Code FBC2020frP12014
Matrix -MP
Weight: 21 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied.
SLIDER Left 2x4 SP No.3 1-5-2
REACTIONS. (size) 4=Mechanical, 2=0-8-0, 5=Mechanical
Max Horz 2=234(LC 12)
Max Uplift 4=-109(LC 12), 2=409(LC 12). 5=-75(LC 9)
Max Grav 4=120(LC 17),2=426(LC 1),5=76(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-4=-208/350
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
[I; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 1-2-5, Interior(1) 1-2-5 to 4-11-4 zone; porch left
and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 109 lb uplift at joint 4, 409 lb uplift at
joint 2 and 75 lb uplift at joint 5.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MIT& USA, Inc. FL Cert 6634
8904 Parke East Blvd. Tampa FL 33910
Date:
November 9,2021
WARNING -Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
--
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall l•
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing iVliTek`
is ahvays required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSbTP11 Quality criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safeeylnformation available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
77930
J7
Jack -Open
26
1
T25912328
I-- r -
Job Reference (optional)
• •- • - • - ^� 8.4.SU s Aug l b 2UZI MI i eK Innustnes, Inc. Mon Nov 6 09:22:37 2021 Pagel
ID:4tBbed8VbYEjpowaV5X9TayML6T-fgO2NsTW1 Vy4MfH]Od?A?GkNv73Pd9GOvvycHzyLHIO
-2-0-0 7-0-0
2-0-0 7-0-0
Scale: 1/2"=l'
7-0.0
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
floc)
Well
Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TIC 0.66
Vert(LL)
-0.08
4-7
>999
360
MT20 244/190
TCDL 15.0
Lumber DOL
1.25
BC 0.41
Vert(CT)
-0.20
4-7
>422
240
BCLL 0.0 '
Rep Stress Incr
YES
WB 0.00
Horz(CT)
-0.01
3
n/a
n/a
BCDL 10.0
Code FBC2020/TPI2014
Matrix -MP
Wind(LL)
0.17
4-7
>486
240
Weight: 26 lb FT = 20%
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 30
REACTIONS. (size) 3=Mechanical, 2=0-8-0, 4=Mechanical
Max Horz 2=292(LC 12)
Max Uplift 3=-169(LC 12), 2=295(LC 12), 4=2(LC 9)
Max Grav 3=227(LC 17). 2=478(LC 1), 4=131(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 6-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 169 lb uplift at joint 3, 295 lb uplift at
joint 2 and 2 lb uplift at joint 4.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/192020 BEFORE USE.
--
Design valid for use only with Mt ek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSUTP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLISRESIDENCE
T25912329
77930
J7A
Jack -Open
6
1
Job Reference (optional)
unamoers I russ, Tort h'ierce, FL - 349t12, 8.430 s Aug 16 2021 Mffek Industries, Inc. Mon Nov 8 09:22:38 2021 Page 1
I D:4tBbed8VbYEjpOwaV5X9TayML6T-7saRaC U8op4xzpsxak:WPXUHXw W M 5McWX8Zh9pPyLH I?
7-"
7-"
3x5 =
LOADING (psf)
SPACING-
2-0-0
CS].
DEFL.
TCLL
20.0
Plate Grip DOL
1.25
TIC 0.71
Vert(LL)
TCDL
15.0
Lumber DOL
1.25
BC 0.51
Vert(CT)
BCLL
0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT)
BCDL
10.0
Code FBC2020/TPI2014
Matrix -MP
Wind(LL)
in
(loc)
I/defl
Lid
-0.09
3-6
>946
360
-0.23
3-6
>366
240
-0.01
2
n/a
n/a
0.21
3-6
>388
240
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 30 BOT CHORD
REACTIONS. (size) 1=0-8-0, 2=Mechanical, 3=Mechanical
Max Horz 1=201(LC 12)
Max Uplift 1=-99(LC 12), 2=184(LC 12), 3=-18(LC 12)
Max Grav 1=314(LC 17), 2=237(LC 17), 3=136(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown
Scale = 1:23.5
PLATES GRIP
MT20 244/190
Weight: 22 lb FT = 20%
Structural wood sheathing directly applied or 6-0-0 oc purlins.
Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) 0-0-0 to 3-0-0, Interior(1) 3-0-0 to 6-114 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fd between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 99 lb uplift at joint 1, 184 lb uplift at joint
2 and 18 lb uplift at joint 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this )
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MITek USA, Inc. FL Cert 6634
8904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
®WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE '011-7473 rev. 5/192020 BEFORE USE.
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and is for an individual building component. not
a truss system. Before use, the building designer must verity the applicability of design parameters and property Incorporate this design into the overall lei'
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing M iTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, sea ANS11TP/1 Qualify Criteria, DSB-99 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss Type
Qty
Ply
BILLIS RESIDENCE
Fruss77930
Jack -Open
q
1
T25912330
r`homhere Tn,« C..M
o:.,..... Cr swoon
Job Reference (optional)
3x4 =
o.—V a rwy 10 cUc I Ivu I ex Inuustnes, Inc. Mon NOV 0 UV:ZZ:3tt ZUZ1 Page 1
I D:4tBb ed8VbYEipOwaV5X9TayM L6T-7sa RaC U8op4xzpsxaKW PXU H icW UdMcWXBZh9pP yLH I7
1-0.0
1-0-0
. r't
0150,
Scale = 1:7.0
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in
(loc)
I/defl
Ud
PLATES GRIP
TOLL 20.0
Plate Grip DOL 1.25
TC 0.02
Vert(LL)
-0.00
6
>999
360
MT20 2441190
TCDL 15.0
Lumber DOL 1.25
BC 0.03
Vert(CT)
-0.00
6
>999
240
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT)
-0.00
2
n/a
n/a
BCDL 10.0
Code FBC2020/rP12014
Matrix -MP
Wind(ILL)
0.00
6
>999
240
Weight: 3 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD
BOT CHORD 2x4 SP No.3 BOT CHORD
REACTIONS. (size) 1=0-8-0, 2=Mechanical, 3=Mechanical
Max Horz 1=29(LC 12)
Max Uplift 1=13(LC 12), 2=20(LC 12), 3=9(1_13 12)
Max Grav 1=45(LC 17), 2=28(LC 17), 3=20(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
Structural wood sheathing directly applied or 1-0-0 oc purlins.
Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 13 lb uplift at joint 1, 20 lb uplift at joint 2
and 9 lb uplift at joint 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MlTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date.
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek0 connectors. This design is based only upon parameters shown, and is for an individual building component, not
--
t
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall
bull ding design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and bracing
11 A��el.'
permanent
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
�V Il
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Cdteda, DSB-89 and SCSI Building Component
Safetylnformation available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601
6904 Parke East Blvd.
Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912331
77930
JA3
Jack -Open
2
1
Job Reference (optional)
e n r u rui r ri —, rL - syaot, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:39 2021 Page 1
3-0-0 ID:4tBbed8VbYEjpOwaV5X9TayML6T-c38poYUmZ7CobzR7821 e4hppnwlA53mhNDRiMryLHI_
3-M
Scale: V=1'
3x4 =
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
I/deft
L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TIC 0.31
Vert(LL)
-0.00
3-6
>999
360
MT20 244/190
TCDL 15.0
Lumber DOL
1.25
BC 0.33
Vert(CT)
-0.01
3-6
>999
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT)
-0.00
2
n/a
n/a
BCDL 10.0
Code FBC2020(rP12014
Matrix -MP
Wind(LL)
0.01
3-6
>999
240
Weight: 10 lb FT = 20%
LUMBER -
TOP CHORD 2x4 SP No.3
BOT CHORD 2x4 SP No.3
REACTIONS. (size) 1=D-8-0, 2=Mechanical, 3=Mechanical
Max Horz 1=85(LC 12)
Max Uplift 1=-41(LC 12), 2=74(1_C 12), 3=-12(LC 12)
Max Grav 1=133(LC 17), 2=97(LC 17), 3=57(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
BRACING -
TOP CHORD Structural wood sheathing directly applied or 3-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or'10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 41 lb uplift at joint 1, 74 lb uplift at joint 2
and 12 Ito uplift at joint 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING - verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/19/2020 BEFORE USE
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing Indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek*
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabriwtlon, storage, delivery, erection and bracing of trusses and truss systems, see ANSM11 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldod, MD 20601 Tampa, FL 36610
Job
Truss Type
City
Ply
RESIDENCE
TJA5SS
JJack-Open
FS T25912332
77930
2
1
eference o tional
Chambers Truss, Fort Pierce, FL - 34982,
3x4 =
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:40 2021 Page 1
I D:4tBbedBVbYEjp OwaV5X9TayML6T-4 FhB?uVO KQ KfD7OKh IYtdvMzoKzKgWOgbtAGtIyLH kz
5-0-0
5-0-0
5-0-0
6-0-0
Scale = 1:17.9
LOADING (psf)
SPACING-
2-0-0
CSI.
DEFL.
in
(loc)
I/deft
Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL
1.25
TC 0.36
Vert(LL)
-0.03
3-6
>999
360
MT20 244/190
TCDL 15.0
Lumber DOL
1.25
BC 0.85
Vert(CT)
-0.07
3-6
>853
240
BCLL 0.0
Rep Stress Incr
YES
WB 0.00
Horz(CT)
-0.00
2
rile
n/a
BCDL 10.0
Code FBC2020rrP12014
Matrix -MP
Wind(LL)
0.08
3-6
>743
240
Weight: 16 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP No.3 BOT CHORD
REACTIONS. (size) 1=0-8-0, 2=Mechanical, 3=Mechanical
Max Horz 1=143(LC 12)
Max Uplift 1=70(LC 12). 2=132(LC 12). 3=-12(LC 12)
Max Grav 1=224(LC 17). 2=172(LC 17), 3=93(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
Structural wood sheathing directly applied or 5-0-0 oc purlins.
Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) 0-0-0 to 3-0-0, Interior(1) 3-0-0 to 4-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 70 lb uplift at joint 1, 132 lb uplift at joint
2 and 12 lb uplift at joint 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33810
Data:
November 9,2021
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verity the applicability of design parameters and properly incorporate this design Into the overall'
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabdcation, storage, delivery, erection and bracing of trusses and truss systems, see ANShTP/t Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912333
77930
JC5
Jack -Open
6
1
Job Reference (optional)
Uhambers Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:41 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-YRFZCEW05kS WgHbWFS3696u8QkP2zn_gXwpPkyLHky
2-M 2-8-0 5 0 0
2-0-0 2-8-0
Scale = 1:19.5
Plate Offsets (X,Y)— [3:0-1-9,0-3-12)
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) Vdefl Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TIC 0.37
Vert(LL) -0.04 6 >999 360
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.45
Vert(CT) -0.11 6 >558 240
BCLL 0.0
Rep Stress Incr YES
WB 0.03
Horz(CT) 0.08 5 n/a n/a
BCDL 10.0
Code FBC2020frP12014
Matrix -MP
Wind(LL) 0.15 6 >390 240
Weight: 21 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 5-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 6-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 4=Mechanical, 2=0-8-0, 5=Mechanical
Max Harz 2=234(LC 12)
Max Uplift 4=-108(LC 12). 2=278(LC 12)
Max Grav 4=188(LC 17), 2=401(LC 1), 5=55(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
NOTES-
1) Wind: ASCE 7-16; VuK=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 4-11-4 zone;C-C for
members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 108 lb uplift at joint 4 and 278 lb uplift at
joint 2.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6834
8904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/fP11 Qualify Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 366110
Job
Truss
Truss Type
CIty
Ply
BILLIS RESIDENCE
77930
K
Common
1
1
T25912334
rti.....r....
Job Reference (optional)
rs.gsU s Aug lb ZUZ1 MI I eK Industries, Inc. Mon Nov 8 09:22:41 2021 Page 1
ID:4lBbed8VbYEjpOwaV5X9TayML6T-YRFZCEW05kS WgHbWFS3696u7ukRIZyF _gXwpPkyLHky
_2'0-0 6-M 13-0-0
2-0 0 6-M 6-6-0
Scale = 1:25.9
4x6 =
6-6-0
13-0.0
6.6.0
6.6.0
LOADING (psf)
SPACING- 2-0-0
CS1.
DEFL. In (loc) Udefl Ltd
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TIC 0.40
Vert(LL) -0.05 5-8 >999 360
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.32
Vert(CT) -0.11 5-8 >999 240
BCLL 0.0
Rep Stress Incr YES
WB 0.12
Horz(CT) 0.01 4 n/a file
BCDL 10.0
Code FBC2020rrPI2014
Matrix -MS
Wind(LL) 0.10 5-8 >999 240
Weight: 49 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing
directly applied or 6-0-0 oc pudins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied
or 9-7-14 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 4=Mechanical, 2=0-8-0
Max Horz 2=160(LC 11)
Max Uplift 4=-266(LC 12), 2=-464(LC 12)
Max Grav 4=574(LC 1). 2=741(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-818/691, 34=813/714
BOT CHORD 2-5=-467/649, 4-5=-467/649
WEBS 3-5=-83/315
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; VuIt=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.0psf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E)-2-0-13 to 0-11-3, Interior(1) 0-11-3 to 6-6-0, Exterior(2R)
6-6-0 to 9-6-0, Interior(1) 9-6-0 to 13-0-0 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate
grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
This Item has been
6) Refer to girder(s) for truss to truss connections.
electronically Signed and
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 266 lb uplift at joint 4 and 464 lb uplift at
sealed by Velez, Joaquin, PE
joint 2
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE M1111-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with Mrrek® connectors. This design Is based only upon parameters shown, and Is for an Individual building component, not A
a buss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall i•
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI?Plt Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912335
77930
KJ5
DIAGONAL HIP GIRDER
3
1
Job Reference (optional)
• "• • • •"• `^� 0.40U b Mug 10 LUZ I IVII I eK InaU6lrles, Inc, mon NOV it UU:ZZ:42 ZU21 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-0epxQaXes2aNS RAipAaLiKRHe8nhlQV73BfMxAyLHkx
-2-9-15 3.8-10 7.0-2
2-9-15 3-8-10 3-3-8
Scale = 1:19.1
I9
a9
rV
N
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in
(loc)
Udefl
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.47
Vert(LL)
0.19
4-7
>4311
240
MT20 2441190
TCDL 15.0
Lumber DOL 1.25
BC 0.34
Vert(CT)
0.21
4-7
>393
180
BCLL 0.0
Rep Stress Incr NO
WB 0.00
Horz(CT)
0.01
2
n/a
n/a
BCDL 10.0
Code FBC2020/TPI2014
Matrix -MP
Weight: 26 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD
BOT CHORD 2x4 SP M 31 BOT CHORD
REACTIONS. (size) 3=Mechanical, 2=0-10-15, 4=Mechanical
Max Horz 2=232(LC 24)
Max Uplift 3=-166(LC 8). 2=619(LC 8), 4=135(LC 5)
Max Grav 3=192(LC 28), 2=576(LC 28), 4=103(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
Structural wood sheathing directly applied or 6-0-0 oc purlins.
Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); porch left and right exposed; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 pelf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 166 lb uplift at joint 3, 619 lb uplift at
joint 2 and 135 lb uplift at joint 4.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 162 lb down and 144 lb up at
1-6-1, 162 lb down and 144 lb up at 1-6-1, and 51 lb down and 72 lb up at 4-4-0, and 51 lb down and 72 lb up at 4-4-0 on top chord
, and 160 lb down and 90 lb up at 1-6-1, 160 lb down and 90 lb up at 1-6-1, and 12 lb down and 5 lb up at 4-4-0, and 12 lb down
and 5 lb up at 4-4-0 on bottom chard. The design/selection of such connection device(s) is the responsibility of others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=70, 4-5=20
Concentrated Loads (lb)
Vert: 8=120(F=60, B=60) 10=102(F=51, B=51) 11=5(F=3, B=3)
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.88182
MiTek USA, Inc. FL Cert 6634
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
®WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE Mll-7473 rev. 5/192020 BEFORE USE. '-'�'
Design valid for use ontywith MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not 4-.��Ypq
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
77930
KJ7
Diagonal Hip Girder
4
1
T25912336
r•ti,m� - T-•
Job Reference (optional)
• • •-• - o.9cu s Hug 113 ZUZ1 MI I eK industries, Inc. Mon Nov 8 09:22:44 2021 Page 1
I D:4tBbedBVbYEj pOwaV5X9TayML6T-yOxirFYvOfg5hkJ5wbdgnl We9xRl m EbQV W 8TO3yLHkv
-2-9-15 5-1-9 9-10-1
2-9.15 5-1-9 4-8-7
Scale: 117"=1'
5-1-9 4.8.7
Plate Offsets (X Y)— [2:0-0-5 Edge]
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) Udefl L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TIC 0.40
Vert(LL) -0.11 7-10 >999 240
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.40
Vert(CT) -0.08 6-7 >999 240
BCLL 0.0
Rep Stress Incr NO
WB 0.41
Horz(CT) 0.01 5 n/a rile
BCDL 10.0
Code FBC2020lrP12014
Matrix -MS
Weight: 44 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP M 30 TOP CHORD Structural wood sheathing directly applied or 6-0-0 do purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
WEBS 2x4 SP No.3
REACTIONS. (size) 4=Mechanical, 2=0-10-15, 5=Mechanical
Max Horz 2=290(LC 8)
Max Uplift 4=134(LC 8), 2=606(LC 8), 5=-189(LC 8)
Max Grav 4=170(LC 1), 2=779(LC 28), 5=384(LC 28)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-911/438
BOT CHORD 2-7=-522/827, 6-7=522/827
WEBS 3-7=-83/274, 3-6=898/566
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 134 lb uplift at joint 4, 606 lb uplift at
This item has been
joint 2 and 189 lb uplift at joint 5.
and electronically Signed
and
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 162 lb down and 144 lb up at
1-6-1. 162 lb down 144 lb
yeez,signed
sealed Velez, PE
Joaquin,
and up at 1-6-1, 51 lb down and 72 lb up at 4-4-0, 51 lb down and 72 lb up at 4-4-0, and 182 lb down
and 137 lb up at 7-1-16, and 182 lb down and 137 lb up at 7-1-15 on top chord, and 101 lb down and 90 lb up at 1-6-1, 101 lb
using a Digital Signature.
down and 90 lb up at 1-6-1, 12 lb down and 53 lb up at 4-4-0, 12 lb down and 53 lb up at 4-4-0, and 49 lb down at 7-1-15, and 49
Printed copies of this
lb down at 7-1-15 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
document are not Considered
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
signed and sealed and the
LOAD CASE(S) Standard
signature must be verified
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
on any electronic copies.
Uniform Loads (plf)
Joaquin Velez PE No.68182
Vert: 14=70, 5-8=20
MiTek USA, Inc. FL Cart 6834
Concentrated Loads (lb)
8904 Parke East Blvd. Tampa FL 33810
Vert: 11=120(F=60, B=60) 13=81(F=-40, B==-40) 14=102(F=51, B=51) 15=5(F=3, B=3) 16=48(F=24, B=24)
Date:
November 9,2021
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE.
M Design valid for use only with Tek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI?P/f Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute. 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Oty
Ply
BILLISRESIDENCE
77930
KJA
Diagonal Hip Girder
2
1
T25912337
Job Reference (optional)
O.4JU smug 1 O zuzl Mimi( eK maustnes, Inc. Mon NOV 6 09:22:45 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayMLST-ODV42bZX9zyyJuuHU183Ky3rzLp_VgDZ19u1YVyLHku
5-1-9 9-10-1
5-1-9 4-8-7
0
Chh
A
3x4 = 2x3 11 4
3x4 =
Scale = 1:23.1
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in
(loc)
I/deft
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.27
Vert(LL)
-0.03
5-6
>999 .
360
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.31
Vert(CT)
-0.07
5-6
>999
240
BCLL 0.0
Rep Stress Incr NO
WB 0.45
Horz(CT)
0.01
4
n/a
n/a
BCDL 10.0
Code FBC2020frP12014
Matrix -MS
Wind(LL)
0.04
6-9
>999
240
Weight: 39 lb FT = 20%
LUMBER -
TOP CHORD 2x4 SP M 30
BOT CHORD 2x4 SP M 30
WEBS 2x4 SP No.3
REACTIONS. (size) 1=0-10-15, 3=Mechanical, 4=Mechanical
Max Horz 1=200(LC 21)
Max Uplift 1=-272(LC 8), 3=136(LC 8), 4=-237(LC 8)
Max Grav 1=503(LC 25), 3=160(LC 1), 4=415(LC 25)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 1-2=-974/505
BOT CHORD 1-6=625/901, 5-6=625/901
WEBS 2-6=-83/304, 2-5=978/679
BRACING -
TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 9-2-5 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional); Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
4) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
5) Refer to girder(s) for truss to truss connections.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 272 lb uplift at joint 1, 136 lb uplift at
joint 3 and 237 lb uplift at joint 4.
7) Hanger(s) or other connection device(s) shall be provided sufficient to support concentrated load(s) 90 Ito down and 34 lb up at
1-6-1. 90 Ito down and 34 lb up at 1-6-1, 139 lb down and 96 lb up at 4-4-0, 51 lb down and 72 lb up at 4-4-0, and 192 lb down and
163 lb up at 7-1-15, and 182 lb down and 137 lb up at 7-1-15 on top chord, and 8 lb down and 13 lb up at 1-6-1, 8 lb down and 13
lb up at 1-6-1, 32 lb down and 22 lb up at 4-4-0, 12 lb down and 53 lb up at 4-4-0, and 52 lb down and 27 lb up at 7-1-15, and 49
lb down at 7-1-15 on bottom chord. The design/selection of such connection device(s) is the responsibility of others.
8) In the LOAD CASE(S) section, loads applied to the face of the truss are noted as front (F) or back (B).
LOAD CASE(S) Standard
1) Dead + Roof Live (balanced): Lumber Increase=1.25, Plate Increase=1.25
Uniform Loads (plf)
Vert: 1-3=70, 4-7=20
Concentrated Loads (lb)
Vert: 12=-97(F=-40, B=57) 13=-13(F=7, B=-7) 14=-14(F=3, B=16) 15=-63(1`=24, B=38)
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 8834
6904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MITek® connectors. This design is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and BCS/ Building Component 6904 Parke East Blvd.
Safety information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912338
77930
MV2
Valley
1
1
Job Reference (opt
Chambers Truss, Fort Pierce, FL - 34982,
3x4 i
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:45 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-QDV42bZX9zyyJuuHUI83Ky3ueLtFVnFZ19u1YVyLHku
2-0.0
2-M
Scale = 1:7.8
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL.
in (loc)
I/defl
Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.10
Vert(LL)
n/a
n/a
999
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.03
Vert(CT)
file
n/a
999
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT)
-0.00 2
n/a
n/a
BCDL 10.0
Cade FBC2020rrPI2014
Matrix-P
Weight: 5 lb FT = 20%
LUMBER -
TOP CHORD 2x4 SP No.3
BOT CHORD 2x4 SP No.3
REACTIONS. (size) 1=2-0-0, 2=2-0-0, 3=2-0-0
Max Horz 1=40(LC 12)
Max Uplift 1=-20(LC 12), 2=-44(LC 12)
Max Grav 1=63(LC 17), 2=54(LC 17), 3=28(LC 3)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
BRACING -
TOP CHORD Structural wood sheathing directly applied or 2-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=oft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements speck
to the use of this truss component.
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Bearing at joint(s) 2 considers parallel to grain value using ANSI/TPI 1 angle to grain formula. Building designer should verify
capacity of bearing surface.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 20 lb uplift at joint 1 and 44 lb uplift at
joint 2.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE. Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verity the applicability of design parameters and properly incorporate this design into the overall ■■■,
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss Type
oty
Ply
BILLIS RESIDENCET25912339
FMV4
77930
Valley
1
1
Job Reference o tional
Puss, run Pierce, FL - 34962,
3x4 i
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:46 2021 Page 1
ID:4tBbed8VbYEjpOwaV5X9TayML6T-uP3SGxa9wG4px2TT20f IsAcwEIAnEEVj_pda5xyLHkt
44W
4-M
3x4 II
2
Scale = 1:12.8
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) Vdefl L/d
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.62
Vert(LL) n/a n/a 999
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.21
Vert(CT) file n/a 999
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) 0.00 n/a n/a
BCDL 10.0
Code FBC2020rTP12014
Matrix-P
Weight: 14 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD
BOT CHORD 2x4 SP No.3
WEBS 2x4 SP No.3 BOT CHORD
REACTIONS. (size) 1=4-0-0, 3=4-0-0
Max Horz 1=94(LC 12)
Max Uplift 1=-47(LC 12), 3=94(LC 12)
Max Grav 1=147(LC 17). 3=158(LC 17)
FORCES. (lb) -Max. Camp./Max. Ten. -All forces 250 (lb) or less except when shown.
TOP CHORD 2-3=-157/256
Structural wood sheathing directly applied or 4-0-0 oc purlins,
except end verticals.
Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
2) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
3) Gable requires continuous bottom chord bearing.
4) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
5) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
6) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 47 lb uplift at joint 1 and 94 lb uplift at
joint 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
WARNING -Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
--
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verity the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSLITP11 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldod, MD 20601 Tampa, FL 36610
Job
s
Truss Type
Qty
Ply
BILLIS RESIDENCE
TPB
T25912340
77930
Piggyback
8
1
Job Reference (optional)
vnon ucr o r r u run nercn, r - ovyoc, 6.43U s Aug 16 ZU21 MiTek Industries, Inc. Mon Nov 8 09:22:47 2021 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-NbcgTHbnhaCfZC2gcjAXPN8CP9XJzhisCTN7dOyLHks
r 2-4-0 441-0
2-4-0 240
3x6 =
3x4 =
3x4 =
Scale = 1:9.3
4-8.0
4-a-0
Plate Offsets (X,Y)— [3:0-3-0,Edge)
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) Vdefi Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.15
Vert(LL) 0.00 4 n/r 120
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.19
Vert(CT) 0.00 4 nlr 90
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) 0.00 4 n/a n/a
BCDL 10.0
Code FBC2020lrP12014
Matrix-P
Weight: 12 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 4-8-0 oc puriins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
REACTIONS. (size) 2=2-10-6, 4=2-10-6
Max Horz 2=39(LC 11)
Max Uplift 2=-108(LC 12), 4=108(LC 12)
Max Grant 2=169(LC 1), 4=169(LC 1)
FORCES. (lb) - Max. Comp./Max. Ten. - All forces 250 (lb) or less except when shown.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Gable requires continuous bottom chord bearing.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 108 lb uplift at joint 2 and 108 lb uplift at
joint 4.
8) See Standard Industry Piggyback Truss Connection Detail for Connection to base truss as applicable, or consult qualified building
This item has been
designer.
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
WARNING - Venty design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE NIII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and Is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall'
building design. Bracing indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
uMiTek•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSI/rPlf Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
Qty
Ply
BILLIS RESIDENCE
T25912341
77930
PBB
Piggyback
2
1
Job Reference (optional)
unambers I russ, Fort Pierce, FL - 34962, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:48 2021 Page 1
ID:4lBbed8VbYEjpOwaV5X9TayML6T-roADgdbPRuLWAMds9QhmxbhO WytWii8?OR76h9gyLHkr
2-0-0 2 8 0 4-8-0
2-0-0 0-8.0 2-13-0
4x4 II
3x4 = 3x4 =
Scale = 1:9.4
LOADING (psf)
SPACING- 2-0-0
CS1.
DEFL.
in
(loc) Vdefl Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.12
Vert(LL)
0.00
4 n/r 120
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.19
Vert(CT)
0.00
4 n/r 90
BCLL 0.0 '
Rep Stress Incr YES
WB 0.00
Horz(CT)
0.00
4 n/a n/a
BCDL 10.0
Code FBC2020/rP12014
Matrix-P
Weight: 12 lb FT = 20%
LUMBER-
BRACING -
TOP CHORD 2x4 SP No.3
TOP CHORD
Structural wood sheathing directly applied or 4-8-0 cc purlins.
BOT CHORD 2x4 SP No.3
BOT CHORD
Rigid ceiling directly applied or 10-0-0 cc bracing.
REACTIONS. (size) 2=2-10-6, 4=2-10-6
Max Horz 2=36(1_13 10)
Max Uplift 2=-108(LC 12), 4=108(LC 12)
Max Grav 2=169(LC 1).4=169(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or
less except when shown.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Gable requires continuous bottom chord bearing.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 108 lb uplift at joint 2 and 108 lb uplift at
joint 4.
8) See Standard Industry Piggyback Truss Connection Detail for Connection to base truss as applicable, or consult qualified building
designer.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
building design. Bracing Indicated Is to prevent buckling of Individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSNTP/1 Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety lntorma ton available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
BILLIS RESIDENCE
T25912342
77930
V4
Valley
2
1
Job Reference (optional)
rtrii rroit;e, rL -. 562, 1:5.43U s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:51 2021 Page 1
ID:4lBbed8VbYEjpOwaV5X9TayML6T-FMsLJfelkpj5l pMRrZFTZDJuumuevVkS75LLm9yLHko
2-M 4.0.0
2-0-0 2-M
3x6 =
2
3x4 i
3x4
Scale = 1:7.7
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/deft Ud
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.18
Vert(LL) n/a n/a 999
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.16
Vert(CT) n/a n/a 999
BCLL 0.0
Rep Stress Incr YES
WB 0.00
Horz(CT) -0.00 3 n/a file
BCDL 10.0
Code FBC2020/TPI2014
Matrix-P
Weight: 11 lb FT = 20%
LUMBER -
TOP CHORD 2x4 SP No.3
BOT CHORD 2x4 SP No.3
REACTIONS. (size) 1=4-0-0, 3=4-0-0
Max Horz 1=27(LC 10)
Max Uplift 1=-60(LC 12), 3=60(1_C 12)
Max Grav 1=124(LC 1), 3=124(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
BRACING -
TOP CHORD Structural wood sheathing directly applied or 4-0-0 oc purlins.
BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) zone;C-C for members and forces & MWFRS for reactions
shown; Lumber DOL=1.60 plate grip DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Gable requires continuous bottom chord bearing.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb 'uplift at joint(s) 1, 3.
This item has been
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 8834
6904 Parke East Blvd. Tampa FL 33810
Data:
November 9,2021
® WARNING -Verity design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE NIII 7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall Iva
building design. Bracing Indicated Is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safetylnformation available from Truss Plate Institute, 2670 Crain Mghway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
BILLIS RESIDENCE
T25912343
77930
V8
Valley
2
1
Job Reference (optional)
Cnarnoers truss, Pon: Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:52 2021 Page 1
ID:4lBbed8VbYEjpOwaV5X9TayML6TjZQj W?fwV6ryfzxdOGm i6RswpADJexsbMl4ulbyLHkn
4-0-0 8-0-0
4-0-0 4-M
3x4 i
2x3 11
4x4 =
3x4
Scale = 1:15.1
8-0-0
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in (loc) I/defl Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TIC 0.74
Vert(LL) n/a file 999
MT20 244/190
TCDL 15.0
Lumber DOL 1.25
BC 0.20
Vert(CT) n/a n/a 999
BCLL 0.0
Rep Stress Incr YES
WB 0.10
Horz(CT) 0.00 3 n/a file
BCDL 10.0
Code FBC2020rrP12014
Matrix-P
Weight: 25 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. (size) 1=8-0-0, 3=8-0-0, 4=8-0-0
Max Horz 1=-66(LC 10)
Max Uplift 1=-93(LC 12). 3=93(LC 12), 4=-108(LC 12)
Max Grav 1=155(LC 1). 3=159(LC 18), 4=299(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
WEBS 2-4=-217/332
NOTES-
1) Unbalanced roof live leads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.Opsf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) 0-7-7 to 3-7-7, Interior(1) 3-7-7 to 4-0-0, Exterior(2R) 4-0-0 to
7-0-0, Interior(1) 7-0-0 to 7-4-9 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Gable requires continuous bottom chord bearing.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 3 except (jt=lb)
This item has been
4=108.
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cert 6834
6904 Parke East Blvd. Tampa FL 33610
Date:
November 9,2021
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE
Design valid for use only with MiTek® connectors. This design Is based only upon parameters shown, and is for an Individual building component, not
a truss system. Before use, the building designer must verity the applicability of design parameters and property Incorporate this design into the overall my
building design. Bracing Indicated is to prevent buckling of individual truss web and/or chord members onty. Additional temporary and permanent bracing MiTek•
Is always required for stability and to prevent collapse with possible personal Injury and property damage. For general guidance regarding the
fabdeation, storage, delivery, erection and bracing of trusses and truss systems, see ANS11TP1I Quality Criteria, DSB-89 and SCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Type
Qty
Ply
BILLIS RESIDENCET25912344
F
77930
V12
2
1
Job Reference (optional)
Chambers Truss, Fort Pierce, FL - 34982,
8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:49 2021 Page 1
ID:4tBbedBVbYEjpOwaV5X9TayML6T-J_kbuzc1 CBTNoWC2j6D7UoEL4y8gRZA9gnsEhGyLHkq
12-0-0
4x6 =
4
3x4 i - 2x3 II 3x4
Scale = 1:21.0
12-M
LOADING (psf)
SPACING- 2-0-0
CSI.
DEFL. in floc) Vdefl Lid
PLATES GRIP
TCLL 20.0
Plate Grip DOL 1.25
TC 0.97
Vert(LL) n/a n/a 999
MT20 2441190
TCDL 15.0
Lumber DOL 1.25
BC 0.50
Vert(CT) n/a n/a 999
BCLL 0.0
Rep Stress Incr YES
WB 0.13
Horz(CT) 0.00 3 n/a n/a
BCDL 10.0
Cade FBC2020rTP12014
Matrix-S
Weight: 39 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied.
BOT CHORD 2x4 SP No.3 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. (size) 1=12-0-0, 3=12-0-0, 4=12-0-0
Max Horz 1=-106(LC 10)
Max Uplift 1=123(LC 12), 3=123(LC 12). 4=-221(LC 12)
Max Grav 1=223(LC 21). 3=231(LC 18), 4=528(LC 1)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
WEBS 2-4=-365/446
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.0psf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
11; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) 0-7-7 to 3-7-7, Interior(1) 3-7-7 to 6-0-0, Exterior(2R) 6-0-0 to
9-0-0, Interior(1) 9-0-0 to 11-4-9 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component.
4) Gable requires continuous bottom chord bearing.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 123 lb uplift at joint 1, 123 lb uplift at
This item has been
joint 3 and 221 lb uplift at joint 4.
electronically Signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6834
8904 Parke East Blvd. Tampa FL 33610
Data:
November 9,2021
® WARNING - Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE.
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design into the overall AiTek,
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing
Is always required for stability and to preverd collapse with possible personal Injury and property damage. For general guidance regarding the iw
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSLITP11 Quality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Tampa, FL 36610
Job
Truss
Truss Type
City
Ply
BILLIS RESIDENCE
T25912345
77930
V16
Valley
2
1
Job Reference o tional
Chambers Truss, Fort Pierce, FL - 34982, 8.430 s Aug 16 2021 MiTek Industries, Inc. Mon Nov 8 09:22:50 2021 Page 1
ID:4lBbedBVbYEjpOwaV5X9TayML6T-nAIz5JdfzVbEQfnFHrkE10mf7MazA1VluRboEiyLHkp
8-0-0 16-0-0
8-0-0 8-0-0
4x4 =
Scale = 1:27.9
3x4 f- a 7 6 3x4
2x3 II 24 II 2x3 II
LOADING (psf)
SPACING-
2-0-0
TCLL
20.0
Plate Grip DOL
1.25
TCDL
15.0
Lumber DOL
1.25
BCLL
0.0
Rep Stress Incr
YES
BCDL
10.0
Code FBC2020/TPI2014
CSI. DEFL. in (loc) Vdefl Lid
TIC 0.44 Vert(LL) n/a n/a 999
BC 0.06 Vert(CT) n/a n/a 999
WB 0.13 Horz(CT) 0.00 5 n/a n/a
Matrix-S
PLATES GRIP
MT20 244/190
Weight: 58 lb FT = 20%
LUMBER- BRACING -
TOP CHORD 2x4 SP No.3 TOP CHORD Structural wood sheathing directly applied or 6-0-0 oc purlins.
BOT CHORD 2x4 SP M 30 BOT CHORD Rigid ceiling directly applied or 10-0-0 oc bracing.
OTHERS 2x4 SP No.3
REACTIONS. All bearings 16-0-0.
(lb) - Max Horz 1=-145(LC 10)
Max Uplift All uplift 100 lb or less at joint(s) 1, 5, 7 except 6=-254(LC 12), 8=254(LC 12)
Max Grav All reactions 250 lb or less at joint(s) 1, 5 except 7=302(LC 1), 6=427(LC 18), 8=427(LC 17)
FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown
WEBS 4-6=-338/427, 2-8=338/427
NOTES-
1) Unbalanced roof live loads have been considered for this design.
2) Wind: ASCE 7-16; Vult=165mph (3-second gust) Vasd=128mph; TCDL=4.2psf; BCDL=3.0psf; h=16ft; B=45ft; L=24ft; eave=4ft; Cat.
II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Extedor(2E) 0-7-7 to 3-7-7, Interior(1) 3-7-7 to 8-0-0, Exterior(2R) 8-0-0 to
11-0-0, Interior(1) 11-0-0 to 15-4-9 zone;C-C for members and forces & MWFRS for reactions shown; Lumber DOL=1.60 plate grip
DOL=1.60
3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
to the use of this truss component,
4) Gable requires continuous bottom chord bearing.
5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
6) • This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
will fit between the bottom chord and any other members.
7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) 1, 5, 7 except
This item has been
(jt=lb) 6=254, 8=254.
electronically signed and
sealed by Velez, Joaquin, PE
using a Digital Signature.
Printed copies of this
document are not considered
signed and sealed and the
signature must be verified
on any electronic copies.
Joaquin Velez PE No.68182
MiTek USA, Inc. FL Cart 6634
8904 Parke East Blvd. Tampa FL 33810
Data:
November 9,2021
® WARNING -Verily design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE MII-7473 rev. 5/19/2020 BEFORE USE.
--
Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
a truss system. Before use, the building designer must verify the applicability of design parameters and property incorporate this design Into the overall
building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTek•
is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSIITP11 Duality Criteria, DSB-89 and BCSI Building Component 6904 Parke East Blvd.
Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf. MD 20601 Tampa, FL 36610
Symbols
Numbering System
General Safety Notes
PLATE LOCATION AND ORIENTATION
314' Center plate on joint unless x, y
offsets are indicated.
6-4-8 dimensions shown in ft-in-sixteenths
(Drawings not to scale)
1
Failure to Follow Could Cause Property
Damage or Personal Injury
Dimensions are in ft-in-sixteenths.
1. Additional stability bracing for truss system, e.g.
Apply plates to both Sides of truss
1 2 3
diagonal or X-bracing, is always required. See BCSI.
and fully embed teeth.
TOP CHORDS
2. Truss bracing must be designed by an engineer. For
0-11fi
C1-2 c2-3
wide truss spacing, individual lateral braces themselves
bracing, Tor I
4
may require or alternative
WEBS 4a Q
p0-13.
bracing should be considered.
Never exceed the design loading shown and never
2 u O
stack materials on inadequately braced trusses.
n U
4. Provide copies of this truss design to the building
00
designer, erection supervisor, property owner and
For 4 x 2 orientation, locate
c7-8 c6-7 05-6 F-
all other interested parties.
plates 0- 'lid' from outside
BOTTOM CHORDS
5. Cut members to bear tightly against each other.
edge of truss.
8 7 6 5
6. Place plates on each face of truss at each
joint and embed fully. Knots and wane at joint
This symbol indicates the
JOINTS ARE GENERALLY NUMBEREDILETTERED CLOCKWISE
locations are regulated by ANSI/TPI 1.
required direction of slots in
AROUND THE TRUSS STARTING AT THE JOINT FARTHEST TO
7. Design assumes trusses will be suitably protected from
connector plates.
THE LEFT.
the environment in accord with ANSI/TPI 1.
Plate location details available in MiTek 20/20
CHORDS AND WEBS ARE IDENTIFIED BY END JOINT
NUMBERS/LETTERS.
8. Unless otherwise noted, moisture content of lumber
software or upon request
shall not exceed 19% at time of fabrication.
9. Unless expressly noted, this design is not applicable for
PRODUCT CODE APPROVALS
use with fire retardant, preservative treated, or green lumber.
PLATE SIZE
ICC-ES Reports:
10. Camber is a non-structural consideration and is the
The first dimension is the plate
responsibility of truss fabricator. General practice is to
4 x 4 width measured perpendicular
ESR-1311, ESR-1352, ESR1988
camber for dead load deflection.
to slots. Second dimension is
ER-3907, ESR-2362, ESR-1397, ESR-3282
11. Plate type, size, orientation and location dimensions
the length parallel to slots.
indicated are minimum plating requirements.
LATERAL BRACING LOCATION
12. Lumber used shall be of the species and size, and
in all respects, equal to or better than that
specified.
Indicated by symbol shown and/or
by text in the bracing section of the
Trusses are designed for wind loads in the plane of the
truss unless otherwise shown.
13. Top chords must be sheathed or pudins provided at
spacing indicated on design.
output. Use T or I bracing
if indicated.
Lumber design values are in accordance with ANSI/TPI 1
14. Bottom chords require lateral bracing at 10 ft. spacing,
or less, if no ceiling is installed, unless otherwise noted.
section 6.3 These truss designs rely on lumber values
BEARING
established by others.
15. Connections not shown are the responsibility of others.
16. Do not cut or alter truss member or plate without prior
Indicates location where bearings
approval of an engineer.
(supports) occur. Icons vary but
reaction section indicates joint
C 2012 MiTek® All Rights Reserved
17. Install and load vertically unless indicated otherwise.
number Where bearings Occur.
Min size shown is for crushing only.
18. Use of green or treated lumber may pose unacceptable
environmental, health or performance risks. Consult with
project engineer before use.
Industry Standards:
19. Review all portions of this design (front, back, words
ANSI/TPI1: National Design Specification for Metal
and pictures) before use. Reviewing pictures alone
is not sufficient.
Plate Connected Wood Truss Construction.
DSB-89: Design Standard for Bracing.
20. Design assumes manufacture in accordance with
BCSI: Building Component Safety Information,
MiTek
ANSI/rPl 1 Quality Criteria.
Guide to Good Practice for Handling,
21.The design does not take into account any dynamic
Installing & Bracing of Metal Plate
Connected Wood Trusses.
MiTek Engineering Reference Sheet: MII-7473 rev. 5l19/2020
or other loads other than those expressly stated.