HomeMy WebLinkAboutBlower Door Test Form04-08-' 22 10:16 FROM- 772-692-9155
T-626 P0001 /0001 F-005
ry-pW"
planning & Development Services
Building & Code Regulation Division
2300 Virginia Ave, Rm 201
Fort Pierce, FL $4902
Phone:772-462-2165 Fax.-772-462.6443
BLOWER POOR TEST FORM.
House Infiltration Test Certification
Prescriptive and Performance Method
Date: 3/28/2022
Contractor: RENAL HOMES,
Permit #: 2106-0593
Job Address: 425 SEAFOAM"CIR
Construction: ( X ) New Construction — Complete ( ) Existing After Addition
House Infiltration Test Fkesults SEC -Climate Zone 2
CFM 1501 _ Test Date:
Volume
ACH (50) = CFM (50) x 60 / Volume = Mec of Ventilation required ton than 3 ACH
Passing results must be & ACH (50) or less 0A Pass ( } Fall
3/28/2022
FBC, Energy
The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceedingg air changes per
hour in Climate Zone 1, 2 and 3 air changes per hour In Climate Zones 3 through 8. Testing shall be conducted with a
blower door at a pressure of 0.2 inches w. g. (50 pascals). Testing shall be conducted by either individuals as defined in
Section 553.993(5) or (7), Florida statutes or individuals licensed as set forth in Section 489.105 (3)(f), (g) or (i) or an
approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building
thermal envelope.
FRC, Residential
Where the air infiltration rate of a dwelling unit is less than 1.0 changes per hour when tested with a blower door at a
pressure of 0.2 inch W. c, (50 Pa) in accordance with Section R402.4.1,2 of the Florida Building Code, Energy Conservation
the dwelling unit shall be provided with whole -house mechanical ventilation in accordance with Section M1507.3.
Testing Compa ECO-INNOVATIVE LLC 10570 S US HWY 9, STE 300. PORT ST LUCE, FL 34952
Company Name: Address:
I hereby certify that the above House Infiltration results demonstrate compliance with FBC Energy Conservation
requirements in acc9rdapce with Se R 2.4.1.2 Climate Zone 2.
Signature: . Y"
Printed Name: KATHLEEN CONNOLLY
License/Certification #: 6060036