HomeMy WebLinkAboutPiping PlanSPRINKLER PIPING PLAN 1st. FI.
SCALE: 3116'=1'-D" SPRINKLER PIPING PLAN 2nd. FI.
SCALE: 3116" =1'-W
GENERAL NOTES
1.) ALL WORK TO CONFORM TO NFPA-13RAND LOCALAUTHORITIES HAVING JURISDICTION.
2.1 SPRINKLER RISER PIPING TO BE SCR 10 WITH GROOVED ENDSAND GROOVED FITTINGS.
3.) ALL CONCEALED PIPING FEEDING UNITS SHALL BE CPVC WITH SLIP FITTINSAND
RESIDENTIAL SPRINKLERS.
4.) ALLAREAS SHALL BE SPRINKLED:
EXCEPTION-I.SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS UNDER 5514.R.
EXCEPNON.2.SPRINKLERS SHALL NOT BE REQUIRED IN CLO., LINEN CLO., OR PANTRIES
VJTTMN THE MELUN13 UNIT WHERE THEAREA DOES NOT EXCEED 24o0.
EXCEPTION-3 SPRINKLERS SMALL NOT BE REQUIRED INAMY GARAGES, PORCHES,
BALCONIES, CORR. AND OR STAIRS THATARE OPENAND ATTACHED,
EXCEPTIONI.SPRINKLERS SMALL NOT BE REWIRED IN ATTICS OR CRAWL SPACES THAT
ARE NOT USED OR INTENDED FOR LIVING PURPOSES.
5.) HANGERS TO BE LISTED AND APPROVEDTWO HOLE STRAPS FOR CPVC PIPING
SPRINKLER PIPING PLAN 3rd. FI.
SCALE: 3116" = 1'4r
CONCRETE DECK
HILT PW
CPVC PIPING
PIPE STRAP
PER PIPE MANUFACTURES SPEC.
TWO HOLE PIPE STRAP
REMOTEAREA#1
REMOTEAREANAME
RefiderAIW NFPAA30
DENSITY
0.050gpMR'fW(2 HEAD DESIGN)
TOTAL HEADS FLOWING
2
K-FACTOR
4.9
SYSTEM FLOW DEMAND
2635
SYSTEM PRESSURE DEMAN
6.236
BASEof RISER -GPM
26.35
RISER - PSI
56.236
6AFETY MARGIN -PSI
:VET,
�8.764(13.5%)
a-rwvmow-n m.
VIKING CONCEALED SPRINKLER OR
• 49 — SER�IIE& iI WHIITEEPPENED DEM, K-4.2, 1NDENr 55 DEGREE
PIPING PLAN FOR LOT 52 HALBERT RESIDENCE
r' I -w T — dr"4 — Y
REV. 0
DATE
DESCRIPTION
DATE: 3.16.16
HALBERT Residence
(At Watersong) LOT 52
4920 Watersong way,
Fort Plerce,FL 34949
i
- � -
��M,,��r t! ? �G �&gg�. -�,-�"
�' tr. /Y,IeGOt'G sBaGr '
+ � ^^3 �//� (1� n �T/ [5�22
;� �hflll `L°�el�'U�ICB%ZC: l,p[fMjJT/�„y_(lfDJJ,
I�
t10YE3
"Pf1�'E SPRI`�1KLER
1047-2w
FIRE SPRINKLER PIPING PLAN AND DETAILS
JOB NUMBER: S111C16A
SHT. 1 OF 1
DRAWN BY: Shelly Schuyler
SCALE: 3116" = 1'-0"