HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot 184Phase 3Watersto...
- wrightsoft® Date: NOVEMBER 1, 2010
Entire House By: DCS
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 License: CMC 1249777
Project• •
For: ADAMSHOMES
5318 Vespera Street, Fort Pierce, FL 34951
Cooling Equipment
Design
Outdoor design DB:
90.4 OF
Sensible gain: 21349
Btuh
Outdoor design W B: 77.4 cF
Latent gain: 3858
Btuh
Indoor design DB:
75.0 °F
Total gain: 25207
Btuh
Indoor RH:
50%
Estimated airflow: 947
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
SpIitASHP
Manufacturer:
Carrier
Model: 25HBC530AP03+FX4DNF031 L00
Actual airflow:
947
cfm
Sensible capacity:
22734
Btuh
106% of load
Latent capacity:
4616
Btuh
120% of load
Total capacity:
27349
Btuh
108%of load SHR: 83%
Heating Equipment
Design Conditions
Outdoor design DB: 41.0 OF Heat loss: 21748 Btuh
Indoor design DB: 70.0 cF
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00
Actual airflow: 947 cfm
Output capacity: 26646 Btuh 123% of load
Supplemental heat required: 0 Btuh
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 947 cfm
Output capacity: 5.8 kW 91 % of load Temp. rise: 19 OF
Meets all requirements ofACCA Manual S.
Entering coil DB: 76.4OF
Entering coil WB: 63.2°F
Entering coil DB: 69.5°F
Capacity balance: 35 OF
Economic balance: -99 OF
Qr -*- wrightsoft®� 2021-JU-210932:39
ti ANi41•/Be6luelleilu—,UmpM RigII-SuteOUriversal2021 21.0.07 RSU23828
Pagel
'�...terstore1480BGL1Lot184Phs3Waterstone1480BGL.nQ Calc=MJ8 Housefaces: N
Wrightsoft® Component Constructions Job: Lot 184 Phase 3 Watersto...
Date: NOVEMBER 1, 2010
Entire House By: DCS
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 LicerLse: CMC 1249777
?-roject Information
For: ADAMS HOMES
5318 Vespera Street, Fort Pierce, FL 34951
Design
Conditions
Location:
Indoor:
Heating
Cooling
St Lude Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 28 °N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr4b)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (OF) -
Wet bulb (OF) -
15 (L
77
) Method
Simplified
Wind speed (mph) 15.0
7.5
Construction quality
Fireplaces
Average
0
Construction descriptions
Or
Area
u-value
Insul R
Htg HTM
Loss Clg HTM
Gain
ft�
Btuh/ftz"F
ftz°F/Btuh
Btuh/ft'
Btuh
Btuh/ft2
Btuh
Walls
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1 /2" gypsum board int fnsh
n
110
0.201
4.1
5.83
643
4.06
448
e
329
0.201
4.1
5.83
1919
4.06
1336
s
246
0.201
4.1
5.83
1432
4.06
997
w
312
0.201
4.1
5.83
1820
4.06
1268
all
997
0.201
4.1
5.83
5813
4.06
4049
Partitions
12C-Osw: Frm wall, 1 /2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
236
0.091
13.0
2.64
623
1.31
309
fnsh, 2N4" wood frm, 16" o.c. stud
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
n
16
0.330
0
9.57
155 8.22
133
thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.42 ft overhang
(5.25 ft window ht, 0.75 ft sep.); 6.67 ft head ht
213-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8"
n
13
0.330
0
9.57
128 9.72
130
thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 5.75 ft overhang
(6.7 ft window ht, 0.75 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
e
7
0.330
0
9.57
66 21.2
146
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.42 ft overhang
(3.17 ft window ht, 0.75 ft sep.); 6.67 ft head ht
W
7
0.330
0
9.57
66 21.2
146
all
14
0.330
0
9.57
131 21.2
291
1 OC-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8"
s
18
0.550
0
15.9
284 16.2
288
thk; NFRC rated (SHGC=0.70); 11.42 ft overhang (6.67 ft window ht, 0.8
ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
s
16
0.330
0
9.57
155 8.52
138
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.42 ft overhang
s
16
0.330
0
9.57
155 8.52
138
(5.25 ft window ht, 0.75 ft sep.); 6.67 ft head ht
W
49
0.330
0
9.57
465 22.0
1069
all
81
0.330
0
9.57
775 16.6
1345
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
s
16
0.330
0
9.57
155 8.52
138
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.42 ft overhang
(5.25 ft window ht, 0.75 ft sep.); 6.67 ft head ht
t WrightsOft' 2021-Jt1-21093239
^�^•�• a•tr ••"•� aim, Rigtt-Stite®Udversa12021 21.0.07 RSU23828 Page 1
terstone1480BGL\Lot184Phs3Waterstone1480BGL.np Calc=MJB Housefaces: N
2A-2ov: 2 glazing, clr IoWe outr, air gas, vnl fan mat, clr innr, 1/4" gap, 1/8" w 32
0.330
0
9.57
310
25.8
835
thk; NFRC rated (SHGC=0.23); 1.42 ft overhang (5.25 ft window ht, 0.75
ft sep.); 6.67 ft head ht
Doors
11 JO: Door, mtl fbrgl type n 20
0.600
6.3
17.4
350
17.6
353
Ceilings
166-30ad:Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" 1618
0.032
30.0
0.93
1501
1.69
2733
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth 178
0.989
0
28.7
5100
0
0
wrightsoft" �2021-JU-21093239 � ^�^•-�...a^.^,..,,�m^.m Right-Sute®Uriversa1202121.0.07RSU23828 Paget
terstore1480BGL\Lot184Phs3Waterstoml480BGL.np Calc=W8 Hoisefaces: N
- wrightsoft® Project
Job: Lot 184Phase 3Watersto...
Date: NOVEMBER 1, 2010
Entire House
By: DCS
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 License: CMC 1249-M
Project•
•
For: ADAMS HOMES
5318 Vespera Street, Fort Pierce, FL 34951
Notes: REVISED 3-23-12 SGT
L. S. 7-21-21 VW K
Desicin Information
Weather: St Lude Co Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41 OF
Outside db
90
OF
Inside db 70 OF
Inside db
75
OF
Design TD 29 OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/lb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure 18511 Btuh
Structure
16853
Btuh
Ducts 3237 Btuh
Ducts
4496
Btuh
Central vent (0 cfm) 0 Btuh
Central vent (0 cfm)
0
Btuh
(none)
(none)
Humidification 0 Btuh
Blower
0
Btuh
Piping 0 Btuh
Equipment load 21748 Btuh
Use manufacturer's data
y
Rate/swin multipplier
1.00
Infiltration
Equipmenisens1 le load
21349
Btuh
Method Simplified
Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0
Structure
2774
Btuh
Ducts
1084
Btuh
Central vent (0 cfm)
0
Btuh
Heating Cooling
(none)
Area (ft2) 1484 1484
Equipment latent load
3858
Btuh
Volume (ft3) 13327 13327
Air charges/hour 0.45 0.23
Equipment Total Load (Sen+Lat)
25207
Btuh
Equiv. AVF (cfm) 100 51
Req. total capacity at 0.75 SHR
2.4
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Make Carrier
Trade CARRIER
Trade CARRIER
Model 25HBC530AP03
Cond 25HBC530AP03
AHRI ref 204840289
Coil FX4DNF031 L00
Efficiency 8.5 HSPF
AHRI ref 204840289
Efficiency 12.5 EER,15 SEER
Heating Input
Sensible cooling
21300
Btuh
Heating output 28200 Btuh 47OF
Latentcooling
7100
Btuh
Temperature rise 27 OF
Total cooling
28400
Btuh
Actual airflow 947 cfm
Actual airflow
947
cfm
Airflowfactor 0.044 cfm/Btuh
Air flow factor
0.044
cfm/Btuh
Static pressure 0.40 in H2O
Static pressure
0.40
in H2O
Space thermostat
Load sensible heat ratio
0.85
Capacity balance point= 35 OF
Iput =p6 kW, Output =19807 Btuh,100 AFUE
Calculations approved byACCAto meet all requirements of Manual. J 8th Ed.
-Pid- =ightsc ft- 2021-J-21 0932:40
MA mwm 1480BGL�Right-SuteOUriversal 2021 21.0.07 RSU23828 Page 1
terstoneLot184Pfs3Waterstone1480BGL.rLp Calc=MJ8 Housefaces: N
- wrightsoft'
Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Pfnne:407-333-2665 License: CMC 1249777
Job: Lot 184 Phase 3 Waterston 1...
Date: NOVEMBER 1, 2010
By: DCS
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
Entire House
177.8 ft
9.0 ft d
1486.0 fF
FAM
33.0 ft
9.0 ft heat/cool
1.0 x 451.0 It
451.0 V
Ty
Construction
number
U-value
(Btuh/ftzf
Or
HTM
(Btuh/ftz)
z
Area (ft)
or perimeter (ft)
Load
(Btuh)
Area (ft)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/PiS
Heat
Cool
6
1 1
V��!—C
I—C
1—p
V►/
P
C
Blk vall sW000 ext
2A 2ov
N26 2N
11J0
Blk vyall, stuoce e�
2A2ov
Blkvalf,`shi000ext
10C-v
2A-2ov .;
2A-20v ,
2A=2ov_,. ,__,.___ _
Blk wall, stucco ext
2A-2ov
2A 2ov
2A 2ov
12C Osn
1613-30ad.
0201
0330
0330
Q600...
0201
0.330
=0201
_.0550
0.330)
;0.930
.�.__:�..0.330
0.201
0.330
0330
0330
0091
0032
989
n
n
n.
n
a
e._
� s
s
s"
s
sue.._..
w
w
w
w
__,
V`
5.83
957
957
__17.40
5.83
957
5.83,
15.95
,957.
957
_:957
5.83
957
957
957
264
093.
28.6$_1
4.06
822
9.72
_17.58
4.06
2123
4.06
1620
" 852
`` ' 852
_.--..:.852
4.06
25.78
2123
22.01
13f
160
16
' 13
:�__�2q-_
336
7
" 312
18
--16
16
_ _LL16.,-
400
32
7
49
236
1618
110
0
0
20,_
155
128
��350__353_�_,_
1919
66
1432
284
' 165
- 155
___ :155
1820
310
66
465
133
- 130
1336
_ 146
997
`288
138
138
' 138
1268
835
146
1069
0
0
0�
0
0
�' 144
18
0
16
._ »0
120
0
0
16
" 0
0
_0_._.._�0
i 0
0
— 170
18
:0
16
__m__ 0
104
0
0
_ 1
_ __505
»_ 33
0
0
0
0
- 641
284
°". 0
155
__ 0.
605
0
0
_ 155
- _T468
0
0.
�_q.
0
0
'_J447
288
�0,
138
•. � 0
421
0
0
_ 356
852
329
1
�246
18
16
16
� ''A6
312
3
1
4
236
1618
78
__-__,•1501
_�510Q
_ _2733
_ � 9
,_� _ 505
451:
1.69
4-
7
--
__
--
- -
-
_.
-- -
6
d) AED
excursion
863
51
Envelope loss/gain
15325
11469
3255
2554
12
a) Infiltration
b) Room ventilation
3186
0
865
0
696
0
189
0
13
Internal gains: Oavpahts@ 230
Appliancesother
4
920
3600
2
460
600
Subtotal (lines 6 to 13)
18511
16853
3951
3803
14
15
Less eMemalload
Lesstransfer
Redistribution
Subtotal
Dud loads
17%
27%1
0
0
0
18511
3237
0
0
0
16853
4496
17%
279/6
0
0
0
3951
691
0
0
0
3803
1015
Total room load
Air required (cfm)
21748
947
21349
9471
4642
202
4818
214
Calculations approved bvACCA to meet all requirements of Manual J &h Ed
-*- wr7ghtsoft^
Right-SuPage 1te®Uriversal 2021 21.0.07 RSU23828 2021-JU-21 093ge 1
...terslone1480BGL\Lol184PFs3Waterstone1480BGL.nis .p CaIc=MJB Hoetaces: N
+ wrightsoft3
Right-M Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, R_ 32771 Pfnne:407-333-2665 Ucense: CMC 1249777
Job: Lot 184 Phase 3 Waterston 1...
Date: NOVEMBER 1, 2010
By. DCS
1
Room name
BR 2
BR 3
2
3
4
5
E)posed wall
Room height
Room dimensions
Room area
10.0 ft
9.0 ft heaMmol
1.0 x 134.0 ft
134.0 ftz
24.9 it
9.0 ft heat/000l
1 D x 146.5 ft
146.5 ftz
Ty
Construction
number
U-value
(Bluh/ftz-fl
Or
HTM
(Btuh/ftz
z
Area (ft)
or perimeter (ft)
Load
(Btuh)
Area (112)
or perimeter (ft) .
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
__.
Blkwall sfucooeA
2A 2ov
2B-2N
11J0 ,- --
Blk wall, stucco e)d
2A-2ov-
Blk yell, stu000 ext
10C-y
2A-2ov
2A-2ov '
2A-2ov___:_.�__ _._.,
well, sucoo ed
2A-2ov
2A-2ov
2A-2ov
_16B 30ad_ _
°_
0201
0330
0.330
-- _0600
0.201
0.330
0201
0.550
0.330
0330
_-i. 0.330
0.201
0330
0230
0330
0032
�._~�0949
n
n
n,
n ;
5B3
957
9.57
_._ 1740
5.83
,_„ 957
1525
957•
'957.
___ _.957
5.83
957
957
9.57
2868.
406
822
9 72
__ 1758
4.06
2123
~ 4.06
1620
852
852
L _852
4.06
25.78
2123
22D1
1_69
_ - 0.00
0
0
0
0
0
0
80
., 0
`0
0
., ,_.._16._p
0
0
0
0
_,; 150
- -.134
- 0
0
0
__0.
0
0
64
J 0
.0
,0
,a 16
0
0
0
0
r.; 150
_ _10
0
0
n 0
_ _:__0
0
__0
A �� 372
0
'
0
".:._,�. J55
0
0
0
0
0
___ _ 139
_
__- 287.E
7 0
0
0
Q
0
0
0
_ 0
112
0
68
0.
18
0.
w__.w-___.0
0
0
0
0
_. 164
— 1_47
µ� 0
0
0
___.� 0
112
,0
72
0
"" 16
0
v �0.._
0
0
0
0
_
0
0
0
0..-
653
0
_ 419
0
155
0
-.0,
0
0
0
0
„ __ 152
_ 715
0
0
0
455
. _ _ _ 0,
— 292
0
: 138
-0
,_______0
0
0
0
0
w___� 277
0
V)/ -
_.
VhBlk
a
- e-_
,s.
s
' s
's
_',s_
w
w
w
w
_ .__'.__
0
_ 0
259
0
0
'` 0
N_._138
0
0
0
0
___0
_ 253
v ._
--. 0
C
E_ �..22A-Q�l
164
�_v
-- 25
6
c) AED excursion
-14
-23
Envelope loss/gain
953
636
2093
1139
12
a) Infiltration
b) Room ventilation
211
0
57
0
527
0
143
0
13
Internal gains: Occupants@ 230
Appliances/other
0
0
300
0
0
300
Subtotal (lines 6 to 13)
1164
993
2620
1582
14
15
Less extemalload
Less transfer
Redistribution
Subtotal
Dud loads
17 %
27 %
0
0
0
1164
204
0
0
0
993
265
17 %
27 %
0
0
0
2620
458
0
0
0
1582
422
Total room load
Airrequired (cfm)
1367
60
1258
56
3079
134
2004
89
Calculations approved byACCAto meet all requirements of Manual J 8th Ed
wrigtftsoft^
Aftk Rtglt-Sute®Uriversal2021 21.0.07 RSU23828 2021-Jul-21 0902.40
...terstone1480BGL1Lot184Pls3Waterstone14806GL.np CaIc=MJB Housetaces: N
Page 2
+ wrightsoft
Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Ucense: CMC 1249777
Job: Lot 184 Phase 3 Waterston 1...
Date: NOVEMBER 1, 2010
By. DCS
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
DIN
8.0 It
90 ft heat/000l
10.0 x 8.0 It
80.0 ftz
Krr
10.0 It
10.0 8 heaUmol
1.0 x 150.0 It
150.0 ftz
Ty
Construction
number
LI-value
(Btuh/ft�-`�
Or
HTM
(Btuh/ tz)
Area z
or perimeter (ft)
(Btuh)
Area(ft')
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/PPS
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
VJ�!—C
I—C
�p
y! i-
_
= _
T—G
P•--__-
C
Blk v4l, stucco ext
2A26v
2B2fv
_11J0�."
Blk wall, stucco eM M
.2A 2ov _
Blkvall,slucooeM, -
10C-v
2A-2ov
.2A-2ov._^_._ _..r
Blk val, stuoao ext
2A-2ov
2A-2ov
2A 2ov
_ _ _
12COsw�:-�
161330ad„
0 201
0.330
0330
�Q600
0.201
__ 0230
M n
n
n
__0_
a
__e
s'
s
's
s'
__"s_
w
w
w
w
-_
d
5 83
957
957
_._ 17.40
5,83
957
5.83
15"95
_ °957
- 957
_..._957
5.83
9.57
9.57
957
_.._
2.64
4:06
822
9.72
___ 17�58
4.06
2123
4,.06
1620
-,. 852
852
___'.852
4.06
25.78
2123
22.01
___
._. 131
0
0
0
._ 0
_�Q
_ _ 0
0
0
':0
0
__"_:0
64
0
0
32
.y-...._,.,.. 0_u.^�0
_.
4 _ 89
_ _ 0
0
0
___ _ 0
0
0
0
0
_,_ _O
0
0
0
__ ______0
184
0
0
310
_. '..,,- 0
83
_0
0
0
0
0
..r. 0.
0
0
0.
128
0
0
713
_ _
_';:_.0_
0
0
0
0
0
_ ..n ..r.
0
0
° `
0
0
0
0
r _ 0
� 100
., O
0
0
� 0
__ _ _
0
0
0
0
0
0
0
0
0
_ _
_ 00
10
t 0
0
0
0
0
0
0
0
0
0
0
0
_ _._ 0
287.
-_-._0
0
0
0
- 0.
-.� 0
0
02A-2ov,
Q:
0
0
0
0
—__ __0,
0
_- 0
0
0
0
0
_,._.._____0
32
0
0
_ 3
89
J8
0201
' 0550
6,330
0.330
,._, _0.330
0.201
0,330
0230
0230
_
.__.__009i_-"
0032_1.69
, _- _
77,
�-
- - - -.-
_--.1_.
433
-22
6
c) AED
excirsion
Envelope loss/gain
807
1425
690
362
12
a) Infiltration
b) Room ventilation
169
0
46
0
0
01
0
0
13
Internal gains: Occupants@a 230
Applianoestother
1
230
0
0
. 0
1200
Subtotal (lines 6 to 13)
975
1701
690
1562
14
15
Less external load
Less transfer
Redistribution
Subtotal
Duct loads
17%
27%
0
0
0
975
171
0
0
0
1701
454 1
17%
27%
0
0
0
690
121
0
0
0
1562
417
Total room load
Air required (dm)
1146
50
215-9
96
811
35
1979
88
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed
Right-SuPage 3te®Uriversal 2021 21.0.07 RSU23828 2021-Jd-21 093ge 3
...terslone1480BGL\Lot184Phs3Waterstone1480BGL.nQ Calc=tviJ8 House faces: N
+ wrightsoft°
Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Ucerse: CMC 1249777
Job: Lot 184 Phase 3 Waterston 1...
Date: NOVEMBER 1, 2010
By. DCS
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
BATH 2
9.0 it
9.0 ft heat/000l
5.0 x 9.0 ft
45.0 ftz
UTIL
16.0 ft
9.0 ft heatbool
9.0 x 7.0 ft
63.0 ftz
Ty
Construction
number
U-value
(Btuhfit -`F)
Or
HTM
(Btuh/ltz)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
Blk mall stu000 ext
2A 2ov
26-2fv
11J0,__.__._0,600_
Blk wall, stu000 exf
.2A 2ov, v _
Blkv�all;stucooex<
16&%((
2A 2ov. ; `
2A-2ov, ",
;2A 2ov ._._ __: `
Blk vtall, stucco eM
2A-2ov
2A-2ov
2A-2ov
1613-30ad .� .
_ ..._».9;f.__..._- _tom..,.
0.201
0.330
0330
6201
0.330
>,t0201'
0.550
0.330
0.330
_ 0.330
0.201
0.330
0.330
0.330
_ 0.032
_........_._..
n
n
n
n.,d_1740._.-1],58_____._
a
e -
s.s
s
' s '
s
_-s_
w
w
w
w
-- -
T
5 83
957
957
5.83
9_57
7,5.63',
1595,
957
957.
,_-:.__957_
957 967
957
957
-- 093
_28_t%$.
__-.a__
4 06
822
972
4.06
2123
_r .
4.06
1620
852
852
-_A52
4.06
25.7878
2123
22.01
-------1 69
_-.v 0.00
__..._�.
0
0
-0
Q.____�0
72
_ 7
,".,, 0
0
0
0
_.__ __,.0
0
0
0
0
50
_ .. ,. 45
_..-._..-
0
0
0
65
1
;� _ 0
0
0
0
_ _. _ �A
0
0
0
0
50
.: .,. ,9
-' 0
0
0
®_ �___.��__
380
66
_ _
_ ,0
,, 0
0
0,
_' 0
. 0�
0
0
264
146
>— _
, 0.
0
{0
0
0
0.
0
Q
56
_e 0
,. 0
0
.. "0
0
0
0
0
0
0
0
0"
0
_0
56
0
;`` 0
0
' 0
0
, '0
0
0
_�-�Q_
326
_ 0
0,
0
0
�___ _0.
0,
0
0
227
0
0
0
0
__�_ 0
0
0
0
0
V�1 " -
_ l G
,
C _.
.__.
0
0
0
0
0
_ 47
..a _ 258
0
0
0
0
0
0
0
0
0
0
0
0
._ ,0
_ 85
.. _. ___,0
70
63
_._.._._.
70
^ 65
119
....
.__,..,...-.
"•-"`
.._.._A.._
�._• �_
_- r....., �..
.-a.__..._ _
6
c) AED excursion
29
-15
Envelopeloss/gain
750
524
1041
426
12
a) Infiltration
b) Room ventilation
190
0
52
0
148
0
40
0
13
Internal gains: Occupants@ 230
Appliancesbther
0
0
0
0
0
600
Subtotal (lines 6to 13)
940
576
1188
1066
14
15
Less external load
Less transfer
Redistribution
Subtotal
Dud loads
17 %
27%
0
0
0
940
164
0
0
0
576
154
17 %
27 %
0
0
0
1188
208
0
0
0
1066
284
Total room load
Air required (ctm)
1104
48
730
32
1396
61
1350
60
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed.
A�%44- wrigtftsoft^ 2021-Jt1-21 0922:40
k Rigk-Sute®Uriversal 2021 21.0.07 RSU23828 Page 4
terstonel480BGLtLotl84Phs3Walerslone1480BGL.rtp Calc=W8 Housefaces: N
* wrightsoft,
Right-JO Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 License: CMC 1249777
Job: Lot 184 Phase 3 Waterston 1...
Date: NOVEMBER 1, 2010
By: DCS
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
MBR
14.9 It
9.0 It heaVcool
1.0 x 1905 ft
190.5 ftz
MBATH
30.0 It
8.0 It heat/cool
1.0 x 109.0 It
109.0 If,
Ty
Construction
number
U-value
(Btuh4tz-9
Or
HTM
(BtuW)
Area (ftz)
or perimeter (ft)
Load
(Btuh)
Area (ft)
or perimeter (ft)
Load
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/5
Heat
Cool
6
11
stucco ext
2A 2ov
2B-2fv
Bik well, stucco e:d
2A-2ov
BIk xell; stugoo eM "
10C-v ".
2A-2ov. :. _
2A 2ov.- . •
2A 2ov' _ __
Blk wall, stucco ext
2A-2ov
2A-2ov
2A-2ov
1613'30ad
0 201
;0.330
0,330
0.201
0.330
0207
0.550
0 330
0:330
d�0330
0.201
0230
0.330
0.330
0091,
0.032
n .
n
n `-
.:n
a
e
s;
s
s '
, s
__s_
w
w
w
w
,
5 83
957
957
__ —174D
5.83
_ 9.57
, :5 83.
1595
' :957
957
�_�957.
5.83
957
957
957
__- 023,
4 06
822
9.72
17.58.,__
4.06
2123
+ 0
0
0
0
0
0
0
.0
0
0
0
0
0
___ 0
0
0
0
.. " 0
' r: 0
0
511
310
0
_ 0
__ 198
. .;. 428
0
0
0
__.0
0
0
.: 0
0
' _ ' 0
.. 0
356
835
0
0
360
104
16
0
40
0
..0
0
" 0
0
96
0
7
0
109
88
0
0
40
0
0
0
' 0
89
0
1
0
109
v 512
- 155
0
' u 233
0
0
0
0
357
133
0
162
0
0
0
0,
362
0
146
0
,_ 184
Vt% -
L
0
0
VVV���III
C_ _ _
4.06,
1620
• ' ;', 852
852
__" 8.52
4.06
25.78
2123
22.01
_____ 1.69
" ~'0
,' 0
0
0
r,__ __0
120
32
0
0
00-
___ 213
0
0,
., . 0
,_.____+ 0
88
3
0
0
213
t 5
520
0
66
0
101.
_ _ 860
6
c) AED exarsion
397
43
Envelope loss(gain
1446
1948
2447
1387
12
a) Infiltration
b) Room ventilation
316
0
86
0
633
0
172
0
13
Internal gains: Occupants@ 230
Applianoes/other
1
230
600
0
0
0
Subtotal (lines 6to 13)
1763
2864
3080
1559
14
15
Less extemal load
Less transfer
Redistribution
Subtotal
Duct loads
17%
27%
0
0
0
1763
308
0
0
0
2864
764
17%1
270/6
0
0
0
3080
5391
0
0
0
1559
416
Total room load
Air required (cfm)
2071
90
3628
161
3618
158
1974
f
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-r- 2021-JU-21 0932AO
Right-Suite®Uriversal 2021 21.0.07 RSU23828 Page 5
terstore1480BGL1Lot184Pfs3Waterstone14808GL.np Calc=MJ8 Housefaces: N
wrightsoft'
Right-M Worksheet
Entire House
DEL -AIR HEATING AND AIR
CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Ucense: CMC 1249777
Job: Lot 184 Phase 3 Waterston 1...
Date: NOVEMBER 1, 2010
By: DCS
1
Room name
WIC
FOYER
2
Exposed wall
7.0 It
15.0 ft
3
Room height
8.0 It heaVcool
8.0 ft heat/cool
4
5
Room dimensions
Room area
1.0 x 47.0 It
47.0 ftz
7.0 x 10.0 It
70.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft)
Load
Area (ftz)
Load
number
(Btuh/ftz'q
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (it)
(Btuh)
Heat
Cool
Gross
N/Pi5
Heat
Cool
Gross
N/P/S
Heat
Cool
6
yII-'
E—{
Blk Hell stu000 ext
2A 2ov
26.2fv
0201
0330
0230
`n
h
n .
9R
957
957
41%
822
72
�0
0
0
0
0
0
0
0
0
0
0
0
__ 7b6
0
13
__ 23
0
- D
a 131
0
128
91
0
130
11J0._._ _ _
..___ _0600
_ R_-
__ 17,40
__ 1758
__ _ Q
__, ___ 01
.__.0.
11
VI�
Blk wall, stucco ext
0201
a
5,83
4.06
56
56
326
227
0
0
0
0
Ai
2A-2ov
BIk v eII, stucco eM _:.,
10C v
2A2ov'
2A-2ov..
0230
0201,
0550
0330
'-0330
a
s .`
s
s
; ,s
957
_ _
: 5 63;
1595,
95T
957
2123
4.06
'1620
852
852
0
0
0
p
0
0
-. ,. 0
0`
0
0>
0
. 0
6
. .;, 0
0
0
.. _ .0
.. 0
0..
:. E0
0
- , 0
.0
- ; 0
0
__ 0
0
0
1 0
0
0
;� __0
,, 0
,,...0
,...0
_ 0
0
0
0
'0
2A-2ov..._",-;."_".._ _
___.!.___0330
—"s_
.v___9.57_
._ �. 852
. 0
__,_0 :
a u_._0
_'0.
0
0
0
0
0
0
0
0
0
0
Bik Hell, stucco ext
2A-2ov
0201
0330
w
w
5.
9.57 57
4.
25.7878
0
0
0
0
0
0
2A-2ov
2A-2ov
0.330
0.330
w
w
957
957
2123
22.01
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
_
264
1<�1
J0
C
1613-30ad _
0.032
989
_ _.
0,93-
_ __28b8"
1 69
0:00
47
. _ _ _ , _47
47
_ _ _ 7
_ 44
e- _ _201
_ 70
__ 70
- 70
_65
, 118.
79
_ _ Y
..
717 7-
..._.
-
7:7-
,
_
6
c) AED exausion
-5
-12
Envelope loss/gain
571
302
1273
766
12
a) Infiltration
148
40
148
40
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
0
0
0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
718
342
1421
806
Less external load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
718
342
1421
806
15
Duct loads 117%
27 %
126
91
17%
27 %
249
215
Total room load
844
433
1669
1021
Air required (cfm)
37
19
73
45
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
li.F- wrigF�tsoFt- 2021-JU-210932:40
= "" ' "`" Right-Sute®Uriversal 2021 21.0.07 RSU23828 Page 6
terstore1480BGL\Lot184Pfs3Waterstone14808GL.np Calc=fvlJB House faces: N
DS SJob: Lot 184 Phase 3 Watersto...
-�+ wrightsoft®uctstemumma Date: NOVEMBER 1, 2010
Entire House By. DCS
DEL -AIR HEATING AND AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 License: CMC 1249777
Project• •
For: ADAMS HOMES
5318 Vespera Street, Fort Pierce, FL 34951
External static pressure
Pressurelosses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.294 in/100ft
947 cfm
116
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.294 in/100ft
947 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH 2
h 1104
48
32
0.336
4.0
Ox 0
VI Fx
16.2
85.0
st2
BR2
h 1367
60
56
0.457
6.0
Ox 0
VIFx
4.5
70.0
BR3
h 3079
134
89
0.333
7.0
Ox 0
VIFx
17.0
85.0
st2
DIN
c 2155
50
96
0.421
6.0
Ox 0
VIFx
10.8
70.0
FAM
c 4818
202
214
0.429
9.0
Ox 0
VIFx
9.2
70.0
FOYER
h 1669
73
45
0.311
5.0
Ox 0
VIFx
24.5
85.0
st1
Krr
c 1979
35
88
0.436
6.0
Ox0
VIFx
8.1
70.0
M BATH
h 3618
158
88
0.294
7.0
Ox 0
VI Fx
30.5
85.0
sti
M BR
c 3628
90
161
0.318
7.0
Ox 0
VI Fx
22.0
85.0
sti
unL
h 1396
61
60
0.324
5.0
Ox 0
VIFx
19.9
85.0
st2
WIC
h 844
37
19
0.299
4.0
Ox 0
VIFx
28.7
85.0
sti
Supply Trunk Detail Table
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FIR
(fpm)
(in)
(in)
Material
Trunk
sti
PeakAVF
357
313
0.294
455
12.0
0 x 0
VinlFlx
s2
PeakAVF
243
181
0.324
550
9.0
0 x 0
VnlFlx
-Orj- wrightsoft,
Right-Sute®Uriversal202121.0.07RSU23828
...terstore1480BGL\Lot184Pfs3Waterstorie1480BGL.nQ Calc=MJB Horsefaces: N
2021-JJ-21 0932:40
Page 1
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb1
Ox 0
947
947
0
0
0
0
Ox 0
VIFx
W rightsoft® 2021-JJ-21 0932:40
A= ,w�.� Rigid-Sute®Uriversal2021 21.0.07RSU23828
Page 2
�+�...terstore14808GL�Lot184Pts3Waterslone14808GL.nQ CaIc=MJB House faces: N
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 184 Phase 3 Waterstone 1480 BGL Builder Name: ADAMS HOMES
Street: 5318 Vespera Street Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
Y
U
Owner: Jurisdiction: 661000
w
Design Location: FL, ST_LUCIE_CO_INTL
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be airtight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
I
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler rover plates and walls or ceilings -
a. In addition, inspection of log walls shall be in accordance with the provisions of ]CC-400.
7/21/2021 9:39 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
-FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed
2020 Duct Leakage Test Report -Performance Method (usually one page)
7/21/2021 9:38:48 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 661000
Permit #:
Job Information
Builder: ADAMS HOMES Community: Lot: NA
Address: 5318 Vespera Street
City: Fort Pierce State: FL Zip: 34951
Air .Leakage Test ReSUIts ., P.assing.resu/ts must meet•either the.Performance,,,Prescriptive, or ERi Method
0 PRESCRIP..TIVE METHOD -The buwlding or -dwelling unit'shatl be tested.and-verified as having'an air'leakage rate of not exceeding' 7 air
changes per hour,.at a pressure ofl i inch w.g: ,(50 PascalsY imClimate` Zones 1 and 2.
.PERFORMANCE'or'ERI.METHOD-The building or dwelling unif shall be tested and verified as having an -air leakage rate of not exceeding
the selected'ACH(50) value; as shown'on'Form R405-2020 (Performance).or R406-2020 ,(ERI),"section labeled as infiltration, sub -section ACH50.
:. ACH(50) specified'on Form R405-2020-Energy. Calc (Performance) or R406-2020 (ER/): _ 7.000
x 60 _ 13356 = Method for calculating building volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
1-1 PASS Code
• software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
7/21/2021 9:39:37 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
DDRESS: A5318 Vespera Street Permit Number:
Fort Pierce, FL, 34951
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
7/21/2021 9:39 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
7/21/2021 9:39 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'/ inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMUIV
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
7/21/2021 9:39 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
7/21/2021 9:39 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
LL the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
7/21/2021 9:39 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5