HomeMy WebLinkAboutLetter Of Truss ApprovalrF D 81 ENGINEERING ASSOCIATES December 10, 2021 Building Department 258 Southhall Lane, Suite 200 Maitland, Florida 32751 P: (321) 972-0491 1 F: (407) 880-2304 1 E: info@fdseng.com Website: www.fdseng.com Ref: Adams Homes Lot: Lot 172 Ph.3 Subdivision: Fort Pierce - Waterstone Address: 5313 Vespera St. Model: 1780 B RHG KA # 21-10556 Truss Company: Builders First Source Date of drawings: 9/14/2021 Job No.: 2867147 Wind Speed: 160 Exposure: C Truss Engineer: Andrew Johnson To whom it may concern, REVIEWED FORE CODE COMPLIANCE ST. LUCIE COUNTY B®CC We have reviewed the truss design package for the project referenced above. This truss package complies with the original design intent and the underlying structure will accommodate all indicated loads. We approve the truss package without comment based upon the truss layout and truss profiles supplied to us by the Truss Company with truss profiles sealed by the Truss Engineer. Please note, this review is only for general conformance with the design concept of the project. Contractor or sub -contractor is responsible for matching all structural components and details shown in the construction documents. Contractor or sub -contractor is also responsible for confirming all quantities and dimensions; selecting appropriate fabrication processes and ��aszaeaa��3� techniques; and coordinating work with all other trades. z'+ F P B O T 00 Note: Truss ID's may vary. ti'�� C E No 87 If you have any questions, please do not hesitate to call. g Sincerely, o` STA OF41 N. 12/10/2021 Carl A. Brown, P.E. FL. # 56126 b� I '+ii iii 12/10/2021 2/10/2021 Scott Lewkowski, P.E. Luis Pablo orres, P.E. FL. #78750 FL. # 8786 FDS Engineering Associates, A TSG Company "Your Building Code Experts" LAN • „ „ „ „ MMMMEMEMEMEMMEME 1. I �1 1. N' 1. Nil in IN- - - --' - - -` - - ---- - - - - -- - - - �� - �i 1�1 mill'lip Ili a ',i i� I�f• VJI�� t� t� t� t� l��l r_-:, OW as fill l Reviewed and Approved ❑ Reviewed with Notations ❑ Revise and Resubmit ❑ Not Reviewed (see explanation) Corrections or comments made on equipment submittals or shop drawings during this review do not relieve contractor from compliance with requirements of the drawings and specifications. This check is only for review of general conformance with the concept of the project and general compliance with the information given in the contract documents. The contractor, is responsible for confirming and correlating all quantities and dimensions: selecting fabrication processes and techniques of construction: coordinating his work with that of all other trades and performing his work in a safe and satisfactory manner FDS ENGINEERING ASSOCIATES Date: 12/10/2021 By. BH Submittal No.: ProjectNo.: 21-10556 ProjectEng.: Luis Project Name: Adams Homes - Ft. Pierce - Lot 172 Ph.3 VERIFY ALL DIMENSIONS AND CERJNG CONDITIONS PRIOR TO APPROVAL SOME CEILING FRAMING REOURED IN FIELD SY BUILDER MAIN WPOJ FORCE RESISTING SYSTEWCC HYBRID WIND ASCO7-16 ENCLOSm IM RTANT EXPOSURE CATEGORYC OCCUPANCY CATEGORY! This Drawing ust Be Approved And WRm M-RTANCE60 FACTOR 1.00 WIND LOAD 1 NCE Returned are Fabrication Will TRUSSES HAVE BEEN DESIONED FOR A MO PSF BOTTOM CHORD LIVE LOAD Begin. For Your Protection Check All HONCONCURRENr WITH ANY OTHER LIVE LOADS Dimensions And Conditions Prior To APBELO Of Plan. SIGNATURE BELOW INDICATES ALL ROOF LOADING FLOOR LOADING NOTES AND DIMENSIONS HAVE TCLL: 20 PSF TCLL• 40 PSF BEEN ACCEPTED. TCDL: 07 PSF TCDL: 10 PSF By Date BCDL• 10 PSF BCDL: 6 PSF TOTAL:* 37 PSF TOTAL: 56 PSF DURATION: 1.25 DURATION: 1.00 CAUTIONH! DO NOT ATTEMPT TO ERECT TRUSSES WITHOUT REFERRING TO THE ENGINEERING DRAWINGS AND BSCI-B1 SUMMARY SHEETS. ALL PERMANENT BRACING MUST BE IN PLACE PRIOR TO LOADING TRUSSES. (le. SHEATHING, SHINGLES, ETC.) ALL INTERIOR BEARING WALLS MUST BE IN PLACE PRIOR TO INSTALLING TRUSSES. REFER TO FINAL ENGINEERING SHEETS FOR THE FOLLOWING. 1) NUMBER OF GIRDER PLIES AND NAILING SCHEDULE. 2) BEARING BLOCK REQUIREMENTS. 3) SCAB DETAILS (IF REQUIRED) 4) UPLIFT AND GRAVITY REACTIONS. WARNING Backcharges Will Not Be Accepted Regardless of Fault Without Prior Notification By Customer Within 48 Hours And Investigation By Builders First Source. NO EXECPTIONS. The General Contractor Is Responsible For All Connections Other Than Truss to Truss, Gable Shear Wall, And Connections. Temporary and Permanent Bracing, And Ceiling And Roof Diaphragm Connections. ROOF PITCH: 6/12 CEILING PITCH: W12 TOP CHORD SIZE. 2 X 4 BOTTOM CHORD SIZE: 2 X 4 OVERHANG LENGTH: 16" END CUT: Plumb CANTILEVER: — TRUSS SPACING: 24" BUILDING CODE: FBC2020 BEARING HEIGHT SCHEDULE BUILDER: Adams Homes PROJECT: Single Family MODEL 1780 B BLK ADDRESS: 5313 VESPERA ST LOT 1 BLOCK: 172 PH3 SUBDIVISION: WATERSTONE CITY: I FORT PIERCE DRAWN BY: KSANCHEZ JOB tS • 2867147 DAIAK 1 09110120211 SCALE: I NTS PLAN DATE: 1 2021 REVISIONS: 1. 2 3. 4. 4408 Airport Road Plant City, FL 33563 Ph. (813)305.1300 Fax (813) 306-1301