HomeMy WebLinkAboutProject Informastion. wrightsoft® Manual S Compliance Repo I " rp k173 a r: �Jlpt Phase 3 Waterson... l' ate: Entire House ` = �-` �`�` '= gy: o'cs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Ucerse: CMG 1249777 Project• • For: ADAMS HOMES 5317 Lugo Street, Fort Pierce, FL 34951 Molina Enuir. Design Conditions Outdoor design DB: 90.4OF Sensible gain: 26399 Btuh Entering coil DB: 76.4°F Outdoor design WB: 77.4°F Latent gain: 4767 Btuh Entering coil WB: 63.2°F Indoor design DB: 75.0 cF Total gain: 31166 Btuh Indoor FIR 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 28185 Btuh 107% of load Latent capacity: 5115 Btuh 1070% of load Total capacity: 33301 Btuh 107% of load SHR: 85% Heating Equipment Design Conditions design DB: 41.0 OF Heat loss: 28570 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31707 Btuh 111 % of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 91 % of load Temp. rise: 20 OF Meets all requirements ofACCA Manual S. Entering coil DB: 69.5°F Capacity balance: 36 OF Economic balance: -99 OF Wrightsoftm 2021-Jt1-211624:15 �M�• v--��•m�� Rigk-SL te®Uriversal 2021 21.0.07 RSU23828 Page 1 terstonel820BGR\Lotl73PIs3Waterstorel820BGR.rLp Calc=MJ8 FrortDoorfaces: E - wrightsoft® Corn onent Constructions p Job: Lot 173 Phase 3 Waterson... Date: Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Licerse: CMC 1249777 Project• • For: ADAMS HOMES 5317 Lugo Street, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lude Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gdlb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (IF) - 15 (L ) Method Simplified Wet bulb (OF) Wind speed (mph) - 77 15.0 7.5 Construction quality Fireplaces Average 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ftz Bqu1VftzT ftz°FBtuh BtUtV t' Btuh BtuWft' Btuh Walls 168-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-0sw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'S<4" wood frm, 16" o.c. stud n 20 0.049 19.0 1.42 28 2.59 52 e 20 0.049 19.0 1.42 28 2.59 52 s 20 0.049 19.0 1.42 28 2.59 52 W 20 0.049 19.0 1.42 28 2.59 52 all 80 0.049 19.0 1.42 114 2.59 207 n 534 0.201 4.1 5.83 3113 4.06 2168 e 127 0.201 4.1 5.83 737 4.06 514 s 611 0.201 4.1 5.83 3561 4.06 2481 w 317 0.201 4.1 5.83 1846 4.06 1286 all 1588 0.201 4.1 5.83 9258 4.06 6449 270 0.091 13.0 2.64 713 1.31 354 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.23); 60% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang s (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht W all 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1 ft overhang (5.3 ft window ht, 3.9 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1 ft overhang (5.3 ft window ht, 5.3 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl fan mat, clr innr, 1/4" gap, 1/8" e thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft sep.); 6.67 ft head ht 7 0.330 0 9.57 66 8.52 59 49 0.330 0 9.57 469 8.52 418 49 0.330 0 9.57 469 8.52 418 33 0.330 0 9.57 313 22.4 730 131 0.330 0 9.57 1251 12.0 1566 16 0.330 0 9.57 156 21.6 353 16 0.330 0 9.57 156 21.6 353 7 0.330 0 9.57 67 11.6 81 wrightsoft`° 2021-JU-211624:15 A a�,,.r ,m• .• b« - Right-Sute®Uriversal 2021 21.0.07 RSU23828 Page 1 terstore1820BGRtLot173Phs3Waterstore1820BGR.rup Calc=MJB FrortDoorfaces: E 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" a 13 0.330 0 thk; NFRC rated (SHGC=0.31); 50%drapes, medium; 9 ft overhang (6.7 9.57 128 13.4 179 ft window ht, 2 ft sep.); 6.67 ft head ht 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" w 18 0.550 0 16.0 285 16.2 thk; NFRC rated (SHGC=0.70); 10.5 ft overhang (6.7 ft window ht, 0.5 ft 289 sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low a outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 33 0.330 0 9.57 313 8.52 279 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.5 ft overhang (5.3 ft window ht, 0.5 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type a 20 0.600 6.3 17.4 355 17.6 359 Ceilings 1613-30ad:Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2" 1835 0.032 30.0 0.93 1703 1.69 3100 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 0 28.7 6080 0 0 1 -F�F wri�ghtscM, 2021-JU-21 1624:15 � •��••��.-,��. Right-Sute®Uriversa1202121.0.07RSU23828 Paget terstore1820BGR\Lot173PIs3Waterstore1820BGR.np Calc=MJ8 FrortDoorfaoes: E - wrightsoft® Project Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM License: CMC 1249777 Proiect Information Job: Lot 173 Phase 3 Waterson... Date: By. DCS For: ADAMSHOMES 5317 Lugo Street, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch L. S. 7-21-21 VW K Desicin Information Weather: St Lude Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db Inside db 41 OF 70 OF Outside db Inside db 90 75 OF cF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 24350 Btuh Structure 20622 Btuh Ducts Central vent (0 cfm) 4220 Btuh 0 Btuh Ducts Central vent (0 cfm) 5777 0 Btuh Btuh none Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28570 Btuh Use manufacturer's data Infiltration Rate/swing multiplier Equipment load 1.00 sensible 26399 Btuh Method Construction quality Simplified Average Latent Cooling Equipment Load Sizing Fireplaces 0 Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh Area (f 2) Heating Coolingg 1820 1820 (none) Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Airchanges/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 31166 Btuh Equiv.AVF (cfm) 116 61 Req. total capacity at 0.75 SHR 2.9 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC537AP03 Cond 25HBC537AP03 AHRI ref 204837926 Coil FX4DNF037L00 Efficiency 8.5 HSPF AHRI ref 204837926 Efficiency 12.5 EER, 16 SEER Heating input Heating output 34600 Btuh @ 47°F Sensible cooling Latentcooling 26250 8750 Btuh Btuh Temperature rise Actual airflow 27 OF 1167 cfm Total cooling Actual airflow 35000 1167 Btuh cfm Airflowfactor Static pressure 0.041 cfm/Btuh 0.30 in H2O Airflowfactor Static pressure 0.044 0.30 cfm/Btuh in H2O Space thermostat Capacity balance point = 36 OF Load sensible heat ratio 0.85 Backup: Input = 8 kW, Output = 25920 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ,g -*- wrishtsoit• 2021-Jtt-21 1624:15 ^- Right-SuteOUriversal2021 21.0.07 RSU23828 Page 1 terstone1820BGRIot173Pts3Waterstore1820BGR.rLip La1c=MJ8 FrontDoorfaces: E '�- wrightsoft® Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax: 407-333-3853 Web: W W W.DELAIR rOM I i--! r-nnr.10eo= Job: Lot 173 Phase 3 Watersone 18... Date: By: DCS 1 2 3 4 Room name Room height Room dimensions Entire House 10.0 ft 212.0 ft d BDRM2 36.0 ft 10.0 ft heat/cool 5 Room area 1835.0 IF 169.0 ft 2 13.0 x 13.0 8 Ty Construction number U-value (BtuhRtzfl Or HTM (BtuhRt� Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/P/S Heat Cool 6 W v_ VL2 _ . _ y� I---G L��_G __ _ P ___ C 16619ad.�_ Blk %dl, stu000 ext 2A 2ov _2A_2ov _ _ _ Blk vsll, stucco eId 2A-2ov 2A-2ov 26-2fv 26-21v 11J0 16B Blk wall, stucco ext 2ov_ . _ Blk v dl, stucco ext 10C-v 2A-2ov 2A 2ov„0 _12C Osnr___ _ - --. 169&30ad _ _._ 0.049 0.201 0.330 _ _-_ 0.330 YY. �0049:_e _ 0201 0.330 0.330 0.330 0.330 0600 �_ _ 0049'�_28 0201 0330 0201 0550 0,330 330 -_—_-0091 0.032 n n _ n e a a a a e:_ s s w w w --w _ -._ 1,42 5.83 9.57 _ 957 5.83 957 957 957 957 1740 5,83 957 __.142 5.83 15.95 9.57 957 2.64: 0.93 _.._259 4.06 852 8.52 _ 4.06 21.62 21.62 11.58 1325 1758 4.06 852 _ 25 - 4.06 1620 2225 852 _,; ._ l21, 1.69 r 2D 590 7 49 ------ 200 16 16 7 13 20 660 _ _ 49 .,._.:_-_._•20 400 18 33 ___ 33 �_270 1835 — 20 y— 534 0 0 _ �28 _52 _J0 100 0 0 0 0 0 0 0 0 _�� 100 0 0 0 0 0 0 0 0 583 0 0 -.—...—_.0: _ 0 0 0 0 0 w 758 0 663 0 156 0 157 0 — 400 0 _ 0 0 0 0 0 0 J 528 0 -0 _ 461 0 365 _ _ 0 286 3113 66 469 2168 59 418 127 0 0 7 11 20 611 49 ._...�.20 y 737 156 156 67 128 �_-355 3561 469 �'� 28 514 353 353 81 179 359_ 2481 �_` _418 __,__52 1286 289 730 _ 279 3100 130 _ 0 `��A 130 0 �-0 130 0 16 0 317 18 2 _ 33 1846 285 313 313 _ 1703 60807. 114 0 1 0 .__� 270 1835 212 169 169 __. _ 0. ---- --- — -- -- — - w excursion 6 c) AED y 908 — 103 Envelope loss/gain 20646 14537 3349 2149 12 a) Infiltration b) Room ventilation 3704 0 1035 0 691 0 193 0 13 Internal gains: Occupants @ 230 Appliancesrother 5 1150 3900 0 0 300 Subtotal (lines 6 to 13) 24350 20622 4040 2642 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 17% 28 % 0 0 0 24350 4220 0 0 0 20622 5777 17 % 28% 0 0 0 4040 700 0 0 0 2642 740 Total room load Air required (ctm) 28570 1167 26399 11671 4740 194 3382 150 - Calculations approved bvACCA to meet all requirements of Manual J 8th Ed A Rigft-Srite®Uriversal 2021 21.0.07 RSU23828 2021-Jt1-21 1624:15 terstore1820BGR\Lotl73Pts3Waterstore1820BGR.rp Calc=MJ8 FrortDoorfaces: E Page - wrightsoft® Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Ucerse: CMC 1249777 Job: Lot 173 Phase 3 Watersone 18... Date: By: DCS 1 Room name BATH BDRM3 2 3 Exposed wall Room height 6.0 ft 13.0 ft 4 Room dimensions 10.0 ft heaUmol 10.0 ft heat/000l 5 Room area 13.0 x 6.0 ft 13.0 x 13.0 ft 78.0 ftz 169.0 ftz Ty Construction U-value Or HTM number (Bluhrlt-9 (Btuh4tz) Area (ftz) Load Area (ftz) Load or perimeter (ft) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/PS Heat Cool Gross N/PJS Heat Cool 6 _W= 16B 19ad 0 049 42 0 Blk MI, stucco e)d - 0.201 ._n._ n -.._i 5.83 _-1259 4.06 _ `� ' 0 . �Q 0 L 0 0 __ - --_ 0 . 0 0 M - O. ' -- —0 2A 2ov 0.330 n 957 852 0 0 0 0 0 0 0 0 0 0 0 0 _ 2A-2ov _ - _ 16619ad ,, _ _ _0.330 ____0049 `n _ „^. 957 142, - m852 -___259 - 0 __ _ _ _0 0 0 __�. _, 0 �- _f 0 _ _0 __- - 0 ----0 _ o �_0 _0 _ 0 _ 0 Blk v dl, stucco eM 2A-2ov 0201 0.330 a a 5.83 957 4.06 21.62 0 0 0 0 - -0 0 -0 0 0 0 0 0 0 0 0 0 0 2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 0 26-2N 0330 a 957 11.58 0 0 0 0 0 0 0 0 26-2fv 0.330 a 957 13.35 0 0 0 0 0 0 0 0 11J0 _. 0.600 _ e t Y 17.40 0 - 0 _ ..-- 0 _0 _0 _ _ .�0 T—G Bik well, stuccoed 0201 s 5.83 4.06 60 60 350 ,- -----0 -----0 244 130 _ _0 114 .:--0- 663 _-0 461 2A-2ov_ 0330 s 957.-�852 _ 0 0 0 0 16 16 156 - VV��II Blk well, stucco ext 10C-v 0201 0550 w w 5.83 15.95 4.06 1620 0 0 6 0 6 0 0 0 0 0 0 0 0 0 0 - 0 0 2A-2ov 0.330 w 957 2225 0 0 0 0 0 0 0 0 ---___-2A-2ov __------_- Osw - 0.330 w_ 957_..-._8.52 ---131. �- 0 0 0 _0 0 0 0 0 C - F-- 16&30ad _ 22Atpl:-_0989 0.032 W 0.93 _ _. 1.69 _. _ 78 - - - -- _ 78 72 - 132 - 169 - __. - 169 157 286 - 6 172 . O169 ,_ 13 ,. _-373 _ _�__0 6 c) AED excursion -18 -57 Envelope loss/gain 594 357 1349 830 12 a) Infiltration b) Room ventilation 115 32 249 70 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 Appiiancesrother 0 1 0 300 Subtotal (lines 6 to 13) 709 389 1598 1199 Less extemalload 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 709 389 0 1598 0 1199 170/6 28% 123 109 179/6 28% 277 336 Total room load Air required (dm) 832 498 1875 1535 34 22 77 68 Calculations approved bvACCAto meet all requirements of Manual J 8th Ed - wrigF�tsoft- �A Right-Sute®Uriversal 2021 21.0.07 RSU2021-JU-211624:15 23828 Page 2 terstore1820BGR\Lot173PIs3Waterstore1820BGR.rtp Calc=MJ8 FrontDoorfaces: E wrightsoft° Right-JO Worksheet Entire House DEL AIR KrG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W nPt Ala cOM I i ­ rnnr I OA.1 Job: Lot 173 Phase 3 Watersone 18... Date: By. DCS 1 2 3 4 5 Room name Exposed wall Room height Room Room areadimensions DINING/FOYER 25.0 ft 10.0 ft heal/cool 1.0 x 276.0 ft 276.0 ftz DENBDRM4 31.0 ft 10D ft heaYbool 13D x 13.0 ft 169.0 ftz Ty I Construction number U-value (Btuh*T) Or HTM (BtuhRt� Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PB Heat Cool Gross N/PB Heat Cool 6 11 1N __ Vjl 166_19ad-_, :__ Blk vdi, stucco ext 2A 2ov 2A_2ov _ 16&19adr r Blk MI, stucco ext 2A-2ov 2A-2ov 2B-2fv 2B-2fv 11JO y Blk yell, stucco ext _2A-2o_v Bik %all, stucco ext 10C-v 2A-2ov _2A 2ov -- - 1613-30ad _ excursion _...:_.._.0.049 0201 0230 0330. �_ 0049 0201 0.330 0.330 0.330 0330 _____0 600 00_49 0201 0,330 0201 0550 0.330 - 0 330 0.09170 0.032 _ n_ n n n ... ._tee e a a a a a ;. __s_� s s _ W . w w w .w! _.._.._ 1.42 5B3 9.57 957 7.42 5,133 957 957 957 957 17.40 1.42 5.83 -�1 A2: 5.83 1525 957 _ 957 0.93 2.59. 4.06 8.52 852 �259 4.06 21.62 21.62 11.58 13.35 1758 _, �2.59 4.06 8.52 _ . 2 59 4.06 1620 2225 _. _ 852 1.69 , 0 0 0 ___ 0 ':- Q 70 0 0 7 13 _ 20 ,-. _ =_.' 0 110 ____•�„33 _. . _ ,;0 0 0 0 0 � O .-.__ ._:3 -f-� 0 0 _ 0 �- Q 170 0 0 67 128 , 355 _-�.TO 451 ._,_ 313 �- 0 0 0 0 - - ___._ 185 256 _v7170� _ 0 0 0 ___,_-0 _ 119 0 0 81 179 359 �: 0 314 279 w �- �=0 50 0 _ 0 _ 130 16 16 0 0 0 �.� � 0 130 0 0 0 0 0 --- - -0 :�0 :' 0 50 0 0 97 0 0 0 0 0 '- ._ _ - 130 0 T 0 0 0 0 ___.___0 169 _ O 4 291 0 0 � 567 156 156 0 0 0 758 0 _..._._... 0 "- 203 0 0 _ 395 353 353 0 0 0 528 _ 0 _ 0 0 0 0 0 0 0 � �0 29 0 0 7 11 �._ _V 20 -_ 0 77 33 .�,0 0 0 0 _ _. _ - 0 276 25 LI-�G W_ VVV���lll C 0 0 0 - ___ ..___92 466 0 0 0 0 276 157 _ 286 169 6 c) AED _100 115 Envelope loss/gain 2642 1788 2975 2233 12 a) Infiltration b) Room ventilation 345 0 97 0 595 0 166 0 13 Internal gains: Occupants@a 230 Applianoesbther 1 230 0 0 0 300 Subtotal (lines 6 to 13) 2987 2114 3570 2699 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 17 % 28 % 0 0 0 2987 518 0 0 0 2114 592 17 % 28% 0 0 0 3570 619 0 0 0 2699 756 Total room load Air required (cfm) 3505 143 2707 120 4189 171 3456 153 Calculations approved byACCAto meet all requirements of Manual J 8th Ed - wrigF�tso�T_[' .4�A Rigid-Srite®Uriversal 2021 21.0.07 RSU23828 2021-Jr1-21 1624:15Page 3 terstore1820BGR\Lot173Pfs3Waterstore1820BGR.rLp Calc=MJB FrortDoorfaces: E - wrightsoft® Right-JO Worksheet Entire House DEL AIR KrG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM HcPrrP• r:Mr. 1Pd4777 Job: Lot 173 Phase 3 Watersone 18... Date: By. DCS 1 2 Room name Exposed wall FAMILY RM NISTR BDRM 3 Room height 13.0 It 10D It heat/cool 41.0 it 10.0 8 heat/000l 4 5 Room dimensions Room area 13D x 22.0 ft 14.0 x 17.0 It 286.0 ftz 238.0 ftz Ty Construction number U-value (Btuhrftz-� Or HTM (BtuhRtz) Area (ftz) Load Area (ftz) Load or perimeter ft () (13 h) or perimeter (ft) (Btuh) Heat Cool Gross N/PrS Heat Cool Gross N/P/S Heat Cool 6 W .- _ V}/ _166 19ad� < Blk vdi, 5ucoo «0 049 _7,0_ _ 259 ..._ 20 -- 20 ':�.�28 _._--52 ' . _ 0 . 0. 0 �__ 0 eM 2A 2ov 0.201 0.330 n n 5.83 957 4D6 852 0 0 0 0 0 0 170 154 896 624 11 lI—�( W 2A 2ov _ _ 16B 19ad_ 0 330 0049 n 957 1.42 852 _ __. 0 _ 0 0 �_ 0 0 0 _." - 52 0 -_ _. 16 0 _ 0 0 ..r 156 0 .__..:_• Blk well, stucco ext 2A-2ov �_ 0201 0,330 .,e a a 683 957 -,259 4.06 21.62 . -- ---20 0 0 20 0 0 28 0 0 _-- . _ 0 0 0 0 0 0 0 0 0 0 0 2A-2ov 0.330 a 957 21.62 0 0 0 0 0 0 0 0 26-2N 0.330 a 957 11.58 0 0 0 0 0 0 0 0 213-2N 0.330 a 957 1335 0 0 0 0 0 0 0 0 vl! 11J0 _16619ad '� :-;_. Blk wall, stu000 eM 0600 __-..0049 0.201 e_ �s s 17.40 1.42 5.83 _ 1758 ,259 4.06 _ 0 .-.._20 - 0 0 -_-20 0 _ 0 , -_� _28:__, ~ -- 0 0 52 0 0 _ _ 0.___._ 100 _ _0 0__, _ 0 _ 0 0 - - 2ov 0.330 s_ 8.52 0 100 583 406 W— - Vy�11 _2A ._ __ 16B 19ad Bik well, stucco ext 10C-v O q49 0.201 0550 v]! _ w w __957 1:42 5.83 15.95 259 4.08 1620 ___0 _ 79 18 0 463 285 0 323 289 _ _ 0 0 0 0 'Q 502 _2020 130 18 -'__ 140 124 �0. 721 2A-2ov 0330 w 957 2225 0 0 0 0 0 16 0 1 0 156 0 365 _. .. C 2A-2ov __,^0091 72C-Osnr-_..u. _ _--. 16B-30ad __- 0330., `_ w - -----957 _2.64 __ 852 �_,131. -__ _.-33 - - 0 33 _ �0 -_...-_._313 279 _ _ 0 ..__� _0 _ _0 _ 0. .22A.-873 0.032 -- 0.93 _ 1.69 286 286 265 483 238 238 _ 221 402 _ 1176 c) AED excursion 6 -1034 l23 Envelope loss(gain 1813 2615 3909 2462 12 a) Infiltration 403 113 787 220 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 1 230 Appliances/other 600 600 Subtotal (lines 6 to 13) 2216 4018 46961 3512 Less extemalload 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 0 0 14 15 Subtotal Duct loads 2216 4018 4696 3512 171/. 28 % 384 1126 179/6 28 % 814 984 Total room load Air required (dm) 2600 5143 1 5510 4495 106 227 12251 199 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. A -r'}+- wrightsoTt^ - R2021-Jt1-21 1624:15 Flight-Sute®Uriversal 2021 21.0.07 RSU23828 Page 4 lerstorel820BGR1Lot173Phs3Waterstore1820BGR.rup Calc=MJ8 FrortDoorfaces: E -�1- wrightsoft Right-M Worksheet Job: Lot 173 Phase 3 Watersone 18... Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Licerse- CMC 124s777 1 2 3 4 5 Room name Exposed wall Room height Room Room dimareensions M BATH 12.6 ft 10.0 It heat/cool 119.0 ftz 1.0 x 119.0 ft M WIC 0 ft 10.0 It heaU000l 7D x 7.0 ft 49.0 ftz Ty Construction number U-value (Btuh/ft-9 Or HTM (f3iuh/ftz) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool Gross N/PiS Heat Coot Gross N/P/S Heat Cool 6 11 W WAR T „- W C _____ 166;19ad_, _-._:_ Blk well, stucco ext 2A-2ov 2A-2ov _ 16B 19ad„ J Blk Ml, stucco ext 2A-2ov 2A-2ov 2B-2fv 2B-2N 11J0 _-_ _ 16B-19ad.. =---,---'.-_-0049__s-_ Blk well, stucco ext .2A-2ov- Blk well, stucco ext 10C-v 2A-2ov 2A-2ov _ 16B-30_ad _ '------004-9, _-._0049 0201 0.330 0 330 �0049 0201 0.330 0.330 0.330 0.330 0600 0201 0.330 . n_ n n n '_e= e a a a a e_ s s w w w w _,.- J.42 5.83 957 957 1.42 5,83 957 957 957 957 —17.40 -- 1,42 5,83 957 1,42 —� __, 259 4.06 852 8.52 '- 2b9 4.06 21.62 21.62 11.58 1325 -._- -1758 - - .259 4.06 -_852 -- 2 4.06 1620 22.35 852 v _.�_ 0 120 7 - _0 0 0 0 0 0 _0 --- - 0 0 0 -. 0. 0 0 0 0 _ -_.._ 0 119 119 �* 659 66 0 0 0 0 0 0 0 ._. `__0 0 _ 0 _ 0_0 0 0 0 0 . _0 110 - __. _0 459 59 _ 0 0 0 0 0 0 0 � 0 ~ 0 0 �..- __ _ 0 0 0 v 0 `o 0- 0 0 0 0 0 ...- W _ ; 0 0 0 _ 0 - --0 - 0 0 0 0 0 --------0_. - 0 40 0 0 0 0 0 0 0 0 0 --- - Q 0 _ 0 ».- 0 �0 0 0 0 113 0 0 0 0 0 0 0 - 0 -0 0 0 »� D. 0 0 0 0 0 0 -. 0 0 0 0 0 0 0 -- -- -- 0 0 _ 0 -.-- 0 0 0 0 _v-_ 0 - -- _0 45 0 0 --, _ 0 �- 0 0 0 _0 _0 49 - - 0 --- =� 0 0 0 _ 0 0 49 - 0.201 0550 0230 0,330 0.032 5.83 15.95 957 957 -21 ,64 0.93 - 0 0 0 ____._ 0 - __ 0_ 201 ' -31 1.69 0.00 .._�- 0 119 _ ., 12 ._ -- 83 - --- excursion c) AED 6 -35 -4 Envelopeloss/gain 1180 684 45 79 12 a) Infiltration b) Room ventilation 230 0 64 0 0 0 0 0 13 Internal gains: Occupants@ 230 Appliancestother 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1410 748 45 79 14 15 Less external load Less transfer Redistribution Subtotal Dud loads 17% 28% 0 0 0 1410 244 0 0 0 748 210 179/6 28% 0 0 0 45 8 0 0 0 79 22 Total room load Air required (dm) 1655 68 958 42 53 2 101 4 Calculations approved byACCA to meet all requirements of Manual J 8th Ed C -r �- wrightsoft- AetA Right-Su2021-JU-21 1624:15 le®Uriversal 2021 21.0.07 RSU23828 Page 5 terstorel820BGR\Lotl73P1s3Watersbre1820BGR.rrp Calc=MJ8 FrortDoorfaces: E -�- wrightsoft- Right-JO Worksheet Entire House DEL AIR WIG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COMUcersevowIP4a777 Job: Lot 173 Phase 3 Watersone 18... Date: By. DCS 1 2 Room name Exposed wall KrrCHENrNOOK LAUNDRY 3 4 Room height Room dimensions 29.0 ft 10.0 ft heat/000l 5.0 n 10.0 ft heat/000l 5 Room area ea 1.0 x 246.0 ft 246 6.0 x 6.0 ft 0 ft2 36.0 ft 2 Ty Construction number Uu alue¢� ( 2 ' Or HTM (BtuhRt2) Area (it') Load Area (ft2) Load r or perimeter (ft) (Btuh) or perimeter (n) (Btuh Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 1661.9ad_, _ _� BlkMI, stu000ext r0049 0.201 _ 11 n __ - __1..49 5.83 -�-�259 __- ' 0 _ __ 0',_ O �- ___ 0 _ __ _ `�-'- 0 _.r__ O _ -� 684 2A 2ov 0.330 n 957 4.06 852 150 117 0 0 476 0 0 0 0 2A toy _ _ _ _ 0330 n _ 957 852 _ _ _33 , _ 0 0 313 0 _ y 279 0 0 _ 0 0 0 0 0 0 0 0 0 0 0 0 Blk wall, stucco erd 2A-2ov 0.201 0330 a a 523 957 4.06 21.62 0 0 ~-- 0 0 0 0 0 0 0 0 2A-2ov 0230 a 957 21.62 0 0 0 0 0 0 0 0 2B-2fv 26-21v 0330 0230 a a 957 957 11.58 1335 0 0 0 0 0 0 0 0 0 0 --� _ W ._'. Vtl _11J0.�_ i6&19ad . ~ _ - Bik v ell, stu000 ext ___ __ 0.600 -: _ 0049 0201 -_e__ _ s;_ s _� 17.40 _, 1,42 5.83 . 1758 —2B9-_p 4.06 _ �_ ._0 0 _ 0 _0_- 0 0 0, 0 0 0 0 0 0 _ _ 0 0 0 �^ '0 -G 2A 2ov_ s 957 852 0 0 0 0 0 0 W _-. 16619ad. - -= _ _0330 ---0049 . _w _ _ _ _ 1.42 -. v, - _ _ 0 0 '_0. - - ^w0 0 0 _ _ 0 -- _- 0 0 BIk %all, stucco ext 10C-v 0201 0550 w w 5.83 1525 4.06 1620 0 0 0 0 0 0 ~�^ �0 0 ^ p, 0 0 0 0 0 0 2A-2ov 2A 2oy 0330 0330 w 957 957 2225 852 0 0 0 0 0 0 0 0 0 0 0 C _._._ .-_ _ 12C Osw_- 16B 30ad _ __ _0.091 -w __- 2,64' .-. 1.31..�_ ,_ _- _.140 _ T.___140 0 _.�_ 369 _ 0 -._, -189 0 -__._-6b _ 0 0 0 0.032 0.93 1.69 246 _ 246 -�29 228 416 -36 36 33 61 excursion 6 c) AED - 119 33 Envelope losstgain 2426 1235 364 106 12 a) Infiltration 288 80 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 Appliances/other 0 1200 600 Subtotal (lines 6to 13) 2714 2515 364 706 Less vernal load 0 Less transfer 0 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 0 15 Duct loads 17% 28% 2714 470 2515 705 17% 28% 364 63 706 198 Total room load Air required (clm) 31 3 427 904 130 142 42 17 40 Calculations approved byACCAto meet all requirements of Manual J 8th Ed wrtigtitsoft^ ,�p� -*- Right-Suite®Uriversal 2021 21.0.07 RSU23828 2021-Jtf-21 1Page6:24:15 5 terstorel820BGRIotl73PFs3WaterstDrel820BGR.rLp Calc=MJ8 FrontDoorfaces: E Duct System Summary Job: Lot 173 Phase 3 Waterson... wrightsoft® Y rY Date: Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Ucerse: CMC 1249777 0-roject Information For: ADAMS HOMES 5317 Lugo Street, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120/0.120 in H2O 0.212 in/100ft 1167 cfm 113 ft Supply Branch Detail Table Cooling 0.30 in H2O 0.06 in H2O 0.24 in H2O 0.120 / 0.120 in H2O 0.212 in/100ft 1167 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 832 34 22 0.278 4.0 Ox 0 VI Fx 16.3 70.0 BDRM2 h 4740 194 150 0.258 8.0 Ox0 VIFx 22.9 70.0 BDRM3 h 1875 77 68 0.305 6.0 Ox 0 VIFx 8.6 70.0 DEN/BDRM4 h 4189 171 153 0.288 7.0 Ox0 MFx 13.2 70.0 DINING/FOYER h 3505 143 120 0.314 7.0 Ox 0 VIFx 6.5 70.0 FAMILYRM c 5143 106 227 0.233 8.0 Ox 0 VIFx 17.9 85.0 sti KrrCHENMOOK c 3220 130 142 0.228 8.0 Ox 0 VIFx 20.1 85.0 sti LAUNDRY c 904 17 40 0.223 4.0 Ox 0 VIFx 22.7 85.0 st1 M. BATH h 1655 68 42 0.224 5.0 Ox 0 M Fx 22.2 85.0 st1 KWIC c 101 2 4 0.225 4.0 Ox0 VIFx 21.9 85.0 sti MSTRBDRM h 5510 225 199 0.212 1 8.0 Ox0 VIFx 28.2 85.0 sti Supply Trunk Detail Table Name Trunk Type Htg (cfm) Cig (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 PeakAVF 549 655 0.212 613 14.0 0 x 0 VinlFlx -Fk- wrightsoft I&S •--- C ­ Right-SuteOUriversal2021 21.0.07 RSU23828 terstore1820BGRIot173PFs3Waterstore18208GR.np Calc=MJ8 FrortDoorfaces: E 2021-JU-21 1624:16 Page 1 Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (Cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 1167 1167 0 0 0 0 Ox 0 MFx -�- wrightsoft- RigIY-Sute®Uriversal 2021 21.0.07 RSU23828 ACCA terstore1820BGR1Lot173PFs3Waterstore1820BGR.np Calc=MJ8 FrortDoorfaces: E 2021-JLI-21 1624:16 Page 2 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 173 Phase 3 Waterstone 1820 BGR Builder Name: ADAMS HOMES Street: 5317 Lugo Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST LUCIE CO INTL — — = U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealingmaterial. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned s ace shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spa s. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be airtight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids n In nrtrtitinn incnnntinn 9or ceilings he ; ,..a.,...... ------.-._.., ... _,___.. _.. ... ...� ......, ... ........ ui c+....v.�an..o VVwI Ll- Fn UVIJIUI IA UI luu-4UU. 7/21/2021 4:33 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 F013M R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 7/21/2021 4:32:44 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: 4WInformation, Builder: ADAMS HOMES Community: Lot: 173 Phase3 Address: 5317 Lugo Street City: Fort Pierce State: FL Zip: 34951 Alr Leakage Test Results Passtng;:restilts must meet either the.Performance, Rrescriptive, or ERI'Method 0- .P.,RESCRIPTIVE,METHOD-The building or dwellmg.unit shall be tested and verified as having an air leakage rate of'not exceeding.7 air, changes per hour at a, pressure:of 0:2 inch w.g. (50 Pascals) in Climate Zones T an l 2:, Q' PERFORMANCE or ERI`METHOD-The building;or dwelling unit shall be teste-&and verified as haviri9 an air leaka9 a Late of not exceeding; the selected ACH(50) value, as shown on Form R405-2020 (Performance),br R406-2020 (ERI); section labeled as infiltration;'sub =section ACH50: ACH(50) specified on Form,R405-2020-Energy Ca/c (Performance) or R406 2020 (ERI): 7.000 x 60 _ 18200 Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans F-1 PASS • Code software calculated EJWhen ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 7/21/2021 4:33:35 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5317 Lugo Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 7/21/2021 4:33 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cirri per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105"F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 7/21/2021 4:33 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). El R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). EJ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 7/21/2021 4:33 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 7/21/2021 4:33 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 ❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ❑ R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. ❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 7/21/2021 4:33 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5