HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Chason-2045Nettles Bl... E-CaIcS Date: Oct 07, 2021 Plug, (tt Entire House By: E-Calcs Plus, Inc. E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 Email: eric@ecalcsplus.com Web: www.ecaicsplus.com License: HERS Rater ID 0757810 Project• • For: Chason - 2045 Nettles Blvd 2045 Nettles Blvd, Hutchinson Island South, FL 34957 Cooling Equipment Design Conditions Outdoor design DB: 90.4'F Sensible gain: 25205 Btuh Entering coil DB: 76.7°F Outdoor design WB: 77.4°F Latent gain: 5215 Btuh Entering coil WB: 63.6°F Indoor design DB: 75.0°F Total gain: 30420 Btuh Indoor RH: 50% Estimated airflow: 1160 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASH Manufacturer: Carrier Model: 25HBC536A00300+FX4DNF037L Actual airflow: 1160 cfm Sensible capacity: 27883 Btuh 111% of load Latent capacity: 5732 Btuh ' 110% of load Total capacity: 33615 Btuh 111% of load SHR: 83% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 23269 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipment type: Split ASHP Manufacturer: Carrier Model: 25HBC536A00300+FX4DNF037L Actual airflow: 0 cfm Output capacity: 34600 Btuh 149% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Carrier Model: AFUE 100 Actual airflow: 0 cfm Output capacity: 7.5 kW 1101/o of load Temp. rise: 50 OF Meets all requirements of ACCA Manual S. Entering coil DB: 70.0°F Capacity balance: 31 OF Economic balance: -62 'F yr wrightoft- 2021-Oct-25 05:45:20 ��'�` , •«•w,.-.-.r...,c:�.y Right-Suite(g)Universal 2021 21.0.08 RSU27537 Page 1 r�+�. Tt ... BIvdlChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E Project Summary s Entire House Pllusus,, Inc. E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 Email: eric@ecalcsplus.com Web: www.ecalesplus.com License: HERS Rater ID 0757810 Proiect Information For: Chason - 2045 Nettles Blvd 2045 Nettles Blvd, Hutchinson Island South, FL 34957 Notes: Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Outside db Inside db Design TD Job: Chason - 2045 Nettles BI... Date: Oct 07, 2021 By: E-Calcs Plus, Inc. Summer Design Conditions 41 °F Outside db 70 °F Inside db 29 °F Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 19785 Btuh Ducts 3484 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 23269 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ftz) 1697 169T Volume (ft3) 14642 14642 Air changes/hour 0.38 0.20 Equiv. AVF (cfm) 93 49 Heating Equipment Summary Make Carrier Trade CARRIER Model 25H BC536AO0300 AHRI ref 9155179 90 'F 75 °F 15 'F L 50 % 57 gr/lb Sensible Cooling Equipment Load Sizing Structure 18662 Btuh Ducts 6543 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swing'multiplier .1.00 Equipment sensible load 25205 Btuh Latent Cooling Equipment Load Sizing Structure 2886 Btuh Ducts 2329 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 5215 Btuh Equipment Total Load (Sen+Lat) 30420 Btuh Req. total capacity at 0.75 SHR 2.8 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond 25HBC536AO0300 Coil FX4DNF037L AHRI ref 9155179 Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 26100. Btuh Heating output 34600 Btuh @ 47° F Latent cooling 8700 Btuh Temperature rise 0 'F Total cooling 34800 Btuh Actual air flow 0 cfm Actual air flow 1160 cfm Air flow factor 0 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0.50 in H2O Static pressure .0.50 in H2O Space thermostat Load sensible heat ratio 0.83 Capacity balance point= 31 'F Backup: Carrier AFUE 100 Input = 8 kW, Output = 25591 Btuh, 100 AFUE Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. ' WrighR?1Fk� •«w- •�.•—.�••. Right -Suite® Universal 2021 21.0.08 RSU27537 Aft 2021-Oct-25 05:45:20 Page 1 BlvdlChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E Load Short Form E-Cabs Entire House Plus, Inc. E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 Email: eric@ecalcsplus.com Web: www.ecalcsplus.com License: HERS Rater ID 0757810 iLroject intormation For: Chason - 2045 Nettles Blvd 2045 Nettles Blvd, Hutchinson Island South, FL 34957 Job: Chason - 2045 Nettles BI... Date: Oct 07, 2021 By: E-Calcs Plus, Inc. Design Information Htg Clg Infiltration Outside db ('F) 41 90 Method Simplified Ins ide db (° F) 70 75 Construction quality Average Design TD (°F) 29 15 Fireplaces 0 Daily range - L Inside humidity (%) 50 50 Moisture difference (gr/lb) 24 57 HEATING EQUIPMENT Make Carrier Trade CARRIER Model 25HBC536AO0300 AHRI ref 9155179 Efficiency 8.5 HSPF Heating input Heating output 34600 Btuh @47-F Temperature rise 0 °F Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0.50 in H2O Space thermostat Capacitybalance point= 31 °F Backup: Carrier AFUE 100 Input = 8 kW_ n,itniit = 9ri5A1 Rtnh Inn API IF COOLING EQUIPMENT Make Carrier Trade CARRIER Cond 25HBC536AO0300 Coil FX4DNF037L AHRI ref 9155179 Efficiency 12.0 EER, 15 SEER Sensible cooling 26100 Btuh Latent cooling 8700 Btuh Total cooling 34800 Btuh Actual air flow 1160 cfm Air flow factor 0.046 cfm/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0.83 ROOM NAME Area (ftz) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) Laundry 48 1505 1202 0 55 BA1 55 788 301 0 14 BR3 130 1704 1702 0 78 BR1 123 2527 1907 0 88 BR2 114 1651 1598 0 74 Foyer 176 0 0 0 0 Great Rm 231 5287 5514 0 254 M BA 126 1994 1400 0 64 M WIC 40 0 0 0 0 PDWR 24 349 595 0 27 M BR 150 2006 3350 0 154 Kitt ivr)in AOr) cAcn gone n - Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 411- wright .oft' 2021-Oct-25 05:45:20 Right -Suite® Universal 2021 21.0.08 RSU27537 Page 1 .. BIvdlChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E Entire House d 1697 23269 25205 0 1160 Other equip loads 0 0 Equip. @ 1.00 RSM 25205 Latent cooling 5215 TnTAI C nnnnn I I I V V r JV•FGu V I I Du Bold/italic'values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. - - wrIghtsoft- ..,r. ww•,._...,�c- Right -Suite® Universal 2021 21.0.08 RSU27537 r CA>s ... BlvMChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E 2021-Oct-25 05:45:20 Page 2 4 E-CaIcs Plus, Inc. Building Analysis Entire House E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 Email: eric@eralcsplus.com Web: www.ecalesplus.com License: HERS Rater ID 0757810 For: Chason - 2045 Nettles Blvd 2045 Nettles Blvd, Hutchinson Island South, FL 34957 Job: Chason - 2045 Nettles BI... Date: Oct 07, 2021 By: E-Calcs Plus, Inc. Design Conditions Location: Indoor: Heating Cooling St Lucie Cc Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 28°N Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 24.4 56.9 Dry bulb (°F) 41 90 Infiltration: Dailyrange (°F) - 15 ( L ) Method Simplified Wet bulb (°F) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces. 0 Component Btuh/ft2 Btuh % of load Walls 4.0 7188 30.9 Glazing 18.2 4374 18.8 Doors 11.3 202 0.9 Ceilings 0.9 905 3.9 Floors 4.3 4160 17.9 Infiltration 1.6 2955 12.7 Ducts 3484 15.0 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 23269 100.0 Cooling Component Btuh/ft2 Btuh % of load Walls 2.5 4447 17.6 Glazing 22.6 5434 21.6 Doors 7.3 130 0.5 Ceilings 1.7 1647 6.5 Floors 0.0 28 0.1 Infiltration 0.4 826 3.3 Ducts 6543 26.0 Ventilation 0 0 Internal gains 6150 24.4 Blower 0 0 Adjustments 0 Total 25205 100.0 Latent Cooling Load = 5215 Btuh Overall U-value =0.146 Btuh/ftz--°F Data entries checked. - - lwrighttsof - AE'4 +�•+_�»». Right -Suite@ Universal 2021 21.0.08 RSU27537 ... Blvd\Chason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E Gazing Lld0r. •J wn (Airs 2021-Oct-25 05:45:20 Page 1 4 v 13 Sup Riser 14" 14" Job M Chason - 2045 Nettles Blvd Performed by E-Calcs Plus, Inc. for: Chason - 2045 Nettles Blvd 2045 Nettles Blvd Hutchinson Island South, FL 34957 First Floor E-Calcs Plus, Inc. . Serving all of Florida Phone: 833.322.5271 www.ecalcsplus.com eric@ecalcsplus.com Scale: 1 : 68 Page 1 RightSuite® Un iversa 12021 21.0.08 RSU27537 2021-Oct-25 05:45:52 ...2045 Nettles Blvd 10.25.2021.rup 4 Sup Riser 14" Job M Chason - 2045 Nettles Blvd Performed by E-Calcs Plus, Inc. for: Chason - 2045 Nettles Blvd 2045 Nettles Blvd Hutchinson Island South, FL 34957 Second Floor E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 www.ecaicsplus.com eric@ecalcsplus.com Scale: 1 : 68 Page 2 RightSuite@ Universal 2021 21.0.08 RSU27537 2021-Oct-25 05:45:52 ...2045 Nettles Blvd 10.25.2021.rup Duct System Summary Job: Chason - 2045 Nettles BI... 4 Ic-CaIcs Date: Oct 07, 2021 Plus, Inc, Entire House By: E-Calcs Plus, Inc. E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 Email: eric@ecalcsplus.com Web: www.eGaicsplus.com License: HERS Rater ID 0757810 Project• • For: Chason ­2045 Nettles Blvd 2045 Nettles Blvd, Hutchinson Island South, FL 34.957 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.50 in H2O 0.16 in H2O 0.34 in H2O 0.240 / 0.100 in H2O 0.120 in/100ft 0 cfm 283 ft Cooling 0.50 in H2O 0.16 in H2O 0.34 in H2O 0.240 / 0.100 in H2O 0.120 in/100ft 1160 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H " W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BA1 c 301 0 14 0 0 Ox 0 VIFx 0 0 BR1 c 1907 0 88 0.151 6.0 Ox 0 VIFx 28.8 130.0 st2 BR2 c 1598 0 74 0.139 6.0 Ox 0 VIFx 38.4 135.0 st3 BR3 c 1702 0 78 0.153 6.0 Ox 0 VIFx 27.0 130.0 st3 Great Rm c 2757 0 127 0.148 7.0 Ox 0 VIFx 32.0 130.0 st3 Great Rm-A c 2757 0 127 0.143 7.0 Ox 0 VIFx 38.2 130.0 st3 KitLivDin c 3818 0 176 0.130 8.0 Ox 0 VIFx 30.2 155.0 st4 KitLivDin-A c 3818 0 176 0.120 8.0 Ox 0 VIFx 45.0 155.0 st4 Laundry c 1202 0 55 0.161 .5.0 Ox 0 VIFx 19.1 130.0 st2 M BA c 1400 0 64 0.163 6.0 Ox 0 VIFx 17.0 130.0 SO M BR c 3350 0 154 0.150 8.0 Ox 0 VIFx 30.3 130.0 st1 PDWR-A c 595 0 27 0.170 4.0 Ox 0 VIFx 15.9 125.0 st6 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st4 Peak AVF 0 351 0.120 447 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 0 570 0.120 533 14.0 0 x 0 VinlFlx st6 Peak AVF 0 27 0.170 314 4.0 0 x 0 VinlFlx st2 st2 Peak AVF 0 170 0.151 488 8.0 0 x 0 VinlFlx st3 Peak AVF 0 406 0.139 516 12.0 0 x 0 VinlFlx Bold/italic values have been manually overridden Wriigtit oft- 2021-Oct-25 05:45:20 �.' ..• .mac i Right -Suite® Universal 2021 21.0.08 RSU27537 Page 1 BlvdlChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat] Trunk rb2 Ox 0 0 1160 83.0 0.120 652 14.8 16x 16 RtFg .Z'V .�,..sai � Right -Suite® Universal 2021 21.0.08 RSU27537 BlvdlChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E 2021-Oct-25 05:45:20 Page 2 Static Pressure and Friction Rate Job: Chason -2045 Nettles BI... CIZI E-Calks Date: Oct 07, 2021 Ptu, Inc. Entire House By: E-Calcs Plus, Inc. E-Calcs Plus, Inc. Serving all of Florida Phone: 833.322.5271 Email: eric@ecalcsplus.com Web: www.ecaicsplus.com License: HERS Rater ID 0757810 For: Chason - 2045 Nettles Blvd 2045 Nettles Blvd, Hutchinson Island South, FL 34957 Heating Cooling (in H2O) (in H2O) External static pressure 0.50 0.50 Pressure losses Coil 0 0 Heat exchanger 0 0 Supply diffusers 0.03 0.02 Return grilles 0.03 0.01, Filter 0.10 0.1 C Humidifier 0 0 Balancing damper 0 0 Other device 0 0 Available static pressure 0.34 0.34 Total• Supply Return (ft) (ft) Measured length of run -out 21 13 Measured length of trunk 24 0 Equivalent length of fittings 155 70 Total length 200 83 Total effective length , 283 Friction Heating Cooling (in/100ft) (in/100ft) Supply Ducts 0.120 OK 0.120 OK Return Ducts 0.120 OK 0.120 OK Supply 4AD=60, 11A=20, 11G=5, 11M=20, 111=10, 11G=5, 1A=35: TotalEL=155 Return 6M=20, 111=10, 5D=40: TotalEL=70 .� . wright oft- 2021-Oct-25 05:45:20 Right -Suite® Universal2021 21.0.08 RSU27537 Pagel ... BlvdlChason - 2045 Nettles Blvd 10.25.2021.rup Calc = MJ8 Front Door faces: E