HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot 114 Phase 3 Waterston...
wrightsoft® p p Date:
Entire House By: ocs
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCOWAY, SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COMLicerse:CMC1249777
For: ADAMS HOMES
5337 Lugo Street, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
Outdoor design DB:
90.4 °F
Sensible gain: 24881
Btuh
Outdoor design W B:
77.4 OF
Latent gain: 4767
Btuh
Indoor design DB:
75.0 °F
Total gain: 29647
Btuh
Indoor RH:
50%
Estimated airflow: 1167
cfrn
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
SpIitASHP
Manufacturer:
Carrier
Model: 25HBC537AP03+FX4DNB037L00
Actual airflow:
1167 cfm
Sensible capacity:
28185 Btuh
113% of load
Latent capacity:
5115 Btuh
1070/. of load
Total capacity:
33301 Btuh
112% of load SHR: 85%
Heating Equipment
Design Conditions
Entering coil DB: 76.4°F
Entering coil WB: 63.2°F
Outdoor design DB: 41.0 °F Heat loss: 28566 Btuh Entering coil DB: 69.5 °F
Indoor design DB: 70.0 °F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: SpIitASHP
Manufacturer: Carrier Model: 25HBC537AP03+FX4DNB037L00
Actual airflow: 1167 cfm
Output capacity: 31707 Btuh 111 % of load Capacity balance: 36 °F
Supplemental heat required: 0 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 1167 cfm ,
Output capacity: 6.8 kW 81 % of load Temp. rise: 18 °F
Meets all requirements ofACCA Manual S. -
A * wrightsoft® 2021-JU-2115U2:04
i� a •� me�� w���m�m Right-Sute®Uriversal2021 21.0.07 RSU23828
Page 1
terstore1820BGR1Lot114Pfs3Waterstone1820BGR.np Caic=W8 FrortDoorfaces: E
Component Constructions Job: Lot 114 Phase 3 Waterston...
- wrightsoft® p Date:
Entire House By: DCS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Licerse: CMC 1249777
smiLeject Intormation
For: ADAMS HOMES
5337 Lugo Street, Fort Pierce, FL 34951
Design
Conditions
Location:
St Lude Cc Intl, FL, US
Indoor:
Indoor temperature (OF)
Heating
70
Cooling
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 28 ON
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (gr/lb)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (T) -
Wet bulb (OF) -
15 (L
77
) Method
Construction quality
Simplified
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Construction descriptions or Area U-value Insul R Htg HTM Loss Clg HTM Gain
W Btuhftz1F ftz"F/Btuh BtuWt' Btuh Btu"Btuh
Walls
1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum
board int fnsh
Blk wall, stucco ext, r--4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, ZM" wood frm, 16" o.c. stud
n 20
0.049
19.0
1.42
28
2.59
52
e 20
0.049
19.0
1.42
28
2.59
52
s 20
0.049
19.0
1.42
28
2.59
52
w 20
0.049
19.0
1.42
28
2.59
52
all 80
0.049
19.0
1.42
114
2.59
207
n 534
0.201
4.1
5.83
3113
4.06
2168
e 127
0.201
4.1
5.83
739
4.06
515
s 611
0.201
4.1
5.83
3561
4.06
2481
w 317
0.201
4.1
5.83
1846
4.06
1286
all 1589
0.201
4.1
5.83
9260
4.06
6450
270
0.091
13.0
2.64
713
1.31
354
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n
thk; NFRC rated (SHGC=0.23); 50%drapes, medium; 1.33 ft overhang
(3.2 It window ht, 0.8 it sep.); 6.67 It head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang s
(5.3 ft window ht, 0.8 ft sep.); 6.67 it head ht w
all
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e
thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1.33 ft overhang
(5.3 It window ht, 1 ft sep.); 6.67 it head ht
2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" e
thk; NFRC rated (SHGC=0.31); 9.33 ft overhang (1.4 ft window ht, 0 ft
sep.); 6.67 It head ht
2B-2fv: 2 glazing, dr low-e outr, air gas, vnl fan mat, dr innr, 1/4" gap, 1/8" e
thk; NFRC rated (SHGC=0.31); 9.33 ft overhang (6.7 ft window ht, 1.5 ft
sep.); 6.67 it head ht
7
0.330
0
9.57
66
8.52
59
49
0.330
0
9.57
469
8.52
418
49
0.330
0
9.57
469
8.52
418
33
0.330
0
9.57
313
22.4
731
131
0.330
0
9.57
1251
12.0
1567
33
0.330
0
9.57
313
21.4
698
7
0.330
0
9.57
67
11.6
81
13
0.330
0
9.57
128
13.2
176
, -rk wrilghtsc ft- 2021-Jt1-21 15:02:04
C�" .a„•k•ia=.�.• u. «.gym m Righd-StiteOUriversal 2021 21.0.07 RSU23828 Page 1
14C
terstore1820BGR1Lot114Phs3Waterstore1820BGR.W Calc=NUB FrortDoorfaces: E
10C-v: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1 /8" w
thk; NFRC rated (SHGC=0.70); 12 ft overhang (6.7 ft window ht, 0.5 ft
sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 12 ft overhang (5.3
ft window ht, 0.5 ft sep.); 6.67 ft head ht
Doors
11 JO: Door, mtl fbrgl type e
Ceilings
16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2"
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth
18
0.550
0
16.0
285
16.2
289
33
0.330
0
9.57
313
8.52
279
20
0.600
6.3
17.4
350
17.6
353
1835
0.032
30.0
0.93
1703
1.69
3100
212
0.989
0
28.7
6080
0
0
t - wrightsc ft- 2021-JU-21 1592:04
rta•ie••w 2x c mo Rght-Srite®Uriversal2021 21.0.07 RSU23828 Page 2
terstore1820BGR\Lot114Phs3Waterstone1820BGR.nQ Calc=W8 FrortDoorfaces: E
-- wrightsoft® Project Summary
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Licerse: CMG 1249777
Job: Lot 114 Phase 3 Waterston...
Date:
By. DCS
For:
ADAMSHOMES
5337 Lugo Street, Fort Pierce, FL 34951
Notes:
JA8-18-15
Change to 3.0 ton 2/16/16 S. Finch
L. S. 7-21-21 VW K
Design
• •
Weather: St Lude Co Intl, FL, US
Winter Design
Conditions
Summer Design Conditions
Outside db
Inside db
41 OF
70 °F
Outside db
Inside db
90
75
OF
Design TD
29 OF
Design TD
15
OF
Daily range
L
Relative humidity
Moisture difference
50
57
%
grAb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure
Ducts
24346 Btuh
Structure
19104
Btuh
Central vent (0 cfm)
4220 Btuh
0 Btuh
Ducts
Central vent (0 cfm)
5777
0
Btuh
Btuh
none
Humidification
0 Btuh
(none)
Blower
0
Btuh
Piping
0 Btuh
Equipment load
28566 Btuh
Use manufacturer's data
y
Infiltration
Rate/swin multiplier
Equipmen�sensble load
1.00
24881
Btuh
Method
Construction quality
Simplified
Average
Latent Cooling Equipment Load Sizing
Fireplaces
0
Structure
3364
Btuh
Ducts
1403
Btuh
Central vent (0 cfm)
0
Btuh
Area (ft2)
Heating Cooling
1820 1820
(none)
Equipment latent load
4767
Btuh
Volume (ft3)
18350 18350
Air changes/hour
Equiv. AVF (cfm)
0.38 0.20
116
Equipment Total Load (Sen+Lat)
29647
Btuh
61
Req. total capacity at 0.75 SHR
2.8
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Make Carrier
Trade CARRIER
Model 25HBC537AP03
AHRI ref 204837926
Cond 25HBC537AP03
Coil FX4DNB0371-00
Efficiency
8.5 HSPF
AHRI ref 204837926
Efficiency 12.5 EER,16
SEER
Heating input
Heating output
34600 Btuh Qa 47°F
Sensible cooling
Latentcooling
26250
8750
Btuh
Btuh
Temperature rise
Actual airflow
27 OF
1167 cfm
Total cooling
Actual airflow
35000
1167
Btuh
cfm
Airflowfactor
Static pressure
0.041 cfm/Btuh
0.40 in H2O
Air flow factor
Static pressure
0.047
0.40
cfm/Btuh
in H2O
Space thermostat
Capacity balance point = 36 °F
Load sensible heat ratio
0.84
Iput = 7 kW, Output = 23253 Btuh, 100 AFUE
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
t � wrightsoft-
1 m Right-Srite®Uriversal2021 21.0.07 RSU23828 2021-Jri-21 15:02:04
�`...terstore182013GRIot114PFs3Waterstone1820BGR.np Calc=W8 FrortDocrfaces: E Page
-- wrightsoft- Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL32771 Phone:407-333-2665 Fax:407-333-3853 Web.WWW nFI AIM r)NAI i,.e—•�U ,— 1 -,
Job: Lot 114 Phase 3 Waterstone 1...
Date:
By: DCS
1
Room name
2
Exposed vdI
Entire House
BDRM2
3
Room height
212.0 ft
10.0 ft
36.0 8
4
Room dimensions
d
10.0 It heat/cool
5
Room area
1835.0
13.0 x 13.0 ft
ft2
169.0 112
Ty
Construction
number
U-value
(Btuh/ft2--q
Or
HTM
(BtuhRt2)
Area (ft2)
Load
Area (ft)
Load
or perimeter P (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/PiS
Heat
Cool
6
W__
1661.9actta��
Blk vdl, stucco ext
0049'n_1.42
5.83
_ ?5" 9
2.. ?- 20..
y
�20
3113
2A 2ov
0.201
0230
n
n
957
4.06
852
590
7
534
2168
100
100
4 583
406
11
_
W �_
2A 2ov_x� �_� _
16B 19.ad _
y 0,330
0 049
n
e.
9,57
.� 852
2 59
49
_20
0
0
66
469
59
�� 418
0
0
" __.0
0
T 0
0
_ 0
0
0
Blk wall, stucco ext
2A-2ov
2B-2fv
0.201
0.330
0,330
^
a
a
_,1.42
5.83
957
_
4.06
21.36
�__
200
33
_ 20
�� 127
1
28
__w 739
313
52
_4 ' 515
698
w.___.__-_0
0
O
0,00
0
0
0
0
2B-2fv
0.330
a
a
9.57
957
11.58
13.17
7
13
7
12
67
128
81
176
0
0
0
0
_w
W,w
y!
11J0
16B^19ad_ �a .
Blk u�all, stu000 eM
_0600
0049
0.201
a
e S
s
1740
_1.42
5.83
1758
259
4.06
20
w _,c20
660
20
- 20.
' y ' 611
350
. w 28
353
- - 52
M� 2481
0
0
p
vw130
0
0
3
0
0
O
0
0
_,0
—
L—G
2A 2ov
0.330
s
957
8.52
49
49
3561
130
758
528
W_Y
16B 19ad v
Blk wall, stucco ext µ'
10c-v
0049
0.201
0550
::�!
w
w
1,42
-' 5B3
1525
- _;259
4.06
1620
_ter, 20
400
18
r C 20
- 317
469
_ __.28
1846
_ 418
1286
_ 0
— 13C
0
r 114
0
.,_.0_
_. 663
0
: 0
461
2A-2ov
2A-2ov
0230
w
957
22.36
33
18
2
285
313
289
731
0
16
0
1
0
156
0
365
�¢
P
C
J2C Osw y
16B 30ad
0.330
0091
w
957
_
2,64
852
131
33
, 270
33
270
313
713
279
_ . _ _7
35_4
_ , 0
0
_ 0
0
F
22A I Yy
_ 0 032
0 93
1 89
1835
1835
1703
��0080157
3100
_
169
169
_ _ 157
286
_
_
-
_
c) AED excursion
r12
905
113
Envelope loss/gain
20642
14519
3349
2160
a) Infiltration
b) Room ventilation
3704
1035
691
193
p
p
0
0
13
Internal gains: Oocu tsCa 230
P�
5
1150
0
Appliances/other
2400
p
0
Subtotal (lines 6 to 13)
24346
19104
4040
2353
Less external load
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
0
15
Duct loads
17%
30%
24346
4220
19104
5777
17%
30%
4040
700
2353
711
Total room load
Airrequired(cfm)
:K�i
4194
30g4
Calculations approved byACCAto meet all requirements of Manual J 8th Ed
,� -�� wr_ YgtitsoR
,&per Right-SuteOUriversal2021 21.0.07 RSU23828 2021-JtJ-21 15 02:04
terstore1820BGR\Lot114Pfs3Waterstone1820BGR.rLp Calc=NU8 FrortDoorfaoes: E Page
- - wrightsoft3 Right-M Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Ucerse: CMC 1249777
Job: Lot 114 Phase 3 Waterston 1...
Date:
By: DCS
1
2
Room name
Exposed wall
BATH 2
BDRM 3
3
4
Room height
Room dimareensions
6.0 ft
10.0 ft heat/000l
13.0 ft
10.0 ft heaV000l
5
Room
13.0 x 6.0 ft
78.0
13.0 x 13.0 ft
ftz
169.0 112
Ty
Con on
number
U-value
(Btuh/ftzf
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
16 E19ad ___ __
Blk Hall, stucco
~ 0 049
��
�1.42
�_-259
_
n
n
0
ext
2A 2ov
0.201
0.330
5.83
957
4.06
852
0
0 0
0 0
0
0
0 0
»� 0
11
V11
2A 2ov
16619ad,__
0.330
- 0049
-,n
_. e_
957
142
852
259
_0
0
0
0 _ 0
0
0
_..
0 0
0 _____ _- _ 0
0
_ 0
523
9.57
0
0
—~ 0
0
0
0
0
Blk Hall, stucoo e)
2A-2ov
0.201
0230
a
a
4.06
21.36
0
0
0
0
0
—_.0.
0
2B-2N
0.330
a
957
11.58
0
0
0
0
0
26-21V
0
0
0
0
0
0
11 JO
0.330
a
9.57
13.17
0
0
0
0
0
0
0
0
W
Vf/
Blk MI, stu
Blk wall, stucco e)d
0.600
0201
a
s
17.40
_
5.83
17.58
„-.. _
259
4.06
0
_ -
0
— 60
0
w
0
._ . , 0
0
0
0
_.�... YO
0
�y ."0
0
_ w-0.
60
350
—J 244
__
130
L- G
2A-2ov
0.330
114
663
461
Blkwall,stuccoext
0.201
s
w
9,57
_.._ 1,42
5.83
8,52
._�_ 2.5.9
4.0-6
_ 0
w
0
0
0
0
0
0
0
_ 0
V 6
__ .._
16
_ 0
-___.__.0
16
�___. _
156
.
139
0
10C-v
0550
w
1525
1620
0
0
0
0
2A-2ov
0
0
0
0
0
0
0
2A-2ov
0.330
w
9.57
22,36
0
0
0
0
0
0
0
0
�—
P d _
C
12C Osnrµ;_: _
16B 30ad
0.330
0091
w
-_
957
_264
852
__v.
0
0
0
0
0
0
0
0
-
_
_
�0 032
—0.93
1 69
_78
78
72
72.
132
_ 169
169
_ 169
13
_157
,..
-.
...,
_...
- ......_
-.
,-.....,m
_ _
.._.__--..,
,
6
c) AED excursion
-19
44
Envelope loss/gain
594
357
1349
842
12
a) Infiltration
b) Room ventilation
115
32
249
70
0
0
0
0
13
Internal gains: Occupants @ 230
0
0
0
Applianoesrother
0
0
0
Subtotal (lines6 to 13)
709
389
1598
912
Less extemalload
0
0
Less transfer
0
0
Redistribution
0
0
0
0
0
0
14
15
Subtotal
Duct loads
709
389
0
1598
0
912
17%
30%
123
118
17 %
30 %
277
276
Total room load
Air required (dm)
832
506
1875
1187
34
24
77
56
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
- wr➢gt�tsoft^ R gk-Sute®Udversal 2021 21.0.07 RSU23828 2021-JU-21 15:02:04
terstorel820BGR\Lotll4PIs3Waterstorel82OBGR.rLp Calc=MJ8 FrontDoorlaees: E Page 2
-�- wrightsoft° Right-M Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Licerse: CMC 1249777
Job: Lot 114 Phase 3 Waterston 1...
Date:
By: DCS
1
2
Room name
Exposed wall
DINING/FOYER
DENBDRM4
3
Room height
25.0 ft
10.0 ft heaU000l
31.0 ft
10.0 ft heaUmol
4
5
Room dimensions
Room area
1.0 x 276.0 It
13.0 x 13.0 It
276.0 ftz
169.0 ftz
Ty
Construction
number
U-vafue
(BtuhHtz
Or
HTM
(Biuh/ftz)
Area (ftz)
or
Load
Area (ftz)
Load.
perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/PB
Heat
Cool
Gross
N/PVS
Heat
Cool
6
4
Blk wall, stucco
_,b_259
�. -
w _
0 ,.. a_:.0
. .. �_
___ ,_._
0_ __ 0
_ _
: _ 0
eM
2A 2ov
0201
0.330
n
n
5.83
957
4.06
852
0
0
0
0
0 0.---
0
50
50
291
203
11
W_
2A 2ov
1.6B 19ad.. __
0330
-_—0049
- ~
n
..;_e,_
9.57
142
852
_ -
0
_ p
T y
0
_____.. 0
0
0
M��172
0
_ 0
_:. : Q
0
:0
0
0 0
0- 0
0
0
Blk Hell, stucco ext
2A-2ov
0.201
a
588
4.06
70
30
120
_
130
�~ 97
_- 567
395
2B-2fv
0.330
0,330
a
a
957
957
2126
11.58
0
7
0
7
0
0
33
1
313
698
2B-2fv
0,330
a
957
13.17
13
12
67
128
81
176
0
0
0
0
0
0
0
0
W
11JO _
16B-19ad �
0600
0049
a
sw
1740
142
1758
259
20
20
350
353
0
0
0
0
µ
Blkvell stuccoe��-
2A 2ov
0201
s
5b3
4.06
110
77
451
314
130
130
758
528
W --=
-
_16&19ad_ �`w_
0.330
.�_ .:0049
s
;�w
957
_
142
852
-T259
33
_.� _0
33
�:..._.
_ 313
.__ _-. �0
_ 279
T_-
-0
0
0
_ 0
Blk Heli, stucco eM
10C-v
0201
0550
w
w
5.83
15.95
4.06
1620
0
0
_0
0
0
0
0
- 0
0
- 0
0
0
0
0
0
0
0
2A-2ov
0,330
w
9.57
22.36
0
0
0
0
0
0
0
0
P
2A 2ov
12C Osw
0.330
0091
w
957
8 52
0
0
0
0
0
0
0
C
_ _
16&30ad
0
185
.,0
_0
r
U9
.
_.
02
0989
0
$68
276
276
25
717
169
- 16-9
_31
17
=M9
r
286F_
_92._
466
�w_
s .-
-
6
c) AED excursion
-102
102
Envelopeloss/gain
2638
1779
2975
2211
12
a) Infiltration
b) Room ventilation
345
97
595
166
0
0
0
0
13
Internal gains: Occupants@ 230
1
230
0
0
Applianoes/other
0
0
Subtotal (lines6 to 13)
2984
2106
3570
2377
Less external load
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
2984
2106
0
3570
0
2377
17%
30%1
517
637
179/6
30%1
619
719
Total room load
Air required (cfm)
3501
2742
4189
3096
143
129
171
145
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
CP. w�rigft,>tsoft� Jr1-2115,02:04
Right-Srite®Uriversal 2021 21.0.07 RSU23828 2021- Page 3
terstore1820BGR\Lot114Pts3Waterstone1820BGR.rup Calc=M18 FrortDoorfaces: E
- wrightsoft° Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCOWAY,,SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web: WWW.DELAIR.COMLicense:CMC1249777
Job: Lot 114 Phase 3 Waterston 1...
Date:
By: DCS
1
2
Room name
Exposed wall
FAMILY RM
IVISTR BDRM
3
Room height
13.0 ft
10.0 ft heat/cool
41.0 ft
10.0 ft heaUmol
4
5
Room dimensions
Room area
13.0 x 22.0 It
14.0 x 17.0 ft
286.0 ft2
238.0 ft2
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load
Area (ft2)
Load
number
(Btuh/itz-cq
(Btuh/ t2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/Pr5
Heat
Cool
6
W._ _
W
Il_�_G
__.
16&19acj. ;
BIk wall, stucco e#
2A-2ov
V`'0049
0.201
_0c
n
r
_ 1;42
5.83
-
_: _259
4.06
-
170
1 b4
898
�y4 624
0 0
0 0
0230
n
957
852
0 0
0 0
0 0
0
0
11
W_,•_,i_
2A 2ov �.�
16B•19ad, — _.
_0.330
0049
M �0201
n
_ems
957
1♦42
_.,5.83
852
,_,-;259
�;;�;�20
0 0
;_.:...`:._20
_ 0
28
_ 0
_'.-;,
_ 16
� -0
0
____......._ 0
156
-�_-.,. ,0
139
Blkxell,stucco ext
2A-2ov
0330
a
a
957
4.06
2126
0
0
p
0
p
0
_..�52
0
0
0
0
0
0
0
.__.,._0
26-21v
0330
a
957
11.58
0
0
0
0
2B-2fv
0
0
0
0
0
0
0.330
a
957
13.17
0
0
0
0
0
0
0
0
VN
11JO
&19ad _ _�"
BIk wall, siucoo ext
0600
-- -_0049
0201
a
- 5
s
1740
__.`t, 2
5.83
1758
_._ ,,25952
4.06
0
0
0
0
0
0
0
0
0
__. 0
0
.. 0,
_ 0
..
0
100
406
I—G
2A-2ov
0330
s
957
852
0
0
0
0
100
683
16Bw1_9ad�_ _� _4
BIk well, stucco ext
10C-v
__. ' _ _ 004
0201
0550
w
w
w
1. 2
µ' 5.83
15.95
259
4.06
1620
20
130
18
._ ",. 20
w�~ 479
18
463
285
.^ 3E3
0
_ t_ 0
140
0
. 0
.__m, 124
0
_O'
-'� ' 721
0
-r __-_O
_
502
2A-2ov
0330
w
957
2226
0
0
0
289
0
0
16
0
1
0
156
0
365
_
2A-2ov
0330
w
,957
852
33
33
313
279
0
0
0
P__ _ ;
C
:12,. Osw . ,__>, __
16B 30ad_
2,64
_.'__ 131
— 0
0
0
M0
Yw
_
0.032
__ 0989
_
_ _
0 93
26.68
_i 69
_-�O,Oq
286
_. 286
286
;` 13
__. _
_ ___ 265
_ 373
. _
483
`
w ..__ 0
_•. _ 238
_ y _238
_
_ 238
_ 41
221
1176
_
402
6
c) AED exwrsion
1033
19
Envelope losstgain
1813
2614
3909
2457
12
a) Infiltration
b) Room ventilation
403
113
787
220
0
0
0
0
13
Internal gains: Occupants@ 230
3
690
1
230
Applianees/other
0
600
Subtotal (lines 6 to 13)
2216
3416
4696
3507
Lessextemal load
0
0
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
2216
3416
0
4696
0
3507
17%
30%
384
1033
17%
30%
814
1061
Total room load
Air required (cfm)
2600
4450
5225
4214
106
209
225
14
Calculations approved bvACCAto meet all requirements of Manual J 8th Ed
-- wr•➢ghtsoft^
Right-Sute®Uriversa12021 21.0.07 RSU23828 2021-JU-21 15:02:04
terstorel820BGR\Lotll4Phs3Waterstoml82OBGR.rLp Calc=NU8 FrortDoorfaces: E Page
- wrightsoft® Right-JO Worksheet
Entire House
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Uoerse: CMC 1249777
Job: Lot 114 Phase 3 Waterston 1...
Date:
By: DCS
1
Room name
M BATH M WIC
2
ExIcosed Hall
12.Oft Oft
3
4
Room height
Room dimensions
10.0 ft heaV000l 10.0 ft heaV000l
5
Room area
1.0 x 119.0 ft 7.0 x 7D ft
119.0 ftz 49.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft2)
Load Area (ft)
Load
number
(Btuh/ftz9
(Btuh/ft2
or perimeter (ft)
(Btuh) or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool Gross
N/PIS
Heat
Cool
6
1N �.._
16f319ad_ , ww
0049'
�n_
_ 1..42
2-
__ ., 0
_ 0
__. 0
_
.M 0 0
:. , 0
-
O,
Blk Hell, stucco ext
2A 2ov
0.201
0230
n
n
5.83
957
4.06
852
120
7
113
0
659
66
_ .�
459 0
59
0
-� - 0
0
2A 2ov _
0.330
n
9.57
_ 852
0
0
0
0
0 0
0
0,
0
0
0
0
11
W4-
i6B•19ad _._:__
Blk Hell, stucco e:d _.
2A-2ov
0049Ye_
�0.201
0.330
a
a
_1..42
5.83
957
..�259
4.06
21.36
T'Q
0.,
- 0
0_.
0
_
_ 0 ._ 0.
JT 0 - 0
-O
~ 0
w _,.
v �0
0
0
2B-2fv
0
0
0
0 0
0
0
0
0.330
a
957
11.58
0
0
0
0 0
0
0
0
2B-2fv
0.330
a
957
13.17
0
0
0
0 0
0
0
0
11J0
0600
a
17.40
1758
0
0
0
0 0_
0
0
0
W v _
V►/
16B 19ad• _
Blk Hell, stuccoext
0049:s'.
0201
s
_, �1..42
5.83
9
- 4.06
_ :�0
0
is 0
0
..
0
0
, _ _8 �.:0
0 - 0
r
�__ _0
~ -
0
-G
2A 2ov
0.330
s
957
852
0
0
0
0
0
0
W -._
;16619ad
Blk oiell, stucco eM
0049
0.201
_ w
w
__ 1.42
5.83
_
_. 259
4.66
_.w.
;, 0
_ _ 0
.. __
0�._
"' 0
�- 0
0
_ _ 0
_..-Q
0 0
0
0
0
_
0
0
0
10C-v
0550
w
15.95
1620
0
0
0
0 0
2A-2ov
0,330
w
957
22.36
0
0
0
0 0
0
0
0
0
0
0
2A 2ov
0.330
w_
957
852
0
0
0
0 0
0
0
0
P ..:;_:
C
•12C Osw_;,, ..-
0091
-
,.2,64
1..31
��.0
0
0
_
0 __ p
-
�.
0
__ -0
F __;_
161330ad_ _ -
:22A,>p�,_.:;,___•------
0
- 032
. �._.:_0.889
-
._.��
093
...:.28,68
19
-n 6
_ _-��0.00
119
_.._..�.119
119
.�.,,_.�.__12
_
-•_� 110
_.�...�;.�.344
201 49
n._
_._�. _� 0 _,.._,_ _..�49._.w_..>�._.0
w�0
_ _ 49
45
_,_..WW_�0
_ 83
., . �_-0
-
-
n
.,...
77
._...,_..._.
..._
._....w__.,.
a
._-..
6
c) AED
excursion
-36
-4
Envelope loss/gain
1180
683
45
79
12
a) Infiltration
230
64
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@a 230
0
0 0
0
Appliances/other
0
0
Subtotal (lines 6 to 13)
1410
747
45
79
Less wdemal load
0
0
0
0
Less transfer
0
0
0
0
Redistribution
14
Subtotal
1410
747
45
79
15
Duct loads
17 %
30%
244
226 17 %
30 %
8
24
Total roam load
Air required (cfm)
1655
973
53
103
68
46
2
5
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
CA - wrigF�tsoft ^ Right-Sute®Uriversal 2021 21.0.07 RSU23828 2021-JU-21 15:02:04Page 5
terstone1820BGR\Lot114Pfs3Waterstore1820BGR.np Calc=MJ8 FrortDoorfaces: E
- wrightsofta Right-JO Worksheet
Entire House
DEL AIR KrG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM License: CMC 124Q777
Job: Lot 114 Phase 3 Waterston 1...
Date:
By: DCS
1
2
Room name
wall
Krl-CHENMOOK
LAUNDRY
3
4
Room height
Room dimensions
29.0 it
10.0 ft heaU000l
6.0 ft
10.0 ft heal/cool
5
Rom area
1.0 x 246.0 ft
246.0 ftz
6.0 x 6.0 ft
36D ftz
Ty
Construction
number
U-value
(Btu hHtz-
Or
HTIVI
(Btuh/ftz)
Area (ft')
Load
Area (ft2)
Load
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
I Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
1N_
166 79ad-_
Blk wall, stu000
. _ _ 0049
'-p_
1,42
5.83
._,_2..:59
�
0 _0
: r._
0 _
eid
2A 2ov
0.201
0.330
n
n
957
4.06
8.52
150
117
684
476
0
0 0
0
2A 2ov _
16&19ad ..
0330
0049
_ n
9,57
1,42
852
__ 33
0 0
_ 0
_ 313
0 0
_ 279
0
_ _ ,0
_
0 0
0 _ 0
0
_0
0
0
Blk well, stucco e)d
2A-2ov
28-21v
-- 0.201
0.330
0.330
_e_
a
a
_ w _
5.83
957
,._259
4.06
21.36
_ 0
0
0
w, 0
0
0
-0
0
0
0
0
0
0
0
0
0
0
0
a
957
11.58
0
0
0
0
0
0
0
0
2B-2fv
11J0
0,330
a
957
13.17
0
0
0
0
0
0
0
0
W "- -
t-GBIk
__�
_16 wall, s
well, stucco eM
__ 0600
__ 0049
0.201
a
s -
s
17.40
_ _
-- 1.92
5.83
1758
259
4.06
0
.__ 0
0
_ 0
__ . 0
0
0
_a 0
Y' l M0
0
- 0
0
- 0
'
0_
.
_ . _. _..,__0
6
0
,. _ 0.
_ 0
2A-2ov
0.330
s
957
852
0
0
0
0
0
0
0
-_
e --
BIk well, stucco e)d
10C-v
-
0049._._v259
0201
0550
w
w
5.83
15.95
4.06
1620
0
0
0
0
w-_ _....__.. 0
0
0
Y _
_ 0
0
0
.0
_ • _.� _ 0
0
0--0
0
0
0
2A-2ov
0,330
w
957
222
0
0
0
0
0
0
0
0
0
0
0
0
2A-2ov _
0,330
w
957
852
0
0
0
0
0
0
0
0
P16B.._
C
16B 30ad_
_ _ _ 2,64
M 131.
_._-_140
,vim. 140
-
F.__.._._
22Aipl_.._:u_:
0032
0,93
1,69
0.00
246
24ti
_246
29
228
�� 832
___ 416
0
.,
_._ _ 36
_-. _ 36
•,
36
v 33
.-
:6
.
r
6
c) AED excursion
-122
-34
Envelope loss/gain
2426
1232
364
105
12
a) Infiltration
288
80
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants pa 230
0
0
0
Appliances/other
1200
0
600
Subtotal (lines 6 to 13)
2714
2512
364
705
Less external load
0
0
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
2714
2512
0
364
0
705
17%
30%
470
760
17%
30%
63
213
Total room load
Air required (cf n)
3184
3272
417
918
18
130
153
17
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed
,C -�- wrigF�tso`ft^ 2021-Jt1-21 15U2:04
�� Right-Srite®Universal 2021 21.0.07 RSU23828 Page 6
terstone1820BGRtLot114Phs3Waterslore18208GR.rLQ Calc=W8 FrortDoorfaces: E
-- wrightsoft® Duct System Summary Job: Lot 114 Phase 3 Waterston...
Date:
Entire House By: DCS
DEL AIR HTG, A/C & REFRIG. INC
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM Licerse: CIVIC 1249777
For: ADAMS HOMES
5337 Lugo Street, Fort Pierce, FL 34951
External static pressure
Pressure losses
Available static pressure
Supply/return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170/0.170 in H2O
0.300 in/100ft
1167 cfm
113 ft
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170/0.170 in H2O
0.300 in/100ft
1167 cfm
Name
Design
(Btuh)
Htg
(cfm)
Cig
(cfm)
Design
FR
Diam
(in)
H x W
(in)
Duct
Mat
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH 2
h 832
34
24
0.394
4.0
Ox 0
VI Fx
16.3
70.0
BDRM2
h 4740
194
144
0.366
8.0
Ox0
VIFx
22.9
70.0
BDRM3
h 1875
77
56
0.433
6.0
Ox0
MR
8.6
70.0
DENr8DRM4
DINING/FOYER
h 4189
171
145
0.409
7.0
Ox 0
VIFx
13.2
70.0
h 3501
143
129
0.444
8.0
Ox 0
VIFx
6.5
70.0
FAMILYRM
c 4450
106
209
0.330
8.0
Ox 0
VIFx
17.9
85.0
sti
KITCHENMOOK
c 3272
130
153
0.323
8.0
Ox 0
VIFx
20.1
85.0
sti
LAUNDRY
c 918
17
43
0.316
4.0
Ox 0
VIFx
22.7
85.0
sti
M.BATH
h 1655
68
46
0.317
5.0
Ox0
VIFx
22.2
85.0
sti
M. WIG
c 103
2
5
0.318
4.0
Ox 0
VI Fx
21.9
85.0
st1
MSTRBDRM
h 5510
225
214
0.300
8.0
Ox0
VIFx
28.2
85.0
st1
Supply Trunk Detail Table
Name
Trunk
Type
Htg
(cfm)
Cig
(cfm)
Design
FIR(fpm)
Veloc
Diam
(in)
H x W
(in)
Duct
Material
Trunk
sti
PeakAVF
549
670
0.300
627
14.0
0 x 0
VnlFlx
l- wrightsoft,
�eN/tr.pMmeaL..a��nepe.y Right-Sute®Uriversal 202121.0.07 RSU23828
��...terstore1820BGRtLot114Pts3Waterstore18208GR.rLp Calc=WS FrortDoorfaces: E
2021-JU-21 15:02:05
Page 1
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(Cfm)
Clg
(Cfm)
TEL
(ft)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb1
Ox 0
1167
1167
0
0
0
0
Ox 0
VIFx
,` -#I&- wrightsoft°
.N/p..6N.. e.Mwycump..Y Right-Sute®Uriversa1202121.0.07 RSU23828
J+C& ...terstore1820BGR1Lot114Pts3Waterstore1820BGR.nQ Calc=W8 FrortDooriaces: E
2021-JU-21 15fl2:05
Page 2
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Lot 114 Phase 3 Waterstone 1820 BGR Builder Name: ADAMS HOMES
Street: 5337 Lugo Street Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number:
Y
Owner: Jurisdiction: 661000
w
Design Location: FL, ST LUCIE CO INTL
— —
=
U
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or'oints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
the insulation and any gaps in the air barrier shall be sealed.
The insulation in any dropped ceiling/soffit
Access openings, drop down stairs or knee wall doors to
shall be aligned with the air barrier.
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
Knee walls shall be sealed.
with a material having a thermal resistance of R-3
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
(including
The air barrier shall be installed at any exposed edge of
insulation.
Floor framing cavity insulation shall be installed to
above -garage
maintain permanent contact with the underside of
and cantilevered
subfloor decking, or floor framing cavity insulation
floors)
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned s ace shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac
as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extpnrl behind and wiring,
Shower/tub
on exterior wall
The air barrier installed at exterior walls adjacent to showers and
piping
Exterior walls adjacent to showers and tubs shall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a. In addition inspection
over I
of log walls shall be in accord th th a I
ance wi a provisions of ICC-400.
7/21/2021 3:53 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
7/21/2021 3:52:32 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 661000
Permit #:
°Job•Information - • . -
Builder: ADAMS HOMES Community: Lot: 114 Phase3
Address: 5337 Lugo Street
City: Fort Pierce State: FL Zip: 34951
Air Leakage Test`Results , Passing,resulrsmustrrmeet;eitizerthePerformance, Prescriptive,,orERi"Method``
•
Q PRESCRIPTIVE METHOD=The building or dwellirig unit shall be. tested and verified as having an airieakage rate of riot exceeding 7'air
changes per, hour at a pressure 6f.02 mcfi w:g (50 ih'.Climate °Zones°1 and 2
•Pascals)
Q ' PERFORMANCE or ERI METHOD The bwldrg or'dwelhng unit;§hall•be tested and verified as having an air leakage rate of not.exceeding
,
theselected ACH(50)value assfiownpn Firm R405-2020 (Rerformance).or.`R406 2020 (ERI)section.labeled `as'infiltration; sub-seetio_mAGH50.
ACH(% •speoified on Form R405-2020-i0ergy Ca/c (Performance} or R406 2020; (ERI): " 7.000
x 60 _ 18200 = Method for calculating buildinq volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
F-1 PASS • Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester:
Printed Name of Tester:
License/Certification #:
Date of Test:
Issuing Authority:
7/21/2021 3:53:24 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1