Loading...
HomeMy WebLinkAboutProject Informationau,GST Air Calcs, LLC Load Short Form Guest House Air Calcs, LLC 7550 Hidden Haninock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicWlyme@airmlm.com Project• • For. Reed Guest House, Telese Builders 10930 Myrtlewood Ln, Port St Lucie, FL 34986 Job: 1714 Date: Jan 06, 2022 By: Vicki Lynne Nisa Design Information Htg Clg Infiltration Outside db (°F) 41 90 Method Blower door Inside db (°F) 70 75 Shielding /stories 3 (partial) / 1 Design TD (°F) 29 15 Pressure /AVF 50 Pa / 904 cfm Daily range - L Inside humidity (%) 30 50 Moisture difference (grAb) 2 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S018 230A** AHRI ref Coil CBA27UHE-018-230*++TDR AHRI ref 10259433 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating input 3.9 kW Sensible cooling 12600 Btuh Heating output 13283 Btuh Latent cooling 5400 Btuh Temperature rise 20 OF Total cooling 18000 Btuh Actual airflow 600 cfm Actual airflow 600 cfirn Air flow factor 0.047 cf n/Btuh Air flow factor 0.047 cfm/Btuh Static pressure 0.70 in H2O Static pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.79 ROOM NAME Area Htg load Clg load HtgAVF CIgAVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Kitchen 161 2604 3534 122 165 Living Room 249 4216 5265 198 246 Bath 75 896 588 42 27 Master Bed 180 3240 2835 152 132 WIC 85 1831 627 86 29 Guest House d 750 12787 12848 600 600 Other equip loads 717 381 Equip. @ 0.95 RSM 12620 Latent cooling 3421 T/1TA1 ��n .11Rrm 1anA1 I;nn son V I t1M_0 - r JV 1 VV 1 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -Fk wrightsoft- 2022-Jan-0615.47:56 At. Rigit-SUte@Univerwl202121.0.11RSU27054 Page /40CA ...eras%WrigtboftHVAC110930MyrtewoodLnGH.rup Calc=WB Front Door faces: N ILS- ®Pallw Air Calm, LLC BuildingAnalysis y Job: Date: Jan an06,2022 Guest House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Flidden Hammock LR Vero Bead, FL32966 Phone: 772.800.8413 Email: viddlynne@aircalmoom Project• • For. Reed Guest House, Telese Builders 10930 Myrtlewood Ln, Port St Lucie, FL 34986 Design • • • Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Latitude: 28°N Design TD (°F) Relative humidity (%) 29 30 15 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 2.4 56.9 Dry bulb (°F) 41 90 Infiltration: Daily range (°F) - 15 (L ) Method Blower door Wet bulb (°F) - 77 Shielding / stories 3 (partial) / 1 Wind speed (mph) 15.0 7.5 Pressure /AVF 50 Pa / 904 cfm Heating Component Btuh/ft2 Btuh % of load Walls 3.2 3318 24.6 Glazing 17.4 1362 10.1 Doors 0 0 0 Ceilings 1.6 1190 8.8 Floors 4.2 3155 23.4 Infiltration 1.9 2183 16.2 Duds 1579 11.7 Piping 0 0 Humidification 0 0 Ventilation 717 5.3 Adjustments 0 Total 135041 100.0 Cooling Component Btuh/ftz Btuh % of load - Walls 2.0 2123 16.0 Glazing 26.1 2044 15.4 Doors 0 0 0 Ceilings 1.2 917 6.9 Floors 0 0 0 Infiltration 0.6 650 4.9 Ducts 1055 8.0 Ventilation 381 2.9 Internal gains 6060 45.8 Blower 0 0 Adjustments 0 Total 1 132291 100.0 Latent Cooling Load = 3421 Btuh Overall U-value = 0.218 Btuh/ftz-°F Data entries checked. wr.Frgtsoft- Right-SLAeOuniversal202121.0.11 RSU27054 /0CA...erds\WrigltsoltHVACk1093OMyrfevmodLnGH.np Calc=MJ8 Front Door faces: N Glazinc Ducts Gains 2022-Jan-0615:47:56 Page 1 Component Constructions Job: 1714 Air Calcs, LLC p Date: Jan 06, 2022 Guest House By- Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone:772.800.8413 Email: viddlM@aircalcs.com e-roject inTormation For: Reed Guest House, Telese Builders 10930 Myrtlewood Ln, Port St Lucie, FL 34986 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 280N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Blower door Wet bulb (OF) - 77 Shielding / stories 3 (partial) / 1 Wind speed (mph) 15.0 7.5 Pressure /AVF 50 Pa / 904 cfm Construction descriptions Or Area U value Insul R Htg HTM Loss Clg HTM Gain ft' Btuhff--°F ft; FBtuh BMW Btuh BUIW Btuh Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8"Thk, 1/2" Gyp Bd Int Fnsh Partitions (none) Windows Impact: Impact; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang (5.2 ft window ht, 2 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.26); foreground = green grass (0.23); 2 ft overhang (1.5 ft window ht, 2 ft sep.); 8 ft head ht Impact: Impact; NFRC rated (SHGC=0.20); foreground = green grass (0.23); 2 ft overhang (8 ft window ht, 2 ft sep.); 8 ft head ht Doors (none) Ceilings DftCathCell: Attic, Tile Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh Floors DftRor. On Grade Depth, Tile Fir Fnsh n 248 0.109 5.1 3.15 781 2.02 500 e 293 0.109 5.1 3.15 922 2.02 590 s 234 0.109 5.1 3.15 739 2.02 472 w 278 0.109 5.1 3.15 877 2.02 561 all 1053 0.109 5.1 3.15 3318 2.02 2123 n 16 0.560 0 16.2 253 11.2 175 s 16 0.560 0 16.2 253 13.2 206 w 16 0.560 0 16.2 253 27.9 435 all 47 0.560 0 16.2 760 17.4 815 e 8 0.430 0 12.5 94 33.6 252 w 24 0.730 0 21.2 508 32.5 779 750 0.405 21.0 1.59 1190 1.22 917 110 0.989 0 28.7 3155 0 0 -rk wrightsoft' 2022-Jan-0615:47:56 Ri Yt-Sute®Unversal2021 21.0.11 RSU27054 �% p„ g Page 1 erds\WrigttsoftHVAC\10930MyrtlewoodLnGH.rup Calc=MJ8 Front Door faces: N Pro ect Summary Job: 1714 Air Calks, LLC J y Date: Jan 06, 2022 Guest House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beadi, FL32966 Phone: 772.8002413 Ermil:%ficWlpm@alrcalcs.com Project• • For. Reed Guest House Telese Builders 10930 Myrtlewood Ln, Port St Lucie, FL 34986 Notes: Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 11208 Btuh Structure 11793 Btuh Ducts 1579 Btuh Duds 1055 Btuh Central vent (23 dm) 717 Btuh Central vent (23 cfm) 381 Btuh Outside air Outside air Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 13504 Btuh Use manufacturer's data n Rate/swin multipplier EquipmenIsensible.load 0.95 12620 Btuh Infiltration Method Blower door Latent Cooling Equipment Load Sizing Shielding / stories 3 (partial) / 1 Pressure /AVF 50 Pa / 904 dm Structure 1884 Btuh Ducts 667 Btuh Central vent (23 cfm) 869 Btuh Heatingg Coolingg Outside air 3421 Btuh Area (ftz) 750 75D Equipment latent load Volume (fi3) 7749 7749 Air changes/hour 0.53 0.30 Equipment Total Load (Sen+Lat) 16041 Btuh Equiv AVF (cfm) 68 38 Req. total capacity at 0.70 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S018-230A** AHRI ref Coil CBA27UHE-018-230*++TDR AHRI ref 10259433 Efficiency 100 EFF Efficiency 13.0 EER,16 SEER Heating Input 3.9 kW Sensible cooling 12600 Btuh Heating output 13283 Btuh Latentcooling 5400 Btuh Temperature rise 20 OF Total cooling 18000 Btuh Actual airflow 600 cfm Actual airflow 600 cfm Airflowfactor 0.047 cfm/Btuh Airflowfactor 0.047 cfm/Btuh Static pressure 0.70 in H2O Stafic pressure 0.70 in H2O Space thermostat Load sensible heat ratio 0.79 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wrightsoft- 2022�Jan-0615.47:56 •�^ Righ-Sute®Universal 2021 21.0.11 RSU27054 Page 1 ACCA entslWrigttsoftHVAC110930MyrlewoodLnGH.rup Calc=MJ8 FrontDoorfaoss: N Air Caics, LLC Right-JO Worksheet Guest House Air Calks, LLC 755n Hidden Hammock Ln Vero Beach FL32966 Phone: 772.800.8413 Erria7il:vicidlynre@aircaics.com Job: 1714 Data: Jan 06, 2022 By: Vicki Lynne Nisa 1 Room name GuestHouse KAdhen 2 F� osed wall 110.0 ft 10.3 ft d 25.5 It 10.0 It heat/cool 3 Room height 14.0 x 11.5 ft 4 5 Room dimensions Room area 750.0 ftz 161.0 ft Ty Construction U-value Or HTM Area (T) Load or (ft) Load (Btuh) number (BtuhAlz-'q (BtuhlftTj or perimeter (ft) (Bivh) perim� Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat I Cool 6 Blk Wall, Stucco E>d 0.109 n 3.15 2.02 264 248 781 500 115 0 115 9---- 362 232 }—G Impact_. --- _- ---- - - 0.5.60 _-n. _-1624.___1120. 16_ -..._...:0.... -253._--...-.._175 - - ... - -- -0 441 - - -0 282 U+J Blk Wall, Stucco 6d 0.109 a 3.15 2.02 300 293 922 590 140 0 140 0- Impact 0.430 - e-- -----1.2.47 33.61 - - - -- 8 - - -0 - -- - - --252 -- - -- - _0 --0 - 11 - --('_ VI/ - BIkVVWl,sw0i End-- -- 0.109 s 3.15 2.02 250 234 739 .472 0 0-- 0 0 0 0 0 .- 0.560 ,S_ ___1624'_.._1320 _... 16_,_._. .16.___..253.._._.._.206.---_ .. .-- _0. ------- 0 Blk Wall, Stucco E)d Impact 0.109 0.560 w w 3.15 1624 2.02 2786 318 16 278 0 877 253 561 435 0 0 0 0 0 0 0 - - C-- Impact - -- - - - - 0.730 w _ . __-21.17 _._._1.59 — 3246 .._. 122-w_-_,750_ - --24 - _0 _ _ 750_.- 4 508 __1190 -- - �9 --_ _917,_ - - -0 _,_161 - - --0 ._161 - 0 _255 - - -0 _- .._19:. -.-.DftCathCeil_-- F- - -DftAor- -- - - - - _-9405_.7,. - - _0289 __ - - 28.68 -- -0.00 - - --760 - 110 -- - -3155 .- - ..-0 ----- 161 --- 26 - -- 731 .-- 6 c) AED e)cjmon 197 -44 Envelope loss/gain 9025 5083 1790 667 12 a) Infiltration 2183 650 492 146 b) Room ventilation 0 0 0 0 13 Interned gains: Occupants@ 230 2 460 1 230 Appliancestother 5600 2200 Subtotal(lines 6to13) 11208 11793 2282 3243 Lesserdemalload 0 0 0 0 Lesstransfer 0 0 0 0 0 0 0 0 14 Redistribution Subtotal 11208 11793 2282 3243 15 Ductloads 14% 9% 1579 1055 149% 9% 321 290 Total room load 12787 1 12848 2604 1 3534 Air required (cfm) 600 600 122 165 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. _- -FI.F wrigF�1 4 - 2022-Jan-0615:47:56 • """ "" to Right Suite® Urmrersal 2021 21.0.11 RSU27054 Page 1 AZUK _.eris\WrigttsoftHVAC110930MyrtlevmodLnGH.rup Calc=NUB Froroorfaoes: N dD Air Calm, LLC Ri ht-M Worksheet Job: 1714 Guest House Date: Jan 06, 2022 By: Vicki Lynne Nisa Air Calm, LLC 7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlyme@aircaks.com 1 Room name Living Room Bath 2 3 FVosed vVall Room height 31.5 ft 11.0 ft heaVaDol 7.5 ft 10.0 ft heaV000l 4 Room dimensions 1.0 x 249.0 It 7.5 x 10.0 It 5 Room area 249.0 82 75.0 ft2 Ty Consfruclion U-value Or HTM Area (fF) Load Area (M Load number (BtuhlftL*q (B or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stuom E)d 0.109 • n 3.15 2.02 1; r --n- - _1624 11.20 . _.-_16 _ 0 253 .------ 175 A _ _- -0 _ 0 0. W _Impact_ Blk Well, Stucco E)d .-_0.560 0.109 a 3.15 2.02 0 0 0 0 0 75 8 68 213 94 136 252 Impact 0.430 _ e_.__ 12A7- _ 33.61 - --0 0..- ---• -------0._.... . .-... .0 - 0 11 _-. L—G -- Blk Wall, StucpD E)d 0.109 s 3.15 2.02 0 0 0 6 0 0 0 0 0..- 0 impad. 0.560 .. s - __ 1624 .. _._ 1320.-.._..-_ ._.0 --- .---- .0 _ _0 _ _ _ _ . ---.__._ _-_ _ _ ..0 0 V�/ Blk Wadi, Stucco E)d Impact 0.109 0.560 w w 3.15 1624 2.02 27.86 198 0 174 0 548 0 351 0 0 0 0 0 0 0 0 II—_GG C_ Impact-- - - - - DftCathCeil..---- 0,730 0.405 _w_ .- - 21.17- _-- 1.59 - 32.46 _ .-_. 122 -24 -- . _ _249 0 - - 508 ._-- -_- 395 — T-779 - _.,_ 304 . - 0 . - -- 0 _ _75 -- - 119 --- Q _ _- --. 92 — - _ _- _249 _ _ _ 75... ....- F _--DflFlor - -_- _------__-- - ___-- 0.989,_-_- - ----28.68 _ ___0.00 ---- 249 _..-__-__32 ---- •-- 903 ____- .___.9._--__.75 ____..--__8 ___--__215 ----_ __-- �- 6 c) AED excursion 127 17 Envelope lossrgain 3027 2003 640 497 12 a) Infillraton 669 199 145 43 b) Room ventilation 0 0 0 0 13 Internal gains Occupants@ 230 1 230 0 0 Applianoesrother 2400 0 Subtotal (lines 6 to 13) 3695 4832 785 540 Less extemalload 0 0 0 0 Lesstransrer 0 0 0 0 0 0 0 0 14 Redistribution Subtotal 3695 4832 785 540 15 DuctloadS 14% 9% 521 432 14% 9% 111 48 Total room load 1 4216 1 5265 896 421 588 27 Air required (ctm) 198 246 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - F wrightsoft® 2022-Jan-0615.47:56 Righ-Wte®Universal 202121.0.11 RSU27054 Page ergslWrigftsoftHVAC110930N*flewoodLnGFLrup Calc=MJ8 Front Door faces: N Air Calm LLC Right-M Worksheet Guest House Air Cales, LLC 7550 Hidden Hammock Ln. Vero Beads. FL32966 Phone: 772.800.8413 Erriail:vicldlyrm@airca[cs.com Job: 1714 Date: Jan 06, 2022 By: Vicki Lynne Nisa 1 2 3 4 5 Room name Exposed vall Room height Room dimensions Room area Nbster Bed 27.0 It 10.0 It heat/000l 120 x 15.0 ft 180.0 ftz WIC 18.5 It 10.0 it heatbDol 8.5 x 10.0 ft 85.0 ft Ty Construction number U-value (BtuhA?-'g or HTM (Btuhfin Area or perimeter (ft) Load (Mh) Area or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Wi -- W !—G W C -_ ..:DttCathCeil- F Blk Wall Stuaoo FAQ Impact - Blk Wall, Stucco E:d Impact- - -- - Blk Wall, Stucco Ext _Impact _ -- _ _ -_ - . Blk Wall, Stucco Ext Impact Impact - - - :. DftFlor - - - - - 0.109 _.. 0.560 0.109 0.430 0.109 - .. 0.560 0.109 0.560 -- 0.730 - A05 - - _0.989 n _--n a e_ s _. s _ w w _ w -. -. _ . - 3.15 __ 1624 315 _ _1247 3.15 ._ __ 1624' 3.15 1624 _a21._17 . _ 1.59 -28.68. 2.02 a 11.20 2.02 . -33-61 2.02 _ 1320 2.02 27.86 _ 32.46 _ ._ 122 - 0.00 0 .._ . --0 0 _0 150 _ _ _ . __ 16 120 16 -- - - 0 ._-_ _- 1W -----180 0 _0 0 - T 0 134 18 104 0 ----0 - . ..1$0 - 0 - 0 0 - - -- 0 423 . - -_--- 253 329 253 - - 0 -- _ - - 286 - 774 0 ---- -0 0 - -- - 0 271 . _ .. -.206 210 435 ^ -._ 220 -.. - - -0 0 - 0 85 -- - 0 100 _--- _.. _. 0 0 0 0 0 - --- -.0 85 .. - - - 0 100 ._ .. _ _ 0__ 0 0 -- -- 0 __... _._85 -- 19 0 - _ - 0 268 --- _ 0 315 _ __ 0 0 0 -- --0 _ _ 135 - 531- 0 __ _ _ 0 171 _- 0_ 202 _ 0 0 0 --- -0 , - _-- 104 - - - 0 -- _ ...__.._85 - - 85 6 c) AED excursion 105 -8 Envelopelossrgain 1 2319 1447 1248 469 12 a) Infiltration b) Room ventilation 521 0 155 0 357 0 106 0 13 Internal gains: Oc upants@ 230 Applianceslother 0 0 1000 0 0 0 Subtotal(lines 6to13) 2840 2602 1605 575 14 15 Less eAemalload Less transfer Redistribution Subtotal Dud loads 14% 9% 0 0 0 2840 400 0 0 0 2602 233 14% 9% 0 0 0 1605 226 0 0 0 575 51 Total room load Airrequired(cim) 3240 1 1521132 2835 1 1831 1 86 627 29 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. -F�F- wrGgF�tsof't� 2022-Jarr0615*47:56 •� �" " — ^-^ 'gFt-Suitte@Universal 2021 21.0.11 RSU27054 Page -.erds\WrighlsoftWAC\10930NyAemodLnGH.nip Calc=NUB FrontDoorfaces: N Air Calcs, LLC Duct System Summary Guest House Air Calks, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlynne@aircalcs.com For. Reed Guest House, Telese Builders 10930 Myrtlewood Ln, Port St Lucie, FL 34986 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.571 / 0.129 in H2O 0.255 in/100ft 600 cfm 275 ft Supply Branch Detail Table Job: 1714 Date: Jan 06, 2022 By. Vicki Lynne Nisa Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.571 / 0.129 in H2O 0.255 in/100ft 600 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bath h 896 50 33 0.261 4.0 Ox 0 VIFx 18.5 200.0 st2 Kitchen c 3534 147 198 0.263 8.0 Ox 0 VIFx 16.9 200.0 st2 Living Room c 2632 119 148 0.255 7.0 Ox 0 VIFx 24.1 200.0 st2 Living Room -A c 2632 119 148 0.267 7.0 Ox 0 MR 14.0 200.0 st1 Master Bed h 1620 91 79 0.266 6.0 Ox 0 VIFx 14.3 200.0 st1 Master Bed -A h 1620 91 79 0.264 6.0 Ox 0 MR 16.5 200.0 st1 WIC h 1831 103 35 0.262 6.0 Ox 0 VIFx 17.9 200.0 st1 Supply Trunk Detail Table Trunk Htg Cig Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) . Material Trunk st1 PeakAVF 404 342 0.262 741 10.0 0 x 0 VinIFIX st2 PeakAVF 316 378 0.255 694 10.0 0 x 0 VinIFIX Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Matl Trunk rb3 Ox 0 286 194 46.7 0.277 524 10.0 Ox 0 VIFx rb2 Ox 0 434 526 50.7 0.255 492 14.0 Ox 0 VIFx wrightsoft® 2022-Jan-0615:47.56 +~. .wR..-re«dw.wx .ommwro Right-SUte®Universal 2021 21.0.11 RSU27054 Page 1 ...ens\WrigftsoftHVAD10930MyrtlewoodLnGH.nup Calc=MJ8 Front Door faces: N Report Job: 1714Manual S Compliance Re Air Calcs, LLC p p Date: Jan 06, 2022 Guest House By: Vicki Lynne Nisa Air Calcs, LLC 7550 Hidden Harnrnodc Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: vicWlynm@aimaics.com Project• • For: Reed Guest House, Telese Builders 10930 Myrtlewood Ln, Port St Lucie, FL 34986 Design Conditions Outdoor design DB: 90.4°F Sensible gain: 13229 Btuh Entering coil DB: 75.7°F Outdoor design WB: 77.4°F Latent gain: 3421 Btuh Entering coil WB: 63.5°F Indoor design DB: 75.0°F Total gain: 16649 Btuh Indoor RH: 50% Estimated airflow: 600 ch Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1S018 230A**+CBA27UHE-018-230*++TDR Actual airflow: 600 ch Sensible capacity: 12600 Btuh 95% of load Latent capacity: 5400 Btuh 158% of load Total capacity: 18000 Btuh 108% of load SHR: 70% Heating Equipment Design. Outdoor design DB: 41.0°F Heat loss: 13504 Btuh Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Manufacturer. Actual airflow: Output capacity: Elec strip Model: 600 clam 3.9 kW 98% of load Meets all requirements ofACCA Manual S. Entering coil DB: 68.7°F Temp. rise: 50 OF ,�, wrightsoft® 2022-Jan-061547:56 kk Right -Site® Urdversal 202121.0.11 RSU27054 Page 1 C'A...erdslWrigHsoftWAC110930MyrtlewoodLnGH.rup Calc=NU8 Front Door faces: N