Air Calcs, LLC
Load Short Form
Guest House
Air Calcs, LLC
7550 Hidden Haninock Ln, Vero Beach, FL32966 Phone:772.800.8413 Email: vicWlyme@airmlm.com
Project• •
For. Reed Guest House, Telese Builders
10930 Myrtlewood Ln, Port St Lucie, FL 34986
Job: 1714
Date: Jan 06, 2022
By: Vicki Lynne Nisa
Design Information
Htg Clg Infiltration
Outside db (°F) 41 90 Method Blower door
Inside db (°F) 70 75 Shielding /stories 3 (partial) / 1
Design TD (°F) 29 15 Pressure /AVF 50 Pa / 904 cfm
Daily range - L
Inside humidity (%) 30 50
Moisture difference (grAb) 2 57
HEATING EQUIPMENT
COOLING EQUIPMENT
Make
Make Lennox
Trade
Trade LENNOX
Model
Cond ML14XC1S018 230A**
AHRI ref
Coil CBA27UHE-018-230*++TDR
AHRI ref 10259433
Efficiency
100 EFF
Efficiency 13.0 EER,16 SEER
Heating input
3.9
kW
Sensible cooling 12600
Btuh
Heating output
13283
Btuh
Latent cooling 5400
Btuh
Temperature rise
20
OF
Total cooling 18000
Btuh
Actual airflow
600
cfm
Actual airflow 600
cfirn
Air flow factor
0.047
cf n/Btuh
Air flow factor 0.047
cfm/Btuh
Static pressure
0.70
in H2O
Static pressure 0.70
in H2O
Space thermostat
Load sensible heat ratio 0.79
ROOM NAME
Area
Htg load
Clg load
HtgAVF
CIgAVF
(ft2)
(Btuh)
(Btuh)
(cfm)
(cfm)
Kitchen
161
2604
3534
122
165
Living Room
249
4216
5265
198
246
Bath
75
896
588
42
27
Master Bed
180
3240
2835
152
132
WIC
85
1831
627
86
29
Guest House d
750
12787
12848
600
600
Other equip loads
717
381
Equip. @ 0.95 RSM
12620
Latent cooling
3421
T/1TA1
��n
.11Rrm
1anA1
I;nn
son
V I t1M_0 - r JV 1 VV 1
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-Fk wrightsoft- 2022-Jan-0615.47:56
At. Rigit-SUte@Univerwl202121.0.11RSU27054 Page
/40CA ...eras%WrigtboftHVAC110930MyrtewoodLnGH.rup Calc=WB Front Door faces: N ILS-
®Pallw
Air Calm, LLC BuildingAnalysis y Job: Date: Jan an06,2022
Guest House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Flidden Hammock LR Vero Bead, FL32966 Phone: 772.800.8413 Email: viddlynne@aircalmoom
Project• •
For. Reed Guest House, Telese Builders
10930 Myrtlewood Ln, Port St Lucie, FL 34986
Design
• • •
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (°F)
70
75
Elevation: 26 ft
Latitude: 28°N
Design TD (°F)
Relative humidity (%)
29
30
15
50
Outdoor: Heating
Cooling
Moisture difference (gr/Ib)
2.4
56.9
Dry bulb (°F) 41
90
Infiltration:
Daily range (°F) -
15 (L
) Method
Blower door
Wet bulb (°F) -
77
Shielding / stories
3 (partial) / 1
Wind speed (mph) 15.0
7.5
Pressure /AVF
50 Pa / 904 cfm
Heating
Component
Btuh/ft2
Btuh
% of load
Walls
3.2
3318
24.6
Glazing
17.4
1362
10.1
Doors
0
0
0
Ceilings
1.6
1190
8.8
Floors
4.2
3155
23.4
Infiltration
1.9
2183
16.2
Duds
1579
11.7
Piping
0
0
Humidification
0
0
Ventilation
717
5.3
Adjustments
0
Total
135041
100.0
Cooling
Component
Btuh/ftz
Btuh
% of load -
Walls
2.0
2123
16.0
Glazing
26.1
2044
15.4
Doors
0
0
0
Ceilings
1.2
917
6.9
Floors
0
0
0
Infiltration
0.6
650
4.9
Ducts
1055
8.0
Ventilation
381
2.9
Internal gains
6060
45.8
Blower
0
0
Adjustments
0
Total
1 132291
100.0
Latent Cooling Load = 3421 Btuh
Overall U-value = 0.218 Btuh/ftz-°F
Data entries checked.
wr.Frgtsoft-
Right-SLAeOuniversal202121.0.11 RSU27054
/0CA...erds\WrigltsoltHVACk1093OMyrfevmodLnGH.np Calc=MJ8 Front Door faces: N
Glazinc
Ducts
Gains
2022-Jan-0615:47:56
Page 1
Component Constructions Job: 1714
Air Calcs, LLC p Date: Jan 06, 2022
Guest House By- Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beads, FL32966 Phone:772.800.8413 Email: viddlM@aircalcs.com
e-roject inTormation
For: Reed Guest House, Telese Builders
10930 Myrtlewood Ln, Port St Lucie, FL 34986
Design
Conditions
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (OF)
70
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 280N
Relative humidity (%)
30
50
Outdoor: Heating
Cooling
Moisture difference (grAb)
2.4
56.9
Dry bulb (OF) 41
90
Infiltration:
Daily range (OF) -
15 (L
) Method
Blower door
Wet bulb (OF) -
77
Shielding / stories
3 (partial) / 1
Wind speed (mph) 15.0
7.5
Pressure /AVF
50 Pa / 904 cfm
Construction descriptions Or Area U value Insul R Htg HTM Loss Clg HTM Gain
ft' Btuhff--°F ft; FBtuh BMW Btuh BUIW Btuh
Walls
Blk Wall, Stucco Ext, R-4.1 Ext Bd Ins, 8"Thk, 1/2" Gyp Bd Int Fnsh
Partitions
(none)
Windows
Impact: Impact; NFRC rated (SHGC=0.24); 50% blinds 45°, medium;
50% outdoor insect screen; foreground = green grass (0.23); 2 ft overhang
(5.2 ft window ht, 2 ft sep.); 8 ft head ht
Impact: Impact; NFRC rated (SHGC=0.26); foreground = green grass
(0.23); 2 ft overhang (1.5 ft window ht, 2 ft sep.); 8 ft head ht
Impact: Impact; NFRC rated (SHGC=0.20); foreground = green grass
(0.23); 2 ft overhang (8 ft window ht, 2 ft sep.); 8 ft head ht
Doors
(none)
Ceilings
DftCathCell: Attic, Tile Roof, R-20 Roof Deck Ins, 1/2" Gyp Bd Int Fnsh
Floors
DftRor. On Grade Depth, Tile Fir Fnsh
n 248
0.109
5.1
3.15
781
2.02
500
e 293
0.109
5.1
3.15
922
2.02
590
s 234
0.109
5.1
3.15
739
2.02
472
w 278
0.109
5.1
3.15
877
2.02
561
all 1053
0.109
5.1
3.15
3318
2.02
2123
n 16
0.560
0
16.2
253
11.2
175
s 16
0.560
0
16.2
253
13.2
206
w 16
0.560
0
16.2
253
27.9
435
all 47
0.560
0
16.2
760
17.4
815
e 8
0.430
0
12.5
94
33.6
252
w 24
0.730
0
21.2
508
32.5
779
750
0.405
21.0
1.59
1190
1.22
917
110
0.989
0
28.7
3155
0
0
-rk wrightsoft' 2022-Jan-0615:47:56
Ri Yt-Sute®Unversal2021 21.0.11 RSU27054
�% p„ g Page 1
erds\WrigttsoftHVAC\10930MyrtlewoodLnGH.rup Calc=MJ8 Front Door faces: N
Pro ect Summary Job: 1714
Air Calks, LLC J y Date: Jan 06, 2022
Guest House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Hammock Ln, Vero Beadi, FL32966 Phone: 772.8002413 Ermil:%ficWlpm@alrcalcs.com
Project• •
For. Reed Guest House Telese Builders
10930 Myrtlewood Ln, Port St Lucie, FL 34986
Notes:
Design Information
Weather: St Lucie Co Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db
41
OF
Outside db
90
OF
Inside db
70
OF
Inside db
75
OF
Design TD
29
OF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
gr/Ib
Heating Summary
Sensible Cooling Equipment Load Sizing
Structure
11208
Btuh
Structure
11793
Btuh
Ducts
1579
Btuh
Duds
1055
Btuh
Central vent (23 dm)
717
Btuh
Central vent (23 cfm)
381
Btuh
Outside air
Outside air
Humidification
0
Btuh
Blower
0
Btuh
Piping
0
Btuh
Equipment load
13504
Btuh
Use manufacturer's data
n
Rate/swin multipplier
EquipmenIsensible.load
0.95
12620
Btuh
Infiltration
Method
Blower door
Latent Cooling Equipment
Load Sizing
Shielding / stories
3 (partial) / 1
Pressure /AVF
50 Pa
/ 904 dm
Structure
1884
Btuh
Ducts
667
Btuh
Central vent (23 cfm)
869
Btuh
Heatingg
Coolingg
Outside air
3421
Btuh
Area (ftz)
750
75D
Equipment latent load
Volume (fi3)
7749
7749
Air changes/hour
0.53
0.30
Equipment Total Load (Sen+Lat)
16041
Btuh
Equiv AVF (cfm)
68
38
Req. total capacity at 0.70 SHR
1.5
ton
Heating Equipment Summary
Cooling Equipment Summary
Make
Make Lennox
Trade
Trade LENNOX
Model
Cond ML14XC1S018-230A**
AHRI ref
Coil CBA27UHE-018-230*++TDR
AHRI ref 10259433
Efficiency
100 EFF
Efficiency 13.0 EER,16
SEER
Heating Input
3.9
kW
Sensible cooling
12600
Btuh
Heating output
13283
Btuh
Latentcooling
5400
Btuh
Temperature rise
20
OF
Total cooling
18000
Btuh
Actual airflow
600
cfm
Actual airflow
600
cfm
Airflowfactor
0.047
cfm/Btuh
Airflowfactor
0.047
cfm/Btuh
Static pressure
0.70
in H2O
Stafic pressure
0.70
in H2O
Space thermostat
Load sensible heat ratio
0.79
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
wrightsoft- 2022�Jan-0615.47:56
•�^ Righ-Sute®Universal 2021 21.0.11 RSU27054 Page 1
ACCA entslWrigttsoftHVAC110930MyrlewoodLnGH.rup Calc=MJ8 FrontDoorfaoss: N
Air Caics, LLC
Right-JO Worksheet
Guest House
Air Calks, LLC
755n Hidden Hammock Ln Vero Beach FL32966 Phone: 772.800.8413 Erria7il:vicidlynre@aircaics.com
Job: 1714
Data: Jan 06, 2022
By: Vicki Lynne Nisa
1
Room name
GuestHouse
KAdhen
2
F� osed wall
110.0 ft
10.3 ft d
25.5 It
10.0 It heat/cool
3
Room height
14.0 x 11.5 ft
4
5
Room dimensions
Room area
750.0 ftz
161.0 ft
Ty
Construction
U-value
Or
HTM
Area (T)
Load
or (ft)
Load
(Btuh)
number
(BtuhAlz-'q
(BtuhlftTj
or perimeter (ft)
(Bivh)
perim�
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat I
Cool
6
Blk Wall, Stucco E>d
0.109
n
3.15
2.02
264
248
781
500
115
0
115
9----
362
232
}—G
Impact_. --- _- ----
- - 0.5.60
_-n.
_-1624.___1120.
16_
-..._...:0....
-253._--...-.._175
- -
... - --
-0
441
- - -0
282
U+J
Blk Wall, Stucco 6d
0.109
a
3.15
2.02
300
293
922
590
140
0
140
0-
Impact
0.430
- e--
-----1.2.47
33.61
- - - -- 8
- - -0
- --
- - --252
-- - --
- _0
--0
-
11
- --('_
VI/
-
BIkVVWl,sw0i End--
--
0.109
s
3.15
2.02
250
234
739
.472
0
0--
0
0
0
0
0
.-
0.560
,S_
___1624'_.._1320
_... 16_,_._.
.16.___..253.._._.._.206.---_
..
.--
_0.
-------
0
Blk Wall, Stucco E)d
Impact
0.109
0.560
w
w
3.15
1624
2.02
2786
318
16
278
0
877
253
561
435
0
0
0
0
0
0
0
- -
C--
Impact - -- - -
- - 0.730
w _
. __-21.17
_._._1.59
— 3246
.._. 122-w_-_,750_
- --24
- _0
_ _ 750_.-
4 508
__1190
-- - �9
--_ _917,_
- - -0
_,_161
- - --0
._161
- 0
_255
- - -0
_- .._19:.
-.-.DftCathCeil_--
F- -
-DftAor- -- - - - -
_-9405_.7,.
- - _0289
__ -
- 28.68
-- -0.00
- - --760
- 110
-- - -3155
.- - ..-0
----- 161
--- 26
- -- 731
.--
6
c) AED e)cjmon
197
-44
Envelope loss/gain
9025
5083
1790
667
12
a) Infiltration
2183
650
492
146
b) Room ventilation
0
0
0
0
13
Interned gains: Occupants@ 230
2
460
1
230
Appliancestother
5600
2200
Subtotal(lines 6to13)
11208
11793
2282
3243
Lesserdemalload
0
0
0
0
Lesstransfer
0
0
0
0
0
0
0
0
14
Redistribution
Subtotal
11208
11793
2282
3243
15
Ductloads
14%
9%
1579
1055
149%
9%
321
290
Total room load
12787
1
12848
2604
1
3534
Air required (cfm)
600
600
122
165
Calculations approved byACCAto meet all requirements of Manual J 8th Ed. _-
-FI.F wrigF�1 4 - 2022-Jan-0615:47:56
• """ "" to Right Suite® Urmrersal 2021 21.0.11 RSU27054 Page 1
AZUK _.eris\WrigttsoftHVAC110930MyrtlevmodLnGH.rup Calc=NUB Froroorfaoes: N dD
Air Calm, LLC Ri ht-M Worksheet Job: 1714
Guest House Date: Jan 06, 2022
By: Vicki Lynne Nisa
Air Calm, LLC
7550 Hidden Hammock LR Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlyme@aircaks.com
1
Room name
Living Room
Bath
2
3
FVosed vVall
Room height
31.5 ft
11.0 ft heaVaDol
7.5 ft
10.0 ft heaV000l
4
Room dimensions
1.0 x 249.0 It
7.5 x 10.0 It
5
Room area
249.0 82
75.0 ft2
Ty
Consfruclion
U-value
Or
HTM
Area (fF)
Load
Area (M
Load
number
(BtuhlftL*q
(B
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat I
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blk Wall, Stuom E)d
0.109
• n
3.15
2.02
1; r
--n-
- _1624
11.20
. _.-_16
_ 0
253
.------ 175
A
_ _- -0
_ 0
0.
W
_Impact_
Blk Well, Stucco E)d
.-_0.560
0.109
a
3.15
2.02
0
0
0
0
0
75
8
68
213
94
136
252
Impact
0.430
_ e_.__
12A7-
_ 33.61
- --0
0..-
---•
-------0._....
. .-... .0
-
0
11
_-.
L—G
--
Blk Wall, StucpD E)d
0.109
s
3.15
2.02
0
0
0
6
0
0
0
0
0..-
0
impad.
0.560
.. s
- __ 1624
.. _._ 1320.-.._..-_
._.0
--- .---- .0
_
_0
_ _ _ _ .
---.__._
_-_
_ _ ..0
0
V�/
Blk Wadi, Stucco E)d
Impact
0.109
0.560
w
w
3.15
1624
2.02
27.86
198
0
174
0
548
0
351
0
0
0
0
0
0
0
0
II—_GG
C_
Impact-- - - - -
DftCathCeil..----
0,730
0.405
_w_
.-
- 21.17-
_-- 1.59
- 32.46
_ .-_. 122
-24
-- . _ _249
0
- - 508
._-- -_- 395
— T-779
- _.,_ 304
. - 0
. - -- 0
_ _75
-- -
119
--- Q
_ _- --. 92
— -
_ _- _249
_ _ _ 75...
....-
F _--DflFlor
- -_-
_------__--
- ___-- 0.989,_-_-
-
----28.68
_ ___0.00
---- 249
_..-__-__32
---- •-- 903
____- .___.9._--__.75
____..--__8
___--__215
----_ __-- �-
6
c) AED excursion
127
17
Envelope lossrgain
3027
2003
640
497
12
a) Infillraton
669
199
145
43
b) Room ventilation
0
0
0
0
13
Internal gains Occupants@ 230
1
230
0
0
Applianoesrother
2400
0
Subtotal (lines 6 to 13)
3695
4832
785
540
Less extemalload
0
0
0
0
Lesstransrer
0
0
0
0
0
0
0
0
14
Redistribution
Subtotal
3695
4832
785
540
15
DuctloadS
14%
9%
521
432
14%
9%
111
48
Total room load
1
4216
1
5265
896
421
588
27
Air required (ctm)
198
246
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed.
- F wrightsoft® 2022-Jan-0615.47:56
Righ-Wte®Universal 202121.0.11 RSU27054 Page
ergslWrigftsoftHVAC110930N*flewoodLnGFLrup Calc=MJ8 Front Door faces: N
Air Calm LLC
Right-M Worksheet
Guest House
Air Cales, LLC
7550 Hidden Hammock Ln. Vero Beads. FL32966 Phone: 772.800.8413 Erriail:vicldlyrm@airca[cs.com
Job: 1714
Date: Jan 06, 2022
By: Vicki Lynne Nisa
1
2
3
4
5
Room name
Exposed vall
Room height
Room dimensions
Room area
Nbster Bed
27.0 It
10.0 It heat/000l
120 x 15.0 ft
180.0 ftz
WIC
18.5 It
10.0 it heatbDol
8.5 x 10.0 ft
85.0 ft
Ty
Construction
number
U-value
(BtuhA?-'g
or
HTM
(Btuhfin
Area
or perimeter (ft)
Load
(Mh)
Area
or perimeter (ft)
Load
(Btuh)
Heat I
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
11
Wi
--
W
!—G
W
C -_ ..:DttCathCeil-
F
Blk Wall Stuaoo FAQ
Impact -
Blk Wall, Stucco E:d
Impact- - -- -
Blk Wall, Stucco Ext
_Impact _ -- _ _ -_ - .
Blk Wall, Stucco Ext
Impact
Impact - - -
:.
DftFlor - - - - -
0.109
_.. 0.560
0.109
0.430
0.109
- .. 0.560
0.109
0.560
-- 0.730
- A05
- - _0.989
n
_--n
a
e_
s
_. s _
w
w
_ w
-. -. _
. -
3.15
__ 1624
315
_ _1247
3.15
._ __ 1624'
3.15
1624
_a21._17
. _ 1.59
-28.68.
2.02
a 11.20
2.02
. -33-61
2.02
_ 1320
2.02
27.86
_ 32.46
_ ._ 122
- 0.00
0
.._ . --0
0
_0
150
_ _ _ . __ 16
120
16
-- - - 0
._-_ _- 1W
-----180
0
_0
0
- T 0
134
18
104
0
----0
- . ..1$0
-
0
- 0
0
- - -- 0
423
. - -_--- 253
329
253
- - 0
-- _ - - 286
- 774
0
---- -0
0
- -- - 0
271
.
_ .. -.206
210
435
^
-._ 220
-.. - - -0
0
- 0
85
-- - 0
100
_--- _.. _. 0
0
0
0
0
- --- -.0
85
.. - - - 0
100
._ .. _ _ 0__
0
0
-- -- 0
__... _._85
-- 19
0
- _ - 0
268
--- _ 0
315
_ __ 0
0
0
-- --0
_ _ 135
- 531-
0
__ _ _ 0
171
_- 0_
202
_ 0
0
0
--- -0
, - _-- 104
- - - 0
--
_ ...__.._85
- - 85
6
c) AED excursion
105
-8
Envelopelossrgain
1 2319
1447
1248
469
12
a) Infiltration
b) Room ventilation
521
0
155
0
357
0
106
0
13
Internal gains: Oc upants@ 230
Applianceslother
0
0
1000
0
0
0
Subtotal(lines 6to13)
2840
2602
1605
575
14
15
Less eAemalload
Less transfer
Redistribution
Subtotal
Dud loads
14%
9%
0
0
0
2840
400
0
0
0
2602
233
14%
9%
0
0
0
1605
226
0
0
0
575
51
Total room load
Airrequired(cim)
3240
1 1521132
2835
1
1831
1 86
627
29
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed.
-F�F- wrGgF�tsof't� 2022-Jarr0615*47:56
•� �" " — ^-^ 'gFt-Suitte@Universal 2021 21.0.11 RSU27054 Page
-.erds\WrighlsoftWAC\10930NyAemodLnGH.nip Calc=NUB FrontDoorfaces: N
Air Calcs, LLC Duct System Summary
Guest House
Air Calks, LLC
7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vicidlynne@aircalcs.com
For. Reed Guest House, Telese Builders
10930 Myrtlewood Ln, Port St Lucie, FL 34986
External static pressure
Pressure losses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.70
in H2O
0
in H2O
0.70
in H2O
0.571 / 0.129
in H2O
0.255
in/100ft
600
cfm
275 ft
Supply Branch Detail Table
Job: 1714
Date: Jan 06, 2022
By. Vicki Lynne Nisa
Cooling
0.70 in H2O
0 in H2O
0.70 in H2O
0.571 / 0.129 in H2O
0.255 in/100ft
600 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
Bath
h 896
50
33
0.261
4.0
Ox 0
VIFx
18.5
200.0
st2
Kitchen
c 3534
147
198
0.263
8.0
Ox 0
VIFx
16.9
200.0
st2
Living Room
c 2632
119
148
0.255
7.0
Ox 0
VIFx
24.1
200.0
st2
Living Room -A
c 2632
119
148
0.267
7.0
Ox 0
MR
14.0
200.0
st1
Master Bed
h 1620
91
79
0.266
6.0
Ox 0
VIFx
14.3
200.0
st1
Master Bed -A
h 1620
91
79
0.264
6.0
Ox 0
MR
16.5
200.0
st1
WIC
h 1831
103
35
0.262
6.0
Ox 0
VIFx
17.9
200.0
st1
Supply Trunk Detail Table
Trunk
Htg
Cig
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FIR
(fpm)
(in)
(in) .
Material
Trunk
st1
PeakAVF
404
342
0.262
741
10.0
0 x 0
VinIFIX
st2
PeakAVF
316
378
0.255
694
10.0
0 x 0
VinIFIX
Return Branch Detail Table
Grille
Htg
Clg
TEL
Design
Veloc
Diam
H x W
Stud/Joist
Duct
Name
Size (in)
(cfm)
(cfm)
(ft)
FIR
(fpm)
(in)
(in)
Opening (in)
Matl
Trunk
rb3
Ox 0
286
194
46.7
0.277
524
10.0
Ox 0
VIFx
rb2
Ox 0
434
526
50.7
0.255
492
14.0
Ox 0
VIFx
wrightsoft® 2022-Jan-0615:47.56
+~. .wR..-re«dw.wx .ommwro Right-SUte®Universal 2021 21.0.11 RSU27054 Page 1
...ens\WrigftsoftHVAD10930MyrtlewoodLnGH.nup Calc=MJ8 Front Door faces: N
Report Job: 1714Manual S Compliance Re
Air Calcs, LLC p p Date: Jan 06, 2022
Guest House By: Vicki Lynne Nisa
Air Calcs, LLC
7550 Hidden Harnrnodc Ln, Vero Beads, FL32966 Phone: 772.800.8413 Email: vicWlynm@aimaics.com
Project• •
For: Reed Guest House, Telese Builders
10930 Myrtlewood Ln, Port St Lucie, FL 34986
Design Conditions
Outdoor design DB:
90.4°F
Sensible gain:
13229
Btuh Entering coil DB: 75.7°F
Outdoor design WB:
77.4°F
Latent gain:
3421
Btuh Entering coil WB: 63.5°F
Indoor design DB:
75.0°F
Total gain:
16649
Btuh
Indoor RH:
50%
Estimated airflow:
600
ch
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SplitAC
Manufacturer:
Lennox
Model: ML14XC1S018 230A**+CBA27UHE-018-230*++TDR
Actual airflow:
600
ch
Sensible capacity:
12600
Btuh
95% of load
Latent capacity:
5400
Btuh
158% of load
Total capacity:
18000
Btuh
108% of load SHR: 70%
Heating Equipment
Design.
Outdoor design DB: 41.0°F Heat loss: 13504 Btuh
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype:
Manufacturer.
Actual airflow:
Output capacity:
Elec strip
Model:
600 clam
3.9 kW 98% of load
Meets all requirements ofACCA Manual S.
Entering coil DB: 68.7°F
Temp. rise: 50 OF
,�, wrightsoft®
2022-Jan-061547:56
kk Right -Site® Urdversal 202121.0.11 RSU27054 Page 1
C'A...erdslWrigHsoftWAC110930MyrtlewoodLnGH.rup Calc=NU8 Front Door faces: N