HomeMy WebLinkAboutNOA ply Roofing Over Wood Deck�MIAMI-QADE MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
- 11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.eov/economy
Sika Sarnafil, A Division of Sika Corp.
100 Dan Road
Canton, *A 02021
'$COPE:
Xi his NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product
or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is
determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein, and has been designed to comply, with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Sika Sarnafil PVC Single Ply Roofing over Wood Deck
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
,*xplratun date may be displaye&in.advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
fNSPECTION: A copy of this entire NOA, shall: be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the, request of the Building Official.
16� is NOA renews NOA No. 19-0513.03 and consists ofpag�es,1 through 12.
Tha,submitted documentation was reviewed by Alex Tigera.
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 1 of 12
ROOFING SYSTEM APPROVAL
Category:
Roofing
Sub -Category:
Single Ply
Material:
PVC
Deck Type:
Wood
Maximum Design Pressure:
-75 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE 1
Test Product
Product Dimensions Specification Description
G410
48, 60, 72 and 80
ASTM D4434
Fiberglass reinforced PVC roofing membrane.
mils
G410 Textured
48, 60, 72 and 80
ASTM D4434
Fiberglass reinforced PVC roofing membrane.
mils
S327
48, 60, 72 and 80
ASTM D4434
Polyester reinforced PVC roofing membrane.
mils
S327 Textured
48, 60, 72 and 80
ASTM D4434
Polyester reinforced PVC roofing membrane.
mils
S327 (10 ft)
48, 60, 72 and 80
ASTM D4434
Polyester reinforced PVC roofing membrane.
mils
S327 Felt
48, 60, 72 and 80
ASTM D4434
Polyester reinforced PVC roofing membrane.
mils
Sikaplan Fastened
45 mils or 60 mils
ASTM D4434
White polyester reinforced PVC roofing
membrane.
Sikaplan Fastened Feltback
45 mils or 60 mils
ASTM D4434
White polyester reinforced PVC roofing
membrane.
Sikaplan Adhered
60 mils
ASTM D4434
White polyester reinforced PVC roofing
membrane.
Sarnacol 2170 VC
Various
Proprietary
Solvent -based, VOC compliant adhesive.
Sarnatred
3.25' x 32.8'
Proprietary
PVC walkway protection sheet.
Sarnaclad
Various
Proprietary
Heat weldable PVC/galvanized steel flashing
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 2 of 12
APPROVED INSULATIONS:
Product
Samatherm
iDensDeck
nensDeck Prime
H-Shield
TABLE 2
Product
Description
Isocyanurate Insulation with fiber
reinforced felt paper facer
Silicon treated gypsum with fiberglass mat
facer
Silicon treated gypsum with an enhanced
fiberglass mat facer
Isocyanurate Insulation with fiber
reinforced felt paper facer
Manufacturer
(with current NOA)
Sika Sarnafil, A Division
of Sika Corp.
Georgia Pacific Gypsum LLC
Georgia Pacific Gypsum LLC
Hunter Panels, LLC
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 3 of 12
APPROVED FASTENERS/ADHESIVES:
TABLE 3
Fastener
Product
Product
Manufacturer
Number
Name
Description
Dimensions
(With Current NOA)
1.
#12 Standard Roofgrip, #14 Insulation and membrane
Various
OMG, Inc.
Roofgrip,
fastener
# 15 Roofgrip
2.
Sarnafastener #12
Insulation and membrane
Various
Sika Sarnafil, A Division
+
fastener
of Sika Corp.
3.
Sarnaplate
Insulation fastening plate.
3" Round
Sika Sarnafil, A Division
of Sika Corp.
4.
Sarnabar
Galvanized or stainless steel
Various
Sika Sarnafil, A Division
membrane fastening bar.
of Sika Corp.
5.
Sarnafastener #14
Insulation and membrane
Various
Sika Sarnafil, A Division
fastener
of Sika Corp.
6.
OMG Heavy Duty
Insulation and membrane
Various
OMG, Inc.
fastener
7.
Sarnafastener-XP
Insulation and membrane
Various
Sika Sarnafil, A Division
fastener
of Sika Corp.
8.
Sarnadisc-XPN
Insulation and membrane
1.5" x 3.75"
Sika Sarnafil, A Division
fastener
of Sika Corp.
9.
Sikaplan Board Fastener
Insulation and membrane
Various
Sika Sarnafil, A Divison of
#12
fastener
Sika Corp.
10.
Sikaplan Fastener #14
Insulation and membrane
Various
Sika Sarnafil, A Division
fastener
of Sika Corp.
11.
Flat Bottom Metal Plate
Insulation fastening plate.
3" Round
OMG, Inc.
12.
3 in. Ribbed Galvalume ,
Round galvalume plated steel
3" Round
OMG, Inc.
Plate
stress plate
13.
Sikaplan Board Plate
Round galvalume plated steel
3" Round
Sika Saranfil, A Division of
stress plate
Sika Corp.
14.
RhinoBond Insulation Plate Black primer coated plate for
3" Round
OMG, Inc.
use with PVC membrane's
15.
Sarnadisc RhinoBond
Black primer coated plate for
3" Round
Sika, Sarnafil, A Division of
use with PVC membranes
Sika Corp.
16.
Sikaplan RhinoBond Disc
Black primer coated plate for
3" Round
Sika Sarnafil, A Division of
use with PVC membranes
Sika Corp.
17.
OMG Eyehook Accuseam
Round galvalume steel plate
23/8" Round
OMG, Inc.
"
Plate
for use with OMG fasteners
18.
Sikaplan Disc
Round galvalume steel plate
23/8" Round
Sika Sarnafil, A Division of
for use with OMG fasteners
Sika Corp
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 4 of 12
EVIDENCE SUBMITTED:
Test Agency
Factory Mutual Research
A
'(Underwriters Laboratories, Inc.
Trinity I ERD
PRI
NEMOjetc.
Test Identifier
3001396
3016201
3021131
3028309
3030053
3032532
3035670
3036355
R8992
S42480.08.12
S44790.06.13
S44790.08.13
S45990.06.14
S44790.07.14-R2
SARN-087-02-02
2-SIKA-18-001.01.19
Description
FM 4470
FM 4470
FM 4470
FM 4470
FM 4470
FM 4470
FM 4470
FM 4470
UL 790
Physical Properties
ASTM D4434
ASTM D4434
ASTM D4434
ASTM D4434
FM 4474 / TAS 114
FM 4470 / TAS 114
Date
05/28/99
01 /28/03
07/07/05
03/30/07
09/12/07
08/05/08
05/13/09
11/10/09
05/15/13
08/20/12
06/05/13
08/26/13
06/02/14
06/01/15
06/22/18
01/03/19
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 5 of 12
APPROVED ASSEMBLIES:
Membrane Type: Single Ply, PVC
Deck Type 1I: Wood, Insulated
Deck Description: 19/32" or greater plywood or wood plank
System Type C(1): All layers of insulation simultaneously fastened; membrane adhered
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are not approved
a and shall not be installed unless said accessories demonstrate compliance with prescriptive Florida Building
Code requirements and are field fabricated utilizing the approved membranes listed in Table 1.
"Thermal Barrier: Minimum 1/2" DensDeck or DensDeck Prime
One or more layers of any of the following insulations:
Base Insulation Laver: Insulation Fasteners Fastener Density/ft'
able 3
Sarnatherm, H-Shield
Minimum 1.5" thick N/A N/A
Note: All layers shall be simultaneously fastened; see top layer below for fasteners and density. Insulation panels
listed are minimum sizes and dimensions; if larger panels are used, the number of fasteners shall be increased
maintaining the same fastener density. Please refer to Roofing Application Standard RAS 117 for insulation
attachment.
Top Insulation Laver (Optional):
Sarnatherm, H-Shield
Minimuml.5" thick
Insulation Fasteners
Table 3
5, 6,14,15
Fastener Density/ft2
See Design Pressure
Note: Insulation panels listed are minimum sizes and dimensions; if larger panels are used, the number of
fasteners shall be increased maintaining the same fastener density. Please refer to Roofing Application Standard
RAS 117 for insulation attachment.
Membrane: Sarnafil S327, S327 Textured or S327 (10 ft) bonded to RhinoBond Insulation Plates with .
RhinoBond Plate bonding tool at 6 seconds per plate so the tool reaches 400°F. Minimum 3"
wide side lap is sealed with a minimum %" wide heat weld.
'Maximum Design
$ressures:
Maximum Pressure
-45 psf
(See General Limitation #7)
Fastener Spacing Fastener Row Spacing
2 ft. 3 ft.
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 6 of 12
Membrane Type: Single Ply, PVC
Deck Type 1I: Wood, Insulated
Deck Description: 19/32" or greater plywood or wood plank
System Type C(2): All layers of insulation simultaneously fastened; membrane adhered
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are not approved
and shall not be installed unless said accessories demonstrate compliance with prescriptive Florida Building
Code requirements and are field fabricated utilizing the approved membranes listed in Table 1.
Fire Barrier: Minimum'/2" DensDeck or DensDeck Prime
leOneor more layers of any of the following insulations:
Base Insulation Laver:
Sarnatherm, H-Shield
Minimum 1.5" thick
Insulation Fasteners
able 3
N/A
Fastener Density/ft'
N/A
Note: All layers shall be simultaneously fastened; see top layer below for fasteners and density. Insulation panels
listed are minimum sizes and dimensions; if larger panels are used, the number of fasteners shall be increased
maintaining the same fastener density. Please refer to Roofing Application Standard RAS 117 for insulation
attachment.
Top Insulation Laver (Optional): Insulation Fasteners Fastener Density/ft2
Table 3
Sarnatherm, H-Shield
Minimum 1.5" thick 6, 10, 14,16 See Design Pressure
Note: Insulation panels listed are minimum sizes and dimensions; if larger panels are used, the number of
fasteners shall be increased maintaining the same fastener density. Please refer to Roofing Application Standard
RAS 117 for insulation attachment.
Membrane: Sikaplan Fastened bonded to Sikaplan RhinoBond Disc, Sarnadisc RhinoBond with
RhinoBond Plate bonding tool at 6 seconds per plate so the tool reaches 400°F. Minimum 3"
wide side lap is sealed with a minimum %" wide heat weld.
Maximum Design Maximum Pressure
Pressures: -45 psf
(See General Limitation #7)
Fastener Spacing Fastener Row Spacing
2 ft. 3 ft.
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 7 of 12
Membrane Type: Single Ply, PVC
Deck Type 1I: Wood, Insulated
Deck Description: Min. nominal 3/a" APA rated CDX plywood or wood plank at 2 ft spans, attached with 8d ring
shank nails 6" o.c.
System Type C(3): Insulation layer fastened through the deck, membrane adhered
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are not approved
and shall not be installed unless said accessories demonstrate compliance with prescriptive Florida Building
• Code requirements and are field fabricated utilizing the approved membranes listed in Table 1.
1
One or more layers of any of the following insulations:
Insulation Layer:
DensDeck Prime
Minimum: 1/2" Thick
Insulation Fasteners Fastener
Table 3 Density/ft'
1 (#12), 2, 3 & 11 1:1.6 ft'
Note: Insulation Layer shall be fastened to the deck; see top layer below for fasteners and density Insulation
panels listed are minimum sizes and dimensions; if larger panels are used the number of fasteners per board
shall be increased maintaining the same fastener density (See Roofing Application RAS 117 for fastener details).
Membrane: Sarnafil G410, G410 Textured, adhered with 2170 VC in a contact -application at a rate of
0.75 — 2.0 gal/sq. to the insulation and 0.5 gal/sq. to the membrane backside. The roof cover
is immediately placed into the adhesive and the top surface rolled with a weighted roller.
Minimum 3" wide side lap is sealed with a 1.5" wide heat weld.
Maximum Design
Pressure: -67.5 psf (See General Limitation #7)
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 8 of 12
Membrane Type: Single Ply, PVC
Deck Type 1I: Wood, Insulated
Deck Description: Min. nominal %" APA rated CDX plywood or wood plank at 2 ft spans, attached with 8d ring
shank nails 6" o.c.
System Type C(4): Insulation layer fastened through the deck, membrane adhered
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are not approved
and shall not be installed unless said accessories demonstrate compliance with prescriptive Florida Building
• Code requirements and are field fabricated utilizing the approved membranes listed in Table 1.
One or more layers of any of the following insulations:
r
Insulation Laver:
DensDeck Prime
Minimum: 1/2" Thick
Insulation Fasteners Fastener
able 3 Density/ft2
1 (#12), 2,3 & 11 1:1.6 ft2
Note: Insulation panels listed are minimum sizes and dimensions; if larger panels are used the number of
fasteners per board shall be increased maintaining the same fastener density (See Roofing Application RAS 117
for fastener details).
Membrane: Sikaplan Adhered with Sarnacol 2170 VC in a contact -application at a rate of 0.75 — 2.0
gal/sq. to the insulation and 0.5 gal/sq. to the membrane backside. The roof cover is
immediately placed into the adhesive and the top surface rolled with a weighted roller.
Minimum 3" wide side lap is sealed with a 1.5" wide heat weld.
Maximum Design
Pressure: -67.5 psf (See General Limitation #7)
NOA No.: 20-0825.09
M ;I EC Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 9 of 12
Membrane Type: Single Ply, PVC
Deck Type 1I: Wood, Insulated
Deck Description: 15/32" or greater plywood or wood plank at 2 ft spans, attached with 2 3/s" ring shank
nails 6" o.c.
System Type D(1): Membrane attached over preliminary fastened insulation.
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are not approved
and shall not be installed unless said accessories demonstrate compliance with prescriptive Florida Building
' Code requirements and are field fabricated utilizing the approved membranes listed in Table 1.
r Fire Barrier: Minimum 1/4" DensDeck Prime, loose -laid.
Membrane: Sikaplan Fastened (min. 60 mil) attached to deck as specified below.
Fastening: Sikaplan Fastener #14, OMG Heavy Duty fasteners with Sikaplan Disc or OMG Eyehook
Accuseam Plates spaced 12" o.c. within the 5.5" side lap spaced 54.5" o.c. and sealed with
a minimum 1.5" weld.
Maximum Design
Pressure: -45 psf (See General Limitation #7)
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 10 of 12
Membrane Type: Single Ply, PVC
Deck Type 1I: Wood, Insulated
Deck Description: 15/32" or greater plywood or wood plank at 2 ft spans, attached with 2 3/s" ring shank
nails 6" o.c.
System Type D(2): Membrane attached over preliminary fastened insulation.
All General and System Limitations apply. Roof accessories not listed in Table 1 of this NOA are not approved
and shall not be installed unless said accessories demonstrate compliance with prescriptive Florida Building
Code requirements and are field fabricated utilizing the approved membranes listed in Table 1.
Fire Barrier: Minimum 1/4" DensDeck Prime, loose -laid.
Membrane: Sikaplan Fastened (min. 60 mil) attached to deck as specified below.
Fastening: Sikaplan Fastener #14, OMG Heavy Duty fasteners with Sikaplan Disc or OMG Eyehook
Accuseam Plates spaced 6" o.c. within the 5.5" side lap spaced 54.5" o.c. and sealed with a
minimum 1.5" weld.
Maximum Design
Pressure: -75 psf (See General Limitation #7)
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 11 of 12
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with Product Control
Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied within the
EVT range and at a rate of 20-40 lbs./sq., or mechanically attached using the fastening pattern of the top layer.
3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved asphalt, panel size shall
be 4' x 4' maximum.
,�4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam insulations
when the base sheet is fully mopped. If no recovery board is used the base sheet shall be applied using spot mopping
with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8" ribbons in three rows, one at each side lap
It and one down the center of the sheet allowing a continuous area of ventilation. Encircling of the strips is not
acceptable. A 6" break shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt application of
either system shall be at a minimum rate of 121bs./sq.
Note: Spot attached systems shall be limited to a maximum design pressure of -45 psf.
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force (F') value of 2751bf., as
tested in compliance with Testing Application Standard TAS 105. If the fastener value, as field-tested, are below
2751bf. Insulation attachment shall not be acceptable.
6. Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based on a minimum
fastener resistance value in conjunction with the maximum design value listed within a specific system. Should the
fastener resistance be less than that required, as determined by the Building Official, a revised fastener spacing,
prepared, signed and sealed by a Florida registered Professional Engineer, Registered Architect, or Registered Roof
Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal resistance value taken from
Testing Application Standards TAS 105 and calculations in compliance with Roofing Application Standard RAS
117.
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas. Fastener
densities shall be increased for both insulation and base sheet as calculated in compliance with Roofing Application
Standard RAS 117 and/or RAS 137. Calculations prepared, signed and sealed by a Florida registered Professional
Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is specifically referred within
this NOA, General Limitation #9 will not be applicable.)
8. All attachment and sizing of perimeter nailers, metal profile, and/or flashing termination designs shall conform to
Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e. field, perimeters,
and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at enhanced
pressure zones (i.e. perimeters, extended comers and corners). (When this limitation is specifically referred
within this NOA, General Limitation #7 will not be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 20-0825.09
Expiration Date: 08/02/26
Approval Date: 03/04/21
Page 12 of 12