Field Density Tests of Compacted Soils Method D-6938
Client: Mel-Ry Construction Date: December 16, 2014
Address: 10967 S. Ocean Drive, Jensen Beach, FL 34957 Order #: ; ; 14-3500
Project: Proposed Single Family Home Permit
Address: 2019 Nettles Blvd.,.Jensen Beach, FL Tech:
Area Tested: Building Pad Compaction Req.:
CO
95%
Material Type: Light Brown Sand Proctor Method: ASTM D-1557
Test
#
TEST LOCATION
Probe
Depth
Elev.
Moist
%
Dry
Density
PCF
Proctor
Value
PCF
Optimum
Moisture
%
Compaction
Pass
1
IN.E. Corner of Footing
12"
SG
6.3
99.1
103.0
12.0
96.2%
Yes
2
Center of Pad
12"
SG
9.7
106.4
103.0
1 12.0
103.3%
Yes
3
S.W. Corner of Footing
12"
SG
7.8
98.9
103.0.
12.0
96.0%
Yes
4
5
6
7
8
9
10
11
12
13
14
Remarks: See Reverse Side (Page 2 of 2) for Disclaimer 4
This is a Compaction Test only on the top 12" of the pad and is not a verif6tlon of So'ij F e3ri g Capacity.
Legend for Elevation:
PR = Proofroll
1,2,3'=.1st, 2nd, 3rd Lift
SL = Springline
FL = Final Lift
SG = Subgrade
BG = Below Grade
BC = Basecourse
BOF = Bottom of Footing
TOP = Top of Pipe
FG = Finished Grade
Submitted by:
r
KEITH LEBLANG
Professional,Engineer #59394 iZ/7/1Y
Cert; of Authorization #547,
State/.of Florida:,
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of,cliehts, and authohza'idn for publication of statements,
egre
conclusions or extracts from or regarding our reports is reserved pending our written approval. A density test determines the de of compaction of the tested layer of material
only. A density does not replace a soil bearing capacity determination. After laying dormant for a period of 90 days or after heavy rain/storms, retesting must be performed on
this work.
PAGE 1 of.2
Compacted Soils Method D-6938 Disclaimer
Pursuant to your request, Federal Engineering & Testing, Inc. (FET) has performed a compaction test at the referenced
project on the reverse side." The- pU rpose of our test was to determine the degree of compaction of the tested layer of
material only. In no way shall a compaction test replace a soil bearing capacity determination. A soil boring test must be
performed by the client.prior to construction to verify subsoil conditions. Our scope of services only included testing the top
12" of added fill material. FET was not contracted to perform supervision of the building pad preparation. This testing of the
added fill material does not include an analysis of the underlying soil materials to determine if they are capable of supporting
the proposed structure without settlement. This density compaction test does not warranty any underlying soil materials or
conditions below the tested top 12 inches of material. If no soil borings have been performed in the location of the proposed
structure, we recommend performing soil borings below all foundation areas of the proposed structure to verify the underlying
soil conditions.
Environmental analysis of the soil materials is not part. of the scope of services. If environmental analysis of the soils is
required, we can provide a proposal for performing an environmental analysis of the soil materials. The scope of services is
for determination of the degree of compaction of the tested layer of material only. No other analysis is implied or warranted.
Job project specifications were not available at the time the work was performed. Determination of the pass/fail compaction
results are based on current common industry requirements of 95% of the ASTM D-1557 standard for building foundations
and 98% of the AASHTO T-180 standard for paved areas such as roadways and parking lots. If different specifications are
required, Federal Engineering & Testing, Inc. shall be notified.
Our findings are relative to the date and areas of our site work and should not be relied upon to represent conditions on other
areas or dates. Any subsequent site disturbances due to water erosion, rain waters, construction activities, utility or footing
excavations, overgrown vegetation, traffic and other disturbances will void this test and the site must be re -compacted and re-
tested prior to construction.
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of our client
and authorization for use, publication of statements, conclusions or extracts from or regarding our reports is reserved
pending our written approval.
It has been a pleasure working with you and we look forward to doing so in the near future.
Page 2 of 2
Phone 954-784 2941
eder-a 800-848.1919
Fax 954-784-7875
& TESTING INC. www.fed-eng.com
250 SW 13th Ave Pompano Beach, FL 33069
Field Density Tests of Compacted Soils Method D-6938
Client: Mel-Ry Construction Date: December 12, 2014
Address: 10967 S. Ocean Drive; Jensen Beach, FL 34957 Order #: 14-3476
Project: Proposed Single Family Home Permit 9.4-
Address: 2019 Nettles Blvd., Jensen Beach, FL Tech:
Area Tested: Footing for Building Pad Compaction Req.:
AM
95%
Material Type: Light Brown Sand w/Some Rock Proctor.Method: ASTM D-1557
Test
#
...TEST LOCATION
Probe
Depth
p
Elev.
Moist
oho::
Dry
Density•
PCF
Proctor
Value:.
PCF
Optimum
Moisture
%
Compaction.-
Pass
1
N.E. Comer of Footing
12"
BOF
7.2
108.6
110.5
10.0
98.3%
Yes
2
IS.W. Comer of Footing
12"
BOF
1 5.1
109.1
1 110.5
10.0
98.7%
Yes
3
S.E. Comer of Footing
12"
BOF
5.8
109.6
110.5
10.0'
99.2%
Yes
4
-.
5
7
8
9
10
11
12
13
14
Remarks: See Reverse Side (Page 2 of 2) for Disclaimer r
This is a Compaction Test only on the top 12" of the pad and is not a .verification of Soil-13ear1ng Capacity.
Legend for Elevation:
PR = Proofroll 1,2,3 = 1st, 2nd, 3rd Lift
Submitted by:
SL = Springline FL = Final Lift " -KEITH LEBLANC -
SG = Subgrade BG = Below Grade Professional Engineer #59394
BC = Basecourse BOF = Bottom of Footing •Cert. of Authorization #5471'
TOP = Top of Pipe FG = Finished Grade Stafe of F!ori�a
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential prope11
rty of clients, 'and authorization for publication of statements,
conclusions or extracts from or regarding our reports is reserved pending our written approval. A density test determines the'degree &,compaction of the tested layer of material
only. A density does not replace a soil bearing capacity determination. After laying dormant for a period of 90 days or after heavy rain/storms, retesting must be performed on
this work.
PAGE 1 of 2
9
Compacted Soils Method D-6938 Disclaimer
Pursuant to your request, Federal Engineering & Testing, Inc. (FET) has performed a compaction test at the referenced
project on the reverse side. The purpose of our test was to determine the degree of compaction of the tested layer of
material only. In no way shall a compaction test replace a soil bearing capacity determination. A soil boring test must be
performed by the client prior to construction to verify subsoil conditions. Our scope of services only included testing the top
12" of added fill material. FET was not contracted to perform supervision of the building pad preparation. This testing of the
added fill material does not include an analysis of the underlying soil materials to determine if they are capable of supporting
the proposed structure without settlement. This density compaction test does not warranty any underlying soil materials or
conditions below the tested top 12 inches of material. If no soil borings have been performed in the location of the proposed
structure, we recommend performing soil borings below all foundation areas of the proposed structure to verify the underlying
soil conditions.
Environmental analysis of the soil materials is not- part of the scope of .services. If environmental .analysis of the soils is
required, we can provide a proposal for performing an environmental analysis of the soil materials. The scope of services is
for determination of the degree of compaction of the tested layer of material only. No other analysis is implied or warranted.
Job project specifications were not available at the time the work was performed. Determination of the pass/fail compaction
results are based on current common industry requirements of 95% of the ASTIVI D-1557 standard for building foundations
and 98% of the AASHTO T-180 standard for paved areas such as roadways and parking lots. If different specifications are
required, Federal Engineering & Testing, Inc. shall be notified.
Our findings are relative to the date and areas of our site work and should not be relied upon to represent conditions on other
areas or dates. Any subsequent site disturbances due to water erosion, rain waters, construction activities, utility or footing
excavations, overgrown vegetation, traffic and other disturbances will void this test and the site must be re -compacted and re-
tested prior to construction.