HomeMy WebLinkAboutEnergy Efficiency CodeFORM R405-2014 I RECEI f . _s 0 2015 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: SYNDER RESIDENCE Builder Name: Street: LOT 515 NETTLES ISLAND Permit Office: City, State, Zip: JENSEN BEACH, FL, Permit Number: Owner: Jurisdiction: Design Location: FL, Fort Pierce 1. New construction or existing New (From Plans) 9. Wall Types (1069.3 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Frame - Wood, Exterior R=19.0 1069.30 ft2 b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 2 d. N/A R= ft2 5. Is this a worst case? No 10. Ceiling Types (1041.0 sqft.) Insulation Area a. Under Attic (Vented) R=30.0 1041.00 ft2 6. Conditioned floor area above grade (ft2) 1041 b. N/A R= ft2 Conditioned floor area below grade (ft2) 0 c. N/A R= ft2 11. Ducts R ft2 7. Windows(191.9 sqft.) Description Area a. U-Factor: Sgl, U=0.45 191.86 ft2 SHGC: SHGC=0.25 b. U-Factor: NIA fI2 12. Cooling systems kBtu/hr Efficiency SHGC: a. Central Unit 35.4 SEER:18.00 c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a. Electric Heat Pump 35.0 HSPF:9.00 SHGC: Area Weighted Average Overhang Depth: 2.000 ft. Area Weighted Average SHGC: 0.250 14. Hot water systems 8. Floor Types (1041.0 sqft.) Insulation Area a. Electric Cap: 40 gallons a. Raised Floor R=30.0 1041.00 ft2 b. Conservation features EF: 0.970 b. N/A R= ft2 None c. N/A R= ft2 15. Credits None Total Proposed Modified Loads: 32.95 Glass/Floor Area: 0.184 PASS Total Baseline Loads: 38.48 1 hereby certify that the plans and specifications covered by Review of the plans and STg�� this calculation are ' mpliance with the Florida Energy specifications covered by this 0V-tRE _4VOff, Code. calculation indicates compliance ��,,,''�'_,�� with the Florida Energy Code. ti rrr �� `=t=�;,';;.�• ��� rrr-- '�;�":.• n O PREPARED BY: Before construction is completedi� , •, DATE: this building will be inspected for compliance with Section 553.908 I hereby certify that this building, as designed, is in compliance Florida Statutes. with the Florida Energy Code, C0 WE OWNER/AGENT: BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.2.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage test report in accordance with R402.4.1.2. 0 10/29/2015 3:42 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software FORM R405-2014 PROJECT Title: Building Type: Owner: # of Units: Builder Name: Permit Office: Jurisdiction: Family Type: New/E)asting: Comment: SYNDER RESIDENCE Bedrooms: 2 User Conditioned Area: 1041 Total Stories: 1 1 Worst Case: No Rotate Angle: 0 Cross Ventilation: Whole House Fan: Single-family New (From Plans) Address Type: Lot # Block/SubDivision: PlatBook: Street: County: City, State, Zip: Street Address LOT 515 NETTLES ISL ST. LUCIE COUNTY JENSEN BEACH, FL, CLIMATE V Design Location IECC Design Temp TMY Site Zone 97.5 % 2.5 % Int Design Temp Heating Design Daily Temp Winter Summer Degree Days Moisture Range FL, Fort Pierce FL ST_LUCIE_CO_INTL 2 39 90 70 75 722 62 Low BLOCKS Number Name Area Volume 1 Blockl 1041 9369 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 Main 1041 9369 Yes 4 2 1 Yes Yes Yes FLOORS # Floor Type Space R-Value Area Tile Wood Carpet 1 Raised Floor Main ____ 1041 ft2 30 0 0 1 ROOF V # Type Roof Gable Roof Materials Area Area Color Solar Absor. SA Emift Tested Emit Deck Pitch Tested Insul. (deg) 1 Hip Metal 1128 ft2 0 ft2 Light 0.6 No 0.9 No 0 22.6 ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Vented 300 1041 ft2 N N CEILING # Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic (Vented) Main 30 1041 ft2 0.11 Wood 10/29/2015 3:42 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 4 FORM R405-2014 WALLS Adjacent TO VV211 Type1 Space Cavity Width Height Sheathing Framing Solar Below W Exterior Frame - Wood Main 19 20 8 5 168.3 ft2 0 0 0.75 0 2 N Exterior Frame - Wood Main 19 18 8 5 151.5 ft2 0 0 0.75 0 3 NE Exterior Frame - Wood Main 19 32 9 288.0 ft2 0 0 0.75 0 4 SE Exterior Frame - Wood Main 19 20 8 160.0 ft2 0 0 0.75 0 _ 5 SW Exterior Frame - Wood Main 19 24 8 192.0 ft2 0 0 0.75 0 6 S Exterior Frame - Wood Main 19 13 8 5 109.4 ft2 0 0 0.75 0 DOORS # Omt Door Type Space Storms U-Value Width Height Area Ft In Ft In 1 NE Insulated Main Metal .28 3 8 24 ft2 2 S Insulated Main Metal .28 3 6 8 20 ft2 WINDOWS Orientation shown is the entered, Proposed orientation. Wall Overhang y # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 N 2 TIM Low-E Single Yes 0.45 0.25 30.0 ft2 2 ft 0 in 3 ft 0 in Drapes/blinds None 2 NE 3 TIM Low-E Single Yes 0.45 0.25 25.0 ft2 2 ft 0 in 3 ft 0 in Drapes/blinds None 3 NE 3 TIM Low-E Single Yes 0.45 0.25 80.0 ftz 2 ft 0 in 3 ft 0 in Drapes/blinds None 4 NE 3 TIM Low-E Single Yes 0.45 0.25 12.0 ft2 2 ft 0 in 3 ft 0 in Drapes/blinds None 5 SE 4 TIM Low-E Single Yes 0.45 0.25 21.0 ft2 2 ft 0 in 3 ft 0 in Drapes/blinds None 6 SW 5 TIM Low-E Single Yes 0.45 0.25 16.4 ft2 2 ft 0 in 3 ft 0 in Drapes/blinds None 7 S 6 TIM Low-E Single Yes 0.45 0.25 7.5 ft2 2 ft 0 in 3 ft 0 in Drapes/blinds None INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Proposed ACH(50) .000286 780.8 42.86 80.61 .2087 5 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Heat Pump None HSPF:9 35 kBtu/hr 1 Ductless COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit None SEER: 18 35.4 kBtu/hr 1062 cfm 0.8 1 Ductless 10/29/2015 3:42 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 4 FORM R405-2014 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric None Main 0.97 40 gal 50 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model # Collector Model # Area Volume FEF None None ftz TEMPERATURES Programable Thermostat: None Ceiling Fans: Heating Jan Feb Feb Mar Apr Apr May Jun May rlr rl Jul Mugug rl Sep Oct Nov Dec Jan Feb X X Mar Jun Jul Sep Oct LXl Nov DecVenting Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (VVD) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 10/29/2015 3:42 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 4 FORM R405-2014 TABLE 402.4.1. AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: SYNDER RESIDENCE Builder Name: Street: LOT 515 NETTLES ISLAND Permit Office: City, State, Zip: JENSEN BEACH, FL, Permit Number: Owner: Jurisdiction: Design Location: FL, Fort Pierce COMPONENT CRITERIA CHECK Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope. Exterior thermal envelope contains a continuous barrier. Breaks or joints in the air barrier shall be sealed. Air -permeable insulation shall not be used as a sealing material. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Comers and headers shall be insulated and the junction of the foundation Walls and sill plate shall be sealed. The junction of the top plate and the top or exterior walls shall be sealed. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Knee walls shall be sealed. Windows, skylights and doors The space between window/door jambs and framing and skylights and framing shall be sealed. Rim joists Rim joists are insulated and include an air barrier. Floors (including above -garage Insulation shall be installed to maintain permanent contact with underside and cantilevered floors) of subfloor decking. The air barrier shall be installed at any exposed edge of insulation. Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or unconditioned space shall be sealed. Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be airtight, IC rated, and sealed to the drywall. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air barrier installed separating them from the showers and tubs. Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or air sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Idil Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shallftl LV_ gasketed doors 10/29/2015 3:43 PM EnergyGauge® USA - FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1 FORM R405-2014 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 86 The lower the EnergyPerformance Index, the more efficient the home. LOT 515 NETTLES ISLAND, JENSEN BEACH, FL, 1. New construction or existing New (From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a. Frame - Wood, Exterior R=19.0 1069.30 ft2 b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 2 d. N/A R= ft2 5. Is this a worst case? No 10. Ceiling Types Insulation Area a. Under Attic (Vented) R=30.0 1041.00 ftz 6. Conditioned floor area (ft2) 1041 b. N/A R= ft2 7. Windows— Description Area c. N/A R= ft2 a. U-Factor: Sgl, U=0.45 191.86 ft2 11. Ducts R ft2 SHGC: SHGC=0.25 b. U-Factor: N/A ft2 SHGC: 12. Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a. Central Unit 35.4 SEER:18.00 SHGC: d. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency Area Weighted Average Overhang Depth: 2.000 ft. a. Electric Heat Pump 35.0 HSPF:9.00 Area Weighted Average SHGC: 0.250 8. Floor Types Insulation Area 14. Hot water systems a. Raised Floor R=30.0 1041.00 ft2 a. Electric Cap: 40 gallons b. N/A R= ft2 EF: 0.97 c. N/A R= ft2 b. Conservation features None 15. Credits None I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. . Builder Signature: Address of New Home: Date: City/FL Zip: 0FTHft ST.gTFoe 0 goo SEE - WE ��y *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 10/29/2015 3:42 PM EnergyGauge® USA - FlaRes2014 -Section R405.4.1 Compliant Software FILE COPY -- wrightsofte Project Summary Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUIO<CALCS@AOL.COM For. SNYDER RESIDENCE LOT 515 NETTLES ISLAND, JENSEN BEACH, FL Notes: Weather. Fort Pierce, FL, US Job: Date: Sep 23, 2016 By: • Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19001 Btuh Structure 17740 Btuh Ducts 4904 Btuh Ducts 7403 Btuh Central vent (21 cfm) 642 Btuh Central vent (21 cfm) 344 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24548 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 24213 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1671 Btuh Ducts 1996 Btuh Heating Cooling Central vent (21 cfm) 872 Btuh Area (ft2) 1041 1041 Equipment latent load 4538 Btuh Volume (ft$) 10433 10433 Air changes/hour 0.45 0.23 Equipment total load 28751 Btuh Equiv. AVF (cfm) 78 40 Req. total capacity at 0.70 SHR 2.9 ton ' Heating Equipment Summary Cooling Equipment Summary Make MITSUBISHI Make MITSUBISHI Trade Trade Model MXZ4B36NA1 Cond MXZ4B36NA1 AHRI ref Coil (4) MSZGE09NA8 AHRI ref Efficiency 9.3 HSPF Efficiency 9.4 EER, 18 SEER Heating input Sensible cooling 24780 Btuh Heating output 34000 Btuh @ 47°F Latent cooling 10620 Btuh Temperature rise 27 OF Total cooling 35400 Btuh Actual airflow 1167 cfm Actual airflow 1167 cfm Air flow factor 0.049 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.85 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. .Qt— wri htsoftm r 9 RightSuite® Universal 2015 15.0.19 RSU08101 2 . IL FlC.&...serslQuickCalcs1Documents\SNYDER RESIDENCE.rup Calc= MJ8 Front Doorfaces: N F 1 - wrightsoft° Right-M Worksheet Job: Entire House Date: Sep 23, 2015 QUICK CALCS, INC. By. 317 ST. LUGE LN., FT. PIERCE, FL34946 Phone: 772-466-6799 Fax 772-4666796 Email: QUICICCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 208.9 ft 27.0 ft 3 Room height 9.9 ft d 8.5 ft heat/cool 4 5 Room dimensions Room area 1052.1 ft2 1.0 x 155.0 ft 155.0 W Ty Construction U-value Or HTM Area (W) Load Area (" Load number (Btuh/ft2-°F) (Btuh/ft`) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12E-Osw 0:068 n 1.96 - 1.35 171 171 326 ' 232 119 119 227 161 W 12E-0sw 0.068 ne 1.90 1.35 102 102 194 138 0 0 0. 0 t. 12E-0sw 0.068 _ a 1.90 . 1.35 165 135 256 ' 182 1111, 81 153 109 -G 1A-c1om 1.270 a 35.56 , .91.12 30 0 1067 2734 30 0 1067 2734 11 12E-0sw 0.068 se 1.90 1.35 639 493 939 668 0 0 0 0 1A-c1om 1.270 se 35.56 70.95 10 0 341 681 0 0 0 0 IA-clom 1.270 se 35.56 70.95 6 0 204 408 0 0 0 0 1Aclom 1.270 se 35.56 70.95 25 0 889 1774 0 0 0 0 1A-clomd 1.270 se 35.56 34.10 79 0 2821 2705 0 0 0 0 11DO 0.390 se 10.92 11.31 26 26 280 290 0 0 0 0 W 12E-0sw 0.068 s 1.90 1.35 40 40 76 -54 0 ". 0 :. 0 0 0.068 sw 1.90 1.35 237 211 401 285 0 _ .. 0 0 0 1A-clom 1.270 sw 35.56 70.95 6 0 213 426 0 0 0 0 N12E-Osw 1Aclom 1.270 sw 35.56 70.95 13 0 444 887 0 0 0 0 1Aclom 1.270 sw 35.56 70.95 8 0 277 553 0 0 0 0 12E-Osw 1Aclom 0.068 1.270 w w 1.90 35.56 1.35 91.12 131 6 104 0 198 213.. 141 547 0 0 _ 0 0 0 0 0 0 11 DO 0.390 w 10:92 . 11.31 21 21 229 238 0 0 0 0 V�I 12E-Osw 0.068 nw 1.90 1.35 503 476 906 644 0 0 0 0 1A-c1om 1.270 nw 35.56 70.43 13 0 455 901 0 0 0 0 IA-clom 1.270, nw 35.56 70.43 15 0 519 1027 0 0 0 0 c 16BSOmd 0.032 - 0.90 ' 1.68 933 933 836 1567, 155 _ 155 139 260 F 22A-tpl 0.989 - 27.69 0.00 936 163 4506 0 155 27 748 0 6 c) AED mcursion 0 -152 Envelopeloss/gain 16593 17081 2333 3112 12 a) Infiltration 2408 659 276 76 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 19001 17740 2611 3188 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19001 17740 2611 3188 15 Duct loads 26% 42% 4904 7403 26% 42% 674 1330 Total room load 23W6 25143 3285 4518 Air required (cfm) 1167 1167 160 210 Calculations approved byACCAto meet all requirements of Manual wrightsoft- RightSuite® Universal 2015 15.0.19 RSU08101 ACCF' ... serslQuick Calcs\DocumentslSNYDER RESIDENCE.rup Calo = MJ8 Front Door faces: N 9 15:47:07 COPY Page 1 - - wrightsoft° Right-M Worksheet Job: Entire House Date: Sep 23, 2015 QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL34946 Phone: 772-466-6799 Fax 772-466.6796 Email: QUICKCALCS@ADL.COM 1 Room name M. BATH LIVING 2 Exposed wall 14.0 ft 16.8 ft 3 Room height 8.5 ft heaticool 9.0 ft heat/cool 4 Room dimensions 1.0 x 60.0 ft 1.0 x 109.0 ft 5 Room area 60.0 ftz 109.0 ft' Ty Construction U-value Or HTM Area (ft) Load Area (ft� Load number (Btuh/ft-F) (13tuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12E-Osw 0.068 ' n •. 1c90 ' ': 1.35 51 51 97 69 0 0 0 0 W 12E-Osw 0.068 ne 1.90 1.35 0 0 0 0 0 0 0 0 1�J 12E-Osw 0.068 a 1.90 1':35 0, 0 0 0 54 54' 103 73 ' G 1A-clom 1.270 'e 35.56 91.12 0 0 0 0 0 0 0 0 11 12E-Osw 0.068 se 1.90 1.35 0 0 0 0 78 53 101 71 1A-clom 1.270 se 35.56 70.95 0 0 0 0 0 0 0 0 1A-clom 1.270 se 35.56 70.95 0 0 0 0 0 0 0 0 1Aclom 1.270 se 35.56 70.95 0 0 0 0 25 0 889 1774 1A-clomd 1.270 se 35.56 34.10 0 0 0 0 0 0 0 0 11 DO 0.390 se 10.92 11.31 0 0 0 0 0 0 0 W _ 12E-Osw, 0.068 s 1.90 1.35 0 0 0 0 _0 0 0 , ,. 0 0 VVV���lll 12E-Osw 0.068 sw 1.90 _._, 1.35 0 0 0 0 19 19 37 26 1A-clom 1.270 sw 35.56 70.95 0 0 0 0 0 0 0 0 1Aclam 1.270 sw 35.56 70.95 0 0 0 0 0 0 0 0 1A-clom 1.270 sw 35.56 70.95 0 0 0 0 0 0 0 0 12E-Osw 01068 'w 1t90 1.35 68 62 118 84 0 ,' 0 0 0 1A-clom 1:270 •w 35.56 91.12 6 0 213 547 0 0:. 0 0 11 D0 0.390 w 10.92 11.31 0 0 0 0 0 0 0 0 12E-Osw 0068 . nw 1.90 1.35 0 0 0 0 0 0 0 0 Ti 1A-clom 1.270 nw 35.56 70.43 0 0 0 0 0 0 0 0 1A-clom 1.270 nw 35.56 70.43 0 0 0 0 0 0 0 0 C 16B-30md 0.032 - 0:90 1.68 60 60 .54 101 109 109. 98 183 F 22A-tpl 0.989 - 27.69 0.00 60 14 388 0 109 17 464 0 6 c) AED wcursion 106 229 Envelope loss/gain 870 9061 1690 2357 12 a) Infiltration b) Room ventilation 144 0 39 0 183 0 50 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1014 946 1873 2407 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1014 946 1873 2407 15 Duct loads 26% 42% 262 395 26% 42% 483 1004 Total room load 1276 1340 2357 3411 Air required (cfm) 62 62 115 158 rACCAto meet all requirements of Manual J 8th 4C= -� wrightsOft' RightSuite® Universal 2015 15.0.19 RSU08101 ..sers\QuickCalcs\Documents\SNYDERRESIDENCE.rup Calc=MJ8 Front Doorfaoes: -1- wrightsoft, Right-M) Worksheet Job: Entire House Bate: Sep 23, 2015 By. QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL34946 Phone: 772-466-6799 Fax 772-4668796 Email: QUICKCALCS@AOL.COM 1 Room name GREAT ROOM STUDIO/BED 2 Exposed wall 27.7 ft 31.3 ft 3 Room height 16.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 198.2 ft 1.0 x 141.8 ft 5 Room area 198.2 ft2 141.8 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2 °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/PIS Heat Cool Gross N/P/S Heat Cool 6 W 12E-0sw 0.068 ' n 1.90 1.35 0 0 0 0 -1 1 3 2 W 12E-0sw 0.068 ne 1.90 1.35 14 14 27 19 24 24 46 33 W 12E-0sw 0.068 a 1.90 1.35 0 0 0 0 0 0 0 .0 --G IA-c1om 1:270 a 35.56 91.12 0 0 0 0 0 0 0 0 11 12E-0sw 0.068 se 1.90 1.35 273 193 368 262 78 78 149 106 1Aclom 1.270 se 35.56 70.95 0 0 0 0 0 0 0 0 1Aclom 1.270 se 35.56 70.95 0 0 0 0 0 0 0 0 N 1Aclom 1.270 se 35.56 70.95 0 0 0 0 0 0 0 0 1Aclomd 1.270 se 35.56 34.10 79 0 2821 2705 0 0 0 0 11 D0 0.390 se 10.92 11.31 0 0 0 0. 0. 0 0 0 W 12E-Nw 0.068 s ' 1.90 . 1.35 _ 6 0 0' 0 0 . 0 „ , . 0 0 12E-0sw 0.068 sw 1.90 1.35 0 0 0 0 34 34 65 46 1Aclam 1.270 sw 35.56 70.95 0 0 0 0 0 0 0 0 1Aclom 1.270 sw 35.56 70.95 0 0 0 0 0 0 0 0 1A-clom 1.270 sw 35.56 70.95 0 0 0 0 0 0 0 0 12E-0sw 6.068 w 1.90 1.35 O 0 0 0 0 0 0 0 1A-clom 1.270 w 35.56 91.12 0 0 0 0 0 0 0 0 11 D0 0.390 w, 10,92 11.31 0 0 0 0 0 0 0 0 �j 12E-0sw 0.068 nw 1.90 1.35 156 156 298 211 113 99 188 133 I- 1Aclom 1.270 nw 35.56 70.43 0 0 0 0 0 0 0 0 �2 1Aclom 1.270 nw 35.56 70.43 0 0 0 0 15 0 519 1027 C 16B30md 0.032 - '0.90 1.68 191 191 171 321 57 ..57 51 96 F 22A tpl 0.989 - 27.69 0.00 198 28 766 0 142 31 868 0 6 c) AE D wcursion 32 109 Envelope loss/gain 4451 3487 1887 1552 12 a) Infiltration 537 147 304 83 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 4988 3634 2191 1635 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4988 3634 2191 1635 15 Duct loads 26% 42% 1287 1516 26% 42% 566 682 Total room load 6275 5150 2757 2318 Air required (cfm) 306 239 1351108 Calculations to meet all reauirements of wrightsoft^ RightSuite@) Universal 2015 15.0.19 RSU08101 ��...sers\QuickCalcs\Documents\SNYDERRESIDENCE.rup Cale=MJ8 Front Door faces: N 2015-Oct-29 15:47:07 Page 3 - wrightsoftm Right-M Worksheet Job: Entire House Date: Sep 23, 2016 By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@POL.COM 1 Room name NTHCEN/DINING LOFT 2 Exposed wall 35.5 ft 49.7 ft 3 Room height 8.0 ft heaticool 9.0 ft heatf000l 4 Room dimensions 1.0 x 174.0 ft 1.0 x 125.0 ft 5 Room area 174.0 ft2 125.0 ft' Ty Construction number Ll-value (Btuh/ft;°F) Or HTM (Btuh/ft') Area (ft') or perimeter (ft) Load (Btuh) Area (ft� or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12E-0sw 0:068 ' n 1.90 1.35 0 0 0 0 0 0_ 0 0 11 w VN L--G 12E-Osw 12E-Osw IA-clom 12E-Osw IA-clom 1Aclom 0.068 0.068 1.270 0.068 1.270 1.270 ne a a se se se 1.90 1.90 35.56 1.90 35.56 35.56 1.35 1.35 91.12 1.35 70.95 70.95 0 0 . 0 57 0 6 0 0 0 25 0 0 0 0 0 48 0 204 0 .0 0_ 34 0 408 64 0 0. 153 10 0 64 0 0 144 0 0 121 0 0, 274 341 0 86 0 0 195 681 0 N 1Aclom 1.270 se 35.56 70.95 0 0 0 0 0 0 0 0 IA-clomd 11 DO 12E-Osw 12E-Osw 1Aclom 1.270 0.390 0.068 0.068 1.270 se se s sw sw 35.56 10.92 1.90, 1.90 35.56 34.10 11.31 1.35 1.35 70.95 0 26 40 114 6 0 26 40' 87 0 0 280 `. 76 166 213 0 290 54 118 426 0 0 0 70 0 0 0_ 0 70 0 0 0 0 134 0 0 0 0 95 0 w yyJJ (--G 1A-clom 1.270 sw 35.56 70.95 13 0 444 887 0 0 0 0 I�GG 1Aclom 1.270 sw 35.56 70.95 8 0 277 553 0 0 0 0 Val 12E-Osw 0.OW w 1.90 1.35 0 0 0 0 0 0 0 D �t_-3 G 1A,clom 11 DO 1.2.70 0.390 w w 35.56 10:92 91.12 11.31 0 0 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 V�J ;-G �G 12E-Osw 1Aclom IA-clom 16BS0md _ 0.068 1.270 1.270 0.032 nw nw nw - 1.90 35.56 35.56 0.90 1.35 70.43 70.43 1.68 74 0 0 146 74 0 0 146 140 0 0 131 100 0 0 245 160 13 0_ 125 147 0 0 126 281 455 0 112 200 901 0 210 C F 22A-tpl 0.989 - 27.69 0.00 174 36 9M 0 9 3 96 0 6 c) AED excursion 81 -280 Envelope loss/gain 2964 3197 1814 2088 12 a) Infiltration 344 94 542 148 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1 3308 3291 23561 2237 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3308 3291 2356 2237 15 Ductloads 26% 42% 854 1373 26% 42% 608 933 Total room load 4162 4664 2964 3170 Air required (cfm) 1 203 216 145 47 ILE CUR Calculations approved byACCAto meet all requirements of Manual J 8th wri htsoft- 2015-Oct-2915:47:07 9 RightSuite® Universal 2015 15.0.19 RSU08101 Page 4 ��...sers\Quick Calcs\Documents\SNYDERRESIDENCE.rup Cale =MJ8 Front Door faces: N - wrightsoft, Right-M Worksheet Job: Entire House Date: Sep 23, 2016 By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL 2 Exposed wall 7.0 ft 3 Room height 9.0 ft heat/cool 4 Room dimensions 1.0 x 89.2 ft 5 Room area 89.2 ft2 Ty Construction U-value Or HTM Area (ftz) Load Area Load number (Btuh/ftz-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12E-Osw 0.068 n 1.90 1.35 0 0 0 0 W 12E-Osw 0.068 ne 1.90 1.35 0 0 0 0 yI 12E-Osw 0.068 a 1.90 1.35 0 0 0 0 L--G IA-clom 1.270 a 35.56 01.12 0 0 0 0 11 12E-Osw 0.068 se 1.90 1.35 0 0 0 0 IA-clom 1.270 se 35.56 70.95 0 0 0 0 IA-clom 1.270 se 35.66 70.95 0 0 0 0 IA-clom 1.270 se 35.56 70.95 0 0 0 0 1A-clomd 1.270 se 35.56 34.10 0 0 0 0 11DO 0.390 se 0 0 0 0 W 12E90 _ .10.92 - .11.31 ! 1.350 0: 0, 0 VV��II 12E-Nw 0.068 sw 1.90 1.35 0 0 0 0 G 1A-clom 1.270 sw 35.56 70.95 0 0 0 0 1A-clom 1.270 sw 35.56 70.95 0 0 0 0 1Aclom 1.270 sw 35.56 70.95 0 0 0 0 V+J 12E-Osw 0.068 w 1.90 ,' 1.35 63 ' 42 80 57 �GD 1Ao1om 1.270. w. 35.56 91.12 0 0 0 0 11010 0.390 w 10.92 11.31 21 21 229 238 V+J 12E-Osw 0.068 nw 1.90 1.35 0 0 0 0 I�-CG 1Aclom 1.270 nw 35.56 70.43 0 0 0 0 1Aclom 1.270 nw 35.56 70.43 0 0 0 0 C 16B-30md 0.032 - 0.90 1.68 89 89 80 150 F 22A tpl 0.989 - 27.69 0.00 89 7 194 0 6 c) PE D excursion S1 Envelope loss/gain 583 383 12 a) Infiltration 76 21 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 659 404 Less extemal load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 659 404 15 Duct loads 26% 42% 170 169 Total room load 830 572 Air required (cfm) 40 27 Calculations approved byACCAto meet all requirements of Manual J 8th EEIVF COPI _ -114+ wrightsoft- RightSuite® Universal 2015 15.0.19 RSU08101 ACC" ... sers\QuickCalcs\Documents\SNYDERRESIDENCE.rup Calc=MJ8 FrontDoorfaces: N 2015-Oct-29 15:47:07 Page 5