Re: Pile Installation Inspection
Snyder Residence
515 Nettles Boulevard
Jensen Beach, Florida
KSM Project #: 161203-pile
Dear Mr. Snyder:
As requested, we were present during the installation. of Ahe.el.even .(1.1) auger -
cast -piles for the proposed structure at the referenced site. Pile layout by others.
The pile installation inspection was generally performed in accordance to the
"Inspector Guide to the Auger Cast -In -Place Piles", published by the Auger Cast -
In -Place Pile Committee of The Deep Foundation Institute.
Based on this inspection, it is our professional opinion, that the piles constructed
for the referenced project were installed as specified .on the construction
drawings. The pile documentation and Location Plan are attached. Please note
that pile 3 and 4 were relocated due to sewer main. The new locations of these
piles are reflected on the location plan.
We are pleased to be of assistance to you on this phase of your project.
have any questions, please feel free to contact the office.
..11111111N.-
If you
NOVEOCO'EIVIE
16 eon
BY:
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
KELLER, SCHLEICHER & MacWILLIAM ENGINEERING AND TESTING, INC.
MARTIN (772) 337-7755 PO, BOX 78-1377 SEBASTIAN FL 32978-1377 SEBASTIAN (772) 589-0712
PALM BEACH (561) 845-7445 www.ksmengineering.net MELBOURNE (321) 768-8488
FAX (561) 845-8876 E-Mail: KSM@KSMENGINEERING.NET ST. LUCIE (772) 229-9093
C.A.: 5693 FAX (772) 589-6469
Pile Installation Inspection
Snyder Residence
616 Nettles Boulevard
Jensen Beach, Florida
KSM Project #: 151203pile Date Installed: 11/09/2015
Pile Location
(See
Location
Plan)
Pile
Diameter
Pile
Length
Pile
Reinforcement
Pump
Strokes
Truck
No.
Time
Installed
Monday, November 9, 2015
1
14"
20'
See Note 3
27
173
9:38
2
99
Is
1926
173
9:47
3
99
9925
173
9:58
4
It
Is24
173
10:06
5
it
it24
173
10:15
6
9923
173
10:23
7
1924
173
10:35
8
it
At24
210
10:45
9
99
&124
210
10:55
10
it25
210
11:05
11
At27
210
11:15
Notes: 1. Pile Reinforcing: 6- #6 Vertical Bars Cont. with #3 Ties at 24" O.C.
2. Grout 28 Days Compression Strength = 5,000 PSI.
3. 1 Pump Stroke = 1.07 cu.ft. of Grout.
Ronald G. Keller, P.E.: 37293 / SI Lic. No.: 860 / Julie E. Keller, P.E.: 68366
I � 7
CMU STEM WALL (SEE SECTION
1'A5)
AUGER CAST CONCRETE PILING
P1
+:->s (SEE PILING NOTES SHEET Al >------------------
8 DETAIL 4-A6)1',, II II1`1 II Iiil K I
O 18' DIAMETER X 24' DEEP -- — —— �— . — . — . — . —
FOOTING W/ 4 #5 BARS r-- •-- • — � I
(SEE SECTION 1-A5)
6'x16' FEMA APPROVED FLOOD 3 12' DEEP x 24' WIDE 4
VENT (12' MAX. ABOVE GRADE) CONC.
® SPREAD
'I FTG/GRADE BM W/ 4
FLOOD VENT CALCULATIONS 875 Sp/FT(ENCLOSED) x 1 #5 REBAR CONT.
SQ/IN = 875 SQ/IN, REQUIRED.-13 B'x16'(1664 SQ/IN) I I
VENTS PROVIDED (OWNER/CONTRACTOR TO VERIFY
CLEAR OPENING OF SELECTED FLOOD VENTS MEETS THE I I I
MINIMUM REQUIREMENT) 8' CMU W/ 1 #5 VERT.
N I I REBAR @ 4'0' O.C. 8 1
#5 BAR CONT. IN TOP i
_ I COARSE. —FILL ALL
4,_0, I
P—O
CELLS SOLID
AG
I I I I
X \
\\ // /.
/ 10
2
` / 8' CMU W/ 1 #5 VERT. \'\ 8 / o
< REBAR @ 4'0' O.C. 8 1 /
#5 BAR CONT. IN TOP \
COARSE. —FILL ALL /
\ Y \ CELLS SOLID \ .\
\ '\ 12' DEEP x 24' WIDE
\ '\ �CONC, SPREAD / \ FTG/GRADE BM W/ 4 / �!
#5 REBAR CONT.
ti
/ O
,OT n2O /1
LOCATION OF PILES
PROJECT: Sn der Residence, 515 Nettles Boulevard, Jensen Beach, Florida
SHEET 1 OF 1IW V lk AN E N ENGIN ERI 0 DRAWN BY: J.L.
PERMIT #+ J AVL
AND TESTINGDESIGNED BY+J,K,PR❑JECT #+ 152203- DATE, 20151112
1 " Lq SCALE: NONE