HomeMy WebLinkAboutSite PlanSTRUCTURAL NOTES: CONCRETE: *SHALL MEET A MINIMUM COMPRESSIVE STRENGTH OF 3000PSI @ 28 DAYS. *SLUMPS SHALL BE 4" MIN AND 6" MAX. *MIN 3% AIR ENTRAINMENT. *MAX WATER/CEMENT RATIO OF 0.55. REINFORCING: *SHALL MEET ASTM STANDARDS FOR 60 GRADE. *ALL REINFORCING STEEL SPLICES SHALL BE LAPPED A MINIMUM 40 BAR DIAMETER ALL HOOKED REINFORCING BARS SHALL HAVE AN EXTENSION OF 12 BAR DIAMETERS BEYOND BEND. *ALL OUTER BARS IN FOOTERS SHALL HAVE CORNER BARS WITH A MINIMUM 40 BAR DIAMETER LAP. ALL FOOTER BARS SHALL HAVE A MIN. 3 CONC. COVER WHERE THE CONC. IS CAST AGAINST EARTH, OR 12" WHERE CONC. IS FORMED AND EXPOSED TO EITHER WEATHER OR EARTH. WOOD: *ALL LOAD BEARING STUDS TO BE: #2 SOUTHERN YELLOW PINE, #2 DOUGLAS FIR -LARCH, #2 SPRUCE -PINE -FIR, OR BETTER PILINi GENERF 1. ALL PI PILES, Z 0" LONC PILING ( 2. PRIOR THE AR( 2.1 2.2 2.3 2. PILIN( FROM D 3. GROU 4. REINF CONFOI INSTALI L ALL PI THE DE 2010 FL( 2. THE A HOLE A TO PRE' 3. CONT INSTAL] TESTIN( 1. PROV] YARDS( DAYS, C FUTURE GENI CONM SURVEY SETBAC LOCATI AND TR THE AR CONDII EIAZARI ANY OT POSITING DURIN( EXCAV) IMMED] ALL BE AREAS: MECHA BEEN L ADEQU SOIL BE BEFORE BE TER] (LOCATION T.B.D.) *ELECTRICAL CONTRACTOR SHALL COMPLY WITH 2O11 N.E.C. AND ALL OTHER APPLICABLE CODES. *ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS, RISER DIAGRAM, & ELECTRICAL PLAN & NOTIFY THE G.C. OF ANY ERRORS OR DISCREPENCES PRIOR TO INSTALLATION. *ELECRICAL CONTRACTOR IS TO SIZE BRANCH CIRCUITS. A MAXIMUM VOLTAGE DROP OF 3 PERCENT IS PERMITTED. *ALL OUTLETS, SWITCHES/DIMMERS, AND LIGHT FIXTURE LOCATIONS TO BE VERIFIED BY OWNER ON WALK-THRU WITH ELECTRICAL CONTRACTOR. *ALL DEVICES SHALL BE SMOOTH TYPE (WHITE) UNLESS OTHERWISE NOTED. *ALL RECEPTACLES INSTALLED OUTDOORS, BATHROOMS, GARAGE, LAUNDRY, AND KITCHENS TO HAVE GROUND FAULT CIRCUIT INTERRUPTER ALL OTHER RECEPTACLE LOCATIONS SHALL BE PROTECTED BY A LISTED ARC -FAULT CIRCUIT INTERRUPTER COMBINATION -TYPE, INSTALLED TO PROVIDE PROTECTION TO THE BRANCH CIRCUIT PER NEC 210.12(B). *PROVIDE/INSTALL TAMPER -RESISTANT RECEPTACLES IN ALL AREAS AS SPECIFIED BY NEC 210.52. *UNLESS OTHERWISE NOTED, MINIMUM SIZE WIRE SHALL BE #12 "AWG", EXCLUDING CONTROL WIRING. *VERIFY ALL CONDUCTORS AND BREAKERS W/ EQUIP. MANUR SPECS. *ALL ELEC. SWITCHES SHALL BE 48" A.F.F. AND ALL RECEPTACLES SHALL BE 12" A F.F. UNLESS OTHERWISE NOTED. *SMOKE DETECTORS TO BE INTERCONNECTED AND HARD -WIRED AND MEET ALL APPLICABLE LOCAL BUILDING CODES. *ELECTRICAL RECEPTACLES TO BE INSTALLED IN ALL ADDITIONAL LOCATIONS AS REQUIRED BY CODE EVEN IF NOT SHOWN ON THE DRAWINGS. *ALL ELECTRICAL DEVICES LOCATED IN NON -CONDITIONED SPACE TO BE OUTDOOR WEATHER RESISTANT RATED. ALL ELECTRICAL FIXTURES LOCATED IN NON-CONDITIONE. SPACE SHALL BE MARKED "SUITABLE FOR WET LOCATION" OR "SUITABLE FOR DAMP LOCATION". G A MICHIN AVE *CONTRACTOR TO VERIFY LOCATION OF ALL UTILITIES AVAILABLE AT SITE BEFORE PROCEEDING W/ CONSTRUCTION. *CONTRACTOR, SUBCONTRACTOR, MATERIAL SUPPLIER, ETC. SHALL MAKE THEMSELVES FAMILIAR WITH THE CONTRACT DOCUMENTS AND SHALL VERIFY ALL DIMENSIONS, CONDITIONS AT JOBSITE, PLANS, SPECIFICATIONS, ETC. AS APPLICABLE AND REPORT ANY DISCREPANCIES, ERRORS OR OMISSIONS TO THE ARCHITECT PRIOR TO ANY WORK BEING PERFORMED. OTHERWISE, THE ARCHITECT ASSUMES NO RESPONSIBILITY FOR ANY ERRORS AND THE CONTRACTOR, SUBCONTRACTOR, MATERIAL SUPPLIER, E7C. SHALL ASSUME FULL RESPONSIBILITY FOR ERRORS AND/OR DELAYS AND CORRECT THEM AT THEIR OWN EXPENSE. LANCE A VOGL SHALL NOT BE LIABLE FOR ANY LOSS, DAMAGE OR INCONVENIENCE ARISING FROM INACCURACIES. *THE ARCHITECT HAS NOT BEEN RETAINED FOR THE SUPERVISION OR THE ADMINISTRATION OF THE EXECUTION OF THE WORK OF THIS PROJECT. *EACH CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES FOR SAFETY PRECAUTIONS AND SHALL COMPLY WITH THE REQUIREMENTS OF O.S.H.A, APPLICABLE BUILDING CODES, AND ALL GOVERNMENTAL AGENCIES HAVING JURISDICTION. *EACH CONTRACTOR SHALL MAKE ALL ARRANGEMENTS FOR, OBTAIN AND PAY FOR ALL PERMITS, TESTS, INSPECTIONS, AND APPROVALS REQUIRED FOR HIS PORTION OF THE WORK. *CAULKING USING A ONE -PART URETHANE PRODUCT SHALL BE APPLIED AT ALL JUNCTIONS OF WALL AND WINDOW AND DOOR FRAMES WITH ABUTTING WALL SURFACES TO PROVIDE A WEATHERTIGHT, WATER-RESISTANT INSTALLATION. *DUROCK SHALL BE USED IN ALL WALL THE AND FLOOR TILE LOCATIONS OTHER THAN OVER CONCRETE. ALL GLASS AT SHOWERS/TUBS TO BE TEMPERED. *PROVIDE EGRESS WINDOW UNITS @ ALL NEW SLEEPING AREAS AS REQUIRED BY CODE. *CONTRACTOR(S) TO COORDINATE WALL BLOCKING REQUIREMENTS W/ CABINETRY AND SHELVING LOCATIONS. *ALL WOOD IN CONTACT WITH MASONRY TO BE PRESSURE TREATED SYP MEETING AWPA STANDARDS TO A MINIMUM 0.4 PCF RETENTION. ALL METAL CONNECTORS, NAILS, & SCREWS IN CONTACT WITH PRESSURE TREATED LUMBER SHALL BE HOT -DIPPED GALVANIZED AND CONFORM TO ASTM STANDARDS. *ALL EXTERIOR DOORS/WINDOWS IN LOCATIONS SUSCEPTABLE TO SOLAR HEAT GAIN SHALL BE A MIN. OF LOWE 240. *ALL WINDOW/DOOR DIMENSIONS ARE NOMINAL (*VERIFY ROUGH OPENINGS WITH MANUFACTURER) *REFER TO BUILDING PLANS & ELEVATIONS FOR DOOR/WINDOW TYPE & CONFIGURATION. *TNTP.RTYIR DOOR STYLE AND TRTM ST'YT.F, TO BF, VERIFIED BY OWNER. DOOR HARDWARE TO BE SELECTED BY OWNER _ _ _ _ _ _ _ _ _ *WALL AND CEILING FINISHES SHALL HAVE A SMOKE -DEVELOPED INDEX OF NOT GREATER THAN 450 PER 2014 FBC R302.9.3 *INSULATION MATERIALS, INCLUDING FACINGS, SUCH AS VAPOR RETARDERS AND VAPOR -PERMEABLE MEMBRANES INSTALLED WITHIN FLOOR/CEILING ASSEMBLIES, ROOF/CEILING ASSEMBLIES, WALL ASSEMBLIES, CRAWL SPACES AND ATTICS SHALL HAVE A FLAME SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING SMOKE -DEVELOPED INDEX NOT TO EXCEED 450 PER 2014 FBC SECTION R203.10. *THE SPIRAL STAIRCASE SHALL PROVIDE A MINIMUM CLEAR WIDTH AT AND BELOW THE HANDRAIL OF 26' WITH EACH TREAD HAVING A 7 J" MIN. TREAD DEPTH AT 12" FROM THE NARROWER EDGE. ALL TREADS SHALL BE IDENTICAL, AND THE RISE SHALL BE NO MORE THAN 9 2'. A MINIMUM HEADROOM OF 6 6" SHALL BE PROVIDED. INDEX OF DRAWINGS Al SITE PLAN & PROJECT DATA A2 FOUNDATION, FLOOR, & FLOOR FRAMING FLANS A3 ROOF/ROOF FRAMING PLANS, SCHEDULES, & PLUMBING RISER A4 ELEVATIONS A5 BUILDING SECTION A6 SECTIONS & DETAILS A7 ELECTRICAL PLAN AREA CALCULATIONS: 1ST FLOOR CONDITIONED SPACE ........... 875 S.F. LOFT.......................................................................166 S.F. COVERED DECKS/PORCHES ......................115 S.F. TOTAL UNDER ROOF....................................1,156 S.F. PAVER DRIVEWAY/WALKS .........................648 S.F. *ALL AREAS CALCULATED TO OUTSIDE DIMENSIONS DATA & DESIGN PRESSURE SCHEDULE 1.WIND LOADS BASED ON FLA. BUILDING CODE 2014, ASCE 7-10 & 2011 N.E.C. 2. TYPE OF CONSTRUCTION: WOOD FRAME 3. BUILDING DESIGN: ENCLOSED 4. WIDTH OF END ZONE: 3' 5. BASIC WIND SPEED: 165 MPH 3 SECOND GUSTS 6. BUILDING CATEGORY: II 7. BUILDING MEAN HEIGHT: 201011 8. EXPOSURE CATEGORY C 9. ADJUSTMENT COEFFICIENT: 1.0 10. COMPONENTS & CLADDING WIND PRESSURE ON: 1OA: ROOF ZONE: 1) +21.8 / -34.6 2) +21.8 / -60.3 3) +21.8 / -90 1OB: WALL ZONE: 4) +37.8 / -41 5) +37.8 / -50.7 1OC: GARAGE DOOR: 6) N/A INTERNAL PRESSURE COEFFICIENT: +/- : 0.18 LOADS: FLOOR: 50 PSF ROOF DEAD/LIVE: 15/30 PSF IMPACT PROTECTION: IMPACT GLASS CONCRETE WEATHERING RISK NEGLIGIBLE TERMITE INFESTATION RISK: VERY HEAVY 1 NOTE: ALL ZONES CALCULATED FOR WORST CASE SCENARIO; (10 S.F. EFFECTIVE WIND AREA) (DOOR/WINDOW PRESSURES MAY VARY BASED ON SIZE OF DOOR/WINDOW OPENING) BUILDING DEPARTMENT PRODUCT APPROVAL PRODUCT MODEL # MANUFACTURER ATTACHMENT METHOD APPROVAL # / BUILDING DESIGN PRESSURES TYPE, SIZE, SPACING & EMBEDMENT EXPIRATION EVALUATION AGENCY PRODUCT DESIGN PRESSURES WINDOW 8100 SERIES VINYL SING. HUNG. CUSTOM WINDOW SYSTEMS AS PER MANUR INSTALL. INSTR AS PER MANUR INSTALL. INSTR- AS PER MANUR INSTALL. INSTR. FL-5823 07/21/2020 +37.8/-50.7 +67.5/ -67.5 E1'A WINDOW 8400 SERIES VINYL AWNING IMPACT CUSTOM WINDOW SYSTEMS FL-7060.1 07/21/2020 +37.8/-50.7 +67.5/ -67.5 FPA SLIDING GLASS DOOR 570 SERIES IMPACT PGT FL-8208.2 11/11/2016 +37.8/ -41 +60/-60 EPA FRONT ENTRY GLAZED FIBERGLASS THERMA TRU AS PER MANUR INSTALL. FL-10975.1 +38.5 / -41.9 DOOR INSTR 12/31/2015 +55/ -55 FPA REAR ENTRY GLAZED FIBERGLASS 'THERMA TRU AS PER MANUR INSTALL. FL-10975.1 +38.5 / -41.9 DOOR INSTR 12/31/2015 +55/ -55 FPA ROOF GULFLOK GULF COAST AS PER MANUR INSTALL. FL-11651.2 -90 SUPPLY & MANUF. INSTR. 04/12/2024 -116 FPA SHUTTERS IMPACT ALUMINUM FLORIDA AS PER MANUR INSTALL. 14-1120.09 +54 / -64 BAHAMA SHUTTERS INC. INSTR. 03/08/2024 +80/ -80 rEAMI DADE FIBER CEMENT SIDING HARDIE-PLANK JAMES I IARDIE AS PER MANUF. INSTALL. INSTR. 15-0122-.04 05/01/2017 -53.8 MIAMI DADE -76 MULL BAR 1760 SERIES CUSTOM WINDOW INSTALLED BY hMANUF. FL-9520.01 +46.1 / -50 MULL BAR SYSTEMS 04/10/2016 EPA 0 1, `( ('. C71 ` iY ia111,111x( i1TVISI)N R LN f C W10 I'9R C , f ,�+w 'E PE 110, I AIr N NN, -NO I ERMIT Nf ST E KEPT ON JOT; kA, NO LN'SITCTION NVILL BE N14WE. d HESE PPNIS AI& t?i ( I'R01POSE€J �IIOR AREi S6EIBA,t' f' 1i Ohh Ali ' MIaZ IkCC OIIfSA�,dS iiW`a( s p rE--4, O O CN 00 O N h N r � U � ®' O U T- *uzi(� ob C �.� a, o c- ►i ,It �o O� Z O N W r� 0 I J.. a .._.� z- V NOOOOO �`--- LLJ < �-.. Z t zii ., z 51TF. PLAN PROJECT DATA PROJECT NO.: SNYDER 1 DRAWN BY: LV DATE: 9.29.15 REVISIONS: A\ 10/29/15 PER BUILD. DEFT. SHEET NO. 1 Al SITE PLAN 1 /4"=1'-0" (1 /8"=11 0" HALF SIZE IT 4�0 Zx10 %v16" ac. vv v /�� �S•.G� vv /i'<vi0. ��v "\ \ OPEN TO BELOW ' \ *ATTACH ALL BEAMS W/ SIMPSON MGU5.62—SDS (W/ LEFT/RIGHT CONCEALED `�v vv Yam' FLANGE AS NEEDED) v LOFT FLOOR FRAMING PLAN 1 /4"-1'-0" (1 /8"=1'O" HALE SIZE) A6 __ (212x12------------------------ - -- ------------------------------------------------ I---I IIr ---T=--�--T----r--7---E--T---I---T-----—--,T III I I I I I I I I I I I I I I III III III I I I I I I I I I `I I I I I I III I I I I I I I I I I I I I I III III I I I I I I I I I I I I I I III III I I I I I I I I I I I I I I II III I I I I I I I I I I I I I I III II I I I I I I I I I I I I I I III III I I I I I I I I I I I I I I I II I I I I I I I I I I I I I III N I I I I I I I I I I I I I I I I III x IIII I I I I I I I I I I I I I I III NII I I I i I I I I I I I I I I III III I I I I ! .I I I I I I I I I II N IIII I I I I I Q� I I I I I I I I I III �I I I I I I T I I I I I I I I I III 111I I I I I 1� I I I I I I I I I I I I I I I I (� I I I I I I I I I I II1N IIyyI 1h' ,� III x I I I I I I I I I I III N � ,o � T2 2x8 III IIIN --- III I I I I I I I I I I I I I I III`i `° A6 N� III I I I I I I I I I I I I I I III ro III I I I I I I I I I I I I I I 1 �N III I I I I I I I I I I I I I I III �IIIIII III I I I I I I I I I I I I I I III I III I I I I I I I I I I I I I I III I I I I I I I I I I I I I I III 1 1 (3) 12x121 1 1 III —_J___1___I___1_ L__ //'n 2X8-/ 6Gk'AMOVERE �J/iv�W/S AI,Rk,X-'/6, / I I I \E< / ,iii' /�ZX12 ' 16" /CP vAv.( / 1Y/ Tvvv / / / , r / / �/,i \Q r' 2x12 Q'16" 9.'C. r' /' ,2���3J,,' %\ \J\ > O'/ ' r/ ' \ // ' // \�< / / +vwv< P- O O� �2 Az 2 LOFT PLAN A2 1/4"=1'-0" (1/8"=110" HALE SIZE) PLAN LEGEND A6 a 2x4 INTERIOR PARTITION — eo'_6'---- —.--- --_� ® 2x6 WOOD FRAME INSULATED EXTERIOR WALL ® (3) 2x6 STRUCTURAL COLUMN 2 LOCATIONS SHOWN ON PLAN I MINI-sEUT 1 SUGGESTED MINI -SPLIT INTERIOR UNIT I-_UNIT-zOwE I LOCATIDN (ASYSTEM TO BE SIZED BY LICENSED HVAC CONTRACTOR) B'O CEILING GRILL W/ IN -LINE FAN & RA ON T-STAT DUCTED AND DRAWING FROM ADJACENT 3 FOUNDATION PLAN 4 FLOOR FRAMING PLA1�T 5 FLOOR PLAN AZ 1 /4"-1'-0" (1 /8"=1'0" H/"LF SIZE) 1 /4"-1'-0" 1 8"-1'0" HALE SIZE A2 (/ - ) AZ 1/4"=1'-0" (1/8"=1'0" HALF SIZE) FILE v m z Q U 0 z 0 uJ „� O AZ- U_ r -LoUa 'o CT o.�� 00 o N /) S/1 Z (D 0 a CII Q H� v� < :: V) U 0 i f'"ey 0( u.x x Lu z V) (4 o Q � (N } Sd z z O 0 �U 'Q Q O W 0 U \°� uJ C3-J I�In vl Z O U Q O � K"N z O W N � Jl z z } Z Q (( C) _ f Q U LLJ z z I 1 I O ,z) O v J o �z lLJ FOUNDATIO> rLOOK, & Q I=LOIOK FKAMING PLAN5 PROJECT NO SNYDER] Go Z DRAWN BY� D O DATE 9.29.1E Q REVISIONS 10/29/15 PER BUILD. DEI U uJ SHEET NO. z W A2 0 SHEATHING NAILING SCHEDULE _ ---- ------ ITEM NAIL SIZE EDGE SPACING FIELD SPACING NOTES fl' ROOF SHEATHING ZONE 1, 2, & s (8d ROUND HEAD (RING SHANKt 4" Q.C. 6" O.C. GLUE ALL PLYWOOD WITHIN 4' OF ROOT' EDGE ROOF SHEATHING TO TOP OF FASCIA 8d ROUND HEAD (RING SHANE� 4' O.C. N/A NAIL 2x FASCIA TO TRUSS ENDS W/ (2) 16d NAILS (MIN.)` H" WALL SHEATHING 8d 4" O.C. 6" O.C. — TT_OOR SHEATHING 10d ROUND HEAD (RING SHANKS 6" O.C. 12" O.C. GLUE ALL & PROVIDE BLOCKING AT SEAMS AT FIRST 2 BAYS FROM PERIMETER TRUSS CON_N_ECTION SCHEDULE TYPICAI. CONNECTION ALL MEMBERS ARE ANCHORED TO CONCRETE BEAM WITH SIMPSON I IHF.TA20 _ NOTES: UNLESS NOTED OTHERWISE. ALL MEMBERS ARE ANCHORED TO FRAME WALLS WITH (2) SIMPSON HTS20 UNLESS NOTED OTHERWISE ON LAYOUT. TRUSS ID SIMPSON FASTENERS MAX ALLOWED NOTES CONNECTOR ID TRUSS TO FRAME WALL HTS20. 20-10d 1450 (EACH) GIRDER TO FRAME WALL HTS20 20-1 Od _ 1450 (EACH) (2) EACH TRUSS END NOTES: _ __ _ _ - _ _ -TRUSS MANUFACTURER IS RESPONSIBE FOR FINAL LAYOUT, SPANS, & ALL TRUSS & HEADER ENGINEERING. L -TRUSS MANUFACTURER TO INDICATE UPLIFT REACTIONS @ TRUSS/GIRDER ENDS & PROVIDE HANGER CAI LOUTS FOR TRUSS TO GIRDER & GIRDER TO GIRDER CONNECTIONS -SIMPSON CONNECTORS SHALL BE ATTACHED PER MANUFACTURERS STANDARDS. VERIFY WITF1 MANUFACTURER PRIOR TO INSTALLATION. -INSTALL, MOISTURE BARRIER BETWEEN CONCRETE AND All,, NON PRESSURE -TREATED WOOD FRAMING. -SUBSTITUTION OF.ANCHORAGE HARDWARE W/ EQUAL OR GREATER VALUES IS PERMITTED WITH APPROVAL FROM ARCHITECT. ARCHITECT ASSUMES NO RESPONSIBILITY FOR SUBSTITUTIONS WHICH DO NOT MEET THE LOAD REQUIREMENTS. I MDR. SIZE I SPECIES I NAILING (2) 2x6 S.P.F. STAGGERED 16d @ 12" O.C. (2) 2x8 HEM/FIR. STAGGERED 16d @ 12" O.0 (2) 2x10 HEM/FIR. STAGGERED 16d @ 12" O.C. (2) 202 HEM/FIR STAGGERED 16d @ 8" O.C. G HEADER SCHEDULE OPENTNU JACKS TULLSTUDS NOTES UP TO Y IV (1) (7j !'t) 4' 0"40" 6'1"-8' 6" (2) -._ 81T'-16' 0" (2) (2) NON -BEARING H HDR. SIZE SPECIES NAILING I OPENING DER SCHEDULE JACKS TFULLSTUDS TNOTFS (2) 2x4 S.P.F. STAGGERED UP TO 3' 1'1" (1) (1) 16d @ 12" O.C. (2) 2x6 S.P.F. STAGGERED 4' 0"-9' 8" (1) (1) 16d @ 12" O.C. (2) 2x10 HEM/FIR. STAGGERED 6 1"4 6" (2) (1) 16d @ 12" O.C. _ (2) 2x12 HEM/FIR. STAGGERED 8' 7"-16' 0"J(2) (2) 16d @ 8" O.C. 1 ROOF PLAN A3 1/411=11 --0" (1/8"=1'0" HALF SIZE) PLUMBING LEGEND VENT PIPIK [p STUDOR VENT (S.VJ } ROOF VENT A. ALL WORK SHALL COMPLY WITH 2O14 FLORIDA PLUMBING CODE, 2014 FLORIDA GAS CODE, AND ANY OTHER APPLICABLE CODES. B. PLUMBING PIPING & VALVES: -COPPER TYPE "K" PIPING AND FITTING BELOW SLAB. -COPPER TYPE "L" PIPING AND FITTINGS ABOVE SLAB. -LEAD FREE SOLDERED JOINTS. -SCHEDULE 40 PVC SANITARY SEWER & VENTS. C. VENT TO REAR OF STRUCTURE D. CONTRACTOR TO VERIFY ALL PIPE SIZES/SPECS PER EQUIPMENT AND APPLICABLE CODE. E. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUF.'S CERTIFIED DRAWINGS. F. BEFORE FABRICATION, VERIFY AND COORDINATE ALL DIMENSIONS IN FIELD. G. ALL EQUIPMENT SHALL BE SUPPORTED AS REQUIRED TO PROVIDE A VIBRATION FREE, RIGID INSTALLATION. H. PROVIDE WATER HAMMER ARRESTORS AT EACH BRANCH LINE. 2"SINK W� DISP. & DISHWASH 3 PLUMBING RISER_ A3 1/4"=1'-0" (1/8"=1'0" HALF SIZE) SANITARY SEWER 2x8 @ 24" O.C. S F s ti� 00 Op" I 2x8 @ 24" O.0 '\ OpF ,> �F tK , h v 2 ROOF FRAMING PLAN A3 1/4"=1'-0 (1/8"=1'0" HALF SIZE) z O O IU 0 U U I� IE—+ C 4 00 u 1 F�1 -'p L Z �-{ Lo d @O �U 00o 4t �(1) 00 I= Q Q Q !r� ; I� N Lfi E W lO 000 rY U) > W _� O N_ 0 � E �wor� o U N a o Q f� Z � � Ld id z G N O U Q J U a.1 t� z O Q to V CZ � 0 z L to Z uJLL- If,\ µ--I O z T- h Q KOOr/ROOF FRAMING PLAN. 0 5CHF DULr.5, PL(IMF)ING Kbr-K Id PROJECT NO,, SNYDER I GDRAWN BYi LV QDATE3 9.29.15 U REVISIONS, U I a.J SHEET NO. A3 I� Z I�7 15 0" (T.0 P.)--Ab.._.,- 14 4" (HEAD HT.) 90 10' 0" (T.O.B.) 0 9' 0" (T.O.P.) v 8• 0" (HEAD. HT.) 0' 7.25 (T.OfI,) 0' 0' (T.O.F.F.) BASE FLOOD ELEVATION -,-_-- AE 6 APPROX. FINISHED GRADE 4.2�— 15 D" (T.O.P.) _ 14 4" (HEAD HT.) 9- 0" (T.O. P.) 8' 0" (HEAD. HT.) @_ 0' 7.25" (T. D.F.F.} -- 7 2 v— BASE FLOOD ELEVATION, �-- EXISTING GRADE 3.45 4 5 v LEFT (SWX ELEVATION 0" (1/8'1'0" HALF SIZE) i FRONT (SE) ELEVA' ION A4 ,' 1 r'--0" (i �" �1'0" HALF SIZE) MG O EXISTING GRADE 3.45— 4 5 15 0" (T.O.P.) 14 4" (HEAD 10' 0" (T.O.B.) 9- 0" (T.O.P.) 8' 0" (HEAD. HT.) 94 6' 8" (HEAD. HT.) Q� 0' 7.25 (T.O.F.F.) 0' 0" (T.O.F.F.) 2 v— BASE FLOOD ELEVATION, AE 6 EXISTING GRADE 4.5 2RIGHT (N. A4 1/4"=1'-0" (1/8"=1'0 ELEVATION HALF SIZE 1 REAR (NW) ELEVATION "I/4"=1'-0" (1/8"=1'0" HALF SIZE) 'u o Ir-r7 U M[-+ 00 N ILL LLN O lu c� U oo O 41; cn N N z 0 Q Q N clq cn E Q O LU dLo W � n �W0�� rr �� N I�.J Q O C� ELEVATIONS PROJECT NO,, SNYDER I DRAWN BY, L\ DATED 9.29. C REVISIONSI 5 0" (r.O.P.)_$ 14 3" (HEAD HT.) SIMPSUN HIS20 (EACH RAFTER) lx2 P.T. DRIP ON lx6 FIBER CEMENT FASCIA FIBER CEMENT SOFFIT - I' x 4" FIBER CEMENT FRIEZE FIBER CEMENT SIDING ON YVEK OR EQ. HOUSE WRAP ON 8" 5-PLY APA RATED PLYWOOD SHEATHING, - SIMPSUN H10 EACH 2x6. STANDING SEAM METAL ROOF ON PEEL-N--STICI( UNDERLAYMENT ON y" PLYWOOD SHEATHING, SPRAY FOAM -CC ( P.) INSULATION - -- .- (w R-20 MIN,) 2x6 @ 24" ❑.C. - 8 ( (HEAD. HT.) SIMPSUN HTSPO (EACH)-- (& BOTTOM OF BEAM) -- 71 33' GUTTER ❑N—� _? _ P.T. Ix2 DRIP ON i-' 0' (T.O. P.) n lx6 FIBER.I; - CEMENT FASCIA = (STUDIO/BEDROOM 2) FIBER CEMENT SOFFIT I" x 4"FIBER CEMENT FR1E/E FIBER CEMENT SIDING ❑N- TYVEK OR EQ, HOUSE WRAP ON 8" 5-PLY OP' RATED PLYWOOD SHEATHING,. 0' 7.2 5 ( T. 0. F. F. ) -- _-__ (*BEYOND) 0' 0'" (T. 0. F. F. ) - -- 7.2 G�--- BAST 1-l_C)OD_EFEVATION� AE 6 EXISTING GRADE 3.45-4.5 SIMPSUN PA51 HOLDDOWN STRAPS @ 32" O.C. STUCCO FINISH- FLOOD VENTS (IN - LOCATIONS AS SHOWN ❑N FOUNDATION PLAN) FINISHED STANDfLIG SLAM METAL ROUE ON PEEL-N-STICI' UNDERLAYMENT ON 8" PLYWOOD SHEATHING SPRAY FOAM-- 12 INSUI MIN4� (TR-20 MIN.) �i R-19 MIN. INSULATION SIMPSUN LSSU29 HANGER (x EACH RAFTER) �2x4 or 2X6 STUBS OFT i L / 16" D.C. —SIMPSUN H8 EACH STUD �—J" DIA. x 7" LAG SCREWS @ / 32" O.C. q" T&G PLYWOOD SUBFLDUR (GLUED & SCREWED) 2x10 FLUOR JOISTS @ 16" O.C. (ATTACH W/ SIMPSUN LUS210 EACH END) I (:_) 2x10 BEAM W/ (2) LAYERS z PI YWIIUD (ATTACH W/ SIMPSUN MGU5.62-SDS-EACH END & ATTACH TO EACH SUPPORT COLUMN W/ SIMPSUN H6) 5!P DRYWALL (CF_ILINGS) Y,IMPSCIIJ I-I8 EACH STUD 2x6 COLLAR TIES @ 24".G.C. (10-101) NAILS EACH END) SEE TYPICAL RAILING DETAIL SIMPSUN H8 EACH STUD q" ➢IA. x 7" LAG SCREWS @ 32" O.C. CEILING BEYOND BEAM (9'0" HTJ (3) 2x10 BEAM W/ (2) LAYERS" PLYWOOD (ATTACH W/ SIMPSUN MGU5.62-SDS-EACH END & ATTACH TO EACH SUPPORT COLUMN W/ SIMPSUN HG (3) 2xI0 BEAM W/ (2) LAYERS �"- PLYWOOD (ATTACH W/ SIMPSUN MGU5.62-SDS-EACH END & ATTACH TO EACH SUPPORT COLUMN W/ SIMPSUN H6 _-- - -- 1/2" DRYWALL CD lV -- PPO'v'IDF BLCJCKING @ ALL SHEATHING PANEL EDGES I9 MIN, INSULATION x ; or ?X( STUDS lh LLC ti MI'Srlhl lib EACI-I STUD - A. I_A[. SCREWS @ (3) 2x12 BEAM ' 12 Di! & 6 FROM ALL r'HRNER : - 2xl2 FLUOR JOISTS @ 16" O.C. (ATTACH -- G 'L1 GUU SUBFLUOR W/ SIMPSUN LUS210 EACH END) ((, IICD + C RJ_:,f D) �PT2x SI_'- PLATL 8 I.MU W/ I q5 VLRI. REBAR P VO' O-C & I A5 BAR COHI IN TOP L IARSF Ft11 AI I flLLC ,ULID ¢ a J DLFP WIDI "CONL SPRF D F IG/NRADE BM W/ 3 1+) BAR , H iP $ BGTTGM nM. I I 3"CLR i FF FOUNDATIFILl P AN FOR --. _.._.. Pli INC, I [ILA (IONS SE E PI! ING KID ILE y SI IE I I AI FUR PI 1NG PI C 1FIC:A-:-ICNS 2 PILING DETAIL 4:A6 R-30 BATT INSULATION 8'x16" CMU PIER W/ 2 #5 VERT. REBAR. -FILL ALL CELLS SOLID 48"x48"xl6" DEEP ETG W/ 4 #5 REBAR EACH WAY .e I' FASTEN BEAM TO CMU PIER W/ SIMPSUN PA51 STRAP a d a oa � 4 a 0 0 I a a a. 3" CLR 3" CLR. 44. �jlj'. \ a -SEE FOUN➢A11ON PLAN FOR PILING LOCATIONS SEE PILING NOTES SHEET Al FOR PILING SPECIFICATIONS & un rnu- n�TAn A.Ac 2" CONCRETE "MUD MAT" SLAB SLOPED TO CRAWL SPACE OPENINGS a d. a - o �j a a a a a r — — — ----14 I_ I a 4 1 112" STANDING SEAM METAL ROOF ON PEEL-N-STICK UNDERLAYMENT ON 8 CDX PLYWOOD SHEATHING ON PRE-ENGINEERED WOOD ROOF TRUSSES. STANDING SEAM METAL ROOF ON PEEL-N-STICK UNDERLAYMENT ON 8" PLYWOOD SHEATHING ON PRE-ENGINEERED WOOD ROOF TRUSSES. ` lx6 T&G PORCH CEILING (2) 2 x 8 BOLTED THROUGH NOTCHED 6x6 POST W/ (2) 811- GALV. LAG SCREWS. (ADD ADDITIONAL 2x8 & 2 LAYERS PLYWOOD BETWEEN COLUMNS) ATTACH BEAM TO SOLID WALL FRAMING W/ SIMPSUN LUS28-2Z OR APPR. EQ. EACH END. al CYl i� I CD P.T. 6x6 POS I_ WRAP COLUMN W/"- FIBER CEMENT TRIM ,-PT. 45x6 DECKING SCREWED DOWN TO P.T. 2x8'S @ 16" U.C. - ATTACH W/ SIMPSUN LUS28Z, LUS28-2Z OR APPR, EQ. EACH END. - Virr SLOPL P.T. 2x8 LEDGER ATTACHED W/ 2-8`o GALV THROUGH BOLTS @ 32" ❑.C. SIMPSUN STRONG TIE: 6x6 UPLIFT POST BASE (ABUG6Z OR EQ.) 1 BUILDING SECTION A5 3/4"-1'-0" -- SIMPSUN H5 CLIP 7112' EACH ❑NT. FLASHING ON P.T. Ix2 DRIP 1"x6" FIBER CEMENT FASCIA "x4" SUB FASCIA FIBER CEMENT SOFFIT 110 FIBER CEMENT SIDING ON TYVEK OR EQ. HOUSE WRAP ON 8" 5-PLY APA RATED PLYWOOD SHEATHING. \ WRAP BEAM W/ FIBER CEMENT TRIM X 18" FIBER CEMENT TRIM FI a a a a a 4. a a da a d a SIMPSUN STRONG TIE: 6x6 UPLIFT POST BASE (ABU66Z OR EQ.) a" X 1141" FIBER CEMENT TRIM T) z O z 0 ILj O z uJ Q U o IW O N O "o � L- L0 U 04 O K o' ) 00 O 4t to N N Z 0 Q`i- CC. Q vNc�O LLl Q >E w N 0 v)N,D W CD r U N LL Q O QII 1 �j q- W CC O z Z Q t_L N 0 O L z Z z j O Z :3) P.T. 2x8 BEAM g �\ :2) SIMPSUN LCE4Z EACH POST O /y P.T. 6x6 POST V \ ate._. O m . �. ISHED GRADE Ems-- ✓f Ll Q � r /Z vJ —18" DIAMETER X 24" DEEP L UILDING FOOTING W/ 4 #5 BARS z SECTION a CLR f-- U a. W Ca PROJECT NO., SNYDER ODRAWN BYt LF DATEI 9.29.1 U REVISIONSi U �0 FILE COPY � SHEET NO. z O W CO A 5 N WRAP OVER TOP PLAT ii AS REQUIRED HCADCP PER SCHEDULE FASTEN HEADER TO STUD COLUMN W/ SIMPSON C16 COILED STRAP III it � i—IIIIIj i i v Z INSTALL_ SIMPSON CS I6 COILED STRAP TO HEADER OPENING STUD EACH SIDE OF o of __--_0 18" DEEP x 24" WIDE CONC. SPREAD FTG/GRADE of I' BM W/ 3 #5 BARS TOP & , BOTTOM CONT. l 3'CLR 4 2_0. { l; 14"x20'0" LONG AUGER CAST PILING W/ 6-#6 BARS & #3 TIES @ 24" O.C. (SEE FOUNDATION PLAN FOR LOCATIONS & PIL.ING I� I SPECIFICATIONS SHEET Al) 4 TYP. PILING DI -,TAIL A6 n„ " -- u WALL FRAMING (+SFE WALL SECTION) TYP. OPENING STRAPPING DETAIL A6 / ; '4 -1 --0 11 _1 :7'- RIFF .d,' 2— /i P F R F[ _F ILL ALL CELLS �LILiD .! IIftIPdUf�i Lrl�l fh!G ' v PI INSTALL ED '1`f `AIT F(f UPER'S .:1=Lf':�IC�.T IDf•I. �/4" T&G PLYWOOD SUBFLOOR; GLUED & NAILED 2x12 WFLOOR JOISTS 16" O.C. (ATTACH SIMPSON LUS210 (3) 2x12 BEAM PT2x8 SILL PLATE FASTEN BEAM TO CMU PIER W/ SIMPSON PA51 STRAP 48'" IS lc' F L w/ a 4 ?SS :2L +AP 4C1 ° 'a ° a a° - o n 3"CLR �• 3"CLf. -SEE FOUNDATION PLAN FOR PII_I LOCATIONS. SEE PILING NOTES SHEET Al FOR PILING SPECIFICATIONS & PILING DETAI 4:A6 STANDING SEAM METAL ROOF ON PEEL-N-STICK UNDERLAYMENT ON B" PLYWOOD SHEATHING. SPRAY FOAM INSULATION CAR-20 MIN.) PRE-ENG, ROOF TRUSSES SIMPSON HTS20 (EACH TRUSS) 4 C 38' GUTTER ON P.T. lx2 DRIP ON CIA 7; r FIBER CEMENT FASCIA � G 9' 0" (T.O.P.) - FIBER CEMENT SOFFIT - I" x 4" FIBER CEMENT FRIEZE FIBER CEMENT SIDING ❑N TYVEK OR EQ. HOUSE WRAP ON 8" 5-PLY APA RATED PLYWOOD SHEATHING. SIMPS:71N PA51 HOLDDOWN STRAPS @ 32" D.C. 010"&017.25" (T.O.F.F.) 7.2&7.8 _ � STUCCO FINISH - BASE FLOOD ELEVATION AE 6 FLOOD VENTS (IN - LOCATIONS AS SHOWN ❑N FOUNDATION PLAN) EXISTING GRADE 3.45-q.5 IfW&IINIXIM, A 2 38' GUTTER ❑N P.T. Ix2 DRIP ON Il lx6 FIBER 5/8" DRYWALL (CEILINGS) CEMENT FASCIA FIBER CEMENT SI➢ING ON TYVEK OR EQ. HOUSE . -SIMSPSON H8 EACH STUD WRAP ON �' ❑SB SHEATHING, WRAP BEAM & COLUMN W/ FIBER CEMENT TRIM y" X 74" FIBER CEMEN TRIM EXTEND 2x6 24" MIN. BEYOND EDGE OF ROOF TRUSS & ATTACH W/ (10 10D NAILS EACH, STANDING SEAM METAL ROOF ❑N PEEL_-N-STICK UNDERLAYMENT ON 8" PLYWOOD SHEATHING, 2x6 @ 24" ❑.C. SIMPSON HTS20 (EACH) 7z �� 112' DRYWALL P.T. 6x6 POST - -PROVIDE BLOCKING @ ALL SHEATHING PANEL EDGES - R-19 MIN. INSULATION -2X4 or 2X6 STUDS 16" O.C. -SIMPSON H8 EACH STUD -j" DIA. x 7" LAG SCREWS @ 32' ❑,C. & 6" FROM ALL CORNERS - TIE: STRONG TIE: 6x6 UPLIFT POST BASE q" T&G PLYWOOD SUBFLOOR (ABU66Z OR EQ.) (GLUED & SCREWED) q" X 11q" FIBER CEMENT TRIM PT2x8 SILL PLATE 8" CMU W/ 1 #5 VERT, REBAR @ 4'0" D.C. & 1 #5 BAR CONT. IN TOP COARSE. -FILL ALL CELLS SOLID EXTERIOR RAILING DETAIL s INTERIOR PIER DETAIL - I ° .0 18" DEEP x 24" WIDE - CONIC. SPREAD FTC/GRADE 6 �6 a ° BM W/ 3 #5 BARS TOP & C) / ) /4 0" ° BOTTOM CONT. F--------� 3" CLR. z-o^ d —SEE FOUNDATION PLAN FOR MEFAL BALUSTERS (*STYLE ° PILING LOCATIONS. SEE FINISH TO BE SELECTED BY n PILING NOTES SHEET Al FOR OWNER) f PILING SPECIFICATIONS & T. I X6 PILING DETAIL 4:A6 WOOD HANDRAIL/NEWEL POST C AC�GERED) +._fYLE FINISH TO BE M, ) SELECTED BY OWNER) ---- ---- `FYP. WALL SECTION BALLUSTERS TO PREVENT i ; " j [� l 2x2 FRAME ATTACHED A6 3/4 =1 —0 PASSAGE OF 4" SPHERE. X POSTS � � 'U 6 6 I l i L1 - N`')ECT SCREEN (IN`>iDE FACE) , I , J _- L__ LOFT GUARDRAIL DETAIL (> SHIPLAP SKIRTING DETAIL - -- - -- ---- (3) P.T. 2x8 BEAM (2) SIMPSON LCE4Z EACH POST P.T. 6x6 POST FINISHED GRF 18" DIAMETER X 24" DEEP FOOTING W/ 4 #5 BARS z O p I� o U Ld H o N � r1 Lo N ct �N@� o `J � � > Z Q O U Q 4 < ry Q V) N !- `=' � E w ®� V OU 0 Q LLJ z (n E W 0 O it � N �� 0 I�.J Q O j� > >- 2 ;_ Q j� - _ -- z z O i 0 ATTACH BEAM TO SOLID WALL FRAMING W/ SIMPSON LUS28-2Z OR APPR. EQ, EACH END. U lx6 T&G CEILING uJ 0 O U z _- P.T. yx6 DECKING U SCREWED DOWN TO P.T. Q 2x8'S @ 16' ❑.C. - ATTACH US SIMPSON R LUS28Z, LUS28-2Z ❑R APPR. EQ. EACH END. ILI L Id P.T. 2x8 LEDGER --< j}'�) ATTACHED W/ 2-B'O oy J GALV. THROUGH BOLTS a O @ 32" O.C. _ SIMPSON STRONG TIE: 6x6 UPLIFT T, POST BASE ABU66Z OR CO.) j DE 144 J i ° O u" j m) h { n z ®@ 1� Z _ _mg r) J s� REAR PORCH SECTION ���. z A� 3/4„_ 1,-0" Q iL 1 Li - -- T_ SECTIONS & z DETAILS 0 , Q U W Q PROJECT NOj SNYDEF z DRAWN BY, I O DATEi 9.29. UREVISIONS, q L SHEET NO, z 6 Ll J J Q ELECTRICAL SERVICE LOADS: 1041 SQ/FT(@ 3 WATTS/SF) -3,12.3 WATTS APPLIANCE CIR.(2 @ 1500 EACH) 3,000 WATTS I_AUNDRY CIR. (1@ 1500 EACH) - 1,500 WATTS RANGE =5,000 WATTS EXHAUSTHOOD =500 WATTS DISHWASHER =1,500 WATTS DISPOSAL =1,500 WATTS MICROWAVE =2,000 WATTS WATER HEATER =5,000 WATTS REFRIGERATOR -1,500 WATTS FREEZER =1,500 WATTS WASHER -1,500 WATT'S DRYER -5,000 WATTS SUB-TOTAL=32,623 WATTS TOTAL PANEL LOAD: A/C #1=10,000 WATTS 1ST 10,000 @ 100% = 10,000 WAT 'S REMAINING @ 40% -9,050 WATTS TOTAL: 29,050 WATTS /240V TOTAL AMPS: =121 AMPS *ELECT CONTRACTOR TO VERIFY TOAD REQL'TRFMFNTS OF ALI,• APPLIANCES, PUMPS, .HVAC. SYSTEMS, ETC. TO ENSURE THE TOTAL REQUIRED AMPS DOES NOT EXCEEDTHE tE PANEL AND HOUSE SERVICE. RISER DIAGRAM 0 (i),41 CU W/ (II # 6 G IN 14" CONIIUII MF,TER — -- -- znn AMr zon nnm m M 200AMI PANF,1. HOUS DISCON_ GROUND PER 2008 N.E.-C. (N4 COPPER GROUND TIE TO FOUNDATION STECI, & ROD) AIN E ICE ELECTRICAL LEGEND 110 VAC DUPLEX OUTLET 110 VAC DUPLEX OUTLET (1 /2-switched) 0GF1 110 VAC DUPLEX OUTLET (ground fault interrupt) ®FLOOR OUTLET (owner to approve location) o* Refer to Manufacturer's 4Y Specifications (Height/Voltage) �R f LIGHT FIXTURE(WP = Weatherproof) (Recessed) UNDER -COUNTER LIGIT o STEP LIGHT aD FLOOD LIGHT (MOTION SENSOR) FLUORESCENT FIXTURE (WP =Weatherproof) CEILING FAN (WP = Weatherproofl (w/light) M LIGHT SWITCH "' THREE/FOUR-WAY LIGHT SWITCH D DIMMER SWITCH Ds DOOR SWITCH LIGHT FIXTURE (WP = WeatherprooO (Ceiling -Mounted) { LIGHT FIXTURE (\XT = WeatherprooO (Wall -Mounted) LIGHT FIXTURE (WP = WeatherprooO (Pendant/Chandelier) i.a; :! ELECTRICAL PANEL EXH. FAN -EXH. FAN/LIGHT TELEPHONE F CABLE/DATA RECEPTACLE GAS LINE DB DOORBELL O THERMOSTAT SMOKE/CARBON DETECTOR GD GARAGE DOOR OPENER LOFT C STUDIO/BEDROOM PLAN LEGEND F-_I 2x4 INTERIOR PARTITION 2x6 WOOD FRAME INSULATED EXTERIOR WALL . TIE -DOWN LOCATION (SEE DETAIL 21A6) ® (3) 2x6 STRUCTURAL COLUMN e LOCATIONS SHOWN ON PLAN f-enwi-Sp l? - j SUGGESTED MINI -SPLIT INTERIOR UNIT L_U,1T-ZONE _.,I LOCATION (wSYSTEM TO BE SIZED BY LICENSED HVAC CONTRACTOR) --1 IN -LINE FAN 6 RA ON T-STAT Iffl DUCTED AND DRAWING FROM — L_J - ADJACENT MINI -SPLIT ZONE MINI -SPLIT AC NERIEY INSIDE UNR LDrpnONS) CLOSET �L\` SYSTEM 1 Cf I FO- I r� L_J u 4P _r MASTER BEDROOM I J BUILT-IN CLOSET SYSTEM =� -- ,/� R , GREAT ROOM � TO ucNTs ABOVE R \\\ ENTRY/DINING I 1 n ELE CTRI CAL PLAN 1/4"=l'-0" (1/8"=1'0" I-IALF SIZE) z z ;� } `.✓ OO O w U I N � LO _1zt O LLI C"i � u1 !U CS K rn z 1�/ W O Q � ai � � O Q < j N :: Li n QLIJ V d U w C 0 z v)N,L1 C o IWo�� o C, o !U Q o Q U z C z 0 O t/ J II� O U Q uJ �1 O U W z _ O Q � � / + Li Li d /< IV -- / to U I Z O � �\ z rz W z F. . < ! i W r-LECTKICAL_. z PLAN 0 n uJ Q PROJECT NO,, SNYDER 0 DRAWN BY, L DATEI 9.29.1 FIU REVISIDNSI LE COP, L_ Id T SHEET NO, Gb z Q A IIR_ WARNING* COMPONENTS AS DEFINED BY WTCA 1 - 1995. 1) FOR THE ERECTION BRACING FOLLOW STRUCTURAL DATA, NUMBER OF GIRDER AND TRUSS DESIGN DEPARTMENT APPROVES THEM IN ADVANCE LL BEARING POINTS MUST BE DIAPHRAMS HAVE NOT BEEN ANALYZED BY NSTRUCTIONS ON THE BCSI-B1 SUMMARY SHEETS PLIES AND THE CONNECTION INFORMATION. ALL HANGERS ARE SIMPSON STRONG -TIE UNLESS OTHERWISE NOTED. INSTALL HANGERS ACCORDING NSTALLED PRIOR TO INSTALLING EAST COAST TRUSS. FOR ERECTION AND INSTALLATION OF TRUSSES 2) PERMANENT BRACIN( FOR THE STRUCTURE IS HE ESPONSIBILITY OF OTHERS. OUR DESIGN DEPARTMENT MUST APPROVE ALTERATIONS AND/OR REPAIRS TO TRUSSES IN TO THE CURRENT SIMPSON STRONG TIE CATALOG NY TRUSSES! FAILURE TO DO SO MAY RESULT FOLLOW INSTRUCTIONS ON THE BCSI-B1 SUMMARY 3) INSTALL WEB BRACING AS STATED ON SEALED ADVANCE. N DAMAGED TRUSSES AND WILL VOID ALL WARANTIES. SHEETS AND SEALED ENGINEERED TRUSS DRAWINGS NGINEERING TRUSS DRAWINGS. Truss a Sheets TRUSS PLACEMENT PLAN ENGINEERED TIMBER TRUSS SYSTEMS PRODUCTS ECT EAST COAST TRUSS 5285 ST. LUC E BLVD. FT. PIERCE, EL 349646 OFFICE: (772) 466-2480 FAX: (772)466-5336 STOMER:Snyder, Dan B NAME: Snyder Res. DRESS:TBD 'Y/COUNTY:Jensen Beach/St. Lucie # 29630 MODEL:Custom SQ FT 6 DATE 10/23/15 IMEST�710123= 61G15"1.003 (3) (C), EAST COAST TRUSS u the "Tress Design Engineer" Trun. ere designed in eC<ortlnna with the Florid. Building Code NOTE: By approving this placement plan(s), signatured anywhere on this sheet, the customer or his representitive acknowledges that this placement plan complies with the structural intent of the project. The customer also acknowledges that this approval..., authorizes EAST COAST TRUSS to manufacture these trusses and deliver them to the project indicated on this x drawing. m, The customer also acknowledges that he/she accepts financial responsibility for any repair, engineering, and` labor required due to errors other than those of EAST'" COAST TRUSS. Signed: Date: DDE = FBC 2014/TP12007 ASCE 7-10 =SIGN CRITERIA =MWFRS CCUPANCY CATEGORY= II (POSURE = C WF SPEED =170 JILDING TYPE =ENCLOSED EAN HEIGHT: 18.00 FLOOR: DUR FACTOR= 1.0 PSF= T CLL-TCDL-BCLL-BCDL 40.0,10.0,0.0,5.0 ROOF: DUR FACTOR= 1.25 PSF=TCLL-TCDL-BCLL-BCDL 20.0-15.0-0.0-10.0 *NON -CONCURRENT BC LL 10psf CONCURRENT BC STORAGE LL 20 psf MWF = MAIN WIND FORCE C&C = COMPONENTS AND CLADDING TOB = TOP OF BEARING TIC = TOP CHORD BC = BOTTOM CHORD LL = LIVE LOAD DL = DEAD LOAD psf = POUNDS PER SQUARE FOOT # = POUNDS UNLESS SHOWN ON ENGINEERED TRUSS DRAWING. ALL GIRDER/COLUMN LOADS MUST BY-PASS FLOOR TRUSS UNLESS SHOWN ON ENGINEERED TRUSS DRAWING. 1- 2- 3- 4- 5- 6- RECOMMENDED ON FLOOR TRUSSES SPANNING 20'0' OR MORE BE SET WITH A SPREADER BAR. THE IDER BAR SHOULD BE AT LEAST 1/2 IN LENGTH AS THE SPAN OF THE TRUSS NG SET. TO BCI-B1 FOR COMPLETE ON AND SAFETY PROCEDURES SUPPORT ANY PLANT SHELVES is i Z U_ W CL G Q U) W J Z D U) U) 07 D W U) 0 I— W U) I-- Q L Designed Bv: LM ' 10123120