HomeMy WebLinkAboutQuest Engineering Service & Testing Report9.
QUEST -
Consulting Engineering Testing
VED
Rubin Custom Homes, LLC
�
4253 SW Meadows Highway
Palm City, FL 34990 OCT 13 2017
Attn: Mr. Steve Rubin""
BY.
Re: Report of Geotechnical Study
Liteplo Screen Porch Addition
2016 NW Laurel Oak Lane
Palm City, Florida
QuEST Report No. J-17214.001
Dear Mr. Rubin:
As requested, Quest Engineering Services & Testing, Inc. (QuEST) has completed
a subsurface study at the subject site. The fieldwork involved the drilling of one Standard
Penetration Test (SPT) boring (ASTM D 1586) with tripod to a depth of 25 feet below existing
grade. The approximate boring location is indicated on the attached Boring Location Plan. The
boring log, which is also attached, indicates the types of materials encountered, the result of the
field test and the measured groundwater depth.
PROJECT CONSIDERATIONS
The subject project site is a single-family residential lot located at 2016 NW Laurel Oak Lane in
Palm City, Florida. We understand that plans are to construct a screen porch addition at the
subject site. The new addition will likely be of CBS construction. While the loading information
was not provided to us, they are expected to be light. For purposes of this study we have
assumed that maximum column loads will 'not exceed 30 kips and wall loads 5 kips per linear
foot (klf).
This geotechnical exploration was required to determine the suitability of the foundation soils in
the addition area to support the planned construction. The field work consisted of drilling one
SPT boring with a tripod to a depth of 25 feet below grade, at the locations indicated on the
attached Boring Location Plan.
STRATIGRAPHY
The stratification of the profile components as shown on the boring log represents the
subsurface conditions at the actual boring location. Variations may occur within a short
distance from the boring. Lines of demarcation represent the approximate boundary between
the types of materials encountered, but the transition may be gradual, or not clearly defined.
The boring disclosed the drilled site area to be mantled by very loose sand to a depth of 2 feet
below grade. This was followed by medium dense sand to the terminal limits of the exploration
at 25 feet below grade.
Quest Engineering Services &Testing, Inc. Jupiter Ph (561)747 8886 Pompano Beach Ph (954)582 9800 Fax(954)582 9836
In
Rubin Custom Homes, LLC - 2 -
QuEST Report No. J-17214-001
Groundwater
The ground water table was encountered at a depth of 4.5 feet below ground surface. In the
absence of other data, we suggest assuming that a 12 to 18-inch rise in the water table could
occur during periods of prolonged rainfall and at the peak of the wet hydroperiod, which
typically occurs in the Fall.
DESIGN RECOMMENDATIONS
Based on the results of our field test, we believe that the site soils can safely support shallow
foundations designed for an allowable bearing pressure of 2,500 pounds per square foot (psf)
provided the earthwork recommendations given in this report are followed. To provide an
adequate factor of safety against a bearing capacity failure, the new footings should bottom a
minimum of 24 inches below the lowest adjacent grade. Continuous footings should have a
width of at least 24 inches and isolated footings, if needed, 36 inches, even if they result in
bearing pressures lower than allowable. Footings should also be reinforced adequately. Such
footings are estimated to sustain maximum total settlements of about 1 inch and differential
settlements of about Y2 inch, provided the loads are within assumed limits.
The slab may be ground supported. A vapor barrier (preferably 10-mil thick) should be placed
over the building pad fill, prior to placement of concrete for the floor slab. This will minimize the
entrance of subgrade moisture into the slab.
CONSTRUCTION RECOMMENDATIONS
Prior to beginning of construction activities, all topsoil, vegetation, roots, uncontrolled fill and
other deleterious material should be removed, in their entirety, from the construction area plus a
5-foot wide perimeter area. - Buried structures/utilities (if any) should also be removed in their
entirety. The excavations should be backfilled with clean granular soils, in 12" thick (loose
measure) lifts and compacted to 95% of the ASTM D 1557 maximum dry density. Care should
be taken to ensure that compaction operations do not cause any distress to nearby structures.
The stripped pad should be compacted to degree specified above. The addition area may then
be filled to .the required slab subgrade elevation. The fill soils should comprise of clean
granular soils having no particle size larger than 3 inches. The fill should also not have more
than 10% fines (material passing the U.S. No. 200 Sieve). The fill should be placed in 12-inch
thick (loose measure) lifts. Each lift of fill should be compacted to 95% of the ASTM D-1557
maximum dry density.
When footing trenches are excavated, the excavation bottoms should be examined. If any
organic, soft or fine-grained soils are encountered in the footing bottoms, they should be
removed in their entirety and replaced with compacted fill. The footing subgrade as well as the
slab subgrade soils should be compacted to 95% of the ASTM D-1557 maximum dry density.
Care should be taken to ensure that compaction operations do not cause any distress to nearby
structures. Likewise, when addition area excavations, including footing excavations, are made
adjacent to the existing building, care should be exercised to ensure that the existing structure's
foundations are not undermined. This may require the use of sheet piling along the existing
building's perimeter areas that are adjacent to the new construction areas.
QUEST
Rubin Custom Homes, LLC - 3 -
QuEST Report No. J-17214-ow
LIMITATIONS OF STUDY
The soils engineer warrants that the findings, recommendations, specifications, or professional
advice contained herein, have been promulgated after being prepared in accordance with
generally accepted professional engineering practice in the field of foundation engineering, soil
mechanics and engineering geology. No other warranties are implied or expressed.
The recommendations prepared for the planned construction are based on information provided
and the available subsurface information gathered. Any revision to the plans for the proposed
structure from that indicated in this report must be brought to the attention of the soils engineer
so that the may determine if changes to the foundation recommendations are required.
This report is also premised on the sub -surface soil conditions throughout the building pad
being similar to that encountered in the borings logs. If deviations from the noted subsurface
conditions are encountered during construction, they should also be brought to the attention of
the soils engineer so that he may evaluate them in light of the foundation design
recommendations, and make modifications if deemed necessary.
After the plans and specifications are more complete, it is recommended that the soils and
foundation engineer be provided the opportunity to review the final design and specifications, in
order that the earthwork and foundation recommendations may be properly interpreted and
implemented. At that time, it may be necessary to submit supplementary recommendations.
Monitoring and testing should also be performed to verify that suitable materials are used for
foundation and building construction.
QuEST appreciates the opportunity to be of service. If we may answer any additional questions
or be of further service, please call.
Sincerely,
Quest Engineering Services & Testing, Inc.
ZVi'
�jR aP.E.
Project Engineer
Florida Registration No. 60223
Attachments: Boring Location Plan
Boring Log
QuEST
Rubin Custom Homes, LLC
QuEST Report No. J-17214..001
APPENDIX
Boring Location Plan
SPT Boring Log
-4-
QuEST
Z"*�
U1
t- 6ttt1t P-l'ilTr,
i � •i
y.
rl�� �C1;�T1t�1�x 9
A ..
BN%tiGR.4QT fG CY+RI
F
QUEST Title:
Project:
Quest Engineering Services & Testing, Inc.
2737 NW 19t" Street
Pompano Beach, FL — 33069 Client:
Project o.
Ph (954) 582 9800 Fax (954) 582 9836 J-17214
iw
N. LR
i I
BORING LOCATION PLAN
Liteplo Screen Porch Addition
2016 NW Laurel Oak Lane
Palm City, Florida
Rubin Custom Homes, LLC
/n sheet No. JREvasion
RJ 1 of 1
* SPT Boring
NTS
BORING LOG
Project Name
Liteplo Screen Porch Addition
Project Number
J-17214
Client Name
Rubin Custom Homes, LLC.
Boring Number
B-1
Boring Location
See Boring Location Plan
Date Drilled
09/29/17
Water Depth
4' - 6"
Drilled By
FE&T
0 10
20 N3�1�� 50 60 70
a
a_
DEPTH
SYM-
DESCRIPTION OF MATERIAL
Blow
Depth
o
, � i F
(FT)
BOL
Counts
(Ft)
0
2
1
•
1
Brown SAND
2
2
3
Gray SAND
11
3
5
•
4
4
5
14
5
•
6
6
7
Dark Brown SAND
11
7
•
8
8
10
g
17
9
10
i
Brown to Dark Brown SAND
10
11
11
12
12
13
13
15
•
14
14
15
18
15
16
111111111
Brown SAND
16
17
17
•
18
18
zo
19
26
19
20
20
21
21
22
22
•
23
23
25
24
21
24
25
25
26
End of Boring
26
27
27
28
28
30
29
29
30
30
31
31
32
32
33
33
35
34
34
35
35
Ground Elev.
Not Known
Completion Depth
25 Feet
Type of Boring
Standard Penetration Test
Casing
N/A
Hammer Wt.
140 Pounds
Hammer Drop Ht.
30 Inches
QuEST