HomeMy WebLinkAboutEvaluation Report`,._I TRINITY ! ERD
EVALUATION REPORT
Owens Corning
One Owens Corning Parkway
Toledo, OH 43659
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT #13
OXFORD, CT 06478
PHONE: (203) 262-9245
FAX: (203) 262-9243
Evaluation Report 037940.02.12-117
FL10674-1112
Date of Issuance:02/06/2012
Revision 7: 04/18/2016
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code
sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. Trinity I ERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 04/18/2016. This does not serve as an electronically signed
document. Signed, sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates. _
2. Trinity l ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
File Copy
� ERD
TRINITY ,
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated
compliance with the following sections of the Florida Building Code and Florida Building Code, Residential Volume
through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements
and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section Pro a Standard Year
1507.2.5, R905.2.4 Physical Properties ASTM D3462 2009
1507.2.7.1, R905.2.6.1 Wind Resistance ASTM D3161 2009
1507.2.7.1, R905.2.6.1 Wind Resistance ASTM D7158 2008
3. REFERENCES:
gaiitt Examination Reference Date
UL LLC (CER9626) Physicals & Wind Resistance File R2453, Vol. 3 02/15/2007
UL LLC (CER9626) Physicals & Wind Resistance 20120516-112453 05/16/2012
UL LLC (TST9628) Physical Properties 06CA20263 04/18/2006
UL LLC (TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC (TST9628) Physicals & Wind Resistance 4786093137 02/01/2014
UL LLC (TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC (TST9628) Physical Properties Classification letter 02/13/2014
UL LLC (TST9628) Physical Properties Classification letter 10/02/2015
Miami -Dade (CER1592) FBC HVHZ Compliance Various NOAs Various
UL LLC (QUA9625) Quality Control Service Confirmation, R2453 Exp. 08/20/2017
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme are fiberglass reinforced, 3-tab asphalt roof shingles.
4.1.2 Berkshire are fiberglass reinforced, 4-tab asphalt roof shingles.
4.1.3 Devonshire- are fiberglass reinforced, 5-tab asphalt roof shingles.
4.1.4 Duration, TruDefinition* Duration*, Duration* Premium Cool, TruDefinition* Duration® Designer Color
Collection, TruDefinition* Oakridge; Oakridge* and WeatherGuard* HP are fiberglass reinforced, laminated
asphalt roof shingles.
4.2 Berkshire Hip & Ridge Shingles, High Ridge, WeatherGuard* HP Hip & Ridge Shingles, ProEdge Hip & Ridge
Shingles and DuraRidgelm Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt roof shingles.
4.3 Starter Strip Shingle, Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory
for fire ratings of this product.
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-R7
Certificate of Authorization #9S03 FL10674-R12
Revision 7: 04/18/2016
Page 2 of 8
i
I�V~ 1
'J TRINITY ! ERD
5.4 Wind Classification:
5.4.1 All Owens Corning shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and
R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for
use in all wind zones up to Vasd = 150 mph (Volt = 194 mph). Refer to Section 6 for installation requirements
to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are Classified
in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the shingles are
acceptable for use in all wind zones up to Vasd cc 150 mph (Vnit =194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less.
Calculations by a qualified design professional are required for conditions outside these limitations. Contact
the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 . All products in the roof assembly shall have quality assurance audit in accordance with the Florida Building
Code and F.A.C. Rule 61G20-3.
6. INSTALLATION:
6.1 Underlavment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval, or be Locally Approved per Rule 61G20-3, per FBC Sections 1507.2.3,1507.2.4 or R905.2.3.
6.2 Asphalt Shinales:
6.2.1 Installation of asphalt shingles shall comply with the manufacturer's current published instructions, using
minimum four (4) nails per shingle in accordance with FBC Sections 1507.2 or R905.2, with the following
exceptions:
➢ Berkshire® shingles require minimum five (5) nails per shingle.
➢ WeatherGuard* HP shingles require minimum six (6) nails per shingle.
➢ Devonshire"' shingles require minimum six (6) nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five (5) nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing — Starter Strip Shingle and Starter Strip Plus:
Felt underlayment
- Deck
Self•adltered
WeatherLocka
= underlayment
Drip_,
� Drip edge
edge
Nails located
2'-3" from eave
Install first
Self-sealing adhesive
Starter Strip
positioned along eave
shingle with
6' removed Starter Strip shingle overhangs eaves and rakes
Exterior Research and Design, I.I.C.
[ertifleate ofAuthorlsotion #9503
Feltunderlayment Deck Sell-adhered
J � WeatherLoekt)
underlayment
Drip edge
Ddp—. '
edge �.
Nab located
2'+••3" from eave
Instal first Starter StriPits Sdtaealin,adhesive
with 6" removed P positioned along eave
Starters jp Plus overhangs eaves and rakes IM-3/4"
Evaluation Report 037940.02.12-R7
FL10674-R12
Revision 7: 04/18/2016
Page 3 of 8
6.2.6 Minimum Nailing —Classic®& Supreme:
Normal Mansard or Area pare
Wind Arena High Wind deavanas y
Area pare "lentos normales Areas "lentos fuertes
6"Exposure
Exposieidn
6.2.7 Minimum Nailing — Berkshire®:
Sealant strip
La Ora do sel4dor
T- �t--► • �--n
B Vi"
• t--►
9 Vi' 9 Vt°
• �--s •
8 Y1'
Standard Fastening Pattern
Exterior Research and Design, LLC.
Cerdjlcate of Authorization #9503
R
i`
TRINITY i ERD
Normal Mansard or Area pare
Wind Areas High Wind desvones v
Area pare "lentos normales Arena viontos fuertes
t°
zt (Ai t. rt° 2.1 (Bl 2" t°
t2t
6 6/1" Exposure
Exposioldn
Sealant strip
La tira do sellador
QT-,arh.. S..
6-Nail Fastening Pattern
Evaluation Report 037940.02.12-R7
FL10674-R12
Revision 7: 04/18/2016
Page 4 of 8
6.2.8 Minimum Nailing — Devonshirer":
8" I g" I 7 " r _ I n
" Gyros
M/8e exposure Sealant location
Exposicibn de 5.5/8 pulg Ubicacibn del sellador
Standard 6-Nail Fastening Pattern
TRINITY; ER®
4v
Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing — Duration®, TruDefinition® Duration, Duration"" Premium Cool & TruDefinition• Duration"
Designer Color Collection:
4-Nall Fastening Pattern
SureNall9 fastening ofea width
Nall, typit:al
1^ 11 2" I 11 2" I7"
6.118" adJa"
� F1 F� F�
Standard Fastening Pattern
6-Nall Fastening Pattern
(� sureNm fastening area width
Nall, ,ypl
1" 12" 1 I l� 2" 1"
{ •cmw6v�• • ..•b •aw..ca�p9vewis �
Fastening for Slopes Greater Than 21:12
sureaaW.0 foetoning area width
Nall, WPlaol
6•tfe"E!7a�. ..
Four t" Spots of Asphalt Roofing Cement
Mansard or Steep Slope Fastening Pattern
6-Nail Fastening Pattern
Exterior Research and Design, I.I.C. Evaluation Report 037940.02.12-R7
Certljlcate ofAuthorkatlon #9503 FL10674-R12
Revision 7: 04/18/2016
Page 5 of 8
t
6.2.1 Minimum Nailing—TruDefinition"Oakridge®, Oakridge®:
4 Nall Pattern
Esquema con 4 ctavos
i
ExpostelMde55/6p1119. Clam
ExposFNon, de 5 5/6 ping. I
Standard Fastening Pattern
9 ; t
`"" I TRINITY; ERD
I i
6 Nall Pattern
Esquema con 6 cfavos
t" r
�— 12° —s{ k-- 12"
SSW' Exposure Cla as 5 6/8" Exposure
Exposid6a de 6616pulg. Exposicidn de 66/8pufg.
6-Nail Fastening Pattern
Fastening for Slopes Greater Than 21:12
Sundlair0 fastening area width
Nall, Typical
17' 1"
•....cm.,y rum>v_. • � l�.r=
s•11s' 5.518"
Four 1" spots of Asphalt adaMg Cement
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing — WeatherGuard® HP:
Exterior Research and Design, U.C.
Certificate of Authorization t/9503
7' I
2`� 1 VIEW faer»ar
it— • 1
:5;:• FWe Nar7lneR IllrlIil!
CbmM3elir 111111 b
Evaluation Report 037940.02.32-R7
FL10674-R12
Revision 7: 04/18/2016
Page 6 of 8
TRINITY ERD
6.3 Hip & Ridge Shingles:
6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard HP Hip and Ridge Shingles and
ProEdge Hip & Ridge Shingles shall comply with the manufacturer's current published instructions, using four
(4) nails per shingle. Installation of DuraRidgelm Hip & Ridge Shingles shall comply with the manufacturer's
current published instructions, using two (2) nails per shingle. Refer to Owens Corning published
information on wind resistance and installation limitations, including the use of hand -sealing for wind
warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing— Berkshire® Hip & Ridge and High Ridge:
Fig. 1 9
`— PmallingWrid
Direction A
Naliiss \\--11- A
\ 4
I I
A I 1
1 1
A I 1
99 i I
I I I I
A I i I 1
Elgloalro
Fig. 2
Tap View SideView
Nails i1 Nails
�•• Z.> Top Laminator
a' Place
I
I
ul
�I
JI
I
I
I
1
I
III 1
I 1Y'�
6.3.4 Minimum Nailing — WeatherGuard® HP Hip and Ridge:
Fig. A 9 q
PM,.ning Wind
�— Dlpxtbn p
A
\ I 1
A I I
p I I
I I
I I
I I I I
A I I I I
I I I I
Expocuro
Exterior Research and Design, I.L.C.
Certificate of Aathorkadon #9503
Fig. C Hip & Ridge Shingle Fastening
TopVAer
Nails Nails
7' 2"
1' 7°
s' Exposure
I t2
Evaluation Report 037940.02.12-R7
FL10674-R32
Revision 7: 04/18/2016
Page 7 of 8
6.3.5 Minimum Nailing - ProEdge Hip & Ridge Shingles:
Prevailing
Wind Direction Sealant Strip
6° Exposure
Fasten 71
Cova"Exposed
Fasteners with
Roof Cement
TRINITY! ER®
Standard +-11
Fastening
Pattern
72' 1 Sealant
7'j=" 6" Exposure
it I�-12"—�`•
6.3.6 Minimum Nailing — DuraRidgeTM Hip & Ridge Shingles:
Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Ptaraifng Wind Direcdcn
Diroaion dornininte du rcac
Dirocdcn del •dente predanirante
4s
81.0w"_
09
J
i l + i
A
7. LABELING:
Top View
Vue en plan
till^ Victatuperior I'IH
Non
-
t199
• Oerom Cotldng StrreNafP •
�I
ch.
I
I�
alai
I
19.8 v
IJ �
I
Imo-
IZ^�
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
S. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named CIA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625; (414) 248-6409; karen.buchmannCul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, I.I.C.
Certipcate of Authorization #9503
Evaluation Report 037940.02.12-R7
FL30674-1112
Revision 7: 04/18/2016
Page 8 of 8