HomeMy WebLinkAboutConstruction Plan & Boundary Survey{( DRAWING INDEX SHEET SHEET TITLE 01 GENERAL NOTES 02, 02A STRUCTURE/FOUNDATION PLANS 03 SUPPLEMENTAL DETAILS 04 SUPPLEMENTAL DETAILS GENERAL NOTES A. DESIGN CRITERIA 1.0 REFERENCED STANDARDS 1.1 FLORIDA BUILDING CODE, 5TH EDITION 1.2 ASCE 7-10 1.3 ASTM SPECIFICATIONS FOR CONCRETE 1.4 ACI 318-LATEST EDITION FOR STRUCTURAL CONCRETE 1.5 ADM 2010 1.6 AA ASM35, AA ADM 1 2.0 DESIGN LOADS 2.1 DEAD LOADS: MEMBER SELF -WEIGHT 2.2 LIVE LOADS: 300 LB VERT. LOAD ON PRIMARY MEMBERS 200 LB VERT LOAD ON PURLINS 2.3 DESIGN WIND SPEED PER F.B.C., CH. 16 LATEST EDITION Vult: 150 M.P.H. Vasd: 116 M.P.H. 2.4 RISK CATEGORY: 1 2.5 EXPOSURE CATEGORY: B 2.6 WIND LOADS PER F.B.C. TABLE 2002.4 (MWFRS) FOR 20x2OxO.O13" MESH SCREEN: HOR PRESSURE ON WINDWARD SURFACES: 31 PSF HOR PRESSURE ON LEEWARD SURFACES: 22 PSF VERT PRESSURE ONSCREEN SURFACES: 09 PSF VERT PRESSURE ON SOLID SURFACES: 25 PSF 2.7 FOR Hx140.013" MESH SCREEN, APPLIED FACTOR: 0.88 2.8 FACTOR APPLIED TO ALLOWABLE STRESS DESIGN PRESSURES: 0.6 B. RESPONSIBILITIES 1.0 A LICENSED CONTRACTOR SHALL PERFORM ALL SITE WORK IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2.0 CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISITNG FIELD CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF DEMOLITION, CONSTRUCTION AND/OR FABRICATION. THE CONTRACTOR SHALL VERIFY THAT THE HOST STRUCTURE/FOUNDATION IS IN GOOD CONDITION WITH SUFFICIENT STRENGTH TO SUPPORT PROPOSED STRUCTURE. THE ENGINEER OF RECORD IS TO BE CONTACTED IN WRITING FOR CLARIFICATION IF DISCREPANCIES ARISE. 3.0 THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS ASSOCIATED WITH WORK TO BE COMPLETED. THIS IS TO INCLUDE ALL SHORING AND/OR BRACING REQUIRED FOR COMPLETION OF PROJECT. 4.0 THE ENGINEER SHALL NOT BE RESPONSIBLE FOR DAMAGES CAUSED AS A RESULT OF THE CONSTRUCTION EFFORTS. 5.0 THESE DRAWINGS AND DETAILS HAVE BEEN PREPARED AND ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND/OR MANUFACTURER. CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD PRIOR TO CONSTRUCTION IF SPECIAL SITE CONDITIONS ARISE FOR THE FOUNDATION OR HOST STRUCTURE. C. MATERIALS 1.0 CONCRETE / FOUNDATION 1.1 SOIL 1.1.1 MIN. ALLOWABLE SOIL BEARING PRESSURE: 500 F 1. 1.2 PRIOR TO CONCRETE PLACEMENT, TREAT E SUBSURFACE FOR TERMITES IN ACCORDANCE WITH F.B.C. REQUIREMENTS FOR SUNROOMS. NOT REQUIRED FOR EXTERIOR SCREENED ENCLOSURES. 1.1.3 CONCRETE PLACED OVER A POLY VAPOR SHIELD WHERE APPLICABLE. HIRS CH PROPERTY 7988 PLANTATION LAKES DR, PORT ST LUCIE, FL 34986 1.2 CONCRETE 1.2.1 ALL CONCRETE SHALL BE 3000 PSI MINIMUM. 1.2.2 CONCRETE SHALL CONFORM TO ASTM C94 FOR: 1.2.2.1 PORTLAND CEMENT, TYPE 1 - ASTM C 150 1.2.2.2 3/4" AGGREGATE MAXIMUM - ASTM C33 1.2.2.3 AIR ENTRAINING, +/- I % - ASTM C260 1.2.2.4 WATER REDUCING AGENT - ASTM C494 1.2.2.5 CLEAN POTABLE WATER 1.2.2.6 OTHER ADMIXTURES SHALL NOT BE PERMITTED 1.2.3 ALL SLABS ON GRADE SHALL BE 4" THICK MINIMUM 1.3 REINFORCEMENT 1.3.1 FIBERMESH (3/4" PER CU. YD.) MAY BE USED IN LIEU OF WELDED WIRE MESH IF APPROPRIATE ACI AND ASTM REQUIREMENTS ARE MET. 1.3.2 METAL WELDED WIRE MESH (WWM) SHALL CONFORM TO ASTM A185. 1.3.3 STEEL REINFORCEMENT SHALL BE ASTM A615 GRADE 60 WITH Fy = 60 KSI (U.O.N.) 1.4 PREPARE AND PLACE CONCRETE IN ACCORDANCE WITH ACI MANUAL STANDARD PRACTICE PARTS 1,2 & 3 ALONG WITH HOT WEATHER CONDITION RECOMMENDATIONS. 1.5 IF UTILIZING AN EXISTING SLAB/FOOTING, CONCRETE SLAB SHALL BE A MINIMUM OF 4" THICK AND VISIBLY FREE OF DETERIORATION, SPALLING OR EXCESSIVE CRACKING. CONTRACTOR TO VERIFY THAT EXISTING FOOTING IS A MINIMUM OF 12" WIDE AND 8" DEEP BELOW EXISTING SLAB. IF NOT, SEE FOOTING DETAILS FOR FOOTING DESIGN MINIMUM REQUIREMENTS. 2.0 ALUMINUM 2.1 ALL STRUCTURAL ALUMINUM SHALL BE MIN: 2.1.1 EXTRUSIONS: 6005 T5 ALLOY 2.1.2 TUBES: 6063 T6 ALLOY 2.2 STRUCTURAL ALUMINUM DESIGN SHALL CONFORM TO "PART 1-A - SPECIFICATIONS FOR ALUMINUMM STRUCTURES - ALLOWABLE STRESS DESIGN" OR "PART 1-B'- SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN" OF THE LATEST ALUMINUM DESIGN MANUAL. 2.3 PROVIDE DIELECTRIC SEPARATION WHERE ALUMINUM COMES IN CONTACT WITH STEEL OR PRESSURE TREATED LUMBER 2.4 ACTUAL WALL THICKNESS OF EXTRUDED ALUMINUM MEMBERS SHALL NOT BE LESS THAN 0.040 INCH 2.5 SELF -MATING BEAM SECTIONS TO BE STITCHED WITH # 12 SMS SPACED AT 6" ON -CENTER FROM THE ENDS AND 24" ON -CENTER THROUGHOUT THE REMAINDER: 2.6 MINIMUM THICKNESS FOR FORMED SHEET ALUMNUM STRUCTURAL WALL PANELS (KICK -PLATES) SHALL BE 0.024". 2.7 Bx140.013" MESH SCREEN SHALL BE USED UNLESS APPROVED BY THE ENGINEER OF RECORD. 2.8 ROOF BRACING SHALL BE A MINIMUM OF 2"x2"x0.050" 2.9 DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY CONTRACTOR. 2.10 FOR PICTURE WINDOW MODIFICATIONS TOEXISTING SCREEN ENCLOSURES, THE CONTRACTOR SHALL VERIFY THE EXISTING SCREEN ENCLOSURE IS IN STRUCTURALLY SOUND CONDITION AND MEETS THE REQUIREMENTS OF THE DETAILS WITHIN THESE PLANS. 2.11 IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPA, THE ENCLOSURE SHALL MEET THE FLORIDA BUILDING CODE, RESIDENTIAL SECTION R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS IN ITS ENTIRETY. 2.12 SCREEN ROOM ALUMINUM ROOF SECTIONS (COMPOSITE OR PAN) SHALL BE SELECTED/DESIGNED FOR THE WIND PRESSURE STATED WITHIN THE WIND LOADS SECTION OF THESE GENERAL NOTES. THE SELECTION OF THESE ROOF SECTIONS WAS BASED ON THE SPAN TABLES PUBLISHED AND CERTIFIED BY INDEPENDENT FLORIDA LICENSED ENGINEERS WITH THE UP-TO-DATE N.O.A. T i i F­ ' P V,NS AidD ALL PRw"`PCStD .fl0RK r AIt SUBJECT TO ANY CORRECTIONS REMUIM BY FIELD INSPECTORS THAT MAY SI?i", NE CES0 A IfY Ie 9 CEDER. TO. ' L CODES. ST LUCIE COUNTY WILDING DIVISION REVIEWED FOR COMPLIANC REVIEWED ED BY PLANS AND PERMIT v MUST BE KEPT ON JO OR �/ •y NO INSPECTION WILL BE MADE 3.0 FASTENERS y. ; IL 3.1 ALL FASTENERS SHALL COMPLY WITH ASTM A153. 3.2 ALL CONCRETE SCEWS SHALL BE TAPCON, SIMPSON, HILTij v% REDHEAD OR APPROVED EQUAL.3.3 ALL LAG BOLTS /// 3.4 INTO USE STAINLESS S LTEEFRAMING. E 3 0 1ALL HAVE A 8 8 FORMED FASTENERS DIA ///i/�► �, CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER, UNLESS OTHERWISE NOTED ON PLANS OR MANUFACTURER OF GALVANIZED BOLTS SPECIFIES FOR USE WITH ACE PRESSURE TREATED WOOD. 3.5 THE MIN CENTER TO CENTER SPACING FOR SMS SHALL BE 3/4" AND THE MIN CENTER TO EDGE DISTANCE SHALL BE 1/2" UNLESS OTHERWISE NOTED. 3.6 FOR lx2 MEMBERS TO MASONRY/CONCRETE USE GALVANIZED 1/4"x2-3/4" TAPCONS OR SIMILAR AT 24" O.C. 3.7 FOR lx2 MEMBERS TO WOOD FRAME USE #14x2-3/4" WOOD SCREW AT 24" O.C. (TYP.) 3.8 FOR lx2 MEMBERS TO ALUMINUM USE #10xl-1/2" SMS OR TEK SCREWS AT 24" O.C. (TYP.) 3.9 FOR lx2 MEMBERS INSTALLED THROUGHOUT AN "OPEN VIEW" OR "PICTURE WINDOW" ASSEMBLY, THE FASTENER SPACING SHALL BE REDUCED TO 12" O.C. MAX. ALUMINUM EXTRUSION DL%IENSIONS HOLLOW SECTIONS 2x2 2"x2"x0.050" 2x3 2"x3"x0.050" 2x4 2"x4"x0.050" 2x5 2"x5"x0.050" OPEN -BACK SECTIONS Ix2 Vx2"x0.044" Ix3 1"xYx0.045" SNAP SECTIONS 2x2 2"x2"x0.045" 2 x 3 2"x3"x0.050" 2x4 2"x4"x0.045" SELF -MATING SECTIONS (SMB) 2 x 4 2" x 4" x 0.044" x 0.100" 2x5 2" x 5" x 0.050" x 0. 118" 2x6 2" x 6" x 0.050" x 0.120" 2x7 2" x 7" x 0.057" x 0.120" 2 x 8 1 2" x 8" x 0.072" x 0.224" 2 x+10 2" x 9" x0.082" x 0.224" 2 x2" x10" x 0.092" x 0.374" H Q A 0 cn Q Q rsi w w a O Ca - Oa ou •� a a 0Aw 0, � F'Fx � O 0 Lei K� ��� lll��� W N Ei 'n wO t W' Na - P: e: (941) 456-7535 admin@southsunengineering.com a; w: www.southsunengineering.com CONTRACTOR: TREASURE COAST HOME - IMPROVEMENTS, INC. PROPERTY ADDRESS: 988 PLANTATION LAKES DI PORT ST LUCIE, FL 34986 DATE: 11/30/2017 PROJECT NO: A1702155 SHEET: - Sol , 6'-10" `' X I N N 1 6'-10" T 2X2 4'-7" 2X5 SMB N N >C 8'-0" 2X5 SMB I 1X2 2X2X.050(TYP) 2X2X.050(TYP) SCREEN ENCLOSURE PLAN SCALE: 1/8" = 1'-0" HOST 24" O/H STRUCTURAL GUTTER � ----- ------------- I I I � Q o' I I ��� 0 1 I I 2X2 I 5'-6" — 2X2 I 2X2 30'-3" X N CIO CIO rA COO X 8'-0,, 21'-6' ! 0'-711 N N N I N N N N 2X2 2X2 2�O`rO z— - Qh0 ti 2X2 2X2 'TYP 0 i 0y /, \���\tyy� \\\ y�. oC) m ////�0�11f I1i11•. T-0" 3'-0" TA i2SE PLAPVS AiND ALPROPOSED— � ���ld ��l�P�t`9' APOSE 2'-6" 1 X2 2X3 � 1X2 ARE JRJECT TO ANY CORRECTIONS . 6 -61- COO �� �� REQUIRED BY HELD INSPECTORS THAT cV N M N N 8'-011�." Rya• tlB'•� ���®Eq. TO ' .. . �� `- ¢_•d, CODES." 2X3 - 2'6"Z-�j 6-10" - -�- 6'-10" 614" -�- 64" --I-- 64"-- 6-10" 64" - - — 2X2X.050(TYP) 45'-9" LEGEND: INDICATES CABLE BRACE. SEE DETAILS 2/03 & 3/03 — 1 N 1 M I-z w w 00 r, l� M i v� � W 0 in Fall 1171y`.J 1 � � �W CHI 04 Z tn \Z C) WN a P: (941) 456-7535 e: admin@southsunengineering.com w: www.southsunengineering.com CONTRACTOR: TREASURE COAST HOME IMPROVEMENTS, INC. PROPERTY ADDRESS: 7988 PLANTATION LAKES DR DATE: 11/30/2017 PROJECT NO: A1702155 S02 24'-0" 20'-0" 17'-0" 1 33'-7" 1 EXISTING DECK BY OTHERS 44'-0" I T-0" VOTREW FDN/SLAB TO EXISTING FDN/SLAB, DRILL A 1/2" DIA HOLE TO A DEPTH OF 6" INTO EXISTING CONCRETE. PROPERLY CLEAN HOLE AND ENSURE CONCRETE SURFACE IS FREE FROM LOOSE AGGREGATE. FILL DRILLED CAVITY W/ STRUCTURAL EPDXY TO PROVIDE A MIN BOND STRENGTH OF 4000 PSI. EMBED A 12" #3 BAR 6" INTO EXISTING CONCRETE. #3 BAR TO BE SPACED AT Y O.C. MAX 20'-0" SLA 31FO,OTING, '3-1/2",SLABNHN/W/6 6,-WI'4.WY.4WWR )RFIB�RMFSfL}ATOM'PRO /PERLjt'COIv�, CN I' % FILL FREE OF ORGAN(CMAfi9F , !' ' , ! [&ff .'I/$"/PERT SLOPE] ,'/'L2"X�12'i1VION0 EO�OTJN,Ci /'/'/'� CONCRETE PLAN FOUNDATION PLAN SCALE: 1/8" = 1'-0" 22'-0" 6X6 W 1.4XW I.4 W WF Q OR FIBERMESH IF ALLOWED a r� �\/ D/ �— \\ \ 0 3000PSI 12"xl2"\� COVER MONO FOOTING W/ cV M (2) 95 BAR CONT OVER STEEL CIYP.) ON 3" CHAIR (PYP.) 12" Q 1 MONOLITHIC FOOTING DETAIL a o w w w GM N 2A SCALE: N.T.S. �Q �aZ \� II I I I1// �-tn z `\\ x U. W d1 QO #5 REINFOON1 8 * C) 25" LAP MIN. / l •• ►- a/ 45 REINFORCING BAR PIK #5 LAP SPLICE 101, #5 STD. 90' HOOK W N 2 LAP SPLICING DETAIL Z In 2A SCALE: N.T.S. H a Fm :?6n T4i Fi 1 YD F� "Tirt��� t��a;l�dS A�d� a,�L ��vl�i�5�� �vGREa; ARE SUBJECT MANY CORRECTIONS W REQUIRED BY FiElb INSPECTORS THA5' Q x RY-II~m onmp TO. .. U W N P-1 P: (941)456-7535 e: admin@southsunengineering.com Copy w: www.southsunengineering.com F L CONTRACTOR: TREASURE COAST HOME IMPROVEMENTS, INC. PROPERTY ADDRESS: 988 PLANTATION LAKES D PORT ST LUCIE, FL 34986 DATE: 11/30/2017 LEGEND: PROJECT NO: A1702155 INDICATES CABLE BRACE. SEE DETAILS 2/03 & 3/03 SHEET: 1\ S02A SECONDARY ANGLE MIN. 1/8" THICK W/ (7) #12 SMS INTO l Z 1/8" STAINLESS STEEL CABLE ' COLUMN EA. SIDE (TYP.) COLUMN VARIES. SEE SHEEP Q f MIN. 3000 PSI CONC W/ 6x6 - i • � 02 FOR SIZING. " � 1/4" CONCRETE ANCHOR (TAPCON XL OR EQUAL) EAVE RAIL WHERE CABLE ATTACHMENT o�bo W.W.M. OR FIBERMESH (TYP.) Q AT EACH ANGLE EA. SIDE W/ MIN. 2-1/4" EMBED. 2"x2"x 1/8" ANGLE W/ (2) #12x3/4" IS INSTALLED ON INTE L COLUMN INTO FOOTING TYP.). NOTE: FOR SECONDARY SMS EA. SIDE (TYP.) ' "U ' "T"E r A '1, R a l • ra a 0 I , c _ e rl�s; rr�:Sa ��;�.� 14L,:a� t°����i�a�P;I, ANGLE, USE 2 ANCHORS FOR COLUMNS 2x6 AND LARGER. WHEN FASTENING TO WOOD USE 1/4" o 0 0 0 1/8" CORNER GUSSET g ` p T ANY R � NS GALV. LAG SCREW IN LIEU OF CONC. ANCHORS o ANGLE BRACKET lRla �LY14E� i�PgY �OfislE�i��B�7 OH 1 "x2" OPEN -BACK BASE PLATE oE� AND ENSURE PENETRATION MIN BENEATH. TYP.)INTO 0 (TYP. EA. SIDE) (9) 914 x 3/4" SMS TO 1 �I . C' 4 s P q p 'ply p d 5 STRUCTURAL FRAMINGBENIEATH.(TYPJ — o WALL MEMBERS (TYP.) dI I E9 FIELD INSPECTORS CI7A 0 4" SLAB MIN. SC E A. x 3" MIN. EMBED. CONC. NOTE: IF PAVERS ARE ALUMINUM EXTRUSION SCREW ANCHOR (TAPCON OR EQUAL) (�: � � ? `� �Fq � A v 9 % C�➢! i ,( �F'47 PRESENT, CONCRETE VARIES (TYR) SE SHEET ANCHORSSHALL 3" MIN. COVER 02FOR SIZES 00.1A A,iplyq •P '•'� p Z' ,.� �...-� . (�') PENETRATE INTO 5/16" EYEBOLT W/DBLNUTS. 2 •�• 1/8" STAINLESS STEEL CABLE "xv.APEll ily o v", �' LIB; d?A �.,00E8, FOOTING 2-1/4" MIN. LOCK NUT & WASHER TO BE p __ _ _ _ _ 2-112" MIN. SPACING (Typ,) - CORROSION RESISTANT o o NUN. 3000 PSI CONC W/ 'r' N M ct MIN. 3000 PSI CONC FTG/SLAB W/ (TYP-) a' v 6x6 - IOx10 W.W.M. OR 6x6 - 1Ox10 W.W.M. OR FIBERMESH W FIBERMESH (TYP.) > 1/8" STAINLESS STEEL CABLE (TYP.) : o t SIDE VIEW w Q w w M cJ COLUMN VARIES. SEE SHEET r W a O 2"x2"xl/8" ANGLE W/ (2) #M3/4" 02 FOR SIZING. ® P�,� I v&84 SMS EA. SIDE (TYP.) 1/4" CONCRETE ANCHOR (TAPCON XL OR EQUAL)���` W z M AT EACH ANGLE EA. SIDE W/ MIN. 2-1/4" EMBEDMENTtl "- } O W Q, SECONDARY ANGLE MIN. 1/8" INTO FOOTING CM.). WHEN FASTENING TO WOODML USE I/4" GALV. LAG SCREW IN LIEU OF CONC. ANCHORS 4" SLAB MIN. 1-1/4"x5-5/8"xl-1/8" FLAT BAR \N . Fa a U THICK W/ (2) #12 SMS INTO AND ENSURE PENETRATION MIN 2-1/4" INTO WITH (2) 3/8"x3" CONCRETE \ • F. z COLUMN EA. SIDE (TYP.) STRUCTURAL FRAMING BENEATH. (TYP.) SCREWS ` v 1,., 2 CABLE TO FRAME CONNECTION 3 CABLE TO FOUNDATION CONNECTION 1 "x2" OPEN -BACK BASE PLATE • = air C7 I/j ANCHORED TOFTG W/ I/4" CONC 03 SCALE: N.T.S. 03 SCALE: N.T.S. _ tiN� SCREW (TAPCON XL OR EQUAL) W/ MIN. 2-1/4" EMBED. CONC SCREW (2) 412 SMS (T STRAP TO BE INSTALLED 6" MAX. FROM (2) #12 SMS AT STRAP EAVE RAIL OPTION 1 OPTION -el � (� TO PURLIN (TYP.) iNt4,ow, OCOLUMN AND SPACED AT 24" O.C. TO EAVE RAIL (TYP.) PERPLAN6"MAX MAX. UPRIGHT OR �MIN.3000 PSI CONC FTG/SLAB W/ (TYP.) 1 "x0.06"x6" STRAP SNAPORS _ 6x6- 1Oxl0 W.W.M. OR FIBERMESH w a: - 0 1/16" ALUMINUM R 77 ') O � EAVE SEE SHEET 02 OPEN- 1 0 (4) # 1 Oxl-1/2" SMS EXTERNAL RECEI G u - FRONT VIEW - BACK L PURLIN PER INTO SCREW BOSSES �) pI% 1 SHEEP 02 I (0.062" ANGLE CLIPS MAY S4' 1 f `•' _ L _1 0 - - I USED W/ (2) #12x3/4" SMS EA. LEG) 1 COLUMN TO FOUNDATION CONNECTION FOR 2x4 OR LARGER _ PURLINPERSHEET02 2"x2"x.125"ANGLE EACH (2) 41 Ox4" SMS o SIDE OF PURLIN-CUT TO — — — — 03 SCALE: N.T.S. INTO SCREW Boss (2) #12 SMS EA. SIDE OF PURLIN I 1 LAP OVER COLUMN -FASTEN TO PURLIN W/(2)#12X5/8" IN LIEU OF I" STRAP ON TOP, MAY SMS EACH SIDE -FASTEN TO USE 0.044N1.125"x2" RECEIVING kn I I COLUMN W/(I)#12X5/8"SMS `./ Ix2 OPEN -BACK W/ CHANNEL. NOTCH 2" SIDE OF EACH SIDE -FASTEN TO EAVE 2x2 / 2x3 N ST (4) #1 Ox3/4" INTO BEAM OR LF•i SE PLAN ON SHET I en M #1 Ox2" SMS SPACED I I CHANNEL TO RECEIVE PURLIN I I RAIL ASSEMBLY W/(3)#12X5/8" UPRIGHT (TYP.) Fr SAVE RAIL PER PLAN AT 24" O.C. AND I I I SMS EACH SIDE 02 (T'YP.) (2) #12x3/4"LEG INTO1171� ON EA. SIDE OF COL. I GIRT OR PURLIN CnT.) WAN 6" MAX. (3) 912 SMS EACH SIDE OF COLUMN FASTEN OPEN -BACK FASTEN JAMB TO INTERSECTING MEMBER W/# 10 SMS I I TO EAVE RAIL W/ Fa�i TO LENGTH TO ENSURE 1-1/2" PENETRATION INTO SCREW #12x2" SMS AT 12" O.C. BOSS OF JAMB CM.) COLUMN PER SHEET 02. AND W/IN 6INCHES OFNOTCH COLUMN AS REQD ALTERNATE INTERSECTING MEMBERS Ei H ALTERNATE: SECTNGMEVICEIVIN4)410S S- 5 SLOPED PURLIN TO COLUMN CONNECTION COLUMN PERSHEET02. 6 BEAM/POST TO GIRT/PURLIN CONNECTION W TO INTERSECTING MEMBER W/ (4) #10 SMS- . . FASTEN JAMB TO RECEIVING CHANNEL W/ (2)#12x5/8"SMSEASIDE(TYP.) 03 SCALE: N.T.S. 03 SCALE: N.T.S. ►� w H BEAM SIZE x 2 O V EX: FOR 2x4 SMB USE 8" HEADER (2) 910x4" SMS INTO SCREW V j 7 E•'1 Fi 7L • • 1 - - - - - BOSSES FOR EDGE MEMBER 2x8 SMB i In 1 FASTEN HEADER AT EA END W/ (4) #I Ox3" SMS THRU 1/8" FLAT PLATE W/ �• ILLUSTRATED O JAMB INTO SCREW BOSS OF HEADER (TYP.) (8) #120/4" SMS W/ ALTERNATELY FASTEN HOR_ Z-BAR TO COLUMN W/ (2) MIN. 1/2" EDGE DISTANCE \• N a # 120/4" SMS EA SIDE AND TO HEADER W/ 9120/4" SMS (NOTE: PLATE MAY BE FASTENED AT TOP CORNERS & 6" O.C. STAGGERED. USE SAME INTERNALLY TO BRACE.) FASTENING PATTERN FOR VERTICAL Z-BAR TO COLUMN EDGE MEMBER ORPURLIN etips� P: (941) 456-7535 FASTEN ANGLE TO CONC W/(1) 1/4"x 3-1/2" TAPCON. 4ti¢' WHERE PAVERS ARE PRESENT INCREASE LENGTH OF e: admin@southsunengineering.com TAPCON TO ENSURE PENETRATION INTO FN1D MIN 2-1/4". z BRACE. SEE SHEET • ' I �� w: www.southsunengineering.com a WHEN FASTENING TO WOOD USE 1/4" GALV. LAG SCREW ¢ 02 FOR SIZE — — EAVE RAIL PER PLAN - FASTEN IN LIEU OF CONC. ANCHORS AND ENSURE PENETRATION a TO CAGE BEAM (INTERNAL) MIN 2-1/4" INTO STRUCTURAL FRAMiNGBENEATH. (TYP.) w BEAM SEE — — — - W/ (4) #10xl-1/2"SMS (TYP.) • . I NOTE: 20 z0 a n• SHEET02 3/16" 6005-T5 GUSSET FABRICATED w w F. CONTRACTOR: FOR SIZE • I • SUCH THAT TT FITS INSIDE SMB Q U U FASTEN DOOR JAMB TO Ix2 BASE PLATE W/ (2) WITH NO SIGNIFICANT SLIP �' w TREASURE COAST HOME 910 SMS THROUGH JAMBINTO SCREW BOSS OF Ix2 OPEN -BACK. FASTEN TO COL TOLERANCE. INSTALL FASTENERS 4to o u p p 1x2 (ENSURE PENETRATION INTO Ix2 MIN 1 ") O • (INTERNAL)W/ (2) #IOx1-1/2" LOCATED ALONG THE TOP AND 4. w U p w U IMPROVEMENTS, INC. O O SMS. FASTEN TO EAVE RAIL BOTTOM EDGE OF THE BEAM SO "'1 rr �• Ix2 OPEN BACK A I W/ #12xl-1/2" SMS WITHIN BEAM TY SMS/SIDE THAT NO LESS THAN A 1-1/8' C Ow 1t BTM PLATE (TYP) I \ I I 6" OF COL. AND AT 24" O.C. 2x5 5 - #12 SEPERATION OCCURS BETWEEN z m PROPERTY ADDRESS: 1 FASTENERS OR 1-1/4" IN THE FASTEN ANGLE TO JAMB I NOTCH BEAM TO RECEIVE COL. 2x6 7 - #12 FIELD. MAINTAIN NO LESS THAN ] w O P w O 988 PLANTATION LAKES D W/ (2) #12x5/8"SMS (TYP.) rFOR EDGE MEMBER FASTEN EACH BEAM FACE TO 2x7 8-#12 dF dnH1/2"FROM EDGE OF GUSSET. Li MIN.3000PSICONCFTG/SLABW/ `ORPURLIN COLUMNW/THE SPECIFIED z 2x9 ]0-#l4 FASTENIERSMAYBESTAGGERED 2X4SMB 9/18/36 PORT ST LUCIE, FL 34986 6x6 -lOxlO W.W.M. OR FIBERMESH QUANTITY OF#12x3/4" SMS 4 TO ALLOW ROOM FOR THE 2XSSMB 9/18/36 (,1.�) PER ADJACENT TABLE (IYP.) 2x ] 0 10 - 14 PROPER QUANTITY. SEE ADJ. BRACE TO BEAM USE 1/8" dd FASTENIER TABLE FOR PROPER 2X6SMB 9/l M6 DATE:T PLATE W/ (8) #12x3/4" W� QUANTITY. INTERNAL PURLIN2X7SMB10l20/4011/30/2017 W/ MIN. 1/2' EDGE DISTANCE ATTACHMENT SCREWS MAY BE TE: PLATE MAY BE FASTENED v COUNTED AS GUSSET 2X8SMB 14/28/56 8/16/32 ERNALLY TO BRACE.) CONNIECTION SCREWS.2X9SMB 14/28/56 PROJECT NO: ERNATELY, IN LIEU CONITRACTOR MAY USE SAME PLATE, USE (2) #12x3" SMS PATTERN FOR A -FRAMED 2X9H SMB 14/28/56 A1702155 PURLIN. SEE SROUGH BRACE INTO BIiAMCONFIGURATIONS. 2XlOSMB 15/30/60 02 FOR SIZE O SLIP TOLERANCE 4 TYPICAL DOOR JAMB/HEAD DETAIL JJAAIALTERNATE:�m VER()# OxI i 2" BTM of 7 ROOF BRACING CONNECTION 8 COLUMN TO BEAM CONNECTION 9 GUSSET CONNECTION SHEET: . SCALE: N.T.S. S03 03 SCALE: N.T.S. N(INITERNAL)INTOSCREWBOSSOFJAMB 03 SCALE: N.T.S. 03 SCALE: .T.S 03 21 2x2xl/8" ANGLE EA SIDE OF BEAM W/ (2) # 12x5/8" SMS INTO BEAM AND (2) 9120-1/2" THRU GIRT INTO GUTTER (TYP.) a a w Ha - BEAM -):--,AGE \ GIRT (I x2 OR 202) FASTENED (INTERNALLY) TO BEAM FACE W/ 41 Oxl-1/2" SMS (2 FOR Ix2 OR 4 FOR 2x2) THROUGH BEAM FACE INTO SCREW BOSS OF GIRT. (TYP.) FASTEN GIRT TO GUTTER FACE W/#12 SMS (xl-1/2" FOR Ix2 AND 2-1/2" �FOR 2x2) 18" O.C. AND _wra 6" OF BEAM (TYP.) CLOSE BOTTOM OF BEAM WHEN TRAMMED, USE.044 RECEVING, CHANNEL - FASTEN W/ (2) #12x1/2" SMS EA SIDE TrYP.) TOP VIEW FASTEN GUTTER TO EXISTING WD FASCIA W/ #14x2" SMS AT 18" O.C. STAGGERED TO PREVENT WD SPLITTING. (TYP.) EXISTING WOOD FASCIA cm.) 1/8" GUTTER "STIFFENER" LOCATED AT EACH BEAM -FOR BEAMS GREATER THAN 2,6 INSTALL FASTENERS AT BEAM LOCATION AND BETWEEN BEAMS. FASTEN STIFFENER TO FASCIA W/(2) 414x2" WD SCREW. FASTEN STIFFENER TO GUTTER FLANGE W/ (3) #12x1/2" SMS. (TYP.) EXISTING ROOF DECKING EXISTING DRIP EDGE • STRUCTURAL NOTE: ROOF CLADDING AND GUTTER TRUSS NOT SHOWN FOR C TY PER PLAN EXISTING WOOD FASCIA PROVIDE.062 BACKING AT EACH BEAM CONNECTION SIDE VIEW I BEAM TO GUTTER CONNECTION 04 SCALE: N.T.S. CAGE BEAM OR PURLIN HORIZONTAL OR SLOPED, FASTEN BEAM PER 8/03, FASTEN PURLIN PER 5/03 r _ " FOR EAVE RAIL CONNECTION SEE DETAIL 8/03 COLUMN -SIZE PER PLAN FASTEN COLUMN TO GUTTER SEE DETAIL 1/04 _ GUTTER STIFFENER - SEE DETAIL 1/04 i II Structural Gutter N V 2 TRANSOM DETAIL 04 SCALE: N.T.S. 912X2" WOOD SCREW IS" O/C AND (4) WITHIN 18" OF CONNECTION WOOD FASCIA GUTTER STRUCTURAL GUTTER "STIFFNER' SEE4-01 LOCATTE WITHJIN 6" OF CONNECTION 1/8"X2"XT ALUMINUM ANGLE FASTEN TO WOOD FASCIA W/ (2) 412X2" WOO SCREW FASTEN TO BEAM W/(2) 912X5/8"SMS BEAM PER PLAN- FASTEN GUTTER BACK BEAM W/(4) #12X5/8" SMS WITHIN 18" OF CORNER #12X5/8" SMS 18" O/C AND (4) WITHIN 18" OF CONNECTION TOP VIEW 3 CORNER CONNECTION GUTTER -EDGE BEAM 04 SCALE: N.T.S. WOOD FRAMING i 1/8"x2"X2"ALU1vflNUM ANGLE CUT TO BEAM LENGTH -FASTEN TO EXISTING WD FRAMINGW/(2) I/a°X2" GALV LAG SCREW THROUGH ANGLE LEG INTO WD FRAMING EACH SIDE•STAGGER TO PREVENT SPLITTING FASTEN TO BEAM W/#12X9/16"SMS THROUGH ANGLE LEG INTO ALUM BEAM EACH SIDE 1/8"x2"X2"ALUMINUM ANGLE QUANTITY Fly =BEAM SIZE LESS 1 CUT TO BEAM LENGTH EX: FOR 2X USE (6) EACH SIDE ALUMINUM BEAM FASTEN TO EXISTING WD FASCIA NOS' MAINTAIN ION I W/(2) 1/4"X2" GALV LAG SCREW () O ANGLE AND FROM EDGE OF ANGLE AND THROUGH ANGLE LEG INTO WD BETWEEN FASTENERS FASCIA EIS -STAGGER TO PREVENT SPLTTING-FASTEN TO BEAM ALUMINUM BEAM W/#12X9/16"SMS THROUGH ANGLE LEG INTO ALUM BEAM - EACH SIDE QUANTITY E/S =BEAM SIZE LESS 1 EX: FOR 2X7 USE (6) EACH SIDE NOTE: MAINTAIN 3/8" SEPERATION TOP VIEW FROM EDGE OF ANGLE AND BETWEEN FASTENERS SIDE VIEW 4 BEAM TO WOOD FASCIA CONNECTION DETAIL 04 SCALE: N.T.S. cLi EAVE RAIL PER PLAN z PROVIDE .062 ALUMINUM PLATE 0 ONE SIDE OF CONNECTION. V] FASTEN PLATE TO COLUMN, 5 BRACE & EAVE RAIL EA. W/ (6) #12x5/8" SMS a K-BRACE PER PLAN PRP.OVIDE.062ALUMINUM PLATE ONE SIDE OF CONNECTION. W 04 O COLUMN q O W V4 FASTEN PLATE TO �- & BRACE EA. W/ (6) #12x5/8" SMS 14„r `zz W W GIRT PER PLAN PER PLAN PROVIDE .062 ALUMINUM PLATE ONE SIDE OF CONNECTION. FASTEN PLATE TO COLUMN & BRACE EA W/ (6) 912x5/8" SMS. FASTEN TO BOTTOM PLATE W/ (3) #12x5/8" SMS 1X2 BOTTOM PLATE 5 K-BRACE W/ SIDE PLATE CONNECTION 04 SCALE: N.T.S. THESE PLANS AiNID ALL PRuPOSEO °J�Oe ., ''1 ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY MELD INSPECTORS THAT TQ (-I I cn I 't w ww 00 as I I � o W N W H � N WO W Na p: (941)456-7535 e: admin@southsunengineering.com w: www.southsunengineering.com CONTRACTOR: TREASURE COAST HOME IMPROVEMENTS, INC. PROPERTY ADDRESS: 988 PLANTATION LAKES D PORT ST LUCIE, FL 34986 DATE: 11/30/2017 PROJECTNO: COPY A1702155 SHEET: SO4 A OD1.1111JAKY ANI1 KtCt1K11 SIIKVl-Y h11K A- KFN (;AIII 1 dH ANI1 IMAM- I - [;Atli I u 0 Boun dory Survey Note:' All Bearings & Distances 1 Are As Per Plat Unless . Noted Otherwise. 1 - IU gLU ,^ �. U y • 0 CD U �. 14.• Ali L� N H A"O V Found Comer 173.89' Offset �6rJ•�� 191.44 on ,c o ,55'W 379 Q v� 113 d9 y\ 9a 3• o m 1 ' � � � m � 1B'•6 �.� � �m � i 0 �o -a rc 3 u 3 oW 7;, . 32h ap • 3 u\ _Found Comer 135.56' Offset , Z 19 I ADDRESS: 7988 Plantation Lakes Drive Port St. Lucie, Florida'''""°'` LEGAL DESCRII=:TION: Lot 18, PLANTATION .RESERVE PHASE IIA, according to. the Plat thereof, as. recorded in Plat Book 26, Page:- 13,. 13A & 13B.' of the Public` Records of St- Lucie County, Florida. CERTIFIED T0: A. KEN GAULT JR. AND DIANE L. CAULT; BANK OF AMEI',;ICA, N.A., , ITS SUCd_SSORS' AND/OR ASSIGNS AS THEIR INTEREST MAY APPEAR; AMERICAN PIOI'-iEER TITLE INSURAN('E COMPANY D/B/A CHELSEA TITLE COMPANY '•i. - LET l, ���'``+ � ��� .... = Found 5/8" 6:4) Rod (No. Cap) CURVE I RADIUS I LENGTH CHORD BEARING DELTA C-1 890.00 125.00' - 1?4.90' S20 41 30'E 08 02 50 C-2 890.00 68.93 — 6B.91 S26'5602 E 047614 NOTE': Underground Power FLOOD ZONE: X 'ESERVE PLANTA f(ON � PH ' IIA Lot 1 t EEtla REVISION � 1.It BY ,' •Ty • i' 1..�D1tYt�� r� •I� ftn AC;1tIr1L1WLLr Vv q ILL�QII111�� CF.13"MCATE: Y'hio cmtlty that tWe 3fI6fCH OF 9URYSY. of the hereon y Land SLu•ve OP deacrlbed propaety wnfelna norLNhle end. ooxieot to the beat of my lmowledye ead be8ef• eutc unlen shown, and'meeta the Illnbnam Tedbnlod . .I' £yC 10566 South Federal Highway Btandaeds eat for Burvayoim parauaut Chapter 6IG17-6 F.A.C. by the Florida Board of Lend Bactlon 472.027, Florida Btatutaa. P.O. FWX 696 JWSKN BEACH, FIDRIDA 34958 ]3078 NOT VALID LURE 9 REAL® 1fflL AN ENBOSMD (772) 398 - 8166 suxvsyoH's seal. PAX (772) 337 - 7404 GEORGE II. Anoli JR, ' legal deacrlpSURM tlon e�itpptied #4016 by cllank • ; r e Ld a y o b I\ N `aZN� o E 1 CONNECTOR SCHEDULE UNM . --- N0. 0.- 1 CONCRETE / CUU QRDER Q XCT—! 1 6300 LBS (2) ]/t'o EPOV BOLT (I6) 10d 11 I -- f115M-. MMO A.T fJJ1 IM � E mc. , C 0 W a u m �N U� U t0 N� Lu 'y 00 0 jr 0 y` Oa �Yu X o -s Wo L0 0) rn J w `L U ai z � z w -� g U w Z tf a O ' L � o z ; 0 0 w 1n CA o w Hn w. ES-15-079 o $� 02.16.16 iy 59 pe S3.0 a El G