HomeMy WebLinkAboutPlot Plan & Vecinity Map 10-26-17-PROJECT DESCRIPTION:
,$x290 HANWHA Q.PEAK BLK-G4.1 290 (290W) MODULES
PROOF MOUNTED SOLAR PHOTOVOLTAIC MODULES
SYSTEM SIZE: 5.22kW DC STC
ARRAY AREA #1: 161.82 SQ FT.
ARRAY AREA #2: 161.82 SQ FT.
EQUIPMENT SUMMARY
18 HANWHA Q.PEAK BLK-G4.1 290 (290W) MODULES
01 SB 3.8-1SP-US-40 INVERTER
SHEETINDEX
A-00
PLOT PLAN & VICINITY MAP
A-01
SYMBOLS & SYSTEM DESCRIPTION
S-01
ROOF PLAN & MODULES
S-02
STRUCTURAL ATTACHMENT DETAILS
E-01
ELECTRICAL LINE DIAGRAM
E-02
WIRING CALCULATIONS
E-03
SYSTEM LABELING
P-01 PV WATTS
DS-01
DATA SHEET
DS-02
DATA SHEET
DS-03
DATA SHEET
DS-04
DATA SHEET
V
1Y
RECEIVE® o
OCT 2 6 2017
PERMITTING
St. Lucie County, FL
GOVERNING CODES:
FLORIDA ELECTRIC CODE, 5TH EDITION 2014 EDITION (FEC)
FLORIDA RESIDENTIAL CODE, 5TH EDITION 2014 (FRC)
FLORIDA PLUMBING CODE, 5TH EDITION 2014 (FPC)
FLORIDA BUILDING CODE, 5TH EDITION 2014 EDITION (FBC)
FLORIDA MECHANICAL CODE, 5TH EDITION 2014 (FMC)
ARTICLE 690, NEC 2011 CODE BOOK
NOTE TO INSTALLER:
FIELD ADJUSTMENTS CAN BE MADE TO THE LAYOUT OF THE ARRAY
PA50 ROBLES BLVD,
(E) GATE (TYP.)
66'-811
1 PLOT PLAN WITH ROOF PLAN
A-00 SCALE: 1 "=20'-0"
l
zo
l
71'-10"
N
W S
S
(E) MAIN DISTRIBUTION
PANEL
1-- ROOF #1
(09) HANWHA Q.PEAK BLK-G4.1 290
(290W) MODULES
I
ROOF #2
(09) HANWHA Q.PEAK BLK-G4.1 290
(290W) MODULES
2
PROJECT SITES
HOUSE PHOTO
ST. LU IE COUNTY
BUILDI DIVISION
REVI WED
FOR C IAN
iEVIEWED RV
PLC!N_3 -,:10 P'Ef t.91T
Pry U,i. 6 rJ A
d
Robles Blvd
6507Doris Drive
Santa Clara Blvd
Citrus Park Blvd Citrus
Park Blwl
9 p.
G
3 VICINITY MAP
A 00 SCALE: NTS
RC ENGINEERING, LLC
COA#MAS
2381 CREST RIDGE COURT
SANFORD,FL32T71
TEL 407-474.9181 ERMOCRATES E
CASTILLO • FL PE M90
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
Signature W p�gal
. tom®
- �
y a
1// $
om�
LL°
V
D
'
OOO
Q
AME
U T_
Z 0)
LU
cM
J
Cl) LL
w OV
J LU
Q � a.
ZCO Il'
0 0
m
SHEET NAME
PLOT PLAN &
VICINITY MAP
SHEET SIZE
ANSI B
1111 X 1711
SHEET NUMBER
A-00
Symbols:
Section ..............
Sheet where
x section is located
x-xx
Elevation ...........
Detail ID Letter
Sheet where
*��sectlon is located
Detail ................
Detail ID Letter
x
Sheet where
section is located
Detail ...............
(Enlarged Plan)
�--- Detail ID Letter
(AArea to be enlarged
x'
Sheet where
section is located
Keyed Notes .......... O Keyed note designation
on applicable sheet
Ground Terminal .....
Grounding Point/rod.... .I.
Solar Panel .........gEn
or 00 odule with Source
MACircuit number
Combiner Box ..........
CB
DC Disconnect ..........
DCD
Main Distribution
MDP
Panel......................
Fuse ......................
�,—
Overcurrent Breaker..
Inverter ....................
Transformer
Automatic ...............
: ATs
Transfer Switch
Abbreviations:
AC
Alternating Current
APPROX
Approximate
AWG
American Wire Gauge
CB
Combiner Box
DC
Direct Current
DCD
Direct Current Disconnect
DISC
Disconnect
(E)
Existing
EL
Elevation
EQ
Equal
JB
Junction Box
MCB
Main Combiner Box
MFR
Manufacturer
MIN
Minimum
MISC
Miscellaneous
(N)
New
OCPD
OverCurrent Protection Device
POCC
Point Of Common Coupling
PV
Photovoltaic
SF
Squarefoot/feet
STC
Standard Test Conditions
TBD
To Be Determined
TYP
Typical
VIF
Verify In Field
WP
Weather Proof
ST. LUCIE COUNTY
BUILDING DIVISION
REVIEWED
FOR CO PLIANT W�✓"'
REVIEWED BY
�'D
System Descriptio DATE -� 16 - 1
Il9l" !'.il TIEIO
This system is a grid -tied, PV system, with PV, `inn consisting'""
18 HANWHA Q.PEAK BLK-G4.1 290 (290W) MODULES with a combined STC ra ed do
output power of 5,220W. The modules are connected into 01 SB 3.84SP-US-40
INVERTER. The inverter has electronic maximum power point tracking to maximize
energy captured by the PV modules. The inverter also has an internal ground fault
detection and interruption device that is set to disconnect the array in the event that a
ground fault that exceeds one ampere should occur. The inverter has DC and AC
disconnect integrated system and labels are provided as required by the National
Electric Code
o°
PV Modules ....... : b
p 00
Microinverters—► Junction 0oo0
Point of ° `�
Box O Utility m
Connection m
Utility Meter e(�
v.0
Figure 1: PV System Block Diagram
When the sun is shining, power from the PV array is fed into the inverter, where
it is converted from DC to AC. The inverter output is then used to contribute to the
power requirements of the occupancy. If PV power meets the requirements of the
loads of the occupancy, any remaining PV power is sold back to the utility. When
utility power is available, but PV power is not available, building loads are supplied by
the utility.
The inverter meets the requirements of IEEE 1547 and UL 1741. This means that
if it detects a loss of utility power, it will automatically disconnect from the utility.
When utility voltage is restored, the inverter automatically reconnects to the utility
grid after verifying utility voltage and frequency stability.
On a day with average Florida sunshine, this system outputs 20.34 kWh per day
on site.
i i�rr r 2
1K� tixr1 14x cd ..
RC ENGINEERING, LLC
COA.28d45
2381 CREST RIDGE COURT
SANFORD, FL 32771
TEL 407474-9181ERMOCRATES E.
CAS'nLLO -FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
®an.erp
f ' na Pat
00000
�CP _ a
�Z Q
.
Qo
PROJEV WkMEe�
Ppn
W
UT
Z
0)
LLI _
IX CM
J
LL
0� OV
0W
Q
U.)a
��
Z
O LL
m
SHEET NAME
SYMBOLS &
SYSTEM
DESCRIPTION
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
A-01
-MODULE TYPE, DIMENSIONS & WEIGHT
NUMBER OF MODULES = 18 MODULES
MODULE TYPE = HANWHA Q.PEAK BLK-G4.1 290 (290W) MODULES
-MODULE WEIGHT = 41.45 LBS / 18.8 KG.
MODULE DIMENSIONS = 65.7" x 39.4" = 17.98 SF
UNIT WEIGHT OF ARRAY = 2.31 PSF
ARRAY & ROOF AREA
CALC'S (ROOF #1)
ARRAY AREA = 161.82 SQ. FT.
ROOF FACE AREA = 201.50 SQ. FT.
161.82 / 201.50 = 80.31% OF ROOF
FACE AREA COVERED BY ARRAY
DESCRIPTION (ROOF #1)
ROOF TYPE - METAL ROOF
ROOF TILT -18.4°
ROOF AZIMUTH - 354°
STANDING SEAM SPECING -16" O.C.
ARRAY & ROOF AREA
CALC'S (ROOF #2)
ARRAY AREA = 161.82 SQ. FT.
ROOF FACE AREA = 201.50 SQ. FT.
161.82 / 201.50 = 80.31% OF ROOF
FACE AREA COVERED BY ARRAY
DESCRIPTION (ROOF #2)
ROOF TYPE - METAL ROOF
ROOF TILT -18.4°
ROOF AZIMUTH -1740
STANDING SEAM SPECING -16" O.C.
2 PVC CONDUIT RUN
TRENCH
Lu
WIND ZONE 2 (TYP.)
WIND ZONE 3 (TYP.)
WIND ZONE 3 (TYP.)
1 ROOF PLAN & MODULES
S-01 SCALE: 1/16" = V-0"
N
w E
S
(E) MAIN DISTRIBUTION PANEL
(E) UTILITY METER
(N) AC DISCONNECT
(N) PV METER (IF REQUIRED)
(N) SB 3.8-1SP-US-40 INVERTER
3/4" PVC CONDUIT RUN
(N) JUNCTION BOX (TYP.)
ROOF #1 /
TILT - 18.4° �.. l.. a_o° WIND ZONE 3 (TYP.)
AZIM. - 354°
a o° I-- "" ROOF #1
�- (09) HANWHA Q.PEAK BLK-G4.1
290 (290W) MODULES
WIND ZONE 3 (TYP.)
ii7WIND
OOF#2
9) HANWHA Q.PEAK BLK-G4.1
0 (290W) MODULES
2) PV ROOF ATTACHMENT @ 16"
32" O.C. MAX
) IRONRIDGE XR10 RAIL (TYP.)
ZONE 2 (TYP-)
GENERAL INSTALLATION PLAN NOTES:
1) DRAWINGS SHOWN MAY NOT REFLECT FIELD CONDITIONS.
CONTRACTOR TO FIELD VERIFY CONDITIONS PRIOR TO
INSTALLATION.
2) CONTRACTOR MAY LOCATE PV MODULES TO DIFFERENT
LOCATION THAN SHOWN, BUT SHALL NOT PLACE PV MODULES
IN WIND ZONE 3. UNLESS NOTED OTHERWISE IN NOTE 3 BELOW.
3) ROOF ATTACHMENTS TO SYP TRUSSES SHALL BE INSTALLED
AS SHOWN IN SHEET S-02 AND AS FOLLOWS FOR EACH WIND
ZONE:
WIND ZONE 1: 4'-0" O.C.
WIND ZONE 2: 2'-8" O.C.
WIND ZONE 3: 1'4" O.0
SEE SHEET S-02 FOR SUPPORTING CALCULATIONS.
4) EXISTING RESIDENTIAL BUILDING IS ASSUMED TO BE METAL
ROOF WITH MEAN ROOF HEIGHT LESS THAN 30 FT AND SYP 2X4
WOOD ROOF TRUSSES SPACED 24" O.C. EXISTING ROOF SLOPE
FOR SOLAR SYSTEM RETROFIT IS ASSUMED TO BE BETWEEN 7
TO 27 DEGREES. CONTRACTOR TO FIELD VERIFY AND SHALL
REPORT TO THE ENGINEER IF ANY DISCREPANCIES EXIST
BETWEEN PLANS AND IN FIELD CONDITIONS.
NOTE TO INSTALLER:
e "
FIELD ADJUSTMENTS CAN BE MADE TO THE LAYOUT OF THE ARRAY
a
® a
�
0
Q
31
`9.4
I
U
L6
Q
HANWHA Q.PEAK
l l
BLK-G4.1 290
(290W) MODULES
LEGEND
JB
- JUNCTION BOX
INv
-INVERTER
Dc
- INTEGRATED DC DISCONNECT
SLD
- SOLAR LOAD CENTER
PM
- PRODUCTION METER
MDP
- MAIN DISTRIBUTION PANEL
O ❑ - VENT, ATTIC FAN (ROOF OBSTRUCTION)
0 - PV ROOF ATTACHMENT
- -RAFTERS
---- - CONDUIT
CB - COMBINER BOX
RC ENGINEERING, LLC
COA 02S345
2381 CREST RIDGE COURT
SANFORD,FL32771
TEL 407.474alSIERMOCMTES E
CASTILLO. FL PE M550
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
ea
e�8d•rry���
00000 e
��® f
o
� a4
°
OJECT N�ll 91
6poloaa°geed•
U
Z rn
W M
0 ❑ J
Fn cn LL
W EE LLI
p
Q �a
w
Z
0 LL
m
SHEET NAME
ROOF PLAN &
MODULES
SHEET SIZE
ANSI B
1ill X 17"
SHEET NUMBER
S-01
130 120 115
1 0 /115 t 1}30
15� / 120
,i , 1
a ice.
(N) END/MID CLAMP v sm,`t�as
I_�; t! 140
ALUMN. "L" BRACKET N UNIRAC RAIL TYP. lag I '-a
PV MODULE � () ise - sly a.�..
W/3/8" SS BOLT & NUT
ISO
140 —
160
Notes: ISO Y
1. Values are ueimata design 3-second gust
wind speeds in miles pexpr hom- (m/s) at SI - _ _ 170
ft (20a) above ground for Eosure C cat- d avo, -
egory.
2. Linear interpolation between contours 160
E 3. 1IslandSTANDING SEAM ROOF is pe.1-dd.
s and coastal arras outside tbe' -- -
lost contour shall use the last wind d 170 My
(N) S-5 PROTEA BRACKET CLAMP rantaur of the coastal areaspee
- I _
4. Mountainous terrain, gorges, ocean �.--
proamnt—ies, and special wind regions [moo 180
Mull be examined for unusual wind condi- -^�
Lions.
5 . wind speeds correspond to approximtely 280 i
a 7% probability of —dance in 50 years
(Amoral Exceedance Probability a 0.00243,-
1 ATTACHMENT DETAIL (SIDE VIEW)
S-02 SCALE: 1" = V-0"
(N) END CLAMP
ALUMN. "L" BRACKET W/3/8" SS
BOLT & NUT
1'-4" ON ZONE 3
2'-8" ON ZONE 2
_ATTACHMENT DETAIL (FRONT VIEW'
S-02 I SCALE: 1" = 1'-0"
(N) MID CLAMP
(E) STANDING SEAM ROOF
(N) S-5 PROTEA BRACKET
NRI 2 700 years,. .o
0
1�
c
a
a
a
FIGURE 9809A ULTIMATE DESIGN WIND SPEEDS, VOLT, FOR RISK CATEGORY 11 BUILDINGS
OTHER STRUCTURES ,
Wind Speed Ult (mph) 1fD 131.; Roof5lope 'Calculator'' r'
Rise'• ' Run Slnee
Risk Cate o
it
Wind Speed ASD (mph)
EF&D
Exposure Category
Mean Roof Height
Roof Slope (degrees)
25
Module Area (sq ft)
MEN=
Kzt
1
Height Adjustment Factor, A
1'
,Roof Zone ,
Pnet'(30)
1
16
-27
2
16
-44.6
3
16
-67
P net=KAK]_ztP_(net(30))
Roof Zone ''
Pnet,
1
16
P
2
16
SM761
3
16
1 -67
18.4 I11#
Maximum Uplift per
*fastener Wind Zone 1
297.0
Safe WorkingLoad of S-5
364
Protea Bracket
* Roof attach. at 48" O/C MAX w 2 rails
Maximum Uplift per
*fastener Wind Zone 2
327.5
Safe Working Load of S-5
Protea Bracket
(Allowable Load / 1.67
364
SF)
"Roof attach. at 32" O/C MAX w 2 rails
Maximum Uplift per
*fastener Wind Zone 3
245.1
Safe Working Load ofS-5
Protea Bracket
(Allowable Load / 1.67
258.5
SF)
RC ENGINEERING, LLC
COA N 28345
2381 CREST RIDGE COURT
SANFORD,FL32771
TEL: 407474-9181ERMOCRATES E.
CASTILLO-FL PE 52580
REVISIONS
DESCRIPTION
DATE
REV
PROJE T DEVELOPER
�baaefd
p0n
• Si Seal
W
ll
oo
Oa00000 }`
ee
OPp
o.a
PROJECT NAME
U r'
Z W
LL1 v
Q M
� J
_
(/1 U-
LU W
X O0
C)
a
Q UCO
Q'
Z
O o
f�
SHEET NAME
STRUCTURAL
ATTACHMENT
DETAILS
SHEET SIZE
ANSI B
11" X 1711
SHEET NUMBER
' Roof attach. at 16" O/C MAX w 2 rai Is S-0
2
-----------------
1 I I (2) #10 AWG USE-2/PV WIRE + Red
(2) #10 AWG USE-2/PV WIRE - Black
EGC #8 BARE CU IN FREE AIR
I
I
I
JUNCTION BOX
600 V, NEMA 3
UL LISTED
I
I
(N) INVERTER: #1
SB 3.8-1SP-US-40
OUTPUT: 240 VAC, 16A
NEMA 3REUL ISEFFICIENCYGHTED LISTED, INTERNAL G DI
1 WITH INTEGRATED DC DISCONNECT
I
+—+— G G FG-1 FNIL2 L1
1 I I I
1 I I I
1 I I I
I I I
1 I I
1l II I
----------
(2) #10 AWG THWN-2 + Red
(2) #10 AWG THWN-2 - Black
EGC #8 THWN-2
USE METAL RACEWAYS
FOR ANY DC CIRCUITS
ENTERING BUILDING
PRIOR TO INVERTER DC
DISCONNECTING MEANS
PER 690.31
1 ELECTRICAL LINE DIAGRAM
E-01 SCALE: NTS
SOLAR ARRAY 5.22 kW -DC STC
(18) HANWHA Q.PEAK BLK-G4.1 290 (290W) MODULES TOTAL
(01) STRING OF 09 MODULES CONNECTED TO SERIES STRING
(01) STRING OF 09 MODULES CONNECTED TO SERIES STRING
PV MODULE
GROUNDING SYSTEM
LINE SIDE TAP USING POLARIS TAPS
OR INSULATION PIERCING
TO UTILITY GRID
BI-DIRECTIONAL
UTILITY METER o
1-PHASE, 240V
(N) AC DISCONNECT:
(N) PV METER 240V, 60AMP FUSED L1
(SMUD/GRIDLEY ONLY) NEMA 3R, UL LISTED
(IF REQUIRED) WITH 20A/2P BREAKER 1
L1 I
L1 L1 L1 '1- r✓� L1 L2
L2 --- L2 •J� L2 —
L1
o°o
N N N N
L2
G G — ---�
I N
3) (2) #6 AWG THWN-2
(#6 AWG THWN-2 I G
(1) AWG THWN-2 GND (1) #8 AWG THWN-2 GND I
IN V PVC CONDUIT RUN L— — — — — — — — —
IN 1" PVC CONDUIT RUN
PROVIDE GROUNDING ELECTRODE
CONDUCTOR FROM THE INVERTER
TO AN EXISTING SERVICE
GROUNDING ELECTRODE PER
690.47(B)
(E) MAIN DISTRIBUTro.
PANEL, 100A RATED-4
®j.
(E) MAIN LUG ONLY "�
BREAKER 240V, 100AI2P I
EXISTING GROUNDING
ELECTRODE SYSTEM
1
RC ENGINEERING, LLC
COAN28345
2381 CREST RIDGE COURT
SANFORD,FL32771
TEL'4074749181ERMOCRATES E
CASTILLO. FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
oa
••yY•u..
adi
Signa Sea t.
000e0000000oOO
s
°o
PROJECT , 'k
-'appfvg1g1
U �-
Z 0)
LLI 0 cM
� J
IL
Lu LL
00
0
Q �a
Z � �
m O
SHEET NAME
ELECTRICAL
LINE DIAGRAM
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
E-01
DC CONDUCTOR AMPACITY CALCULATIONS:
ARRAY TO JUNCTION BOX (INV #1):
EXPECTED WIRE TEMP (In Celsius)
33'
TEMP. CORRECTION PER TABLE (310.16)
0.96
NO. OF CURRENT CARRYING CONDUCTORS
4
CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)
0.80
CIRCUIT CONDUCTOR SIZE
10 AWG
CIRCUIT CONDUCTOR AMPACITY
40A
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B)
1.25 X 1.25 X Ise
15.05A
DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16
TEMP. CORRECTION PER TABLE (310.16) X
30.72A
CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X
CIRCUIT CONDUCTOR AMPACITY
Result should be greater than (15.05A) otherwise less the entry for circuit conductor size
and ampacity
DC CONDUCTOR AMPACITY CALCULATIONS:
FROM JUNCTION BOX TO INVERTER (INV #1);
AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT
PER NEC 310.15(B)(2)(c)
+22°
EXPECTED WIRE TEMP (In Celsius),
33'+2Z = 55°
TEMP. CORRECTION PER TABLE (310.16)
0.76
NO. OF CURRENT CARRYING CONDUCTORS
4
CONDUIT FILL CORRECTION PER NEC 310.15(8)(2)(a)
0.80
CIRCUIT CONDUCTOR SIZE
10 AWG
CIRCUIT CONDUCTOR AMPACITY
40A
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B)
15.05A
1.25 X 1.25 X Ise
DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16
TEMP. CORRECTION PER TABLE (310.16) X 24.32A
CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X
CIRCUIT CONDUCTOR AMPACITY
Result should be greater than (15.05A) otherwise less the entry for circuit conductor size
and ampacity
ELECTRICAL NOTES
1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED
. FOR ITS APPLICATION.
2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90
DEGREE C WET ENVIRONMENT.
3.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL
BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO
THE NEAREST RIDGE, HIP, OR VALLEY.
4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING
ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS,
CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,
SUPPORTS, FITTINGS AND ACESSORIES TO FULFILL APPLICABLE
CODES AND STANDARDS.
6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE
NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND
READILY VISIBLE.
8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
MANUFACTURER'S INSTRUCTION.
9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY -IN LUG.
AC CONDUCTOR AMPACITY CALCULATIONS:
No. OF INVERTER
1
EXPECTED WIRE TEMP (In Celsius)
33°
TEMP. CORRECTION PER TABLE (310.16)
0.96
NO. OF CURRENT CARRYING CONDUCTORS
3
CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)
1
#1 CIRCUIT CONDUCTOR SIZE
10 AWG
CIRCUIT CONDUCTOR AMPACITY
40A
INVERTER OUTPUT CONDUCTORS (INV #1
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B)
1.25 X MAX INVERTER OUTPUT CURRENT
20.00A
DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16
TEMP. CORRECTION PER TABLE (310.16) X
38.40A
CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X
CIRCUIT CONDUCTOR AMPACITY
Result should be greater than (20.00A) otherwise less the entry for circuit conductor size
and ampacity
DC PHOTOVOLTAIC POWER SOURCE TO BE INSTALLED
AT INVERTER #1 PER NEC 690.53 & 690.54
OPERATING CURRENT
18.14A
OPERATING VOLTAGE
287.64V
SHORT CIRCUIT CURRENT
24.08A
MAXIMUM SYSTEM VOLTAGE
398.56V
SOLAR MODULE SPECIFICATIONS
MANUFACTURER
HANWHA
MODEL #
Q.PEAK BLK-G4.1 290
PMAX
29OW
VMP
31.96V
IMP
9.07A
VOC
39.19V
ISC
9.63A
MODULE DIMENSION
65.7"L x 39A' W x 1.26"D (In Inch)
INVERTER #1 SPECIFICATIONS
MANUFACTURER
SUNNY BOY INVERTER
MODEL #
SS 3.8-1 SP-US-40
NOMINAL AC POWER
3.8 KW
NOMINAL OUTPUT VOLTAGE
240V
NOMINAL OUTPUT CURRENT
16A
PERCENT OF
VALUES
NUMBER OF CURRENT
CARRYING CONDUCTORS IN
EMT
0.80
4-6
0.70
7-9
0.50
10-20
RC ENGINEERING, LLC
COAR28345
2381 CREST RIDGE COURT
SANFORD, FL 32771
TEL:4W-074.9181ERMOCRATES E.
CASTILLO-FL PE52590
REVISIONS
DESCRIPTION
DATE
REV
1
PROJECT DEVELOPER
�a
tlbOO eoo�.• r
w
cam rd
c
da cv
P
0 �
0
oOee 000, �.
Cyr
ROJ6GT We
U
Z 0)
LV M
U) ILL
OV
Qa
CO
�
Z
O o
m
SHEET NAME
WIRING
CALCULATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEETNUMBER
E-02
ELECTRIC SHOCK HAZARD
IF A GROUND FAULT IS INDICATED
NORMALLY GROUNDED CONDUCTORS
MAY BE UNGROUNDED AND ENERGIZED
LABEL LOCATION:
DC DISCONNECT, INVERTER
(PER CODE: NEC 690.35(F))
[To be used when inverter is ungrounded]
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE UNGROUNDED
AND MAY BE ENERGIZED
LABEL LOCATION:
DC DISCONNECT, INVERTER
(PER CODE: NEC 690.35(F))
[To be used when inverter is ungrounded]
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
DC VOLTAGE IS ALWAYS PRESENT
WHEN SOLAR MODULES ARE
EXPOSED TO SUNLIGHT
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: NEC 690.17(E))
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: NEC 690.17(E), CB
LABEL LOCATION:
INVERTER, JUNCTION BOXES (ROOF), AC DISCONNECT
(PER CODE: NEC690.13.G.3 & NEC 690.13.G.4)
LABEL LOCATION:
CONDUIT, COMBINER BOX
(PER CODE: NEC690.31(G)(3)(4) & NEC 690.13(G)(4)
ADHESIVE FASTENED SIGNS:
• THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT
WHERE IT IS INSTALLED.
• WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD
APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD
COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING].
• ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF
PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER
RESISTANT [IFC 605.11.1.31
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: NEC690.54)
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(D)(7))
[Not required if panelboard is rated not less than sum of ampere ratings
of all overcurrent devices supplying it]
LABEL LOCATION:
EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS. COVERS OR ENCLOSURES
OF PULL BOXES AND JUNCTION BOXES. CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE
CONDUIT OPENINGS ARE UNUSED. (PER CODE: NEC 690.31)
LABEL LOCATION:
DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: NEC690.13(B))
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: CEC 705.12(D)(4))
LABEL LOCATION:
POINT OF INTERCONNECTION
(PER CODE: CEC690.15, 690.13(B))
3" -j
NOTICE
THIS BUILDING CONTAINS
DUAL POWER SOURCES.
THE SECOND SOURCE IS A ih
PHOTOVOLTAIC SYSTEM.
DISCONNECTS FOR THIS
SYSTEM ARE LOCATED IN
MAIN DISTRIBUTION PANEL
LABEL TO BE PLACED AT METER
CAUTION:
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN
AT:® METER AND MAIN
DISTRIBUTION PANEL
AC DISCONNECT
PV METER
ENPHASE AC COMBINER BOX
r%"-N#mlw/j
MARKING CONTENT AND FORMAT
• RED BACKGROUND
• WHITE LETTERING
• MINIMUM 3/8" LETTER HEIGHT
• ALL CAPITAL LETTERS
• ARIAL OR SIMILAR FONT, NON -BOLD
• REFLECTIVE WEATHER RESISTANT
MATERIAL SUITABLE FOR THE
ENVIRONMENT (DURABLE ADHESIVE
MATERIALS MUST MEET THIS
REQUIREMENT)
Pq I
RC ENGINEERING, LLC
COAC2WS.
2381 CREST RIDGE COURT
SANFORD. FL 32771
TEL 407-074-9181ERMOCRATES E.
CASTlLLO. FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
yy0aea••��
e000 esieH, 11i 'als
aw
�pT
PRQJAqT, NAME
LU
Z rn
LU
Q Q
Cf) U.
OV
Z
O o
m
SHEET NAME
SYSTEM
LABELING
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
E-03
10/18/2017 PVVlhatts Calculator
";4NREL
RESULTS
7,423
kWh/Year*
Cautbn: PlmmwBak 5ysten p-f—
pR.fiQbltf alNmtw W PVWaCs', -bde
many bhetent assumpli s am
Month
Solar Radiation
AC Energy
Energy Value
uncetablis ant do M refle2 ra,ucmns
bet— PV tedmot gles = s,L Wm ¢ 1
( kWh r m2 / day)
( kWh l
(g l
dwla testits —W as repesmted by
PVWattsw inpu Pow e.ample, PV —Was
..ul beOc permmarce am not
January
4.30
546
NIA
dMerentidpel tvRtgn PVIVd115L°�' hen lesser
pet(—V modules. Both M+a ane °'"a"
February4.79
650
NIA
mmpanxor s p-ide me wphetkuted PV
-de im mots (such as the System Adviw
MWel at tntp.11samXM.9ov) that allmv rot
March
6.48
681
NIArme
P-se and canp�t modeling of FV
,
April
5.82
695
WA
The a pwed range is b3wd m 30 years or !
actual x�tta data at the 9Nen bcatbn
ane Is mtemed m pm'tl an imitation of
May
5.69
705
,
NIAl
Ole yareem you myht see For more
.
InfomaUnp'easetEfato MSNREL MpDd:
June
5.38
634
WA '
TM Evm Ramt.
,
July
6.66
686
NIA
Dsoar . The PVWal:MS Model (-r
August
5.59
678
N/A
is
s P nded by Itk Natbral R—able
E.W Lebteatay CNRa ), r'rNch Is
oWated by Me AMWM for SustamWe
September
5.27
620
N/A
Energy, LIC CArErce7 I. Me US.
Lxpanmmt Of Ene9v CDOE-) am may be
October
4.85
594
NIA i
used for any Purpose ry Mtseever.
i
The nary DO`IRRISWALLIANCE slag nat
November
4.33
523
NIA
be used In any tepa tatlm, adv dlsf 9,
pub6dN m utter manner what— to t
mememprmmtearry eu,ta'that ad�Cs pr
December
4.02
510
WA
uses Me MWeL DO:JNRWALUANCE shall
not provde ;
Annual
5.10
7,422
0
any support o>rsotmg, tra my m
'
aS ImCa of any IvW wdh rep"'to the use )
of the Mald m any Updates, revmNs m
new.emms or Me Model
YOU AGREE TO If DEANIFY
Location and Station Identification
DOE/NREJAILIANCE, AND T1S AFFILIATES,
OFFICERS ANY
ANID f3DEMA D,
AGAINST ANY 11AIF1 OR DEMAND,
CLAIM
Requested Location
Q
6507 Doris Dr Fort Pierce, FL 34951 USA
INCLUDING REASaiAB1E ATTORNEYS 1
FEES. RELATED 7019UR USE, RaIANCE,
OR ADOPTION OF THE MOD°-L. FOR ANY
Weather Data Source
(TMY2) WEST PALM BEACH, FL
63 mi
PURPOSE NMATSOEVM THE M3 L IS
PRZIdMED BY DOF/Mia./AU14NCE -AS IS- . <
Latitude
26.68° N
AND ANY F)(PRRESS OR IMPLIED
WARRANTIES, INCLUDING BUT NOT
LIMITED TO THE IMPLIED WARRANnES OF
dB
Longitude
80.1° WIIU
I
MERCNANTABILrTY AND FITNESS FOR A 4
---
PARTICULAR PURPOSE ARE EVRESSLY
DISOAIMED. IN NO EVENT SMALL
PV System Specifications (Residential)
'
r
DWNREIALLWICE BE LIALRE FOR ANY
SPECIAL, IWIRSCT OR CONSEQUENTIAL
DMIAGES OR ANY DAMAGES VMATSOEVER,
DC System Size
5.22 kW
INCLUDING BUT NOT LIMITED TO CLAIMS
ASSOCIATED IVIIMTHE LOSS OF DATA DR
MOdUteT a
YP
Standard
PROFITS, WHICH MAY RESULT FROM ANY
,
ACTION IN COlMXT, NEGLIGENCE OR
OrNaNTOmous cUUMTHAT ARISES our
OF OR IN CONNEjCr1a1 WITH TIM USE OR
Array Type
Fixed (open rack)
PERFORMANCE OF THE MODEL.
Array Tilt
18.4°
The ..W oUW I.V.Istamed m l
_'M m 3D yeas of hetm¢al weade
dala (br na rby, , am is Intended m provide
Array
Arra Azimuth
174°
an Imtt i d Me Posw. Waanmral
Varldblily inge—awn for a Fbad (open
System Losses
141%
2ck) PV sy5em at th's bcadm.
Inverter Efficiency
96%
DC to AC Size Ratio
1.1
Economics
Average Cost of Electricity Purchased
No utility data available
from Utility
Performance Metrics
Capacity Factor 16.2%
httpJ/pvwatts.nrel.gov/pvwatts. php
H
sir
RC ENGINEERING, LLC
COAY28345
2381 CREST RIDGE COURT
SANFORD, FL 32771
TEL• 497-474.9191ERMOCRATES E
CASTILLO -FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT D LOPER
too
+���08911�S�y
IFIF��U,
s �^
� OSOO •oO�� � y�® .
°�Q000000°° a
P OJECT E pon
$010609LlgpsQV4
W
U r-
Z rn
w (M
vJ CO LL
LLN�/l w
0 0
J W
Q L a
Co�
Z
0 0
m
SHEET NAME
PV WATTS
SHEET SIZE
ANSI B
11FF X 17"
SHEET NUMBER
P-01
With its top performance and completely black design the new
QYEAK BLIC-134. t is the ideal solution for all residential rooftop applications
thanks to its innovative cell technology UNTUR The world -record cell
design was developed to achieve the best performance under real condi-
tions - even with low radiation intensity and on clear, hot summer days.
LOWELECTRICITY GENERATION COSTS
G Higher yield per surface area and lower BOS costs thanks to
higher power classes and an efficiency rate of up to 18.3%.
l�INNOVATIVE ALL-WEATHER TECHNOLOGY
Optimal yields, whatever the weather with excellent low -light
and temperature behavior.
ENDURING HIGH PERFORMANCE
iLong-term yield security with Anti-PID Technology',
Hot -Spot -Protect and Traceable Quality Tra.QT11.
EXTREME WEATHER RATING
High-tech aluminum alloy frame, certified for high snow
(540OPa) and wind loads (4000Pa) regarding IEC.
MAXIMUM COST REDUCTIONS
Up to 10% lower logistics costs due to higher module
capacity per box.
® A RELIABLE INVESTMENT
Inclusive 12-year product warranty and 25-year
linear performance guarantee2.
THE IDEAL SOLUTION FOR:
toRooftop arrays on
residential buildings
Engineered in Germany
'EUPd aESEAR_
MODULES
Quality Testetl
u>o
ID.40032587
QCELLS
..rosrorm
Phnln�n
OfELL4`
Best porycyslallim
sdw mood. 2014
or�ma
' APT test conditions: Cells at-1500V
against grounded, with conductive me-
tal toil covered module surface, 25'C,
168h
2 See data sheet on rear for further
information.
OCELLS
SPECIFICATIONMECHANICAL
Format 65.7 in x 39.4 in x 1.26 in (including frame)-•1
(1670mm x 1000mm x 32mm)
Weight 41.45lbs(18.8kg) +
Front Cover 0.13 in (3.2 mm) thermally pre -stressed glass with anti -reflection technology
Back Cover Composite film
Frame Black anodized aluminum + + -1
Cell 6 x 10 monocrystalline Q.ANTUM solar cells --
Junction box 2.60.3.03 in x 4.37-3.54In x 0.59-0.75 in (66-77 mm x 111-90mm x
15-19mm), Protection class IP67, with bypass diodes + .•r...,.,..amm.,, '-°�""�
Cable 4mm' Solar cable; (+) z:39.37 in (1000mm), W i39.37 in (1000mm) rr@�
Connector Multi -Contact MC4 or MC4 itaermateable, IP68
POWER CLASS
2SO
295
300 '
MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC' (POWER TOLERANCE +5 W /-O
Po War at MPP'
P_ IW1
290
295
300
Short Circuit Current*
1. [A]
9.63
9.70
9.77
open circuit Voltage*
V. R9
39.19
39.48
39.76
Current at MPP•
IW [A]
9.07
9.17
9.26
Voltage at MPP•
V_ M
31.96
32.19
32.41
Efficiency'
9 [%]
t 17.4
Z 17.7
z 18.0
MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NOC'
Power at MPP'
Pr„ IWl
214.4
218.1
221.8
e Short Circuit Current,
Ix [A]
7.77
7.82
7.88
Open Circuit Voltage*
V. M
36.65
36.92
37.19
Current at MPP'
I_ [A]
7.12
7.20
7.27
Voltage at MPP•
Ve,P M
30.12
30.30
30.49
`1000W.W% 25T. spectrum AM 1.5G
'Measurement tderances STC_3%; NOC c5% 3800W/m*. NOCT, spectrum AM 1.5G
•typzel ralu actual relues may differ
R CELLS PERFORMANCE WARRANTY
.- -
PERFORMANCE AT LOW IRRADIANCE
19 - At least 986/ of nominal power during first year.
aa..
Thereafter max. 0.6%de degradation ear.
s = r •,®,e+n.+,.,....,.,.r 8'a per y
E ________________________ At least 92.6% of nominal power up to 10 years.
z a At least 83.6 % of nominal power up to 25 years.
ti
All data within measurement tolerances.
Full warranties in accordance with the warranty
A s'� terms of the QCELLS sales organisation of your
respective country.
I[LRe
W i
------------------
: I
IRM.IAR4 wwm'1
Typical module pedarmance under low irradiance conditions in
comparison to STCconditicns 4256C, ]000W1m2).
TEMPERATURE COEFFICIENTS
Temperature Coefficient of IQ
a
[%/K] +0.04
Temperature Coefficient of V,c
P [%/K] -0.28
Temperature Coefficient of Pm.
v
[%/K] - 0.39
Normal Operating Cell Temperature
NOCT [11 113 s 5.4 (45 m3°C)
PROPERTIES FOR SYSTEM DESIGN
Maximum System Voltage V_
IV]
1000 (IEC) / 1000 (UL)
Safety Class
I I
Maximum Series Fuse Rating
(A OCI
20
Fire Rating
C (IEC) ! TYPE 1 (UL)
Design load, push (UL)'
(Ibs/ft']
75 (360OPa)
Permitted module temperature
-407 up to +185'F
on continuous duty
(-40•C up to+85°C)
Design load, pull (ULP
Ilbs/119
55.6 (2666Pal,
'see installation manual
QUALIFICATIONS I CERTIFICATES
PACKAGING INPORMATION
UL 1703; VDE Quality Tested; CE-compliant;
Number of Modules per Pallet
32
IEC 61215 (Ed.2); IEC 61730 (Ed. 1) application class A
Number o1 Pallets per 53' Container
30
♦ Se®
Number of Pallets per 40' Container
26
�vE 0 v� US,
C C
Pallet Dimensions ( L x W x H)
68.7 in x 45.3 in x 46.1 in
aH„
G745mm x 1150mm x 1170mm)
Pallet Weight
1435Ins (651 kg)
NOTE: Installation instructions must be followed. See the installation
and operating manual or contact our technical service department for further
information on approved installation and use
of this product.
Nanwha QCELLS America Inc.
.900 Spectrum Center Drive, Suite 1250, Irvine, CA 92618, USA I TEL+1 949 748 59 96I EMAIL inquiry®us.q-cells.com I W® vmnv.gtells.us
�m�QA
RC ENGINEERING, LLC
COAM29345
2381 CREST RIDGE COURT
SANFORD,FL32771
TEL: 407-0749181ERMOCRATES E.CASTILLO - FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
t�
qee®tiY.edo
4�n
Sig lla[ ' y al ®•
^ �y ♦
W �
2.
y a
�
aD
pO
o
O
'00000
\y wry
0aP
PRO
NAME
U11.0
�-
Z
rn
W
Q c�M
0
0 ,J
CO ILL.
W
W
a
J
Q
0
� fY
Z
0
0
LL
W
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
1111 X 17"
SHEET NUMBER
DS-01
Value -Added Improvements
• Superior integration with SMA's
MLPE Power+ Solution
• World's first Secure Power Supply -
now offers up to 2,000 W
• Full grid management capabilities
ensure a utility -compliant solution
for any market
Reduced Labor
• New Installation Assistant with
direct access via smartphone
minimizes time in the field
• Integrated disconnect simplifies
equipment stocking and speeds
installation
Unmatched Flexibility
• SMA's proprietary OptTroc7m
Global Peak technology mitigates
shade with ease
• Multiple independent MPPTs
accommodate hundreds of
stringing possibilities
SMA
Trouble -Free Servicing
• Two-part enclosure concept
allows for simple, expedited
servicing
• Enhanced AFCI technology reduces
false tripping while improving
sensitivity in real arcs
SUNNY BOY
3.0-US / 3.8-US / 5.0-uS / 6.0-US / 7.0-US / 7.7-US
Reduce costs across your entire residential business model
The residential PV market is changing rapidly. Your bottom line matters more than ever -so we've designed a superior
residential solution to help you decrease costs at every stage of your business operations. The Sunny Boy 3.0-US/3.8-
US/5.0-US/6.0-US/7.0-US/7.7-US join the SMA lineup of field -proven solar technology backed by the world's #1
service team, along with a wealth of improvements. Simple design, improved stocking and ordering, value -driven sales
support and streamlined installation are just some of the ways that SMA helps your business operate more efficiently.
And, Sunny Boy's superior integration with the innovative Power+ Solution means installers have even more flexibility in
addressing their toughest challenges. www.SMA-America.com
Technical data
Sunny Bay 3.0-US
208 v
240 V
Input (DC)
Max. usable DC power
3100 W
31 DO W
Max. DC voltage
Rated MPP voltage range
155 . A80 V
MPPT operating voltage range
Min.' DC voltage / start voltage
Max. operating Input current per MPPT
Max. short circuit current per MPPT
Number of MPPT tracker / string per MPPT tracker
Output (AC)
AC nominal.power
3000 W
30DO W
Max. AC apparent power
3000 VA
3000 VA
Nominal voltage / adjustable
208 V / •
240 V / •
AC voltage range
183 - 229 V
211 - 264 V
AC grid frequency
Max. output current
14.5 A
12.5 A
Power factor (cos gyp)
Output phases / line connections
Harmonics
Efficiency
Max, efficiency
97.2 %
97.6 %
CEC efficiency
96 %
96.5 %
Protection devices
Sunny Boy 5.0-US
208 V
240 V
5150 W
515O W
220 - 480 V
3/1
5000 W
5000 W
5000 VA
5000 VA
208 V / •
240 V / •
183 - 229 V
211 - 264 V
24.0 A
24.0 A
97.2 %
07.5 %
96.5 %
97
DC disconnect device
•
DC reverse polarity protection
•
Ground fault monitoring / Grid monitoring
•
AC short circuit protection
•
Allpole sensirwe residual current monitoring unit (RCMU)
•
Arc fault circuit interrupter (AFCI)
•
Protection class / overvoliage category
I / IV
General data
Dimensions (W / H / D) in mm (in)
535 x 730 x 198 (21.1 x 28.5 x 7.8)
Packaging dimensions (W / H / D) in mm (in)
60D x 800 x 300 (23.6 x 31.5 x 11.8)
Weight/ packaging weight
26 kg (571b) / 30 kg (66 Ib)
Operating temperature range
- 25•C.. +60•C
Noise emission (typical)
39 dBlAl
Internal power consumption at night
< 5 W
Topology
Tronsformedess
Cooling concept
Convection
Features
Ethernet ports
2
Secure Power Supply
•'
Display 12x 16 characters)
•
WIAN
•
Sensor module / External MAN antenna
0/0
Warranty. 10 / 15 / 20 years
0/0/0
Certificates and approvals
UL 1741, UL 1998, UL 1699B, IEEE1547, FCC Part 15 (Class A & 8), CAN/CSA V22.2 107.1.1
• Standard features O Optional features - Not available
Data at nominal conditions NOTE US inverters ship with gray lids. • Not functional with Power+ -Solution
Type designation
583.0.1SP-US-40 SB3.8.1SNU&O S05.04SP-USd0
Accessories
q - Sensor module EXarnalTANT WIAN amenna `¢ - -, SMA RaoBep
MO.SEtJL5d0 �� EMANT-USdO Communimnon Kii
1 ROOFCOMMKR-PLUS
-------- ----
............. - ....... -•-j EffidencycurveSUNNY BOY 6.0-lSP-US-40 i--------•------'--
.-_.._'_--._.._.....'....... - .................. .._, i
98
qb......-......................................
94
i�
92 F
70
1 -.•.• Eta lv.-220V1 ra 16-- !
88 _ Etatv�.-375VI
86 ! -•• Era lVw-480A
i
0.0 0.2 0.4 0.6 0.8 1.0
Output power/ Rated power
�t O
9[
RC ENGINEERING, LLC
COA 028345
2381 CREST RIDGE COURT
SANFORD, FL 32771
TEL 407-474-9181ERMOCRATES E
CASTILLO- FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
natar&XttSeal
l
0000ee
Oa
•a • G
fl
cp
r>r!
f 1
'A'` ao' �� a•-�s
0
J1 Cr .�
fp
P
oQ�4sa40999d0
LLJ
Z 0)
w of cM
0 of
W U) LL
W OV
a
L
CO
Z
o
co
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
DS-02
s
am I RAC
A IPLII C4.0UP L06AS.n.Y
SolarMount Technical Datasheet
Pub 100602-1td V1.0 June 2010
SolarMount Module Connection Hardware.................................................................. 1
BottomUp Module Clip.................................................................................................1
MidClamp....................................................................................................................2
EndClamp....................................................................................................................2
SolarMount Beam Connection Hardware......................................................................3
L-Foot...........................................................................................................................3
SolarMountBeams..........................................................................................................4
SolarMount Module Connection Hardware
BE
SolarMount Bottom Up Module Clip
Part No. 321001, 321002
� 1.24
� I-
�
L-►X r1c
Dimensions specified in inches unless noted
• Bottom Up Clip material: One of the following extruded aluminum
alloys: 6005-T5, 6105-T5, 6061-T6
• Ultimate tensile: 38ksi, Yield: 35 ksi
• Finish: Clear Anodized
• Bottom Up Clip weight: -0.031 Ibs (14g)
• Allowable and design loads are valid when components are
assembled with SolarMount series beams according to authorized
UNIRAC documents
• Assemble with one ''/"-20 ASTM F593 bolt, one'/,"-20 ASTM F594
serrated flange nut, and one 1/4" flat washer
• Use anti -seize and tighten to 10 ft-Ibs of torque
• Resistance factors and safety factors are determined according to
part 1 section 9 of the 2005 Aluminum Design Manual and third -
party test results from an IAS accredited laboratory
• Module edge must be fully supported by the beam
* NOTE ON WASHER: Install washer on bolt head side of assembly.
DO NOT install washer under serrated flange nut
Applied Load
Direction
Average
Ultimate
Ibs (N)
Allowable
Load
Ibs (N)
Safety
Factor,
FS
Design
Load
Ibs (N)
Resistance
Factor,
m
Tension, Y+
1566 (6967)
686 (3052)
2.28
1038 (4615)
0.662
Transverse, X±
1128 (5019)
329 (1463)
3.43
497 (2213)
0.441
Sliding, Z±
66 (292)
1 27 (119)
1 2.44
1
41 (181)
0.619
SolarMount Mid Clamp
Part No. 320008, 320009, 320019, 320020, 320021,
320084, 320085, 320086, 320087, 320120, 320122
Mid
Clam
1.00 DISTpN�
8ETIVEEN MODULES^ n
i
Y -
E ►X
Dimensions specified in inches unless noted
SolarMount End Clamp
PartNo. 320002, 320003, 320004, 320005, 320006,
320012, 320013, 320014, 320015, 320016, 320017,
320079, 320080, 320081, 320082, 320083, 320117,
320118, 320123, 320124, 320173, 320185, 320220,
320233.320234. 320331
-►x
_ 1.5 _
MINIMUM
L
NIIGHT r
vAatEs
MODULE
DULL4Pin
vvm TNIoESS
Dimensions spec-u ess- ed
s
SIM
sm UNIRAC
A !'iLTi UNIRAC
• Mid clamp material: One of the following extruded aluminum
alloys: 6005-T5, 6105-T5, 6061-T6
• Ultimate tensile: 38ksi, Yield: 35 ksi
• Finish: Clear or Dark Anodized
• Mid clamp weight: 0.050 Ibs (23g)
• Allowable and design loads are valid when components are
assembled according to authorized UNIRAC documents
• Values represent the allowable and design load capacity of a single
mid clamp assembly when used with a SolarMount series beam to
retain a module in the direction indicated
• Assemble mid clamp with one Unirac 1/4"-20 T-bolt and one Y4"-20
ASTM F594 serrated flange nut
• Use anti -seize and tighten to 10 ft-Ibs of torque
• Resistance factors and safety factors are determined according to
part 1 section 9 of the 2005 Aluminum Design Manual and third -
party test results from an IAS accredited laboratory
Applied Load
Direction
Average
Ultimate
Ibs (N)
Allowable
Load
Ibs (N)
Safety
Factor,
FS
Design
Load
Ibs (N)
Resistance
Factor,
4)
Tension, Y+
2020 (8987)
891 (3963)
2.27
1348 (5994)
0.667
Transverse, Z±
520 (2313)
229 (1017)
2.27
346 (1539)
0.665
Sliding, X±
1194 (5312)
t490 (2179)
1 2.441
741 (3295)
0.620
• End clamp material: One of the following extruded aluminum
alloys: 6005-T5, 6105-T5, 6061-T6
• Ultimate tensile: 38ksi, Yield: 35 ksi
• Finish: Clear or Dark Anodized
• End clamp weight: varies based on height: -0.058 Ibs (26g)
• Allowable and design loads are valid when components are
assembled according to authorized UNIRAC documents
• Values represent the allowable and design load capacity of a single
end clamp assembly when used with a SolarMount series beam to
retain a module in the direction indicated
• Assemble with one Unirac'W-20 T bolt and one %%20 ASTM F594
serrated flange nut
• Use anti -seize and tighten to 10 ft-Ibs of torque
• Resistance factors and safety factors are determined according to
part 1 section 9 of the 2005 Aluminum Design Manual and third -
party test results from an IAS accredited laboratory
• Modules must be installed at least 1.5 in from either end of a beam
Applied Load
Direction
Average
Ultimate
Ibs (N)
Allowable
Load
Ibs (N)
Safety
Factor,
FS
Design
Loads
Ibs (N)
Resistance
Factor,
m
Tension, Y+
1321 (5876)
529 (2352)
2.50
800 (3557)
0.605
Transverse, Z±
63 (279)
14 (61)
4.58
21(92),
0.330
Sliding, X±
142 (630)
1 52 (231)
1 2.72
79 (349)
- 0.555
RC ENGINEERING, LLC
COA • 28345
2381 CREST RIDGE COURT
SANFORD,FL32771
TEL' 407-074.9181ERMOCRATrS E.
CASTILLo. FL PE 52590
REVISIONS
DESCRIPTION
DATE
REV
PROJECT DEVELOPER
P
•••ua••.
o®OooSJCPi��®o �e.c
F
0
LLI
U
Z rn
W �
f) LL
W X LLI
0 X
Q �
0 0
m
SHEET NAME
DATA SHEET
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
DS-03