COMMENT
Comment:
PLANS EXAMINER REVIEW INCOMPLETE William Durden 1215/2017
12/5/2017 Comment: • PLEASE SUBMIT GEOTECHNICAL REPORT IN COMPLIANCE WITH R401 OF THE 2014 RESIDENTIAL
BUILDING CODE.
Comment: • PLEASE FURNISH THE MANUFACTURES TRUSS PLACEMENT DRAWINGS IN DUPLICATE REVIEWED AND
12151217 0APPROVED BY THE DESIGN PERSON OF RECORD IN ACCORDANCE WITH 61G15-30.005 OF THE FLORIDA
ADMINISTRATIVE CODE
12/5/2017 Comment: • PLEASE FURNISH TRUSS ENGINEERING IN DUPLICATE PER 107.2.1 OF THE 2014 FLORIDA BUILDING
CODE
Comment: • ELEVATION ON SURVEY SHOWS THE NEW STRUCTURE'S FINISH FLOOR TO BE FINISHED AT BASE
12/512017 FLOOD ELEVATION. PLEASE SHOW ON PLANS THAT ALL MATERIALS BELOW BASE FLOOD MEETING THE
REQUIREMENTS OF CHAPTER 3 SECTION 322 SUBSECTION R322.1.8 FLOOD RESISTANT MATERIALS. SEESlIRVEY
Comment: • PLEASE FURNISH EITHER THE [CC EVALUATION REPORT OR A EVALUATION REPORT FROM A AND SNT A-4 Tf/EIST NOTE
12/512017 CERTIFIED TESTING LABORATORY THAT THE INSULATION LOCATED BELOW BASE FLOOD MEETS THINNOER GENERAL NOTES
REQURRMENTS OF SECTION R322.1.8 OF THE 2014 FLORIDA RESIDENTIAL CODE FLOOD RESISTANT
MATERIALS. SEE REPORT
12/5/2017 Comment: SEE PAGE A-8 SECTION B FINISH FLOOR ELEVATION IS INCORRECT. SEE SECTION 107 OF THE 2014
FLORIDA BUILDING CODE. ZFVrA-8
DON J. NUELLE , P.E.
11634 SW Rowena ST
Port Saint Lucie, FL 34987
P.E. # 52046
PH. # 561-629-6975
APPLICATION # 1710-0579
CONTRACTOR L & C Construction Inc
OWNER NAME SHERRY ANDERSON
ADDRESS 10725 SOUTH OCEAN DRIVE #482
JENSEN BEACH, FL., 34957
I
•aye �
Comment:
• PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION BLOCK CONTAINING
THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN PROFESSIONAL SPECIFYING THE
12l5/2017
CUBIC VOLUME OF THE CONDITIONED SPACE. SEE CHAPTER 1 SECTION 107 OF THE 2014 FLORIDA
BUILDINGCODE. SEES1TA-2
12/5/2017 Comment
• INSULATION R VALUES STATED ON THE ENERGY CALC'S DO NOT MATCH THE SUBMITTED DRAWINGS RF(4KFCD FNFRGYCALCS TO
FOR REVIEW_ SEE CHAPTER 4 SECTION 402 SUBSECTION 402.1.2 OF THE 2014 FLORIDA ENERGY CODE. SNOW INSULATION IN FIRST
Comment:
PLEASE CLARIFY THE DOOR LOCATED IN THE GARAGE NEAR THE BACK LEFT SIDE. IF THIS IS A DOOR
121512017
PLEASE SHOW THE TRANSITION FROM THE HOUSE TO THE GARAGE FLOOR ELEVATION. SEE SECTION FLOOR TRUSSFS
107 OF THE 2014 FLORIDA BUILDING CODE. T#IS IS A DOOR TO GO UNDER TNF FLOOR TRUSSES
Comment:
SURVEY SHOWS 5 INCH SEPARATION FROM THE PROPERTY LINE. PLANS SHOW 6 INCH SEPARATION. IF
12/512017
THE SURVEY IS CORRECT THE GUTTER IS 5 3/4 OF AN INCH WHICH PUTS YOU OVER THE PROPERTY
LINE. PLEASE CORRECT AND SUBMIT. SEE SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Comment
INCOMPLETE PRODUCT REVIEW AFFIDAVIT. SURKMWOULD SAY 611
• SUBMIT THE PRODUCT APPROVALS, IN DUPLICATE OR PRODUCT REVIEW AFFIDAVIT COMPLETE WITH
FLORIDA PRODUCT APPROVAL OR N.O.A. NUMBER WITH INSTULATION INSTRUCTIONS AND SIGNED
12/5/2017
SEALED AND DATED BY THE DESIGN PERSON OF RECORD FOR ALL COMPONETS AND CLADING IN
ACCORDANCE WITH 553.842 OF THE FLORIDA STATUTES. PRODUCT APPROVALS MUST BE HIGHLIGHTED
OR MARKED IDENTIFYING THE OPENING OR CLADDING COMPONENTS, WITH FASTENERS AND DESIGN
PRESSURES. SEE SPIT A-j
Comment NOTE: IF SUBMITTING 2 COPIES OF PRODUCT APPROVALS (I.E. N.O.A. OR STATE OF FLORIDA
APPROVAL) IN LUE OF THE PRODUCT APPROVAL AFFIDAVIT DOCUMENTS MUST BE HIGHLIGHTED OR
12/5/2017
MARKED IDENTIFYING THE OPENING OR CLADDING COMPONENTS, WITH FASTENERS AND DESIGN
PRESSURES.
Comment: • PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
12/5/2017
SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS.
ZONING REVIEW
INCOMPLETE Lydia Galbraith 111212017
Comment: PROPERTY HAS TWO DIFFERENT FLOOD ZONE ELEVATIONS, AE-7 AND AE-8, BOTH NEED TO BE
11/212017
INDICATED ON THE SURVEY.PLEASE INDICATE THE DIVIDING LINE OF AE-7 AND AE-8 ON THE SURVEY AS
WELL. SFESURW
1102017
Comment: PLEASE PROVIDE THE COST OF CONSTRUCTION.
11=017
Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW_ THE PLANS
EXAMINER MIGHT HAVE ADDITIONAL COMMENTS.