HomeMy WebLinkAboutEvaluation Report Roofing UnderlaymentCREEK
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
TECHNICAL SERVICES, LLC (813)480-3421
EVALUATION REPORT FLORIDA BUILDING. CODE, r EDITION (2014)
Manufacturer: TAMKO BUILDING PRODUCTS, INC. Issued August 22, 2016
P.O. Box 1404
Joplin, MO 64802 RECEIVED
(417) 624-6644
httg://www:tamko.com
Quality Assurance: UL LLC (QUA9625) OCT 2 4 2017
SCOPE Permitting Department
'
Category: Roofing
Subcategory: Underlayments
Code Sections: 1507.2.3, 1507.2.4, 1507.2.8, 1507.2.9.2, 1507.3.3, 1507.4.5.1, 1507.4.5.2, 1507.4.5.3,
1507.53; 1507:5.3.2, 1507.6,3, 1507.6.3.2, 1507.6.5, 1507.7.3, 1507.7.3:2, 1507.8.3,
1507.8.3.2. 1507.8.8. T1507.8,
1507.9.3, 1507.9.3.2. 1507.9.5, 1507.9.9
Properties: Physical properties
THESE PLANS AND
ALL Pg0A0SED WOFch
ARE SUBJECT TO ANY
CORRECTIONS
"D BY FIELD
MAQ
REFERENCES
BE IN THAT_
SpSAL
COMPLY WITH ER TO
LdAPPLICABLE
Enti
d
Report No. Stan ar5.
PRI Construction Materials Technologies (TST6049)
TAP-191-02-01REV ASTM D 1970 2009
PRI Construction Materials Technologies (TST6049)
TAP-192-02-01 ASTM D 1970 2009
PRI Construction Materials Technologies (TST6049)
TAPA93-02-01 ASTM D 1970 2009
PRI Construction Materials Technologies (TST6049)
TAP-214-02-01 ASTM D 4869 2005e01
PRI Construction Materials Technologies (TST6049)
TAP-215-02-01 ASTM D 226 2006
PRI Construction Materials Technologies (TST6049)
PRI Construction Materials Technologies (TST6049)
TAP-216-02-03 ASTM D 6380 2003(2009)
TAP-217-02-01 REV ,CONCE��VER 2003(2009)
PRI Construction Materials Technologies (TST6049)
PRI Construction Materials Technologies (TST6049)
TAP-218-02-01 S G R AM,.-
TAP-219-02-01 AR02266aw
PRI Construction Materials Technologies (TST6049)
TAP-220-02-01 SIBILP$( 009)PRI
Construction Materials Technologies (TST6049)
TAP-222-02-01 OF REC(O° 1
PRI Construction Materials Technologies (TST6049)
TAP=319-02-01.1 ACC 188 2
UL LLC (TST9628)
13CAI2269 ASTM D 226 2006
PRODUCT DESCRIPTION AND APPLICATION
TAMKO® ASTM Slate ASTM D 6380, Class M, Type 11 underayment constructed from organic felt saturated
S rfaced Roll Roofing with asphalt and coated on both sides with asphalt and surfaced with granules.
ST. LU CIE COUNTY BL-II .M-�TC Dfftyh- W:
UEVIE'ii'ED F`ORCOIZPL NCE
r,6EVIE ED B1' ication.:
DATE �A17
PLANS AND PE_ l31IT I`'IUST BE KEPT ON d03
OR NO INSPECTION WILL BE MADE.
2:12
The underlayment shall be installed with minimum 2"
side laps and minimum 4° staggered end laps and in
accordance with FRSA/TRI 07230 for the
applications.
Allowable roof coverings: Attachment of asphalt shingle valleys and clay and
concrete tile shall be permitted in accordance with
the FBC.
TBP14001.3 FL12328-R7 Page 1 of 4
This evaluation report is:provided for State of Florida product approval under Rule 611320-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other pro bd esethat Grp not
specifically addressed herein.
CREEK TAMKO BUILDING PRODCUTS, INC.
TAMKO Underlayments
TECHNICAL SERVICES, LLC
TAMKOO ASTM Tile ASTM D 6380, Class M,, Type II underlayment constructed from an organic felt saturated
Underfayment with asphalt then coated on both sides with asphalt and surfaced with. granules.
.Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4" staggered end laps and in
accordance with FRSAITRI 07230 for tile
applications.
Allowable roof coverings: Attachment of clay and concrete file shall be
permitted in accordance with the FBC.
TAMKOO Master
ASTM D 6380, Class S, Type IV underlayment constructed from an organic felt saturated
Smooth
with asphalt then coated on both sides with. asphalt and surfaced with a fine mineral.
Application: The underlayment shall be installed along the valley
in accordance with FBC requirements.
Allowable roof coverings: Attachment of asphalt shingle valleys shall be
permitted in accordance with the FBC.
TAMKO® Moisture
Self -adhered, ASTM D 1970, fiberglass reinforced, modified bitumen sheet membrane
Guard Plus®
with a mineral surfacing and a removable release film on the adhesive side.
Application: The underlayment shall be attached by adhering
directly to the roof deck with minimum 3-1I2" side
laps and minimum 6" staggered end laps.
Min. application temperature: 40"F.
Allowable roof coverings: Attachment of asphalt shingles and mechanically
fastened concrete and clay file roofing shall be
permitted in accordance with the FBC.
TAMKOO No.15 ASTM
ASTM D 226, Type I underlayment constructed from a non -perforated organic felt that is
Asphalt Saturated
saturated with asphalt.
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4" end laps.
Allowable roof coverings: Attachment of asphalt shingles; metal roofing, wood
shingles, wood shakes, and roll roofing shall be
permitted in accordance with the FBC.
TAMKO® No. 15 UL
ASTM D 226, Type I underlayment constructed from a non -perforated organic felt that is
Asphalt Saturated
saturated with asphalt.
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4" end laps.
Allowable roof coverings: Attachment of asphalt shingles; metal roofing; wood
shingles, wood shakes, and roll roofing shall be
permitted in accordance with the FBC.
TBP14001.3 FL12328-R7 Page 2 of 4
This. evaluation report is:provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical .Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed Herein.
CREEK TAMKO BUILDING PRODCUTS, INC.
TAMKO Underlayments
TECHNICAL SERVICES, LLC
TAMKOO No. 30 ASTM ASTM D 226, Type II underlayment constructed from a non -perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4" end laps.
Allowable roof coverings:
Attachment of asphalt shingles; metal roofing, clay
and concrete tile, slate shingles, wood shingles,
wood shakes, and roll roofing shall be permitted in
accordance with the FBC.
TAMKOO No. 30 UL
ASTM D 226, Type II underlayment constructed from a non -perforated organic felt that is
Asphalt Saturated
saturated with asphalt.
Organic Felt
Application:
The underlayment shall be installed with minimum 2"
side laps and minimum 4" end laps.
Allowable roof coverings:
Attachment of asphalt shingles, metal roofing, clay
and concrete tile, slate shingles, wood shingles,
wood shakes, and roll roofing shall be permitted in
accordance with the FBC.
TAMKO® TW Metal and
Self -adhered, flexible, ASTM
D 1970, rubberized asphalt sheet membrane with a
Tile Underlayment
polymer film on the surface and a removable release film on the adhesive side.
Application:
The underlayment shall be attached by adhering
directly to the roof deck with minimum 4" side laps
and minimum 6" staggered end laps.
Min. application temperature:
40"F
Allowable roof coverings:
Attachment of asphalt shingles, metal roofing, and
mechanically fastened clay and concrete tiles shall
be. permitted in accordance with the FBC.
TAMKO®TW
Self -adhered, flexible, ASTM
D 1970, rubberized asphalt sheet membrane with a
Underlayment
polymer film on the surface and a removable release film on the adhesive side.
Application:
The underlayment shall be attached by adhering
directly to the roof deck with minimum 4" side laps
and minimum 6" staggered end laps.
Min. application temperature:
40OF
Allowable roof coverings:
Attachment of asphalt shingles and metal roofing
shall be permitted in accordance with the FBC.
TAMKO® TAM -FELT
Alternate to ASTM D 226, Type I and Type II underlayment constructed from a non -
perforated organic felt that is saturated with asphalt.
Application:
The underlayment shall be installed with minimum 2"
side laps and minimum 4" end laps.
Allowable roof coverings:
Attachment of asphalt shingles shall be permitted in
accordance -with the FBC.
TBP14001.3 FL12328-R7 Page 3 of 4
This evaluation report is provided for State of Florida product approval under'Rule 61 G20-3. The manufacturer shall notify CREEK
Technical. Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODCUTS, INC.
TAMKO Undedayments
TECHNICAL SERVICES, LLC
LIMITATIONS
1) This evaluation report is not for use in the HVHZ..
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance in not within scope of this evaluation.
4) Installation of the evaluated productzhall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Minimum application temperature shall be 50'F unless otherwise noted. Contact the manufacturer when
installing at temperatures below the minimum application temperature.
6) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
7) The roof deck shall be constructed of closely fitted sheathing for new or existing construction. Roof deck
shall be installed in accordance with FBC requirements.
8) Unless otherwise stated, the minimum roof slope shall be in accordance with FBC requirements.
9) All underiayments shall be installed with the roll length parallel to the eave, starting at the eave, and lapped
in successive courses installed up the deck in a manner that effectively sheds water from the deck. End
laps shall be staggered between courses in accordance with the manufacturer's application instructions.
10) The underiaymentmay be used as,descnbed in other current FBC product: approval documents.
11.) The underlayment shall not be installed over existing roof coverings.
12) Contact the manufacturer regarding specific exposure limits for each underlayment.
13) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E, have demonstrated compliance with the Florida Building
Code, 5'' Edition (2014) as evidenced in the referenced documents submitted by the named manufacturer.
G�P�Y ' R p9i����
No 74021
STATE OF
CERTIFICATION OF INDEPENDENCE
2016.08.2
2 09:35:39
�WPM.W,d YIIr1�,0.M1 �F.u•. u•� 044
LL>w 1001
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical. Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this
evaluation.
CREEK Technical Services,, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest.in any company manufacturing or distributing products under this evaluation.
Zachary R. Priest,; P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product.
END OF REPORT
TBP14001.3 FL12328-R7 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical. Services, LLC of any productchanges or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply Warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.